FM REVIEW (2) Fire Marshal Division April 19, 2008 Classic Customs & Collision 303 E. Cornelius Harnett Blvd Lillington, NC 27546 Mike Edwards 115 Bestwood Drive Clayton, NC 27520 Application Number 08-50019314 Mr. Edwards, Thank you for submitting the plans for the Classic Customs Collision. The plans have been carefully reviewed by a qualified code enforcement official to examine for full compliance with the North Carolina Fire Prevention Code and all other fire protection regulatory documents. There are some items that were found during the plan review process that need to be addressed before a final inspection of the new facility can be given. These items are outlined and described below. ? 1504.6.2 Automated spray application operations. Where protecting automated spray application operations, automatic fire- o extinguishing systems shall be equipped with an approved interlock feature that will, upon discharge of the system, automatically stop the operation of spraying operations and work piece conveyors into and out of the spraying area. Where the building is equipped with a fire alarm system, discharge of the automatic fire-extinguishing system shall also activate the building alarm notification appliances. ? 1504.2.1 Operation. Mechanical ventilation shall be kept in operation at all times while o spraying operations are being conducted and for a sufficient time thereafter to allow vapors from drying coated articles and finishing Spraying equipment shall be material residue to be exhausted. interlocked with the ventilation of the spraying area such that spraying operations cannot be conducted unless the ventilation system is in operation ? 904.3.2 Actuation. Automatic fire-extinguishing systems shall be automatically actuated o and provided with a manual means of actuation in accordance with Section 904.11.1. ? 904.4.1 Inspection. ? Prior to conducting final acceptance tests, the following items shall be inspected: ? Hazard specification for consistency with design hazard. ? Type, location and spacing of automatic- and manual- initiating devices. ? Size, placement and position of nozzles or discharge orifices. ? Location and identification of audible and visible alarm devices. ? Identification of devices with proper designations. ? Operating instructions. Thank you again for submitting the plans for the Classic Customs & Collision. Please review the plans and adhere to any notes and alterations that were made in addition to the original drawings. These remarks are for the plans that were submitted and its original intent. These remarks do not apply if the original intent changes or what was submitted on the above date changes. If you have any questions, please do not hesitate to call this office. Again, thank you and we look forward to working with you during the construction period! Sincerely, T.J. McLamb, CFI Chief Deputy Fire Marshal Plan Review, Inspection and Permit Fees 08-50019314 Application Number $100.00 Explosive Materials (90 Days) $35.00 Explosive Materials (48 Hrs) $25.00 Fireworks Public Display $ 20.00 Final Inspection $ 25.00 Fire Alarm Testing $ 25.00 Fixed Fire Suppression $ 10.00 Insecticide Fog/Fumigation $ 50.00 Testing of Pipes/UST/AGST 2 $ 50.00 Plans up to 5000 ft 22 $100.00 Plans 5001 ft to 10,000 ft 22 $150.00 Plans 10,001 ft to 25,000 ft 2 $250.00 Plans 25,001 ft and over $ 25.00 Sprinkler Certification Test $ 25.00 Standpipe Testing $ 25.00 Special Assembly $ 10.00 Temporary Kiosks/Displays 2 $ 10.00 Tents greater than 700 ft $ 50.00 Tank Installation (charge for each tank) $ 50.00 Tank Removal (charge for each tank) $ 25.00 Total Teddy Joe Mclamb 04/17/08 Code Enforcement Official Date Ø¿®²»¬¬ ݱ«²¬§ Office of the Fire Marshal P.O. Box 370 Lillington, N.C. 27546 (910)-893-7580 л®³·¬ Ý»®¬·º·½¿¬» Business Name: Classic Customs & Collions Address: 303 E CORNELIUS HARNETT BLVD LILLINGTON, NC 27546 OFFC 910-893-3680 Phone: The following permit has been issued:Permit No. 2008024 Type: 047 Fixed Fire Suppression 04/17/2008 Issued Date: 04/17/2008 Effective Date: Expiration Date: 07/17/2008 ̸·­ °»®³·¬ ½»®¬·º·½¿¬» ¸¿­ ¾»»² ·­­«»¼ º±® Å Ã ½±²­¬®«½¬·±² ñ Å Ã ±°»®¿¬·±²¿´ °«®°±­»­ ´±½¿¬»¼ ¿¬ ¬¸» ¿¾±ª» ¾«­·²»­­ ´±½¿¬·±²ò ̸·­ °»®³·¬ ¸¿­ ¾»»² ·­­«»¼ ¿²¼ ©·´´ ¾» »²º±®½»¼ ·² ¿½½±®¼¿²½» ©·¬¸ ­»½¬·±² ïðë ±º ¬¸» ÒòÝò ͬ¿¬» Ú·®» Ю»ª»²¬·±² ݱ¼»ò д»¿­» ½±²¬¿½¬ ±«® ±ºº·½» º±® ¿²§ º«®¬¸»® ¯«»­¬·±²­ ®»¹¿®¼·²¹ ¬¸·­ °»®³·¬ò Inspector:Date Teddy Joe McLamb 1 Page 04/17/2008