INSPECTIONS
PREPARED 3/24/09, 13:59:38 INSPECTION TICKET PAGE 13
Harnett Cgunty INSPECTOR: IVR DATE 3/25/09
ADDRESS . : 5920 US 401 N SUBDIV:
CONTRACTOR : PHONE
OWNER : MCDOUGALD JESSIE H & JOELINA G PHONE
PARCEL : 08-0655- - -0136- - -
APPL NUMBER: 08-50020908 CP DAYCARE
DIRECTIONS : US 401N. NEAR 5920 US 401. 401N
TOWARS FUQUAY 4 MI ON RIGHT.
T/S: 09/12/2008 01:47 PM VBROWN
STRUCTURE: 000 000 DAYCARE 90PRESCHOOLERS, 35AFT 15EMP
FLOOD ZONE . . . . : FLOOD ZONE X
PROPOSED USE . . . . . . . DAYCARE SEPTIC - EXISTING? . . . . : NEW TANK
WATER SUPPLY . . . . . . . COUNTY
PERMIT: CBCO 00 CP BUILDING COMMERCIAL
REQUESTED INSP DESCRIPTION
TYP/SQ COMPLETED RESULT RESULTS/COMMENTS
C151 01 3/25/09 TI__ _ C*BLDG FOOTING VRU 001747245
- - COMMENTS AND NOTES
Mar-24. 2009 4 03PM ENOCH ENGINEERS, PA No.6452 P. 2/3
Enoch
FS eers, P. A.
lne r•.. Gnlwin Sr., PR, P.L.S. Consulting Engineers & Surveyors VNW: (419) 89a-5731
(919)WA-7%5
Kevin X. Alin, P.H. 1403 NC Ilwy 50 South FW (919) 8"4190
Benson, NC 27504 Few& jue~uJen chenF noets.oom
March 24, 2009
Naylor~~nstrtrucdon, Inc.
289 3hl~+"Vgd Road
Newton Grove, NC 28366
Attn: Robert Naylor
RF.: Compaction Test Results
Suhject: Lilly Pad Daycare,
Highway 401
Lillington, NC
Nur Mr. Naylor:
Please find the enclosed compaction test results on the above referenced project for your
review and use. Should you have any further questions please feel free to contact us at
the above listed number.
5'
` k CARo r~~•
i~ 7
J1 FG~odwin , P.E. ;a SEA
r'
t L
eers, P.A. ? 9517 F
%
yGINE~e'cQ` ~r
r Mar.24. 1009 4:03PM ENOCH ENGINEERS. PA No 6452 P. 3/3
z
(2p N NNppN NN+++++++ 80 m •400 A W N+
1/ 4~A W N+O ~D m.101 fJ~Pw N+ M
z m CD 0
n o x ~ ~ ~ ►ner
~ ce tot ~ TCSj O F+
0
g z z
a n ~
o o
y
n; N w a
0
°Ci C~J1
o
m co
m
N
7
v
v
O
O
V
D
O
c
7
_a O --1
o
n N y+
0 N
N
11111 jjj~j
O
N
2
O Z
N
CX f,A
d 1
`mac ~
n
Z
0n
m y
m ~
m o~
9
aR
Nov O!~ 08 12:51p Detter & Associates 910-485-5883 p.t
C_~; O
a
DETTER & ASSOCIATES r; GJ~
Consulting Engineer
Post Office Box 53827
Fayetteville, N C 28305
910/485-7778:voice
9101485-5883:fax
e-mail: jamesdetter@embargmail.com
F A C S !MILE (total of 2 pages including this cover page)
November 5, 2008
To: Lynwood McDonald, Building Codes Administrator
Inspections Department
Harnett County
P. O. Box 65
Lillington N C 27546
Fax: 910.814.6459
FROM: James D. Defter, P.
RE: Lillypads Child Development Center. U. S. Hwy 401
Lillington, N C
Attached is a drawing of a portion of drawing P-200. An interior hose bibb (P-10
in the fixture schedule) is being added to the Kitchen 113 and Laundry/Stor. 112
in lieu of a trap primer as a means of providing a water seal in the trap of the floor
drain that is in each of these two rooms.
Attachment as
Cc: Robert Naylor, Owner
:Q
c S t
tit
%1.06.0'9
Nov 05 08 12:51p Detter Associates 910-485-5883 p.2
J
orb
THOMAS GOE:7Z
N Prl rAlw-A 12M Fact moat RW CHILD DETTER k ASSOCIATES ro;QlaEisaio .
sIM 2" DEVELOPMENT auwa/&W ~iiaeerYr~
PFA ,
A 0. WX 53928 P. O. Vox saw
FAYETTME, NC 2UN CENTER Fa~yetce ule. Nc 28305
=
1FLE (910) 485-3000 $10/486-7778 voice E P
Foe (910) 313-3911 Its NWt 401 ✓ ' R E,:'
ULL Na1oN, NC 911/486-6888 fax i GIME, ~Q.,
® EPN: 996-08
A4CNITEC T. PA NEW FlplOl' 080466%, 14.08
SHEET N0. 2 TO DWQ P-20U
SCALE: AS NOTED
LAUNDRY STOR_
112
P-6
1
r P-3 1/2" I 3 4 1/2"
HW
3/4!*
I
7- ~J
:i
P-14
1 I P-4: ~
, KITCHEN 60 7--CW /2
~e3i I P-10 113 - I P-10 "
1 Lei
REF, j 3 =
I
1
I 1 3/4"
^i I rF-
!Illli I
1 PLUMB% - HOT COLD WATER PLAN
SCALE 3/16" = 1'-0`
rf
PREPARED 4/02/09, 13:59:24 INSPECTION TICKET PAGE 8
Harnett County INSPECTOR: IVR DATE 4/03/09
'ADDRESS . : 5920 US 401 N SUBDIV:
CONTRACTOR : PHONE
OWNER MCDOUGALD JESSIE H & JOELINA G PHONE
PARCEL 08-0655- - -0136- - -
APPL NUMBER: 08-50020908 CP DAYCARE
DIRECTIONS : US 401N. NEAR 5920 US 401. 401N
TOWARS FUQUAY 4 MI ON RIGHT.
T/S: 09/12/2008 01:47 PM VBROWN
STRUCTURE: 000 000 DAYCARE 90PPESCHOOT.ERS, 35AFT 15EMP
FLOOD ZONE . . . . : FLOOD ZONE X
PROPOSED USE . . . . . . . DAYCARE SEPTIC - EXISTING? . . . . : NEW TANK
WATER SUPPLY . . . . . . . COUNTY
PERMIT: CPEC 00 CP ELECTRICAL COMMERCIAL
REQUESTED INSP DESCRIPTION
TYP/SQ COMPLETED RESULT RESULTS/COMMENTS
E267 01 4/03/09 TI C*ELEC TEMP SERVICE POLE TIME: 17:00 VRU 001750801
- - COMMENTS AND NOTES -
PREPARED 4/14/09, 13:59:10 INSPECTION TICKET PAGE 5
Harnett County INSPECTOR: IVR DATE 4/15/09
ADDRESS . : 5920 US 401 N SUBDIV:
CONTRACTOR : PHONE
OWNER MCDOUGALD JESSIE H & JOELINA G PHONE
PARCEL 08-0655- - -0136- - -
APPL NUMBER: 08-50020908 CP DAYCARE
DIRECTIONS : US 401N. NEAR 5920 US 401. 401N
TOWARS FUQUAY 4 MI ON RIGHT.
T/S: 09/12/2008 01:47 PM VBROWN
STRUCTURE: 000 000 DAYCARE 90PRESCHOOLERS, 35AFT 15EMP
FLOOD ZONE . . . . : FLOOD ZONE X
PROPOSED USE . . . . . . . : DAYCARE SEPTIC - EXISTING? . . . . : NEW TANK
WATER SUPPLY . . . . . . . : COUNTY
PERMIT: CPPC 00 CP PLUMBING COMMERCIAL
REQUESTED INSP DESCRIPTION
TYP/SQ COMPLETED RESULT RESULTS/COMMENTS
- - - -
P357 01 4/15/09 TI _ C*PLUMB UNDER SLAB VRU 001755318
V/1~,fJi~lL}-
COMMENTS AND NOTES
PREPARED 4/15/09, 14:00:57 INSPECTION TICKET PAGE 8
Harnett County INSPECTOR: IVR DATE 4/16/09
- - - - -
ADDRESS . : 5920 US 401 N SUBDIV:
CONTRACTOR : PHONE
OWNER MCDOUGALD JESSIE H & JOELINA G PHONE
PARCEL 08-0655- - -0136- - -
APPL NUMBER: 08-50020908 CP DAYCARE
DIRECTIONS : US 401N. NEAR 5920 US 401. 401N
TOWARS FUQUAY 4 MI ON RIGHT.
T/S: 09/12/2008 01:47 PM VBROWN
PLEASE CALL CAMERON ADCOCK AFTER YOU DO
THE INSPECTION SO THEY CAN CALL THE EL
ECTRICAL CONTRACTOR TO COME. 814-7195.
STRUCTURE: 000 000 DAYCARE 90PRESCHOOLERS, 35AFT 15EMP
FLOOD ZONE . . . . : FLOOD ZONE X
PROPOSED USE . . . . . . . DAYCARE SEPTIC - EXISTING? . . . . : NEW TANK
WATER SUPPLY . . . . . . . COUNTY
PERMIT: CPPC 00 CP PLUMBING COMMERCIAL
REQUESTED INSP DESCRIPTION
TYP/SQ COMPLETED RESULT RESULTS/COMMENTS
- -
P357 01 4/15/09 C*PLUMB UNDER SLAB VRU 001755318
4/15/09 DP no plans at jobsite. $50 reinspection fee
P357 02 4/~ /09 C*PLUMB UNDER SLAB VRU /0001756162 / n ,{~Jp
COMMENTS AND NOTES -C--e.4LL.------ L/71V -~~IC~~ -
/nom CT1i/~~ ~lU
y
PREPARED 4/16/09, 13:58:56 INSPECTION TICKET PAGE 21
Harnett County INSPECTOR: IVR DATE 4/17/09
ADDRESS . : 5920 US 401 N SUBDIV:
CONTRACTOR : PHONE
OWNER MCDOUGALD JESSIE H & JOELINA G PHONE
PARCEL 08-0655- - -0136- - -
APPL NUMBER: 08-50020908 CP DAYCARE
DIRECTIONS : US 401N. NEAR 5920 US 401. 401N
TOWARS FUQUAY 4 MI ON RIGHT.
T/S: 09/12/2008 01:47 PM VBROWN
PLEASE CALL CAMERON ADCOCK AFTER YOU DO
THE INSPECTION SO THEY CAN CALL THE EL
ECTRICAL CONTRACTOR TO COME. 814-7195.
STRUCTURE: 000 000 DAYCARE 90PRESCHOOLERS, 35AFT 15EMP
FLOOD ZONE . . . . : FLOOD ZONE X
PROPOSED USE . . . . . . . DAYCARE SEPTIC - EXISTING? . . . . : NEW TANK
WATER SUPPLY . . . . . . . COUNTY
PERMIT: CPEC 00 CP ELECTRICAL COMMERCIAL
REQUESTED INSP DESCRIPTION
TYP/SQ COMPLETED RESULT RESULTS/COMMENTS
- - - -
E267 01 4/03/09 BS C*ELEC TEMP SERVICE POLE TIME: 17:00 VRU 001750801
4/03/09 AP
E259 01 4/17/09_ ,T~I, C*ELEC UNDER SLAB VRU 001756717
(~"D MR. TOMMY WOULD LIKE YOU TO GO AS LATE AFTER LUNCH AS
POSSIBLE.
xxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxx
COMMENTS AND NOTES
PREPARED 4/21/09, 13:58:53 INSPECTION TICKET PAGE 12
Harnett County INSPECTOR: IVR DATE 4/22/09
ADDRESS . : 5920 US 401 N SUBDIV:
CONTRACTOR : PHONE
OWNER MCDOUGALD JESSIE H & JOELINA G PHONE
PARCEL 08-0655- - -0136- - -
APPL NUMBER: 08-50020908 CP DAYCARE
DIRECTIONS : US 401N. NEAR 5920 US 401. 401N
TOWARS FUQUAY 4 MI ON RIGHT.
T/S: 09/12/2008 01:47 PM VBROWN
PLEASE CALL CAMERON ADCOCK AFTER YOU DO
THE INSPECTION SO THEY CAN CALL THE EL
ECTRICAL CONTRACTOR TO COME. 814-7195.
STRUCTURE: 000 000 DAYCARE 90PRESCHOOLERS, 35AFT 15EMP
FLOOD ZONE . . . . : FLOOD ZONE X
PROPOSED USE . . . . . . . DAYCARE SEPTIC - EXISTING? . . . . : NEW TANK
WATER SUPPLY . . . . . . . COUNTY
PERMIT: CBCO 00 CP BUILDING COMMERCIAL
REQUESTED INSP DESCRIPTION
TYP/SQ COMPLETED RESULT RESULTS/COMMENTS
C151 01 3/25/09 BS C*BLDG FOOTING VRU 001747245
3/25/09 AP compaction test attached
A814 01 4/16/09 TI ADDRESS CONFIRMATION TIME: 17:00 VRU 001756360
C159 01 4/22/09 TI C*BLDG SLAB INSP VRU 001758495
y aI-a9 Affl~
COMMENTS AND NOTES - -
PREPARED 6/09`19, 13:59:36 INSPECTION TICKET PAGE 13
Harnett County E~ INSPECTOR: IVR DATE 6/10/09
ADDRESS 59: US 401 N SUBDIV:
P
CONTRACTOR ~5 PHONE
OWNER MCDOUGALD JESSIE H & JOELINA G PHONE
PARCEL 08-0655- - -0136- - -
APPL NUMBER: 08-50020908 CP DAYCARE
DIRECTIONS : US 401N. NEAR 5920 US 401. 401N
TOWARS FUQUAY 4 MI ON RIGHT.
T/S: 09/12/2008 01:47 PM VBROWN
PLEASE CALL CAMERON ADCOCK AFTER YOU DO
THE INSPECTION SO THEY CAN CALL THE EL
ECTRICAL CONTRACTOR TO COME. 814-7195.
STRUCTURE: 000 000 DAYCARE 90PRESCBOOLERS, 35AFT 15EMP
FLOOD ZONE . . . . : FLOOD ZONE X
PROPOSED USE . . . . . . . DAYCARE SEPTIC - EXISTING? . . . . : NEW TANK
WATER SUPPLY . . . . . . . COUNTY
PERMIT: CBCO 00 CP BUILDING COMMERCIAL
REQUESTED INSP DESCRIPTION
TYP/SQ COMPLETED RESULT RESULTS/COMMENTS
C151 01 3/25/09 BS C*BLDG FOOTING VRU 001747245
3/25/09 AP compaction test attached
A814 01 4/16/09 TI ADDRESS CONFIRMATION TIME: 17:00 VRU 001756360
4/24/09 AP 5976 US 401 N
C159 01 4/22/09 BS C*BLDG SLAB INSP VRU 001758495
4/22/09 AP
C153 01 /y 10/09 T.I C*BLDG-ROUGH IN TIME: 17:00 VRU 001779321
/,i.,/GI}\N ~LAQI/[1-
PERMIT: CPEC 00' P ELE ICAL COMMERCIAL
REQUES ED I SP DESCRIPTION
TYP/SQ COMP LE ED RE ULT RESULTS/COMMENTS
E267 01 4/03/ 9 BS C ELEC TEMP SERVICE POLE TIME: 17:00 VRU 001750801
4/03 09 AP
E259 01 4/17 09 BS C*ELEC UNDER SLAB VRU 001756717
4/17 09 AP MR. TOMMY WOULD LIKE YOU TO GO AS LATE AFTER LUNCH AS
POSSIBLE.
E251 01 6/10 09 fREULT C*ELEC ROUGH IN TIME: 17:00 VRU 001779339
-
PERMIT: CPMC 00 CP ME COMMERCIAL
REQUE TED DESCRIPTION
TYP/SQ COMPL TED RESULTS/COMMENTS
M459 01 6/09..09 C*MECH ROUGH IN VRU 001779008
6/08 09 M459 02 6/10 09 C*MECH ROUGH IN TIME: 17:00 VRU 001779347
PERMIT: CPPC 00 CP PLUMBING COMMERCIAL
REQUE TED INSP DESCRIPTION
TYP/SQ COMPLETED RESULT RESULTS/COMMENTS
CONTINUED ONTO NEXT PAGE Iii
PREPARED 6/09/09, 13:59:36 INSPECTION TICKET PAGE 14
Harnett County INSPECTOR: IVR DATE 6/10/09
ADDRESS 592,,1 US 401 N SUBDIV:
CONTRACTOR PHONE
OWNER MCDOUGALD JESSIE H & JOELINA G PHONE
PARCEL 08-0655- - -0136- - -
APPL NUMBER: 08-50020908 CP DAYCARE
REQUESTED INSP DESCRIPTION
TYP/SQ COMPLETED RESULT RESULTS/COMMENTS
- - - - -
P357 01 4/15/09 BS C*PLUMB UNDER SLAB VRU 001755318
4/15/09 DP no plans at jobsite. $5O reinspection fee
P357 02 4/16/09 BS C*PLUMB UNDER SLAB VRU 001756162
4/16/09 AP
P351 01 6/10/09 C*PLUMB ROUGH IN TIME: 17:00 VRU 001779354
Vlf1~--------------- COMMENTS AND NOTES
PREPARED 6/11/09, 14:06:10 INSPECTION TICKET PAGE 9
Harnett County INSPECTOR: IVR DATE 6/12/09
ADDRESS 5920 US 401 N SUBDIV:
CONTRAC OR PHONE
OWNER MCDOUGALD JESSIE H & JOELINA G PHONE
PARCEL 08-0655- - -0136- - -
APPL NUMBER: 08-50020908 CP DAYCARE
DIRECTIONS : US 401N. NEAR 5920 US 401. 401N
TOWARS FUQUAY 4 MI ON RIGHT.
T/S: 09/12/2006 01:47 PM VBROWN
PLEASE CALL CAMERON ADCOCK AFTER YOU DO
THE INSPECTION SO THEY CAN CALL THE EL
ECTRICAL CONTRACTOR TO COME. 814-7195.
STRUCTURE: 000 000 DAYCARE 90PRESCHOOLERS, 35AFT 15EMP
FLOOD ZONE . . . . : FLOOD ZONE X
PROPOSED USE . . . . . . . DAYCARE SEPTIC - EXISTING? . . . . : NEW TANK
WATER SUPPLY . . . . . . . COUNTY
PERMIT: CBCO 00 CP BUILDING COMMERCIAL
REQUESTED INSP DESCRIPTION
TYP/SQ COMPLETED RESULT RESULTS/COMMENTS
C151 01 3/25/09 BS C*BLDG FOOTING VRU 001747245
3/25/09 AP compaction test attached
A814 01 4/16/09 TI ADDRESS CONFIRMATION TIME: 17:00 VRU 001756360
4/24/09 AP 5976 US 401 N
C159 01 4/22/09 BS C*BLDG SLAB INSP VRU 001758495
4/22/09 AP
C153 01 6/10/09 C*BLDG ROUGH IN TIME: 17:00 VRU 001779321
6/10/09 DA brace trusses per truss documents
C153 02 6/12/09 I C*BLDG ROUGH IN TIME: 17:00 VRU 001780964
•0
fly 5
PERMIT: CPEC 0 CP ELECTR COMMERCIAL
REQU STED IN DESCRIPTION
TYP/SQ COMP ETED RES T RESULTS/COMMENTS
E267 01 4/0 /09 BE C*ELEC TEMP SERVICE POLE TIME: 17:00 VRU 001750801
4/0 /09 AP
E259 01 4/ 7/09 BS C*ELEC UNDER SLAB VRU 001756717
4/ 7/09 AP MR. TOMMY WOULD LIKE YOU TO GO AS LATE AFTER LUNCH AS
POSSIBLE.
E251 01 6/ 0/09 C*ELEC ROUGH IN TIME: 17:00 VRU 001779339
6/ 0/09 DA need electrical change from 3 phase system to single phase
from engineer to complete electrical inspection. 2. Bond
for cold water line must be ahead of shutoff valve
E251 02 6/ 2/09 TI C*ELEC ROUGH IN TIME: 17:00 VRU 001780972
PERMIT: CPMC 0 CP MECOMMERCIAL
RE ESTED DESCRIPTION
TYP/SQ COMPLETED RESULTS/COMMENTS
M459 01 6/09/09 C*MECH ROUGH IN VRU 001779008
6/08/09 M459 02 6 10/09 C*MECH ROUGH IN TIME: 17:0 0 VRU 001779347
- CONTINUED ONTO NEXT PAGE - - - -
PREPARED 6/11/09, 14:06:10 INSPECTION TICKET PAGE 10
Harnett County INSPECTOR: IVR DATE 6/12/09
- - - - - - - -
ADDRESS . : 5920 US 401 N SUBDIV:
CONTRAC'17OR : .I PHONE
OWNER MCDOUGALD JESSIE H & JOELINA G PHONE
PARCEL 08-0655- - -0136- - -
APPL NUMBER: 08-50020908 CP DAYCARE
REQUESTED INSP DESCRIPTION
TYP/SQ COMPLETED RESULT RESULTS/COMMENTS
6/10/09 need engineers letter on hallway supply duct sourced into 1
boot from 2 different units
M459 03 6/12 09 C*MECH ROUGH IN TIME: 17:00 VRU 001780998
PERMIT: CPPC 00 CP PLUMBING COMMERCIAL
REQUESTED INSP DESCRIPTION
TYP/SQ COMPLETED RESULT RESULTS/COMMENTS
- - - -
P357 01 4/15/09 BS C*PLUMB UNDER SLAB VRU 001755318
4/15/09 DP no plans at jobsite. $50 reinspection fee
P357 02 4/16/09 BS C*PLUMB UNDER SLAB VRU 001756162
4/16/09 AP
P351 01 6/10/09 C*PLUMB ROUGH IN TIME: 17:00 VRU 001779354
6/10/09 DA Plumbing DWV test must have a 10 foot head. 3 foot is only
allowed for residential aplications
P351 02 6/12/09 TI C*PLUMB ROUGH IN TIME: 17:00 VRU 001780980
/ R
- COMMENTS AND NOTES
PREPARED 6/23/09, 13:58:32 INSPECTION TICKET PAGE 8
Harnett County INSPECTOR: IVR DATE 6/24/09
ADDRESS . : 5920 US 401 N SUBDIV:
CONTRACTOR : PHONE
OWNER MCDOUGALD JESSIE H & JOELINA G PHONE
PARCEL 08-0655- - -0136- - -
APPL NUMBER: 08-50020908 CP DAYCARE
DIRECTIONS : US 401N. NEAR 5920 US 401. 401N
TOWARS FUQUAY 4 MI ON RIGHT.
T/S: 09/12/2008 01:47 PM VBROWN
PLEASE CALL CAMERON ADCOCK AFTER YOU DO
THE INSPECTION SO THEY CAN CALL THE EL
ECTRICAL CONTRACTOR TO COME. 814-7195.
STRUCTURE: 000 000 DAYCARE 90PRESCHOOLERS, 35AFT 15EMP
FLOOD ZONE . . . . : FLOOD ZONE X
PROPOSED USE . . . . . . . : DAYCARE SEPTIC - EXISTING? . . . . : NEW TANK
WATER SUPPLY . . . . . . . : COUNTY
PERMIT: CPIC 00 CP INSULATION COMMERCIAL
REQUESTED INSP DESCRIPTION
TYP/SQ COMPLETED RESULT RESULTS/COMMENTS
I185 01 ~6~/2~4//0,,9q AM C*INSULATION INSPECTION VRU 001785344
~v
COMMENTS AND NOTES - -
PREPARED 7/06/09, 14:03:46 INSPECTION TICKET PAGE 6
Harnett County INSPECTOR: IVR DATE 7/07/09
ADDRESS . : 5920 US 401 N SUBDIV:
CONTRACTOR : PHONE
OWNER MCDOUGALD JESSIE H & JOELINA G PHONE
PARCEL 08-0655- - -0136- - -
APPL NUMBER: 08-50020908 CP DAYCARE
DIRECTIONS : US 401N. NEAR 5920 US 401. 401N
TOWARS FUQUAY 4 MI ON RIGHT.
T/S: 09/12/2008 01:47 PM VBROWN
PLEASE CALL CAMERON ADCOCK AFTER YOU DO
THE INSPECTION SO THEY CAN CALL THE EL
ECTRICAL CONTRACTOR TO COME. 814-7195.
STRUCTURE: 000 000 DAYCARE 90PRESCH0OLERS, 35AFT 15EMP
FLOOD ZONE . . . . : FLOOD ZONE X
PROPOSED USE . . . . . . . DAYCARE SEPTIC - EXISTING? . . . . : NEW TANK
WATER SUPPLY . . . . . . . COUNTY
PERMIT: CPPC 00 CP PLUMBING COMMERCIAL
REQUESTED INSP DESCRIPTION
TYP/SQ COMPLETED RESULT RESULTS/COMMENTS
- - -
P357 01 4/15/09 BS C*PLUMB UNDER SLAB VRU 001755318
4/15/09 DP no plans at jobsite. $50 reinspection fee
P357 02 4/16/09 BS C*PLUMB UNDER SLAB VRU 001756162
4/16/09 AP
P351 01 6/10/09 BS C*PLUMB ROUGH IN TIME: 17:00 VRU 001779354
6110109 DA Plumbing DWV test must have a 10 foot head. 3 foot is only
allowed for residential aplications
P351 02 6/12/09 BS C*PLUMB ROUGH IN TIME: 17:00 VRU 001780980
6/12/09 AP
P357 03 7/07/09 TI C*PLUMB UNDER SLAB TIME: 17:00 VRU 001790807
7-22gq T/S: 07/06/2009 01:15 PM JBROCK
COMMENTS AND NOTES
PREPARED 7/08/09, 14:03:32 INSPECTION TICKET PAGE 5
Harnett County INSPECTOR: IVR DATE 7/09/09
ADDRESS . : 5976 US 401 N SUBDIV:
CONTRACTOR : PHONE
OWNER MCDOUGALD JESSIE H & JOELINA G PHONE
PARCEL 08-0655- - -0136- -02-
APPL NUMBER: 08-50020908 CP DAYCARE
DIRECTIONS : US 401N. NEAR 5920 US 401. 401N
TOWARS FUQUAY 4 MI ON RIGHT.
T/S: 09/12/2006 01:47 PM VBROWN
PLEASE CALL CAMERON ADCOCK AFTER YOU DO
THE INSPECTION SO THEY CAN CALL THE EL
ECTRICAL CONTRACTOR TO COME. 814-7195.
STRUCTURE: 000 000 DAYCARE 90PRESCHOOLERS, 35AFT 15EMP
FLOOD ZONE . . . . : FLOOD ZONE X
PROPOSED USE . . . . . . . DAYCARE SEPTIC - EXISTING? . . . . : NEW TANK
WATER SUPPLY . . . . . . . COUNTY
PERMIT: CPPC 00 CP PLUMBING COMMERCIAL
REQUESTED INSP DESCRIPTION
TYP/SQ COMPLETED RESULT RESULTS/COMMENTS
P357 01 4/15/09 BS C*PLUMB UNDER SLAB VRU 001755318
4/15/09 DP no plans at jobsite. $50 reinspection fee
P357 02 4/16/09 BS C*PLUMB UNDER SLAB VRU 001756162
4/16/09 AP
P351 01 6/10/09 BS C*PLUMB ROUGH IN TIME: 17:00 VRU 001779354
6/10/09 DA Plumbing DWV test must have a 10 foot head. 3 foot is only
allowed for residential aplications
P351 02 6/12/09 BS C*PLUMB ROUGH IN TIME: 17:00 VRU 001780980
6/12/09 AP
P357 03 7/07/09 BS C*PLUMB UNDER SLAB TIME: 17:00 VRU 001790807
7/07/09 AP T/S: 07/06/2009 01:15 PM JBROCK
For the addition of the kitchen grese trap drains
P355 01 7/ C*PLUMB SEWER CONNECTION TIME: 17:00 VRU 001791953
T/S: 07/08/2009 01:20 PM JBROCK
COMMENTS AND NOTES
PREPARED 8/04/09, 14:22:02 INSPECTION TICKET PAGE 10
Harnett County INSPECTOR: IVR DATE 8/05/09
ADDRESS . : 5976 US 401 N SUBDIV:
CONTRACTOR : PHONE
OWNER MCDOUGALD JESSIE H & JOELINA G PHONE
PARCEL 08-0655- - -0136- -02-
APPL NUMBER: 08-50020908 CP DAYCARE
DIRECTIONS : US 401N. NEAR 5920 US 401. 401N
TOWARS FUQUAY 4 MI ON RIGHT.
T/S: 09/12/2008 01:47 PM VBROWN
PLEASE CALL CAMERON ADCOCK AFTER YOU DO
THE INSPECTION SO THEY CAN CALL THE EL
ECTRICAL CONTRACTOR TO COME. 814-7195.
STRUCTURE: 000 000 DAYCARE 90PRESCHOOLERS, 35AFT 15EMP
FLOOD ZONE . . . . : FLOOD ZONE X
PROPOSED USE . . . . . . . DAYCARE SEPTIC - EXISTING? . . . . : NEW TANK
WATER SUPPLY . . . . . . . COUNTY
PERMIT: CPPC 00 CP PLUMBING COMMERCIAL
REQUESTED INSP DESCRIPTION
TYP/SQ COMPLETED RESULT RESULTS/COMMENTS
P357 01 4/15/09 BS C*PLUMB UNDER SLAB VRU 001755318
4/15/09 DP no plans at jobsite. $50 reinspection fee
P357 02 4/16/09 BS C*PLUMB UNDER SLAB VRU 001756162
4/16/09 AP
P351 01 6/10/09 BS C*PLUMB ROUGH IN TIME: 17:00 VRU 001779354
6/10/09 DA Plumbing DWV test must have a 10 foot head. 3 foot is only
allowed for residential aplications
P351 02 6/12/09 BS C*PLUMB ROUGH IN TIME: 17:00 VRU 001760980
6/12/09 AP
P357 03 7/07/09 BS C*PLUMB UNDER SLAB TIME: 17:00 VRU 001790807
7/07/09 AP T/S: 07/06/2009 01:15 PM JBROCK
For the addition of the kitchen grese trap drains----------
P355 01 7/09/09 BS C*PLUMB SEWER CONNECTION TIME: 17:00 VRU 001791953
7/09/09 AP T/S: 07/08/2009 01:20 PM JBROCK
T/S: July 09, 2009 09:57 AM BSUTTON
P353 01 8/~05/~0-799 C*PLUMB WATER CONNECTION VRU 001804657
COMMENTS AND NOTES
Z iU/uy, 1Y:u4:~3 irvarn~:ilvrv lli&nl rv~n 1
Ha ty INSPECTOR: IVR DATE 8/19/09
AODRE 5976 US 401 N SUBDIV:
CONT OR - PHONE
OWNFaZ._ MCDOUGALD JESSIE H & JOELINA G PHONE
PARCEL 08-0655- - -0136- -02-
APPL NUMBER: 08-50020908 CP DAYCARE
- - - - -
DIRECTIONS : US 401N. NEAR 5920 US 401. 401N
TOWARS FUQUAY 4 MI ON RIGHT.
T/S: 09/12/2008 01:47 PM VBROWN
PLEASE CALL CAMERON ADCOCK AFTER YOU DO
THE INSPECTION SO THEY CAN CALL THE EL
ECTRICAL CONTRACTOR TO COME. 814-7195.
STRUCTURE: 000 000 DAYCARE 90PRESCHOOLERS, 35AFT 15EMP
FLOOD ZONE . . . . : FLOOD ZONE X
PROPOSED USE . . . . . . . DAYCARE SEPTIC - EXISTING? . . . . : NEW TANK
WATER SUPPLY . . . . . . . COUNTY
PERMIT: CTPC 00 CP TEMPORARY POWER CERTIFICATE
REQUESTED INSP DESCRIPTION
TYP/SQ COMPLETED RESULT RESULTS/COMMENTS
E253 01 8/19/09 ~I C*ELEC TEMP POWER CERT TIME: 17:00 VRU 001810779
1 - 1~ Y T/S: 08/18/2009 02:04 PM DJOHNSON
COMMENTS AND NOTES
EXPIRE DATE T 4 515
TEMPORARY POWER
CERTIFICATE
JOB NAME S ~'.G,~ 1G ~c~Je_~oJ1 L%u ~b2
OWNER,.Je6sie r 3cej(Na &"u+ 44DDRESS _q UI412I PPHONE
LOCATION
T The power company shall, not be required to
terminate electric service supplied to the premises'described above on or after
the expiration date specified in this certificate, unless" and until it is notified in
writing by the: Harnett County Electrical Inspector to do so.
I the undersigned understand' that this certificate is for Temporary Power only
and that a final inspection is required before permanent power will be approved.
I shall also comply with any special requirement requested by the Harnett
County Inspection Department.
Date -1 706*/27 a
Owner or.Authorized Signature
Th4certificate issued pursuant to the requirements of Section 105 of the North
Carolina eSiate Building Code certifying at the time of issuance this structure was
in temporary compliance with the various ordinances of the County of Harnett
regulating building constructiomor use.
Date
Building Official
PREPARED 9/11/09, 13:59:58 INSPECTION TICKET PAGE 4
Harnett County INSPECTOR: IVR DATE 9114109
- - - - - -
ADDRESS . : 5976 US 401 N SUBDIV:
CONTRACTOR : PHONE :
OWNER MCDOUGALD JESSIE H & JOELINA G PHONE :
PARCEL 08-0655- - -0136- -02-
APPL NUMBER: 06-50020908 CP DAYCARE
DIRECTIONS : US 401N. NEAR 5920 US 401. 401N
TOWARS FUQUAY 4 MI ON RIGHT.
T/S: 09/12/2008 01:47 PM VBROWN
PLEASE CALL CAMERON ADCOCK AFTER YOU DO
THE INSPECTION SO THEY CAN CALL THE EL
ECTRICAL CONTRACTOR TO COME. 814-7195.
STRUCTURE: 000 000 DAYCARE 90PRESCAO0LERS, 35AFT 15EMP
FLOOD ZONE . . . . : FLOOD ZONE X
PROPOSED USE . . . . . . . DAYCARE SEPTIC - EXISTING? . . . . : NEW TANK
WATER SUPPLY . . . . . . . COUNTY
PERMIT: CPLU 00 CP LAND USE PERMIT
REQUESTED INSP DESCRIPTION
TYP/SQ COMPLETED RESULT RESULTS/COMMENTS
Z820 01 14 09 TI PZ*ZONING/FINAL INSPECTION TIME: 17:00 VRU 001820901
WA d4z ~Cl T/S: 09/11/2009 01:17 PM DJOHNSON
- - COMMENTS AND NOTES - - -
PREPARED 9/16/09, 9:18:05 INSPECTION TICKET PAGE 1
Harnett County INSPECTOR: IVR DATE 9/16/09
ADDRESS . : 5976 US 401 N SUBDIV:
CONTRACTOR : PHONE
OWNER MCDOUGALD JESSIE H & JOELINA G PHONE
PARCEL 08-0655- - -0136- -02-
APPL NUMBER: 08-50020908 CP DAYCARE
DIRECTIONS : US 401N. NEAR 5920 US 401. 401N
TOWARS FUQUAY 4 MI ON RIGHT.
T/S: 09/12/2008 01:47 PM VBROWN
PLEASE CALL CAMERON ADCOCK AFTER YOU DO
THE INSPECTION SO THEY CAN CALL THE EL
ECTRICAL CONTRACTOR TO COME. 814-7195.
STRUCTURE: 000 000 DAYCARE 90PRESCHOOLERS, 35AFT 15EMP
FLOOD ZONE . . . . : FLOOD ZONE X
PROPOSED USE . . . . . . . DAYCARE SEPTIC - EXISTING? . . . . : NEW TANK
WATER SUPPLY . . . . . . . COUNTY
PERMIT: CPLU 00 CP LAND USE PERMIT
REQUESTED INSP DESCRIPTION
TYP/SQ COMPLETED RESULT RESULTS/COMMENTS
- - - - -
Z820 01 9/14/09 AD PZ*ZONING/FINAL INSPECTION TIME: 17:00 VRU 001820901
9/14/09 DA T/S: 09/11/2009 01:17 PM DJOHNSON
PARKING STOPS MUST BE INSTALLED IN ALL PARKING WITHOUT
CURBING. DUMPSTER SITE MUST BE SCREENED. HANDICAPPED SPACES
MUST BE MARKED AS HANDICAPPED. T/S: 09/14/2009 10:32 AM
ADRIGGER
Z820 02 9/16/09 TI PZ*ZONING/FINAL INSPECTION TIME: 17:00 VRU 001822717
nPL T/S: 09/16/2009 09:17 AM NTART
- COMMENTS AND NOTES - - - - -
COUNTY OF HARNETT
DEPARTMENT OF BUILDING INSPECTION
AND PLANNING/DEVELOPMENT
CERTIFICATE OF OCCUPANCY
This certificate issued pursuant to the requirements of Section 105 of the North Carolina State Building
Code and the Barnett County Zoning Ordinance certifies at the time of issuance this stricture was in
compliance with the various ordinances of the County of Harnett regulating development and building
construction or use. For the folbwing:
_ Use ClaSSf(iWhOn: Group E Daycare Ceneter Conditional Use Permit No.: NA
Type of Construction: V BuildingPer hNo.: OB-50020908
Ownerof Building: Robert Naylor Electrical Permit No.: 08-50020908
Building Address: 5976 US 901 N Puquay Va rina Insulation PermHNo.: 08-50020908
Zoning District: NA PlumbingPernitNo.: 08-50020908
Zoning Permit No.: NA Mech.PernRNo.: 08-50020908
Date: 09-22-09 Envir. C.O. No.: 08-50020908
Brad Sutton
Building Official Zoning Official
PREPARED 9/21/09, 13:00:26 INSPECTION TICKET PAGE 1
Harnett County INSPECTOR: IVR DATE 9/21/09
ADDRESS 5976 US 401 N SUBDIV:
CONTRACTOR : PHONE
OWNER : MCDOUGALD JESSIE H & JOELINA G PHONE
PARCEL : 08-0655- - -0136- -02-
APPL NUMBER: 08-50020908 CP DAYCARE
DIRECTIONS : US 401N. NEAR 5920 US 401. 401N
TOWARS FUQUAY 4 MI ON RIGHT.
T/S: 09/12/2008 01:47 PM VBROWN
PLEASE CALL CAMERON ADCOCK AFTER YOU DO
THE INSPECTION SO THEY CAN CALL THE EL
ECTRICAL CONTRACTOR TO COME. 814-7195.
PERMIT: CBCO 00 CP BUILDING COMMERCIAL
REQUESTED INSP DESCRIPTION
TYP/SQ COMPLETED RESULT RESULTS/COMMENTS
C151 01 3/25/09 BS C*BLDG FOOTING VRU 001747245
3/25/09 AP compaction test attached
A814 01 4/16/09 TI ADDRESS CONFIRMATION TIME: 17:00 VRU 001756360
4/24/09 AP 5976 US 401 N
C159 01 4/22/09 BS C*BLDG SLAB INSP VRU 001758495
4/22/09 AP
C153 01 6/10/09 BS C*BLDG ROUGH IN TIME: 17:00 VRU 001779321
6/10/09 DA brace trusses per truss documents
C153 02 6/12/09 BS C*BLDG ROUGH IN TIME: 17:00 VRU 001780964
6/12/09 AP
F854 01 9/16/09 TM FM*FINAL INSPECTION TIME: 17:00 VRU 001823426
9/16/09 AP T/S: 09/16/2009 03:32 PM NTART
T/S: 09/16/2009 03:36 PM NTART
C179 01 9/17/09 TI C*BLDG FINAL TIME: 17:00 VRU 001823434
9/16/09 CA T/S: 09/16/2009 03:34 PM NTART
p T/S: 09/16/2009 03:45 PM NTART
C179 02 T~crc~ C*BLDG FINAL TIME: 17:00 VRU 001824978
T/S: 09/21/2009 11:29 AM NTART
H822 01 9/21/09 GG ENVIR. HLTH/SANITATION FINAL TIME: 17:00 VRU 001824622
9/21/09 AP T/S: 09/21/2009 08:08 AM SSTEWART
T/S: 09/21/2009 08:08 AM SSTEWART
H824 01 9/21/09 OT ENVIR. OPERATIONS PERMIT TIME: 17:00 VRU 001824879
9/21/09 AP T/S: 09/21/2009 11:15 AM SSTEWART
T/S: 09/21/2009 11:15 AM SSTEWART
PERMIT: CPEC 00 CP ELECTRICAL COMMERCIAL
REQUESTED INSP DESCRIPTION
TYP/SQ COMPLETED RESULT RESULTS/COMMENTS
E267 01 4/03/09 BS C*ELEC TEMP SERVICE POLE TIME: 17:00 VRU 001750801
4/03/09 AP
E259 01 4/17/09 BS C*ELEC UNDER SLAB VRU 001756717
4/17/09 AP MR. TOMMY WOULD LIKE YOU TO GO AS LATE AFTER LUNCH AS
POSSIBLE.
E251 01 6/10/09 BS C*ELEC ROUGH IN TIME: 17:00 VRU 001779339
6/10/09 DA need electrical change from 3 phase system to single phase
from engineer to complete electrical inspection. 2. Bond
for cold water line must be ahead of shutoff valve
CONTINUED ONTO NEXT PAGE
PREPARED 9/21/09, 13:00:26 INSPECTION TICKET PAGE 2
Harnett County INSPECTOR: IVR DATE 9/21/09
ADDRESS 5976 US 401 N SUBDIV:
CONTRACTOR : PHONE
OWNER MCDOUGALD JESSIE H & JOELINA G PHONE
PARCEL 08-0655- - -0136- -02-
APPL NUMBER: 08-50020908 CP DAYCARE
REQUESTED INSP DESCRIPTION
TYP/SQ COMPLETED RESULT RESULTS/COMMENTS
E251 02 6/12/09 BS C*ELEC ROUGH IN TIME: 17:00 VRU 001780972
6/12/09 AP
E265 01 9/17/09 TI C*ELEC FINAL TIME: 17:00 VRU 001823442
9/16/09 CA T/S: 09/16/2009 03:34 PM NTART
T/S: 09/16/2009 03:45 PM NTART
E265 02 21/0 TI C*ELEC FINAL TIME: 17:00 VRU 001824986
C
T/S: 09/21/2009 11:29 AM NTART
PERMIT: CPMC 00 CP MECHANICAL COMMERCIAL
REQUESTED INSP DESCRIPTION
TYP/SQ COMPLETED RESULT RESULTS/COMMENTS
M459 01 6/09/09 BS C*MECH ROUGH IN VRU 001779008
6/08/09 CA
M459 02 6/10/09 BS C*MECH ROUGH IN TIME: 17:00 VRU 001779347
6/10/09 AE need engineers letter on hallway supply duct sourced into 1
boot from 2 different units
M459 03 6/12/09 BS C*MECH ROUGH IN TIME: 17:00 VRU 001780998
6/12/09 AP
M465 01 9/17/09 TI C*MECH FINAL TIME: 17:00 VRU 001823467
9/16/09 CA T/S: 09/16/2009 03:34 PM NTART
T/S: 09/16/2009 03:45 PM NTART
M465 02 TC*MECH FINAL TIME: 17:00 URU 001824994
AM -TART
- ---T/S_ 09/21/2009 11:29
-
PERMIT: CPPC 00 CP PLUMBING COMMERCIAL
REQUESTED INSP DESCRIPTION
TYP/SQ COMPLETED RESULT RESULTS/COMMENTS
P357 01 4/15/09 BS C*PLUMB UNDER SLAB VRU 001755318
4/15/09 DP no plans at jobsite. 850 reinspection fee
P357 02 4/16/09 BS C*PLUMB UNDER SLAB VRU 001756162
4/16/09 AP
P351 01 6/10/09 BS C*PLUMB ROUGH IN TIME: 17:00 VRU 001779354
6/10/09 DA Plumbing DWV test must have a 10 foot head. 3 foot is only
allowed for residential aplications
P351 02 6/12/09 BS C*PLUMB ROUGH IN TIME: 17:00 VRU 001780980
6/12/09 AP
P357 03 7/07/09 BS C*PLUMB UNDER SLAB TIME: 17:00 VRU 001790807
7/07/09 AP T/S: 07/06/2009 01:15 PM JBROCK
For the addition of the kitchen grese trap drains----------
P355 01 7/09/09 BS C*PLUMB SEWER CONNECTION TIME: 17:00 VRU 001791953
7/09/09 AP T/S: 07/08/2009 01:20 PM JBROCK
T/S: July 09, 2009 09:57 AM BSUTTON
P353 01 8/05/09 BS C*PLUMB WATER CONNECTION VRU 001804657
8/05/09 AP T/S: August 05, 2009 08:37 AM BSUTTON
P361 01 9/17/09 TI C*PLUMB FINAL TIME: 17:00 VRU 001823475
CONTINUED ONTO NEXT PAGE
PREPARED 9/21/09, 13:00:26 INSPECTION TICKET PAGE 3
Harnett County INSPECTOR: IVR DATE 9/21/09
ADDRESS• . 5976 US 401 N SUBDIV:
CONTRACTOR : PHONE
OWNER MCDOUGALD JESSIE H & JOELINA G PHONE
PARCEL 08-0655- - -0136- -02-
APPL NUMBER: 08-50020908 CP DAYCARE
REQUESTED INSP DESCRIPTION
TYP/SQ COMPLETED RESULT RESULTS/COMMENTS
9/16/09 CA T/S: 09/16/2009 03:34 PM NTART
T/S: 09/16/2009 03:45 PM NTART
P361 02 21/09 T~„ C*PLUMB FINAL TIME: 17:00 VRU 001825009
T/S: 09/21/2009 11:29 AM NTART
COMMENTS AND NOTES -
DCD 304.1 Identification /t
Rev. 9 O8 t~ County
Date of Inspection
BUILDING INSPECTORS INSPECTION FORM FOR CHILD CAPE CENTERS
NAME OF OPERATION
ADDRESS -57"7 Gam- TELEPHONE:
CITY F~Wg4"4--r /'A" ,.,I STATE ZIP
BUILDING INSPECTORS CERTIFICATE
i,
1. The areas in the building that are designated as the licensed space are required by the licensing agency
to meet the Building Code in effect when an application for licensure is submitted to the regulating agency.
Does the building listed above, to the extent observable, meet the current North
Carolina Building Code? YesI/No_
2. If no, list question numbers which do not comply, explain the violation and whether equivalent protection
for the safety of the children is provided:
1)
2)
3)
4)
3 Are any of the above violations of a life safety concern? Yes No i!
If yes, please list question numbers
4. In your opinion based on the violations listed above, do you recommend that the
Division of Child Development issue a provisional license to allow time for
correction of the violations? - Yes No If yes, how long (30-60-90 days) and for which violations?
(Vote: All violations must be corrected before a license can be issued unless a provisional time period is
recommended or equivalent protection.is documented.)
5. Number of rooms approved for occupancy by children?
(Attach sketch of building with rooms identified)
6. Specify any local zoning restriction:
Signature of Inspector / i • r r.' _ /Date
Jurisdiction f /Phone: w
The Inspectors Certificate and Building Inspection Form is required to be completed in its entirety before the Division of Child
Development (DCD) can consider the document complete. All questions must be answered; any NO answers must have a written
explanation.
This form was developed through the cooperation of the Division of Child Development and the Engineering Division of the Department of
Insurance. Please note that the inspection forms do not cover all areas of the Code, but are intended to be used as a guide for the local inspector.
If additional Code items which are not addressed on these forms are found to be in violation of the Code, please document them on the back of this
form.
Prepare in quadruplicate: Original & copy to DCD, 1 copy kept by inspector, 1 copy kept by operator.
J:
t ~
Identification #
County
j Date of Inspection
CHILD CARE BUILDING INSPECTION FORM
SECTION A: The following general questions should be answered for BOTH Educational and Institutional type occupancies.
LIGHT& VENTILATION
1. Is the total area of all windows in the child care room equal to or greater
than 8% of the floor area or is artificial light provided? Yes No_
2.a Does the room have natural ventilation from a minimum amount of operable window
or door area to the outside that would allow a clear opening that is
equal to or greater than 4% or more of the floor area?
(If NO, go to question 2b). Yes L No-
b Is space mechanically ventilated as required by North Carolina Mechanical Code?
(N/A if an existing building) NIA Yes No
FIRE
3. Does this building have a manually operated fire alarm system
(electrically installed system with pull box stations)? Yes f- f No
EXITS
4. Are there at least 2 exits (doors, stairs, smoke proof towers, ramps, or
horizontal exits) remote from each other on each floor or fire section
of the building? Yes No
5. Is the exit capacity adequate? Yes No
6. Are all means of egress adequately illuminated at all times that the building
is occupied? Yes No_
7. Are the means of egress identified by readily visible exit signs when the exit
or way to reach it is not immediately obvious to the occupants? Yes ' No
8. Is emergency power provided for centers with more than 300 occupants ri
or for centers providing night care as required by the Building Code? N/A v' Yes_ No
CORRIDORS AND ACCESS TO EXITS
9. Are all means of egress unobstructed without passing through a closet, /
storage area, kitchen, restroom, or other hazardous space? Yes d~ No
10. Are all exit corridors a minimum 1-hour fire resistance? N/A Yes {r No
(If yes, go to Question 12) (N/A applies only if there are no corridors)
it. If corridors are not 1 hour fire rated, do all child care rooms, spaces, and areas
have a direct level of discharge exit to the outside? Yes G~ + No
12, a. Do all corridors, ramps, and passageways have a minimum 6 feet
clear width in all areas serving as means of egress for capacity of 100 or more?
(N/A if capacity is less than 100) N/A Yes i., No-
b. Are all corridors, ramps, and passageways not less than 44" clear width in all
areas serving as means of egress for capacity of less than 100? /
(N/A if capacity is more than 100) N/A L/ Yes_ No
13. Are all dead-end corridors no more than 20 feet in length? N/A G~ Yes_ No_
(N/A applies only if no dead-end occurs)
Page 2 of 5
14. .t` qo all doors have a minimum clear opening width of 32" (min. door width of 36")
to the following locations:
a. between occupied rooms and required exits? Yes No
b;, exit doors leading to the exterior? Yes No
15. Are all doors in the line of exit travel a swinging door (side hinged)? Yes No
16. Do doors to rooms that accommodate more than 50 people swing in the
direction of travel ? N/A Yes No
(N/A applies if room accommodates less than 50 people)
17.a Do all required egress and exit doors have single motion, self-unlocking type
handle, lever, push pad, or. panic hardware? Yes No
b. If room accomdates 100 or more people, do all required egress and exit doors
have push pads or panic hardware? - N/AYes No
STAIRS (NOTE: If no stairs, interior or exterior, check N/A_ and go to Question 22. If applicable, all questions must be
answered)
18.a Are all stairs serving 50 :or more occupants.at least 44 inches in width? N/A Yes_ No
b Are all stairs serving less than 50 occupants, at least 36" in width? N/A Yes_ No
19. Are all stairs with four or more steps provided with proper handrails
and guardrails? Yes No
20. Are all interior stairs enclosed with I-hour rated walls and I-hour
rated "B" labeled doors that are at least 36" wide? Yes No
21. Are the stair enclosure doors self-closing? Yes_ No
WALLS AND CEILINGS
22. a. Are all wall and ceiling coverings throughout building non-combustible?
(Use of untreated combustible fiber boards, wood, and other combustible
fiber boards, wood and other combustible finishes is prohibited). Yes No
b. Do interior wall and ceiling finish materials meet the flame spread ratings
as required by the Minimum Interior Finish Classification Table, NCBC. YesJ~ No
23. Do ceilings in habitable rooms have a minimum of T-6" clear height? Yes t ~ No
HEATING SYSTEMS/MECHANICAL 24 `Is the building free of unvented fuel burning or portable electric space heaters? Yes 1Z No
25. Have air conditioning, ventilation, heating, cooking, and other service i
equipment been inspected and approved by the appropriate inspectors? yes-,, No
Date Inspected
26. a. Is combustion and ventilation air for boiler or heater rooms taken directly
from and discharged to the outside of the building? N/A-' Yes_ No
(N/A if electric heat is installed) -
b. If inside air is used for fuel-burning appliance does it meet the requirements of f
Chapter 7 of the North Carolina Mechanical Code. N/A V Yes_ No_
(N/A if inside air is not used)
PLUMBING
27. Does the number of waterclosets and lavatories comply with the Plumbing /
Code as determined by the appropriate inspector? Yesl_ No
(I watercloset per 15 children, I lavatory per 25 children)
Maximum # of persons allowed by plumbing facilities?
Date Inspected_-
Page 3 of 5
;j
t
ELECTRICAL
28. Do a visible and accessible portions of the electrical system comply with applicable
sections of the Electrical Code as determined by the appropriate inspector? Yes / No
Date Inspected
MIXED AND MULTI-USE OCCUPANCIES
29: Are all child care areas separated from adjacent occupancies in accordance with
the requirement of mixed occupancies and the Occupancy Separation
Requirements Table? (N/A if no mixed occupancies) N/A .G- Yes_ No
30. Do all multi-use areas comply with the most restrictive applicable sections of the
State Building Code for each intended use? N/A L/ Yes_ No
(N/A if no multi-use areas)-
(Multi-use is defined as an area which will be used for different functions
at different times and not concurrent. Example: child care to fellowship hall.)
ACCESSIBILITY CODES
31. Does this building comply with applicable State Building Codes for access/use f
by persons with disabilities? Yes t/ No
SECTION B: The following questions should be answered only for educational occupancy in addition to the questions answered in
Section A above.
32. Does the building comply with the Allowable Heights and Building Areas Table
for Educational Ocepancy? (If NO, go to Section Q. Yes No
33. a. Are all rooms, approved for use by children below grade 2, on the 1
level'of exit discharge? (If NO go to Section C) Yes V' No-
b. Are rooms used by children in grades 2 and higher no more than one story above the
level of exit discharge? Yes ✓ No
34. a. Do rooms used by children who are less than 2 'h years have a direct exit to the outside?
(N/A applies only if center, does not serve children under 2 '/2 yrs) N/A Yes .Z No
b. Do rooms used by childen under 2 'h years qualify as alcoves to adjacent spaces with
direct exit to the outside? Yes No
c. If the squat`& footage of the child care area is > 20,000 square feet, do all rooms
for all children have direct exits? (N/A if sq. footage is < 20,000) N/A Y Yes -No
.(If NO to both a and b or c, go to Section C)
35i "Are all rooms approved for use by children provided with an operable'
window which complies with Special Exit Requirements for Educational Occupancy? N/A tt YesNo
(N/A if direct exit to outside)
36. Is the most remote point in every room occupied by children, including
dining room, not more than 200 feet from the nearest exterior exit ?
(non-sprinklered building) Yes is No
37. Are smoke detectors provided in the corridors in accordance with /
Automatic Fire Detection and NFPA72 for child care use? Yes i No
SECTION C: The following questions should be answered only for institutional occupancy in addition to the questions answered in
Section A above.
38. Does the building comply with the Allowable Heights and Building Areas Table
for Institutional Occupancy? Yes_ No_
Page 4 of 5
SECTIO 'C cont.:
39:- Je smoke detectors provided in the corridors in accordance with Automatic
Fire Detection and NFPA72? Yes No
40. Does the building provide protection from hazardous areas as required by
Special Institutional Occupancies, Group I Unrestrained Occupancies, Protection
from Hazardous Areas? Yes No
41. Does the building have an approved automatic sprinkler system in accordance with Special
Institutional Occupancies Group I Unrestrained Occupancies? Yes_ No_
42. Is the most remote point in every room occupied by children, including the dining room,
not more than 200 feet from the nearest exterior exit? Yes No
i
i
Page 5 of 5