INSPECTIONS
PREPARED 12/18/08, 14:53:14 INSPECTION TICKET PAGE 1
Harnett County INSPECTOR: IVR DATE 12/19/08
ADDRESS . : 2495 RAY RD MAIN BLDG SUBDIV:
CONTRACTOR : HARNETT COUNTY SCHOOLS PHONE (910) 893-4808
OWNER : HCBE-OVERHILLS HIGH-BRICKMASON PHONE (910) 893-8151
PARCEL : 01-0513- - -0201- - -
APPL NUMBER: 08-50021009 CP NEW SCHOOLS & EDUCATIONAL
-
DIRECTIONS : OVERHILLS HIGH SCHOOL
210 SOUTH APPROX 14 MILES THEN RIGHT
ONTO RAY RD OVERHILL HIGH IS 2.5 MILES
ON LEFT.
T/S: 09/29/2008 12:56 PM DJOHNSON
STRUCTURE: 000 000,36X76 BRICXMA.SON CLASSROOM/SHOP BLDG
FLOOD ZONE . . . . : FLOOD ZONE X
PROPOSED USE . . . . . . . : SHOP SEPTIC - EXISTING? . . . . : NA
PERMIT: CPEC 00 CP ELECTRICAL COMMERCIAL
REQUESTED INSP DESCRIPTION
TYP/SQ COMPLETED RESULT RESULTS/COMMENTS
E257 01 12/19/08 TI C*ELEC OVERHEAD TIME: 17:00 VRU 001719715
-A 12- fil 12
PERMIT: CPPC00 CP PLUMBING COMMERCIAL
REQUESTED INSP DESCRIPTION
TYP/SQ COMPLETED- RESULT RESULTS/COMMENTS
- -
P357 01 12/19/08 TI C*PLUMB UNDER SLAB TIME: 17:00 VRU 001719517
ae-M
COMMENTS AND NOTES
PREPARED 12/22/08, 14:08:40 INSPECTION TICKET PAGE 16
Harnett County INSPECTOR: IVR DATE 12/23/08
ADDRESS . : 2495 RAY RD MAIN BLDG SUBDIV:
CONTRACTOR HARNETT COUNTY SCHOOLS PHONE (910) 893-4808
OWNER HCBE-OVERHILLS HIGH-BRICKMASON PHONE (910) 893-8151
PARCEL 01-0513- - -0201- - -
APPL NUMBER: 08-50021009 CP NEW SCHOOLS & EDUCATIONAL
DIRECTIONS : OVERHILLS HIGH SCHOOL
210 SOUTH APPROX 14 MILES THEN RIGHT
ONTO RAY RD OVERHILL HIGH IS 2.5 MILES
ON LEFT.
T/S: 09/29/2008 12:56 PM DJOHNSON
STRUCTURE: 000 000 3GX76 BRICKMASON CLASSROOM/SHOP BLDG
FLOOD ZONE . . . . : FLOOD ZONE X
PROPOSED USE . . . . . . . : SHOP SEPTIC - EXISTING? . . . . : NA
PERMIT: CBCO 00 CP BUILDING COMMERCIAL
REQUESTED INSP DESCRIPTION
TYP/SQ COMPLETED RESULT RESULTS/COMMENTS
- - - -
C155 01 12/23/08 C*BLDG FOUNDATION VRU #:-001720523
M~`~ 4r
COMMENTS AND NOTES
PREPARED 12/29/08, 14:01:03 INSPECTION TICKET PAGE 29
Harnett County INSPECTOR: IVR DATE 12/30/08
- -
ADDRESS . : 2495 RAY RD MAIN BLDG SUBDIV:
CONTRACTOR HARNETT COUNTY SCHOOLS PHONE (910) 893-4808
OWNER HCBE-OVERHILLS HIGH-BRICKMASON PHONE (910) 893-8151
PARCEL 01-0513- - -0201- -
APPL NUMBER: 08-50021009 CP NEW SCHOOLS & EDUCATIONAL
DIRECTIONS : OVERHILLS HIGH SCHOOL
210 SOUTH APPROX 14 MILES THEN RIGHT
ONTO RAY RD OVERHILL HIGH IS 2.5 MILES
ON LEFT.
T/S: 09/29/2008 12:56 PM DJOHNSON
STRUCTURE: 000 000 36X76 BRICKMASON CLASSROOM/SHOP BLDG
FLOOD ZONE . . . . : FLOOD ZONE X
PROPOSED USE . . . . . . . : SHOP SEPTIC - EXISTING? . . . . : NA
PERMIT: CBCO 00 CP BUILDING COMMERCIAL
REQUESTED INSP DESCRIPTION
TYP/SQ COMPLETED RESULT RESULTS/COMMENTS
-
C155 01 12/23/08 JH C*BLDG FOUNDATION VRU 001720523
12/23/08 DA not ready for inspection
C159 01 12/30/08 TI_ C*BLDG SLAB INSP VRU 001721281
COMMENTS AND NOTES - - - - -
PREPARED 5/19/09, 13:58:47 INSPECTION TICKET PAGE 4
Harnett County; INSPECTOR: IVR DATE 5/20/09
t
ADDRESS . : 2495 RAY RD MAIN BLDG SUBDIV:
CONTRACTOR HARNETT COUNTY SCHOOLS PHONE (910) 893-4808
OWNER HCBE-OVERHILLS HIGH-BRICKMASON PHONE (910) 893-8151
PARCEL 01-0513- - -0201- - -
APPL NUMBER: 08-50021009 CP NEW SCHOOLS & EDUCATIONAL
DIRECTIONS : OVERHILLS HIGH SCHOOL
210 SOUTH APPROX 14 MILES THEN RIGHT
ONTO RAY RD OVERHILL HIGH IS 2.5 MILES
ON LEFT.
T/S: 09/29/2008 12:56 PM DJOHNSON
STRUCTURE: 000 000 36X76 BRICKMASON CLASSROOM/SHOP BLDG
FLOOD ZONE . . . . : FLOOD ZONE X
PROPOSED USE . . . . . . . : SHOP SEPTIC - EXISTING? . . . . : NA
PERMIT: CBCO 00 CP BUILDING COMMERCIAL
REQUESTED INSP DESCRIPTION
TYP/SQ COMPLETED RESULT RESULTS/COMMENTS
C155 01 12/23/08 JH C*BLDG FOUNDATION VRU 001720523
12/23/08 DA not ready for inspection
C159 01 12/30/08 JH C*BLDG SLAB INSP VRU 001721281
12/30/08 AP -
C153 01 5/20/09 TI C*BLDG ROUGH IN VRU 001770247
S 20•x+ DA-M~Z
PERMIT: OPEC 00 CP ELECTRICAL COMMERCIAL
REQUESTED INSP DESCRIPTION
TYP/SQ COMPLETED RESULT RESULTS/COMMENTS
E257 01 12/19/08 MR C*ELEC OVERHEAD TIME: 17:00 VRU 001719715
12/19/08 AP underground
E251 01 5/20/09 TI C*ELEC ROUGH IN VRU 001770254
5.20.2 ~
UA-
PERMIT: CPMC 00 CP MECHANICAL COMMERCIAL
REQUESTED INSP DESCRIPTION
TYP/SQ COMPLETED RESULT RESULTS/COMMENTS
M459 01 5/20/09 T~ v C*MECH ROUGH IN VRU 001770262
20.°)
PERMIT: CPPC 00 CP PLUMBING COMMERCIAL
REQUESTED - INSP DESCRIPTION
TYP/SQ COMPLETED RESULT RESULTS/COMMENTS
P357 01 12/19/08 MR C*PLUMB UNDER SLAB TIME: 17:00 VRU 001719517
12/19/08 AP
P351 01 5/20/09 TI „ C*PLUMB ROUGH IN VRU 001770270
S'2afl
COMMENTS AND NOTES
HARNETT COUNTY
Building Inspections Dept.
108 E. Front St.
Lillington, NC 27546
910-893-7525
DO NOT REMOVE
DATE: 05-20-09
PERMIT# 08-50021009
ADDRESS: 2495 ray rd
VIOLATIONS:
1. NEC 250.90B bonding bushings are required at meter on both steel
pipes
2. NEC 200.6 white conductors cannot be used as travelers or switch-legs
except for romex installations
3. NEC 314.3 Plastic boxes not permitted.
4. LB type boxes cannot be installed behind drywall. They must be
Accessible
5. Finish window framing in batrhroom
6. Finish vents through roof on plumbing
7. Need water in test on plmb.
8. Need pressure test on water pipes on plmb
9. NEC 250.64E requires bonding of grounding conductors at both ends
when installed in a metal pipe.
Harnett County Building Department
Mike Reatic cell# (910) 984- 4772
PREPARED 5/21/09, 14:10:00 INSPECTION TICKET PAGE 2
HzT7nett Cohnty INSPECTOR: IVR DATE 5/22/09
- - - - -
ADDRESS . : 2495 RAY RD MAIN BLDG SUBDIV:
CONTRACTOR : HARNETT COUNTY SCHOOLS PHONE (910) 893-4808
OWNER- : HCBE-OVERHILLS HIGH-BRICKMASON PHONE (910) 893-8151
PARCEL : 01-0513- - -0201- - -
APPL NUMBER: 08-50021009 CP NEW SCHOOLS & EDUCATIONAL
DIRECTIONS : OVERHILLS HIGH SCHOOL
210 SOUTH APPROX 14 MILES THEN RIGHT
ONTO RAY RD OVERHILL HIGH IS 2.5 MILES
ON LEFT.
T/S: 09/29/2008 12:56 PM DJOHNSON
STRUCTUR.E: 000 000 36X76 BRICKMASON CLASSROOM/SHOP BLDG
FLOOD ZONE . . . . : FLOOD ZONE X
PROPOSED USE . . . . . . . : SHOP SEPTIC - EXISTING? . . . . : NA
PERMIT: CBCO 00 CP BUILDING COMMERCIAL
REQUESTED INSP DESCRIPTION
TYP/SQ COMPLETED RESULT RESULTS/COMMENTS
C155 01 12/23/08 JH C*BLDG FOUNDATION VRU 001720523
12/23/08 DA not ready for inspection
C159 01 12/30/08 JH C*BLDG SLAB INSP VRU 001721281
12/30/08 AP .
C153 01 5/20/09 MR C*BLDG ROUGH IN VRU 001770247
5/20/09 DA @.. NEC 250.90B bonding bushings are required at meter on
both steel pipes 2. NEC 200.6 white conductors cannot be
used as travelers or switch-legs except for romex
installationsQO- NEC 314-P& Plastic boxes not permitted.
Qhwj, LB type boxes cannot be installed behind drywall. They
must be Accessible-S- Finish window framing in batrhroom
Finish vents through roof on plumbing
"1►. Need water in test on plmb.
C153 02 5/22/09 TI C*BLDG ROUGH IN VRU 001771369
,9--2-2.9 DA-M(7~_
- CONTINUED ONTO NEXT PAGE -
PREPARED 5/21/09, 14:10:00 INSPECTION TICKET PAGE 3
Harnett County INSPECTOR: IVR DATE 5/22/09
ADDRESS . : 2495 RAY RD MAIN BLDG SUBDIV:
CONTRACTOR : HARNETT COUNTY SCHOOLS PHONE (910) 893-4808
OWNER- : HCBE-OVERHILLS HIGH-BRICKMASON PHONE (910) 893-8151
PARCEL : 01-0513- - -0201- - -
APPL NUMBER: 08-50021009 CP NEW SCHOOLS & EDUCATIONAL
DIRECTIONS : OVERHILLS HIGH SCHOOL
210 SOUTH APPROX 14 MILES THEN RIGHT
ONTO RAY RD OVERHILL HIGH IS 2.5 MILES
ON LEFT.
T/S: 09/29/2008 12:56 PM DJOHNSON
STRUCTURE: 000 000 36X76 BRICRMASON CLASSROOM/SHOP BLDG
FLOOD ZONE . . . . : FLOOD ZONE X
PROPOSED USE . . . . . . . : SHOP SEPTIC - EXISTING? . . . . : NA
PERMIT: CPEC 00 CP ELECTRICAL COMMERCIAL
REQUESTED INSP DESCRIPTION
TYP/SQ COMPLETED RESULT RESULTS/COMMENTS
E257 01 12/19/08 MR C*ELEC OVERHEAD TIME: 17:00 VRU 001719715
12/19/08 AP underground
E251 01 5/20/09 MR C*ELEC ROUGH IN VRU 001770254
5/20/09 DA 1. NEC 250.90B bonding bushings are required at meter on
both steel pipes 2. NEC 200.6 white conductors cannot be
used as travelers or switch-legs except for romex
installations 3. NEC 314.3 Plastic boxes not permitted.
4. LB type boxes cannot be installed behind drywall. They
must be Accessible 5. Finish window framing in batrhroom
6. Finish vents through roof on plumbing
7. Need water in test on plmb.
8. Need pressure test on water pipes on plmb
9. NEC 250.64E requires bonding of grounding conductors at
both ends when installed in a metal pipe.
E251 02 5/22/09 TI C*ELEC ROUGH IN VRU 001771377
CONTINUED ONTO NEXT PAGE
PREPARn 5/21/09, 14:10:00 INSPECTION TICKET PAGE 4
Harriett CMnty INSPECTOR: IVR DATE 5/22/09
ADDRESS . : 2495 RAY RD MAIN BLDG SUBDIV:
CONTRACTOR HARNETT COUNTY SCHOOLS PHONE (910) 893-4808
OWNER HCBE-OVERHILLS HIGH-BRICKMASON PHONE (910) 893-8151
PARCEL 01-0513- - -0201- - -
APPL NUMBER: 08-50021009 CP NEW SCHOOLS & EDUCATIONAL
DIRECTIONS : OVERHILLS HIGH SCHOOL
210 SOUTH APPROX 14 MILES THEN RIGHT
ONTO RAY RD OVERHILL HIGH IS 2.5 MILES
ON LEFT.
T/S: 09/29/2008 12:56 PM DJOHNSON
STRUCTURE: 000 000 36X76 BRICKMASON CLASSROOM/SHOP BLDG
FLOOD ZONE . . . . : FLOOD ZONE X
PROPOSED USE . . . . . . . : SHOP SEPTIC - EXISTING? . . . . : NA
PERMIT: CPPC 00 CP PLUMBING COMMERCIAL
REQUESTED INSP DESCRIPTION
TYP/SQ COMPLETED RESULT RESULTS/COMMENTS
P357 01 12/19/08 MR C*PLUMB UNDER SLAB TIME: 17:00 VRU 001719517
12/19/08 AP
P351 01 5/20/09 MR C*PLUMB ROUGH IN VRU 001770270
5/20/09 DA
P351 02 5/22/09 TI C*PLUMB ROUGH IN VRU 001771385
COMMENTS AND NOTES
PREPARED 5/26/09, 14:00:10 INSPECTION TICKET PAGE 9
Harnett County INSPECTOR: IVR DATE 5/27/09
ADDRESS . : 2495 RAY RD MAIN BLDG SUBDIV:
CONTRACTOR HARNETT COUNTY SCHOOLS PHONE (910) 893-4808
OWNER HCBE-OVERHILLS HIGH-BRICKMASON PHONE (910) 893-8151
PARCEL 01-0513- - -0201- - -
APPL NUMBER: 08-50021009 CP NEW SCHOOLS & EDUCATIONAL
DIRECTIONS : OVERHILLS HIGH SCHOOL
210 SOUTH APPROX 14 MILES THEN RIGHT
ONTO RAY RD OVERHILL HIGH IS 2.5 MILES
ON LEFT.
T/S: 09/29/2008 12:56 PM DJOHNSON
STRUCTURE: 000 000 36X76 BRICKMASON CLASSROOM/SHOP BLDG
FLOOD ZONE . . . . : FLOOD ZONE X
PROPOSED USE . . . . . . . : SHOP SEPTIC - EXISTING? . . . . : NA
PERMIT: CPEC 00 CP ELECTRICAL COMMERCTAT•
REQUESTED INSP DESCRIPTION
TYP/SQ COMPLETED RESULT RESULTS/COMMENTS
E257 01 12/19/08 MR C*ELEC OVERHEAD TIME: 17:00 VRU 001719715
12/19/08 AP underground
E251 01 5/20/09 MR C*ELEC ROUGH IN VRU 001770254
5/20/09 DA 1. NEC 250.90B bonding bushings are required at meter on
both steel pipes 2. NEC 200.6 white conductors cannot be
used as travelers or switch-legs except for romex
installations 3. NEC 314.3 Plastic boxes not permitted.
4. LB type boxes cannot be installed behind drywall. They
must be Accessible 5. Finish window framing in batrhroom
6. Finish vents through roof on plumbing
7. Need water in test on plmb.
8. Need pressure test on water pipes on plmb
9. NEC 250.64E requires bonding of grounding conductors at
both ends when installed in a metal pipe.
E251 02 5/22/09 MR C*ELEC ROUGH IN VRU 001771377
5/22/09 DA 14 2:,~-=r white conductors cannot be used for hot
cou""OZA
E251 03 5/27/09 TI C*ELEC ROUGH IN VRU 001772441
X27 9 4p_t
COMMENTS AND NOTES - -
1
PREPARED 7/2j)/09, 13:59:34 INSPECTION TICKET PAGE 9
Harnett Cou(I, INSPECTOR: IVR DATE 7/21/09
r _
-
ADDRESS 5 RAY RD MAIN BLDG SUBDIV:
CONTRAC~'OR RNETT COUNTY SCHOOLS PHONE (910) 893-4808
OWNER -O VERHILLS HIGH-HRICKMASON PHONE (910) 893-8151
PARCEL . . : 01-0513- - - 0201-
- -
APPL NUMBER: 08-50021009 CP NEW SCHOOLS & EDUCATIONAL
DIRECTIONS : OVERHILLS HIGH SCHOOL
210 SOUTH APPROX 14 MILES THEN RIGHT
ONTO RAY RD OVERHILL HIGH IS 2.5 MILES
ON LEFT.
T/S: 09/29/2008 12:56 PM DJOHNSON
STRUCTURE: 000 000 36X76 BRICKMASON CLASSROOM/SHOP BLDG
FLOOD ZONE . . . . : FLOOD ZONE X
PROPOSED USE . . . . . . . : SHOP SEPTIC - EXISTING? . . . . : NA
PERMIT: CPEC 00 CP ELECTRICAL COMMERCIAL
REQUESTED INSP DESCRIPTION
TYP/SQ COMPLETED RESULT RESULTS/COMMENTS
E257 01 12/19/08 MR C*ELEC OVERHEAD TIME: 17:00 VRU 001719715
12/19/08 AP underground
E251 01 5/20/09 MR C*ELEC ROUGH IN VRU 001770254
5/20/09 DA 1. NEC 250.90B bonding bushings are required at meter on
both steel pipes 2. NEC 200.6 white conductors cannot be
used as travelers or switch-legs except for romex
installations 3. NEC 314.3 Plastic boxes not permitted.
4. LB type boxes cannot be installed behind drywall. They
must be Accessible 5. Finish window framing in batrhroom
6. Finish vents through roof on plumbing
7. Need water in test on plmb.
8. Need pressure test on water pipes on plmb
9. NEC 250.64E requires bonding of grounding conductors at
both ends when installed in a metal pipe.
E251 02 5/22/09 MR C*ELEC ROUGH IN VRU 001771377
5/22/09 DA NEC 200.7 white conductors cannot be used for hot
conductors
E251 03 5/27/09 MR C*ELEC ROUGH IN VRU 001772441
5/27/09 AP
E257 02 7/21/09 TI C*ELEC OVERHEAD TIME: 17:00 VRU 001796887
7- 2- 1-*~ /7Q- Mt2 T/S: 07/20/2009 08:15 AM JBROCK
PERMIT: CPMC 00 CP MECHANICAL COMMERCIAL
REQUESTED INSP DESCRIPTION
TYP/SQ COMPLETED RESULT RESULTS/COMMENTS
-
M459 01 5/20/09 MR C*MECH ROUGH IN VRU 001770262
5/20/09 AP
M463 01 7/21/09 TI C*MECH OVERHEAD TIME: 17:00 VRU 001796903
7-21-9 T/S: 07/20/2009 08:16 AM JBROCK
PERMIT: CPPC 00 CP PLUMBING COMMERCIAL
REQUESTED INSP DESCRIPTION
TYP/SQ COMPLETED RESULT RESULTS/COMMENTS
P357 01 12/19/08 MR C*PLUMB UNDER SLAB TIME: 17:00 VRU 001719517
12/19/08 AP
- - CONTINUED ONTO NEXT PAGE -
PREPARED 7/20/09, 13:59:34 INSPECTION TICKET PAGE 10
Harnett Countz INSPECTOR: IVR DATE 7/21/09
-----------j - - -
ADDRESS`2495 RAY RD MAIN BLDG SUBDIV:
CONTRACTOR HARNETT COUNTY SCHOOLS PHONE (910) 893-4806
OWNER HCBE-OVERHILLS HIGH-BRICKMASON PHONE (910) 893-8151
PARCEL 01-0513- - -0201- - -
APPL NUMBER: 08-50021009 CP NEW SCHOOLS & EDUCATIONAL
. REQUESTED INSP DESCRIPTION
TYP/SQ COMPLETED RESULT RESULTS/COMMENTS
P351 01 5/20/09 MR C*PLUMB ROUGH IN VRU 001770270
5/20/09 DA
P351 02 5/22/09 MR C*PLUMB ROUGH IN VRU 001771385
5/22/09 AP
P359 01 7/21/09 TI C*PLUMB OVERHEAD TIME: 17:00 VRU 001796911
2•(• D A -MFZ T/S: 07/20/2009 08:16 AM JBROCK
- - COMMENTS AND NOTES -
HARNETT COUNTY
Building Inspections Dept.
108 E. Front St.
Lillington, NC 27546
910-893-7525
DO NOT REMOVE
DATE: 07-21-09
PERMIT # 08-50021009
ADDRESS: 2495 Ray Rd.
VIOLATIONS:
1. Fire rated mechanical penetrations are not installed per drawings
2. Pull back insulation from gas heater flues at roof and install insulation
shields and provide manufacturers specs. on required distance
3. Architect specifies aluminum facing on all exposed insulation(sheet 6-
note 1-C)
If this is a change provide letter
4. Install and wire the water heater
Harnett County Building Department
Mike Rearic cell# (910) 984- 4772
PREPARED 8/03/09, 13:59:31 INSPECTION TICKET PAGE 9
Harnett County INSPECTOR: (IVR DATE 8/04/09
ADDRESS . : 2495 RPOY RD MAIN BLDG SU13DIV:
CONTRACTOR HA$NET7,+ COUNTY SCHOOLS PHONE (910) 893-4808
OWNER HCBE-OVERHILLS HIGH-BRICKMASON PHONE (910) 893-8151
PARCEL 01-0513- - - 0201-
- -
APPL NUMBER: 08-50021009 CP NEW SCHOOLS & EDUCATIONAL
DIRECTIONS : OVERHILLS HIGH SCHOOL
210 SOUTH APPROX 14 MILES THEN RIGHT
ONTO RAY RD OVERBILL HIGH IS 2.5 MILES
ON LEFT.
T/S: 09/29/2DO8 12:56 PM DJOHNSON
STRUCTURE: 000 000 36X76 BRICKMASON CLASSROOM/SHOP BLDG
FLOOD ZONE . . . . : FLOOD ZONE X
PROPOSED USE . . . . . . . : SHOP SEPTIC - EXISTING? . . . . : NA
PERMIT: CPEC 00 CP ELECTRICAL COMMERCIAL
REQUESTED INSP DESCRIPTION
TYP/SQ COMPLETED RESULT RESULTS/COMMENTS
E257 01 12/19/08 MR C*ELEC OVERHEAD TIME: 17:00 VRU 001719715
12/19/08 AP underground
E251 01 5/20/09 MR C*ELEC ROUGH IN VRU 001770254
5/20/09 DA 1. NEC 250.90B bonding bushings are required at meter on
both steel pipes 2. NEC 200.6 white conductors cannot be
used as travelers or switch-legs except for romex
installations 3. NEC 314.3 Plastic boxes not permitted.
4. LB type boxes cannot be installed behind drywall. They
must be Accessible S. Finish window framing in batrhroom
6. Finish vents through roof on plumbing
7. Need water in test on plmb.
8. Need pressure test on water pipes on plmb
9. NEC 250.64E requires bonding of grounding conductors at
both ends when installed in a metal pipe.
E251 02 5/22/09 MR C*ELEC ROUGH IN VRU 001771377
5/22/09 DA NEC 200.7 white conductors cannot be used for hot
conductors
E251 03 5/27/09 MR C*ELEC ROUGH IN VRU 001772441
5/27/09 AP
E257 02 7/21/09 C*ELEC OVERHEAD TIME: 17:00 VRU 001796887
7/21/09 DA T/S: 07/20/2009 06:15 AM JBROCK
T/S: 07/21/2009 02:28 PM MREARIC
water heater over bathroom is not wired
E257 03 8/04/09 TI V/C*ELEC OVERHEAD TIME: 17:00 VRU 001804129
4,9 $ T/S: 08/03/2009 11:32 AM JBROCK
PERMIT: CPMC 00 CP MECHANICAL COMMERCIAL
REQUESTED INSP DESCRIPTION
TYP/SQ COMPLETED RESULT RESULTS/COMMENTS
M459 01 5/20/09 MR C*MECH ROUGH IN VRU 001770262
5/20/09 AP
M463 01 7/21/09 C*MECH OVERHEAD TIME: 17:00 VRU 001796903
7/21/09 DA T/S: 07/20/2009 08:16 AM JBROCK
T/S: 07/21/2009 02:29 PM MREARIC
1. fire damper collars are not instalkled through wall per
plans
CONTINUED ONTO NEXT PAGE
PREPARED 8/03/09, 13:59:31 INSPECTION TICKET PAGE 10
Harnett County INSPECTOR: IVR DATE 8/04/09
- - - - -
ADDRESS . : 2495 RAY RD MAIN BLDG SUBDIV:
CONTRACTOR HARNET-.COUNTY SCHOOLS PHONE (910) 893-4808
OWNER HCB~-OVRHILLS HIGH-BRICKMASON PHONE (910) 893-8151
PARCEL 01-0513- - -0201- - -
APPL NUMBER: 08-50021009 CP NEW SCHOOLS & EDUCATIONAL
- -
REQUESTED INSP DESCRIPTION
TYP/SQ COMPLETED RESULT RESULTS/COMMENTS
2. pull back insulation at flues on heaters and install
insulation shields and provide manuf. specs on installation
M459 02 8/04/09 TI C*MECH ROUGH IN TIME: 17:00 VRU 001804137
8 ,g -9 j P-Mr,, T/S: 08/03/2009 11:32 AM JBROCK
PERMIT: CPPC 00 CP PLUMING COMMERCIAL
REQUESTED INSP DESCRIPTION
TYP/SQ COMPLETED RESULT RESULTS/COMMENTS
P357 01 12/19/08 MR C*PLUMB UNDER SLAB TIME: 17:00 VRU 001719517
12/19/08 AP
P351 01 5/20/09 MR C*PLUMB ROUGH IN VRU 001770270
5/20/09 DA
P351 02 5/22/09 MR C*PLUMB ROUGH IN VRU 001771385
5/22/09 AP
P359 01 7/21/09 C*PLUMB OVERHEAD TIME: 17:00 VRU 001796911
7/21/09 DA T/S: 07/20/2009 08:16 AM JBROCK
T/S: 07/21/2009 02:31 PM MREARIC
install water heater
P359 02 8/04/09 TI JC*PLUMB OVERHEAD TIME: 17:00 VRU 001804152
6,-1,9 ~-.T/S: 08/03/2009 11:32 AM JBROCK
- COMMENTS AND NOTES
PREPARED 8/04/09, 14:22:02 INSPECTION TICKET PAGE 11
Harnett County INSPECTOR: IVR DATE 8/05/09
J
ADDRESS 2495 RAY RD MAIN BLDG SUBDIV:
CONTRACTOR HARNETT COUNTY SCHOOLS PHONE (910) 893-4808
OWNER HCBE-OVERHILLS HIGH-BRICKMASON PHONE (910) 893-8151
PARCEL 01-0513- -0201- - -
APPL NUMBER: 08-50021009 CP NEW SCHOOLS & EDUCATIONAL
DIRECTIONS : OVERHILLS HIGH SCHOOL
210 SOUTH APPROX 14 MILES THEN RIGHT
ONTO RAY RD OVERHILL HIGH IS 2.5 MILES
ON LEFT.
T/S: 09/29/2008 12:56 PM DJOHNSON
STRUCTURE: 000 000 36X76 BRICKMASON CLASSROOM/SHOP BLDG
FLOOD ZONE . . : FLOOD ZONE X
PROPOSED USE . . . . . . . : SHOP SEPTIC - EXISTING? . . . . : NA
PERMIT: CPEC 00 CP ELECTRICAL COMMERCIAL
REQUESTED INSP DESCRIPTION
TYP/SQ COMPLETED RESULT RESULTS/COMMENTS
E257 01 12/19/08 MR C*ELEC OVERHEAD TIME: 17:00 VRU 001719715
12/19/08 AP underground
E251 01 5/20/09 MR C*ELEC ROUGH IN VRU 001770254
5/20/09 DA 1. NEC 250.90B bonding bushings are required at meter on
both steel pipes 2. NEC 200.6 white conductors cannot be
used as travelers or switch-legs except for romex
installations 3. NEC 314.3 Plastic boxes not permitted.
4. LB type boxes cannot be installed behind drywall. They
must be Accessible 5. Finish window framing in batrhroom
6. Finish vents through roof on plumbing
7. Need water in test on plmb.
8. Need pressure test on water pipes on plmb
9. NEC 250.64E requires bonding of grounding conductors at
both ends when installed ina metal pipe.
E251 02 5/22/09 MR C*ELEC ROUGH IN VRU 001771377
5/22/09 DA NEC 200.7 white conductors cannot be used for hot
conductors
E251 03 5/27/09 MR C*ELEC ROUGH IN VRU 001772441
5/27/09 AP
E257 02 7/21/09 MR C*ELEC OVERHEAD TIME: 17:00 VRU 001796887
7/21/09 DA T/S: 07/20/2009 08:15 AM JBROCK
T/S: 07/21/2009 02:28 PM MREARIC
water heater over bathroom is not wired
E257 03 8/04/09 MR C*ELEC OVERHEAD TIME: 17:00 VRU 001804129
8/04/09 AP T/S: 08/03/2009 11:32 AM JBROCK
T/S: 08/04/2009 01:10 PM MREARIC
E267 01 8/05/09 TI_ C*ELEC TEMP SERVICE POLE VRU 001804947
------------------OMMENTS J;r N TES
C ~q lease
kCt)
"~FOPwnyy' ymy°m..'~'4S ~p'nt~-fuT'A'yy4ri~ V3+:sP..,v.~,l'fi5~' A.P}+311'~:~J".t`~y,ayw'+n'qr~`y'KY"°f4~i'm"1~Z'•9.°41"}'Msnryi.'"h5C4*' ~n~%.~.'.•i.yr.vu . ~r"v'kN"hh•NY'a`v'^~.`P~~"
EXPIRL DATE O T 5110
TEMPORARY POWER
CERTIFICATE
JOB NAME QIlerL)tS 9f* Sclool " rLeW I~r;~kvuasok ~l~ol
OWNER ADDRESS PHONE /
LOCATION f SY
The power company shall not be required to
terminate electric service supplied to the premises described above on or after
the expiration date specified in this certificate, unless and until it is notified in,
writing by the Harnett County Electrical Inspector to do so.
s
I the undersigned understand that this certificate is for Temporary Power only
and that a final inspection is required before permanent power will be approved.
I; shall also comply with any special requirement requested by the Harnett
County Inspection Department.
J1~1nn//,, ss.
Date
Owner or Authorized Signature
This certificate issued pursuant to the requirements of Section 105 of the North
Carolina State Building Code certifying at the time of issuance this structure was
in temporary compliance with the various ordinances of the County of Harnett
regulating building construction or use.
~A-
Date
Building Official
PREPARED 8/11/09, 14:51:16 INSPECTION TICKET PAGE 1
Harnett County INSPECTOR: IVR DATE 8/12/09
ADDRESS- 2495 RAY RD MAIN BLDG SUBDIV:
CONTRACTOR HARNETT COUNTY SCHOOLS PHONE (910) 893-4808
OWNER HCBE-OVERHILLS HIGH-BRICKMASON PHONE (910) 893-8151
PARCEL 01-0513- - -0201- - -
APPL NUMBER: 08-50021009 CP NEW SCHOOLS & EDUCATIONAL
DIRECTIONS : OVERHILLS HIGH SCHOOL
210 SOUTH APPROX 14 MILES THEN RIGHT
ONTO RAY RD OVERBILL HIGH IS 2.5 MILES
ON LEFT.
T/S: 09/29/2008 12:56 PM DJOHNSON
STRUCTURE: 000 000 36X76 BRICXMASON CLASSROOM/SHOP BLDG
FLOOD ZONE . . . . : FLOOD ZONE X
PROPOSED USE . . . . . . . : SHOP SEPTIC - EXISTING? . . . . : NA
PERMIT: CBCO 00 CP BUILDING COMMERCIAL
REQUESTED INSP DESCRIPTION
TYP/SQ COMPLETED RESULT RESULTS/COMMENTS
- -
C155 01 12/23/08 JH C*BLDG FOUNDATION VRU 001720523
12/23/08 DA not ready for inspection
C159 01 12/30/08 JH C*BLDG SLAB INSP VRU 001721281
12/30/08 AP
C153 01 5/20/09 MR C*BLDG ROUGH IN VRU 001770247
5/20/09 DA 1. NEC 250.90B bonding bushings are required at meter on
both steel pipes 2. NEC 200.6 white conductors cannot be
used as travelers or switch-legs except for romex
installations 3. NEC 314.3 Plastic boxes not permitted.
4. LB type boxes cannot be installed behind drywall. They
must be Accessible 5. Finish window framing in batrhroom
6. Finish vents through roof on plumbing
7. Need water in test on plmb.
C153 02 5/22/09 MR C*BLDG ROUGH IN VRU 001771369
5/22/09 AP
F854 01 8/11/09 JB FM*FINAL INSPECTION TIME: 17:00 VRU 001807775
8/11/09 AP T/S: 08/11/2009 01:59 PM JBROCK
INSPECTION BY DAVE W/ FM
T/S: 08/11/2009 02:00 PM JBROCK
C179 01 8/12/09 TI C*BLDG FINAL TIME: 17:00 VRU 001807841
pia ~q T/S: 08/11/2009 02:50 PM NTART
PERMIT: CPEC 00 CP ELECTRICAL COMMERCIAL
REQUESTED INSP DESCRIPTION
TYP/SQ COMPLETED RESULT RESULTS/COMMENTS
-
E257 01 12/19/08 MR C*ELEC OVERHEAD TIME: 17:00 VRU 001719715
12/19/08 AP underground
E251 01 5/20/09 MR C*ELEC ROUGH IN VRU 001770254
5/20/09 DA 1. NEC 250.908 bonding bushings are required at meter on
both steel pipes 2. NEC 200.6 white conductors cannot be
used as travelers or switch-legs except for romex
installations 3. NEC 314.3 Plastic boxes not permitted.
4. LB type boxes cannot be installed behind drywall. They
must be Accessible 5. Finish window framing in batrhroom
6. Finish vents through roof on plumbing
- - CONTINUED ONTO NEXT PAGE
PREPARED 8/11/09, 14:51:16 INSPECTION TICKET PAGE 2
Harnett County INSPECTOR: IVR DATE 8/12/09
ADDRESS- . :,495 RAY RD MAIN BLDG SUBDIV:
CONTRACTOR HARNETT COUNTY SCHOOLS PHONE (910) 893-4808
OWNER HCBE-OVERHILLS HIGH-BRICKMASON PHONE (910) 893-8151
PARCEL 01-0513- - -0201- - -
APPL NUMBER: 08-50021009 CP NEW SCHOOLS & EDUCATIONAL
REQUESTED INSP DESCRIPTION
TYP/SQ COMPLETED RESULT RESULTS/COMMENTS
7. Need water in test on plmb.
8. Need pressure test on water pipes on plmb
9. NEC 250.64E requires bonding of grounding conductors at
both ends when installed in a metal pipe.
E251 02 5/22/09 MR C*ELEC ROUGH IN VRU 001771377
5/22/09 DA NEC 200.7 white conductors cannot be used for hot
conductors
E251 03 5/27/09 MR C*ELEC ROUGH IN VRU 001772441
5/27/09 AP
E257 02 7/21/09 MR C*ELEC OVERHEAD TIME: 17:00 VRU 001796887
7/21/09 DA T/S: 07/20/2009 08:15 AM JBROCK
T/S: 07/21/2009 02:28 PM MREARIC
water heater over bathroom is not wired
E257 03 8/04/09 MR C*ELEC OVERHEAD TIME: 17:00 VRU 001804129
8/04/09 AP T/S: 08/03/2009 11:32 AM JBROCK
T/S: 08/04/2009 01:10 PM MREARIC
E267 01 8/05/09 MR C*ELEC TEMP SERVICE POLE VRU #c 001604947
8/05/09 AP T/S: 08/05/2009 11:12 AM MREARIC
temporary electrical final
E265 01 8/12/09 TI_ C*ELEC FINAL TIME: 17:00 VRU 001807874
- :~f~ T/S: 08/11/2009 02:50 PM NTART
PERMIT: CPMC 00 CP MECHANICAL COMMERCIAL
REQUESTED INSP DESCRIPTION
TYP/SQ COMPLETED RESULT RESULTS/COMMENTS
- - -
M459 01 5/20/09 MR C*MECH ROUGH IN VRU 001770262
5/20/09 AP
M463 01 7/21/09 MR C*MECH OVERHEAD TIME: 17:00 VRU 001796903
7/21/09 DA T/S: 07/20/2009 08:16 AM JBROCK
T/S: 07/21/2009 02:29 PM MREARIC
1. fire damper collars are not instalkled through wall per
plans
2. pull back insulation at flues on heaters and install
insulation shields and provide manuf. specs on installation
M459 02 8/04/09 MR C*MECH ROUGH IN TIME: 17:00 VRU 001804137
8/04/09 AP T/S: 08/03/2009 11:32 AM JBROCK
T/S: 08/04/2009 01:10 PM MREARIC
M465 01 8/G lz/o9 C*MECH FINAL TIME: 17:00 VRU 001807882
T/S: 06/11/2009 02:50 PM NTART
PERMIT: CPPC 00 CP PLUMBING COMMERCIAL
REQUESTED INSP DESCRIPTION
TYP/SQ COMPLETED RESULT RESULTS/COMMENTS
-
P357 01 12/19/08 MR C*PLUMB UNDER SLAB TIME: 17:00 VRU 001719517
12/19/08 AP
CONTINUED ONTO NEXT PAGE - -
PREPARED 8/11/09, 14:51:16 INSPECTION TICKET PAGE 3
Harnett County INSPECTOR: IVR DATE 8/12/09
- - -
ADDRESS- . :•2495 RAY RD MAIN BLDG SUBDIV:
CONTRACTOR HARNETT COUNTY SCHOOLS PHONE (910) 893-4808
OWNER HCBE-OVERHILLS HIGH-BRICKMASON PHONE (910) 893-6151
PARCEL 01-0513- - -0201- - -
APPL NUMBER: 08-50021009 CP NEW SCHOOLS & EDUCATIONAL
- - - - -
REQUESTED INSP DESCRIPTION
TYP/SQ COMPLETED RESULT RESULTS/COMMENTS
-
P351 01 5/20/09 MR C*PLUMB ROUGH IN VRU 001770270
5/20/09 DA
P351 02 5/22/09 MR C*PLUMB ROUGH IN VRU 001771385
5/22/09 AP
P359 01 7/21/09 MR C*PLUMB OVERHEAD TIME: 17:00 VRU 001796911
7/21/09 DA T/S: 07/20/2009 08:16 AM JBROCK
T/S: 07/21/2009 02:31 PM MREARIC
install water heater
P359 02 8/04/09 MR C*PLUMB OVERHEAD TIME: 17:00 VRU 001804152
8/04/09 AP T/S: 06/03/2009 11:32 AM JBROCK
T/S: 08/04/2009 01:10 PM MREARIC
P361 01 8/12/09 T C*PLUMB FINAL TIME: 17 VRU 001807890
" T/S: 08/11/2009 02:50 PM NTART
COMMENTS AND NOTES -
Off
~.a+P } P M E 1 o t fir,, k n k
COUNTY OF HARNETT fJ
DEPARTMENT OF BUILDING INSPECTION
AND PLANNING/DEVELOPMENT
CERTIFICATE OF OCCUPANCY
l a This certificate issued pursuant to the requirements of Section 105 of the North Carolina State Building
Code and the Harnett County Zoning Ordinance certifies at the time of issuance this structure was in,
compliance with the various ordinances of the County of Harnett regulating development and building
J
construction or use. For the following:
1 ,1711\
Use Classification: 1U('4 1 o /kq PERMIT NUMBERS
! Owner: Building Permit No.: FJ
911 Address: 1 Electrical Permit No.:
a
Insulation Permit No.:
Plumbing Permit No.: I I 30 0,/OO
State: Zip Code: Mech. Permit No.: Y;>Q- Ic,,
Dater - Y MFG. Home:
- 111f
u
p,,Building) icial x ate
,I