Loading...
FM-SR-01 In lieu of hydrants, it is recommended that a NFPA 13-D residential sprinkler system be  installed in the residences that could receive its water form the domestic tap off the 4" line. LONGE RANGE:  Page 2 of 2FIRE MARSHAL STAFF REPORT FIRE MARSHAL STAFF REPORT Harnett County, North Carolina Planning Department 108 E. Front Street, Lillington, NC 27546 Phone: (910) 893-7525 Fax: (910) 893-2793 Development Name: Cinnamon Hill Property Description PIN(s): 9691-48-6636 Acreage: 8.56 acres Address/SR No.: Lawrence Road Fire District: Boone Trail HTE No: Emergency Access & Circulation Multiple Ingress/Egress Points: Yes No *It is highly recommended that subdivisions have multiple points Ingress/Egress Points are Acceptable Comments: Vertical Clearance is Acceptable *Minimum height of thirteen and one-half feet (13’ 6”) Comments: Existing Road Width is Acceptable * Minimum road width of twenty feet (20’) Comments: Security Gates are Acceptable Comments: None Shown Cul-de-sac Turning Radius is Acceptable Comments: Fire Apparatus Access Roads are Acceptable Comments: Fire Protection & Hydrants Fire Hydrant location indicated on Preliminary Plan: Yes No The water line size of 4" is Acceptable *Fire hydrants must be located off of a minimum 6” water line Fire Hydrant Locations are Acceptable *A 20’ All-Weather Proof Drive may need to be installed to provide adequate Fire Protection Sprinkler System N/A Comments: In lieu of hydrants, it is recommended that a NFPA 13-D residential sprinkler system be installed in the residences that could receive its water from the domestic tap off the 4" line. Ballot REVIEWER: Michael Martin Date: 10/15/08 VOTE: Approve CONDITIONS: SHORT TERM: Page 1 of 2FIRE MARSHAL STAFF REPORT