PU-SR-03
PUBLIC UTILITIES STAFF REPORT
Harnett County, North Carolina
Planning Department
108 E. Front Street, Lillington, NC 27546
Phone: (910) 893-7525 Fax: (910) 893-2793
Development Name: Keith Hills West Tract J – Preliminary
Property Description
PIN(s): 0579-19-1768.000 Acreage: 23.12 acres
Address/SR No.: Keith Hills Road (Private 60’ ROW)
Water
Public water is available for this development (via Campbell University & Harnett County)
Water capacity is available for this development
Nearest water line location (Road name & SR#): Keith Hills Road
Nearest water line size: 6”
Fire flow is available for this development
Lines permitted under DENR Permit: (DEH Serial Number)
Sewer
Public sewer is available for this development (via Campbell University & Harnett County)
Sewer capacity is available for this development
Nearest sewer line location (Road name & SR#): Keith Hills Road
Nearest sewer line size: 8”
Lines permitted under DENR Permit: (DWQ Serial Number)
Additional Requirements
As-Built Record Drawings Yes No N/A
Cost Statement for water improvements Yes No N/A
Cost Statement for sewer improvements Yes No N/A
Professional Engineer’s Certifications for water/sewer extension Yes No
N/A
Final Plat & As-Built Record Drawings are identical Yes No N/A
DOT Encroachment Agreement Yes No N/A
Distance to nearest water/sewer lines noted (Site Plan Only) Yes No N/A
Master Plan submitted for additional phases if intended Yes No N/A
Ballot
REVIEWER: Tim Payseur Date: April 29, 2008
VOTE: Conditionally Approve
CONDITIONS:
SHORT TERM:
The lot numbers are not consecutively numbered which has changed from the previous plat
submitted to the DRB.
The fire hydrant legs should not be located under the pavement. Once fire hydrant locations
are approved by the Fire Marshal then adjust the water line accordingly to avoid this situation.
Water lines should be located on the right side of the street as viewed when entering the
subdivision.
To provide consistency between phases, identify the adjoining tracts or phases on the plat or at
least label the phases or tracts at the end of stub roads leading to those respective phases or
tracts.
Page 1 of 2 PUBLIC UTILITIES STAFF REPORT
LONG RANGE:
Please visit www.harnett.org/utilities for more information on the approval process.
The developer’s engineer must provide utility plans, and engineers report, project specifications
along with the NCDENR applications to HCDPU for review and approval. No construction may
begin on the water and sewer lines without the required NCDENR permits and approval from
HCDPU.
The water and sewer lines for the existing Keith Hills subdivision currently belong to Campbell
University. Campbell University is planning to sell or give these utilities to Harnett County in
the near future. Permitting for the proposed water and sewer lines will need to be approved by
HCDPU, Campbell University and NCDENR at this time. HCDPU will be the permittee once the
transfer of the existing utilities have been turned over to Harnett County.
Harnett County Dept of Public Utilities (HCDPU) must be provided a twenty (20’) feet wide
easement for each water and sewer line once the project construction is completed and
approved by HCDPU Campbell University and NCDENR.
Three gate valves will be required at each tee where the water lines are looped and water can
flow in different directions. Add gate valves as necessary to allow HCDPU to isolate main lines
for repairs so that no more than 20 customers would be shut off at any given time due to line
repairs.
Water lines should be three (3’) feet to five (5’) feet off the edge of pavement including around
cul-de-sacs. Adjust water line layout around the cul-de-sac at then end of Rhyne Lane and
terminate the water main with a two (2”) inch blow off assembly.
Page 2 of 2 PUBLIC UTILITIES STAFF REPORT