HomeMy WebLinkAbout13499 Install SetFIRST FLOOR
SECOND FLOOR
FACP
NFW2-100
AA
AB
ELECTRICAL
AA
AB
FSDR
EOL AB
DEDICATED
12VAC
GUTTER
AA
SD DD R AA
EOL AB
FAAP
F0.0 FIRE ALARM TITLE PAGE & RISERDRAWING NO 1 OF 3
A / O AUDIO / ONLY
A / V AUDIO / VISUAL
ADA AMERICANS WITH DISABILITES ACT
ADJ ADJACENT
AFF ABOVE FINISHED FLOOR
AHU AIR HANDLING UNIT
ALT ALTERNATIVE
ANNUN ANNUNCIATOR
APPROX APPROXIMATE
ARCH ARCHITECT
BLDG BUILDING
BTM BOTTOM
CCTV CLOSED CIRCUIT TELEVISION
â„„CENTER LINE
CLG CEILING
CM CONTROL MODULE
CONN CONNECTION
CONST CONSTRUCTION
CONT CONTINUOUS
COORD COORDINATE
CTL CONTROL
DC DOOR CONTACT
DD DUCT DETECTOR
DEMO DEMOLITION
DH DOOR HOLDER
DWG DRAWING
EA EACH
EC ELECTRICAL CONTRACTOR
ELEC ELECTRICAL
ELEV ELEVATOR
ENGR ENGINEER
EQ EQUAL
ES EACH SIDE
EW EACH WAY
EXIST EXISTING
EXT EXTERIOR
FAAP FIRE ALARM ANNUNCIATOR PANEL
FACP FIRE ALARM CONTROL PANEL
FAEP FIRE ALARM EVACUATION PANEL
FE FIRE EXTINGUISHER
FLR FLOOR
FP FIRE PROTECTION
FT FOOT / FEET
GA GAGE
GC GENERAL CONTRACTOR
HD HEAT DETECTOR
HORIZ HORIZONTAL
HR HOUR
HT HEIGHT
HVAC HEATING, VENTILATING AND AIR CONDITIONING
INFO INFORMATION
INSUL INSULATION
INT INTERIOR
LOC LOCATED / LOCATION
MAX MAXIMUM
MC MECHANICAL CONTRACTOR
MD MOTION DETECTOR
MFR MANUFACTURER
MIN MINIMUM
MISC MISCELANEOUS
MM MONITOR MODULE
MS MOTION SENSOR
N / A NOT APPLICABLE
NAC NOTIFICATION APPLIANCE CIRCUIT
NFPA NATIONAL FIRE PROTECTION ASSOCIATION
NIC NOT IN CONTRACT
NTS NOT TO SCALE
OPP OPPOSITE
PNL PANEL
REQ'D REQUIRED
REV REVISE / REVISION
RM ROOM
RTU ROOF TOP UNIT
SCHED SCHEDULE
SD SMOKE DETECTOR
SHT SHEET
SIM SIMILAR
SLC SIGNALING LINE CIRCUITS
SPECS SPECIFICATIONS
SPKR SPEAKER
TEMP TEMPORARY
TV TELEVISION
TYP TYPICAL
UNO UNLESS NOTED OTHERWISE
V / O VISUAL ONLY
VERT VERTICAL
VIF VERIFY IN FIELD
WG WIRE GUARD
WP WEATHER PROOF
W /WITH
W / O WITH OUT
&AND
@ AT
F0.0 FIRE ALARM TITLE SHEET & RISER
F0.1 FIRE ALARM DETAILS
F1.0 FIRE ALARM PLAN
DEVICE LEGEND
SYMBOL DESCRIPTION
DEVICE LEGEND NOTES:
1.SEE DETAIL 1/F0.1 FOR TYPICAL MOUNTING HEIGHTS.
2.SEE F0.1 FOR STANDARD WIRING & INSTALLATION DETAILS.
3.ALL VISUAL NOTIFICATION DEVICES SHALL HAVE A 15 CANDELA RATING UNLESS SHOWN
OTHERWISE ON PLANS (i.e. 30cd, 75cd, etc...).
4."XX" SHOWN ON NOTIFICATION APPLIANCES NOTATES NAC CIRCUIT, SEE WIRE LEGEND
FOR LIST OF CIRCUITS.
FACP
SD
F
XX
M T,F,P
J
FAAP
HD
DD
A V
V
FIRE ALARM CONTROL PANEL
SMOKE DETECTOR
HEAT DETECTOR
DUCT DETECTOR
PULL STATION
AUDIO / VISUAL INDICATING DEVICE - WALL MOUNT
VISUAL ONLY INDICATING DEVICE - WALL MOUNT
MONITOR MODULE (T = TAMPER, F = FLOW, P = PRESSURE)
FIRE ALARM ANNUNCIATOR PANEL
AUDIO / VISUAL INDICATING DEVICE - CEILING MOUNT
VISUAL ONLY INDICATING DEVICE - CEILING MOUNT
JUNCTION BOX (HORIZONTAL WIRING)
RELAY MODULE
REMOTE INDICATOR WITH TEST STATION (KEYED) FOR DUCT DETECTORT
XX
XX
XX
C CONTROL MODULE
R
DH
NAC FIRE ALARM REMOTE POWER SUPPLY PANEL
DOOR HOLDER
J JUNCTION BOX (VERTICAL WIRING / RISER)
END OF LINE (EOL) RESISTOR
I ISOLATION MODULE
REPRESENTS WIRE OR CIRCUIT COMING "IN"
REPRESENTS WIRE OR CIRCUIT GOING "OUT"
REMOTE INDICATOR FOR DUCT DETECTORIDISPLAY MESSAGE ON FACP LCDACTIVATE ALL HORN/STROBE DEVICESACTIVATE TROUBLE SIGNAL ON THE FACPACTIVATE ALARM SIGNAL ON THE FACPACTIVATE HVAC SHUTDOWNMANUAL PULL STATION1
2
3
4
5
6
7
8
9
10
SMOKE DETECTOR
HEAT DETECTOR
OPEN CIRCUIT SLC/IDC (TROUBLE)
OPEN CIRCUIT - NAC (TROUBLE)
GROUND FAULT (TROUBLE)
WIRE TO WIRE SHORT (TROUBLE)
REMOVAL OF DEVICE (TROUBLE)
FACP TROUBLE
LOSS OF FIRE ALARM SYSTEM 120V OPERATING POWER
A B C D ESYSTEM INPUTS SYSTEM OUTPUTSOPERATING SEQUENCE MATRIX
11
12
13
SPRINKLER TAMPER
DUCT SMOKE DETECTOR
SPRINKLER WATER FLOW ACTIVATE SUPERVISORY SIGNAL ON THE FACPF
Th e In t e g rat i o n o f Tec h n o l o g y an d Li fe Safet y
Fire, Security & Communications
A Subsidiary of TriTek Fire & Security, LLC
FACP NFW2-100
PANEL SCHEDULE
PANEL DESCRIPTION LOCATION
FAAP N-ANN-80
ELEC/DATA 105
LOBBY 108
ABBREVIATIONS
DRAWING INDEX
TRITEK PROJECT TEAM
FIRE ALARM RISER DIAGRAM
FIRE ALARM SYSTEM PROTECTION FIRE ALARM DRAWING NOTES
OPERATION SEQUENCE MATRIX SCHEDULES LEGENDS
DATE
ES
CHECKED BY:
JA
DRAWN BY:CCCC AUTO RESTORATION220 OLIVE FARM DRIVESANFORD, NORTH CAROLINA 27332PROJECT NUMBER:TheIntegrationofTechnologyandLifeSafetyFire, Security & CommunicationsA Subsidiary of TriTek Fire & Security, LLCREVISIONNO.BYDATEFOR CONSTRUCTIONCURRENT PHASE:SUBMITTALROUGH-ININSTALLPROGRAMMINGPUNCH LISTAS BUILTINSPECTIONPRINTED:TECHNICIAN:RETURNED:XX/XX/XXXX/XX/XXXX02-12-18
13499
SECTION A.10.4.4 OF THE NATIONAL FIRE ALARM CODE HANDBOOK STATES THAT
SMOKE DETECTION SHALL BE PROVIDED AT THE LOCATION OF EACH FACP, NAC AND
SUPERVISING STATION TRANSMITTING EQUIPMENT TO PROVIDE NOTIFICATION OF
FIRE AT THAT LOCATION.
·EXCEPTION #1: WHERE AMBIENT CONDITIONS PROHIBIT INSTALLATION
OF AUTOMATIC SMOKE DETECTION, AUTOMATIC HEAT DETECTORS
SHALL BE PERMITTED.
SMOKE DETECTOR INSTALLATION LOCATION:
SECTION A.17.4.10 STIPULATES:
·WHERE THE CEILING IS 15ft IN HEIGHT OR LESS, THE SMOKE DETECTOR
SHOULD BE LOCATED ON THE CEILING OR THE WALL WITHIN 21ft OF THE
CENTERLINE OF THE FIRE ALARM CONTROL UNIT BEING PROTECTED BY
THE DETECTOR IN ACCORDANCE WITH 17.3.2.1
·WHERE THE CEILING EXCEEDS 15ft IN HEIGHT, THE AUTOMATIC SMOKE
DETECTOR SHOULD BE INSTALLED ON THE WALL ABOVE AND WITHIN
60in FROM THE TOP OF THE CONTROL UNIT.
FACP 1
BACKBOX SCHEDULE
DEVICE TYPE PART #QTY.BACKBOX
BACKBOX NOTES:
= PROVIDE PLASTER RING
= PROVIDE WITH EXTENSION OR 218" BOX***
MOUNT
NFW2-100 INCLUDED
FAAP 1N-ANN-80
HORN/STROBE 12GEC3-24WR 4"x4"x112"
STROBE 6GES3-24WR
SMOKE DETECTOR 6NP-100 3.5" OCTAGON
PULL STATION 6NOT-BG12LX SINGLE GANG
4"x4"x112"
SURFACE
SURFACE
WALL
WALL
SURFACE
SURFACE
INDICATOR LIGHT 2RA-100Z
INCLUDED
SINGLE GANG
RELAY MODULE 3NC-100R 4"x4"x112"SURFACE **
VA AA
VA 75CD
AA
V AA
V AA
EOLAA
1AA 1AA
2AA (TYP BRANCH CIRCUIT)2AA
2AA
1AA
MAIN TRUNK LINE FROM
FACP OR NAC PANEL
WIRE LEGEND
LABEL DESCRIPTION PANEL LOCATION
A 18-02 UNS SOL FPLR (SLC)FACP 1ST FLOOR
B 2#14 THHN, Solid (24VDC)FAAP 1ST FLOOR
C #18-02 Shielded, FPLR, Solid FAAP 1ST FLOOR
D #18-02 UNS SOL FPLR duct det.SEE PLAN
AA (2) #14 THHN, Solid 1ST FLOOR
AB 1ST FLOOR(2) #14 THHN, Solid
FACP
FACP
SYSTEM DESIGNER
EDDIE STEVENS (NICET 4 - #98485)
SALES PERSON
JIMMY RUSS
FIRE ALARM DRAWING NOTES:
1.ALL FIRE ALARM SYSTEMS SHALL BE INSTALLED IN ACCORDANCE WITH
APPLICABLE PROVISIONS OF NFPA, FIRE CODE, BUILDING CODE AND ANSI
STANDARDS.
2.ALL CONDUIT TO BE 34" EMT UNLESS NOTED OTHERWISE.
3.FIRE ALARM DEVICES AND MASS NOTIFICATION ALERT DEVICES SHALL BE
SYNCHRONIZED.
4.PRIOR TO PROGRAMMING AND ROUGH-IN, COORDINATE ROOM NUMBERS WITH
OWNER AND ARCHITECT.
5.VOLTAGE DROP CALCULATIONS ARE BASED ON CONDUIT LOCATIONS SHOWN ON
FIRE ALARM DRAWINGS. FINAL CONDUIT LOCATIONS TO BE PROVIDED BY
ELECTRICAL CONTRACTOR.
6.JUNCTION BOXES NOT SHOWN FOR CLARITY. JUNCTION BOX LOCATIONS TO BE
PROVIDED BY THE ELECTRICAL CONTRACTOR.
7.FIRE ALARM SYSTEM TO BE CLASS 'B' SUPERVISED SYSTEM (STYLE 'B' INITIATING
DEVICE CIRCUITS, STYLE 4 SIGNALING LINE CIRCUITS, CLASS 'B' NOTIFICATION
APPLIANCE CIRCUITS). FURNISH & INSTALL END-OF-LINE (EOL) RESISTORS WHERE
SHOWN ON PLANS.
8.ALL WIRING SHALL BE RUN IN WALLS AND ABOVE CEILING IN METAL RACEWAYS.
RACEWAYS SHALL BE RUN CONCEALED WHERE PRACTICAL.
9.SMOKE DETECTORS SHALL BE LOCATED AS NEAR THE CENTER OF THE ROOM AS
PRACTICAL. DO NOT LOCATE ANY DETECTOR WITHIN 3'-0" OF AN HVAC SUPPLY
GRILLE. PROVIDE AUXILIARY CONTACT ON SMOKE DETECTORS LOCATED IN
CORRIDORS AT SMOKE DOORS. WIRE MAGNETIC DOOR HOLDERS THRU
AUXILIARY CONTACT TO RELEASE DOOR WHEN THOSE DETECTORS ARE
ACTUATED.
10.DUCT DETECTORS SHALL BE TURNED OVER TO MECHANICAL CONTRACTOR FOR
INSTALLATION. CONTROL WIRING WILL BE BY THE MECHANICAL CONTRACTOR.
PROVIDE AUXILIARY CONTACT ON EACH DUCT DETECTOR FOR DIVISION 23 USE. A
RELAY MODULE AND REMOTE TEST STATION MAY NOT BE DISPLAYED ON PLANS
FOR CLARITY. REFER TO DETAIL 3/F0.1 FOR INFORMATION.
11.LOCATE MANUAL PULL STATIONS WITHIN 5'-0" OF THE EXIT DOOR PER NFPA AND
IBC REQUIREMENTS. PROVIDE ANY SPECIAL ADAPTER PLATES OR COVER PLATES
REQ'D TO MOUNT PULL STATIONS IN DOOR MULLIONS WHERE APPLICABLE.
12.EACH HORN / STROBE LOCATED AT THE END OF A CORRIDOR MUST BE WITHIN
15'-0" OF THE END WALL PER NFPA 72. HORN / STROBES IN CLASSROOMS AND
OFFICES MUST BE ROUGHLY CENTERED ON WALL PER NFPA 72. DO NOT ADJUST
THE LOCATIONS OF ANY HORN / STROBES WITHOUT CONSULTING THE ENGINEER
AND OBTAINING WRITTEN PERMISSION.
13.FIELD VERIFY LOCATION OF FIRE ALARM CONTROL PANEL "FACP" AND FIRE ALARM
ANNUNCIATOR PANELS "FAAP" WITH OWNER AND AUTHORITY HAVING
JURISDICTION PRIOR TO ROUGH-IN.
14.LETTERS "I" AND "O" ARE NOT USED IN SCHEDULES DUE TO CONFLICTS WITH
NUMBERS THAT LOOK SIMILAR.
15.ALL NOTIFICATION APPLIANCES ARE SUPERVISED, THEREFORE REQUIRING A FULL
CIRCUIT BETWEEN DEVICES UP UNTIL THE LAST DEVICE WHERE THE END OF LINE
RESISTER IS GENERALLY LOCATED. WIRE PATHS THAT ARE BRANCHED OFF FROM
THE MAIN TRUNK LINE AND ARE NOT LABELED WITH A CIRCUIT TAG ARE ASSUMED
TO HAVE (2) PAIRS OF WIRE IN THE WIRE PATH. SEE EXAMPLE BELOW: (SYMBOLS
SHOWN ON EXAMPLE MAY NOT REFLECT EXACT SYMBOLS SHOWN ON PLANS).
60" TO TOP60" TO CENTER OF DISPLAY PANEL80" TO BOTTOM48" TO TOP MAX4" MIN
FIRE
PUSH INPULL DOWN
SEE NOTE 5PULL STATION HORN, CHIME
OR STROBE
FIRE ALARM
ANNUNCIATOR
PANEL (FAAP)
FIRE ALARM CONTROL
PANEL
(FACP)
SMOKE DETECTOR
AT CORNER6" MINDETECTORS
BETWEEN BEAMS12'-0" MAX12" MAX1/2 S S S 1/2 S
3'-0"3'-0"
S = SPACE BETWEEN DETECTORS
3
3'-0" MIN
DIFFUSER
(SUPPLY OR
RETURN)
S S
S = SPACE BETWEEN DETECTORS
SMOKE DETECTOR
ON SLOPED CEILING (PEAKED)
SMOKE DETECTOR
ON SLOPED CEILING (SHED)
SMOKE DETECTOR
ADJACENT TO DIFFUSER
1 2
1
KEYED NOTE SCHEDULE
MARK DESCRIPTION
LOCATE SMOKE DETECTORS AT BOTTOM OF BEAMS (OR JOISTS) OR AT CEILING. (REDUCE SPACING BY .5
PERPENDICULAR TO BEAM OR JOIST DIRECTION). PER NFPA 72-2013 17.6.33.2
2 LOCATE HEAT DETECTORS AT BOTTOM OF BEAMS IF EITHER D/H < .1 OR W/H < .4: OTHERWISE LOCATE IN BEAM
POCKET.
3 LOCATE SMOKE DETECTOR ANYWHERE IN SHADED AREA. PER NFPA 72-2013 17.6.3.4
W
D4" MIN12" MAX1/2 S 3'-0" MAX
FIRE ALARM DEVICE MOUNTING NOTES:
1.ALL MOUNTING HEIGHTS SHOWN ARE TYPICAL UNLESS NOTED OTHERWISE ON PLANS.
2.VISUAL UNIT (NOTIFICATION): DEVICE 80" ABOVE HIGHEST FLOOR LEVEL OR 6" BELOW CEILING, WHICHEVER
IS LOWER (ADA 1993). BOTTOM OF DEVICE 80 AFF (NFPA).
3.AUDIO UNIT (NOTIFICATION): TOP OF UNIT AT LEAST 90" AFF OR 6" BELOW CEILING, WHICH EVER IS LOWER
(NFPA).
4.AUDIO / VISUAL UNIT (NOTIFICATION): LOCATION DETERMINED BY VISUAL UNIT REQUIRMENTS (NFPA).
5.PULL STATION (ACTIVATION): HIGHEST OPERABLE PART SHALL NOT BE MORE THAN 48" ABOVE THE FLOOR
(FRONT APPROACH) ADA 1993. OPERABLE PART (T-HANDLE) SHALL BE NOT LESS THAN 42" AFF (NFPA).SEE NOTES 2, 490" TO TOPAUDIO
ONLY 6" MINSEE NOTE 34 PER NFPA 72-2013 A.17.7.4.1
4
SCALE:
1
F0.1
TYPICAL FIRE ALARM MOUNTING DETAILS
NO SCALE
POWER FIRE PRE-ALARM SECURITYSUPERVISORYALARM SYSTEMTROUBLE SILENCEDSIGNALS DISABLEDPOINT
TESTLAMPRESETSYSTEMDRILLHOLD 2 SECONDSSIGNALSILENCEDSCROLL DISPLAYACKNOWLEDGE
1
Q W
2
E
3
R
4
T
5
Y
6
U
7
I
8
O
9
P
0
SPACENMBVCXZ
A S D F G H JKL
!,@ =%:\.I ?
LOWERCASE
SELECTIONNEXT
SELECTIONPREVIOUS
ENTRYLAST
NUMBERINCREMENT
RECALL
BATTERY
MODULE
LEVELS
OUTPUT
DETECTOR
Enter
Esc
LCD-80
ACKGLOBAL
TIME SET
TIMESELECT
ADJ.CONTRAST
HOLD FORLAMP TESTSTEPDISPLAY
POWER IN COMMON OUTCONTACTSCOMMON IN
EARTH GROUNDPOWER OUT
EIA-485 OUT (-)EIA-485 OUT (+)EIA-485 IN (-)
N.C. TROUBLEEIA-485 IN (+)
5 PER NFPA 72-2013 17.7.3.2.1
5
F0.1 FIRE ALARM DETAILSDRAWING NO 2 OF 3
DATE
ES
CHECKED BY:
JA
DRAWN BY:CCCC AUTO RESTORATION220 OLIVE FARM DRIVESANFORD, NORTH CAROLINA 27332PROJECT NUMBER:TheIntegrationofTechnologyandLifeSafetyFire, Security & CommunicationsA Subsidiary of TriTek Fire & Security, LLCREVISIONNO.BYDATEFOR CONSTRUCTIONCURRENT PHASE:SUBMITTALROUGH-ININSTALLPROGRAMMINGPUNCH LISTAS BUILTINSPECTIONPRINTED:TECHNICIAN:RETURNED:XX/XX/XXXX/XX/XXXX02-12-18
13499
SCALE:
2
F0.1
SMOKE / HEAT DETECTOR DETAIL
NO SCALE
CLASS A OPTIONAL WIRINGFACPTYPICAL WIRING DIAGRAM FOR 2-WIRE LOOP
NOTES:
1.NO EOL RESISTOR REQUIRED FOR SLC APPLICATION.
2.EOL REISISTOR REQUIRED FOR HARD WIRE APPLICATION.
3.DO NOT LOOP WIRE UNDER TERMINAL 1 OR 2. BREAK WIRE RUN TO PROVIDE
SUPERVISION OF CONNECTIONS.
3-1/2" OCTAGON BACKBOX
(PROVIDED BY ELECTRICAL
CONTRACTOR)
SNAP ON
DECORATIVE RING
DETECTOR BASE
1
2
3
AIR FL
O
W
TEST S
W
I
T
C
H
DUCT
CEILING
2
1
4
5
RELAY
MODUL
E
3
DUCT
DETEC
T
O
R
KEY NOTE SCHEDULE
SYMBOL DESCRIPTION
#18 / 2 WIRE (SLC) IN 34" CONDUIT.1
2 (2) #18 / 2 WIRE IN 34" CONDUIT (TEST STATION), OR #18 / 2 WIRE IN 3/4" CONDUIT
(REMOTE INDICATOR)
3
4
DUCT DETECTOR MOUNTED IN MECHANICAL DUCTWORK. SEE MECHANICAL
DRAWINGS FOR INSTALLATION INFORMATION.
5
TEST SWITCH WITH INDICATOR LIGHT. SEE PLANS FOR MOUNTING LOCATION
(CEILING, WALL).
RELAY MODULE INSTALLED BY MECH. (TO BE WITHIN 3'-0" FROM DUCT DETECTOR).
SCALE:
3
F0.1
NOTIFIER DNR -
DUCT DETECTOR WIRING DETAIL
NO SCALE
NOTES:
1.REFER TO FIRE ALARM DRAWINGS FOR LOCATION AND QUANTITY OF DUCT DETECTORS.
2.REFER TO PLANS FOR SPECIFIED COMBINATIONS (DUCT DETECTOR + TEST SWITCH, DUCT
DETECTOR + TEST SWITCH + RELAY MODULE)
3.DUCT DETECTOR TO BE INSTALLED BY MECHANICAL CONTRACTOR.
TYPICAL FOR EACH
DUCT DETECTOR
SHOWN ON PLANS
R
DD
I
#18/2
#18/2
STRIP
GAUGE
1 2 3 4
SLCSLC
FROM
FACP
TO NEXT
ADDRESSABLE
DEVICE
SCALE:
4
F0.1
NOTIFIER NOT-BG12LX -
PULL STATION DETAIL
NO SCALE
NOTES:
1.REFER TO DETAIL 1/F0.1 FOR MOUNTING HEIGHTS.
(+)
(+)
(-)(-)
SCALE:
5
F0.1
RELAY MODULE (NC-100R)
NO SCALE
RELAY COMMON 2
NORMALLY CLOSED 2
NORMALLY OPEN 2
RELAY COMMON 1
NORMALLY CLOSED 1
UNUSED
NORMALLY OPEN 1
(+)
(-)SLC
(+)
(-)
TO NEXT
DEVICE
(+)
(-)
FROM PANEL OR
PREVIOUS
DEVICE
SYMBOL SHOWN ON PLANS =R
(-)
(+)
FROM NOTIFICATION
APPLIANCE OR POWER
SUPPLY
EOLR
OUT TO NEXT DEVICE FROM LAST DEVICEOUT
OUTIN
IN IN / OUTMOUNTING PLATE
(VIEW ROTATED FOR
CLARITY)
COVER ISOMETRIC
INSCALE:
6
F0.1
GENTEX STROBE, HORN / STROBE WIRING DETAIL (GES3-24W & GEC3-24W)
NO SCALE
Lobby
108
Men
110
Women
109
Office
103
Office
104
Storage
111
Janitor
106
Electrical/
Data
105Classroom101 Paint Booth
113
Paint
Mixing
112
Frame Machine
114
Shop Area
115
Classroom
102
Compressor
118
Breakroom
107
Vehicle Lift
117
Vehicle Lift
116
AA AAAA
AB
AB
AB
AB
AA
AA
AA
AB
FACPFAAPAAAA
ABAB
30cd
110cd 110cd 110cd
110cd
110cd110cd
30cd
30cd
110cd
AB AB
60cd
60cd
SD
SD
SD
DD
SD
DD
SD
SD
AB
F F F F F
F
I
I
R
R
EOL
4.7k
1A,1AA
1A,1AA 1A,1AA 1A 1A
1A,1AA
1A,1AB 1A,1AB
1A,1AB
1A,1AB
1A,1AB
EOL
4.7k
2A,2AB
2AB
L1D01
L1D02
L1D03
L1D04
L1D05
L1D06
L1D07
L1D08
L1M01 L1M02 L1M03 L1M04 L1M05
L1M06
L1M07
L1M08
1
2
SEPARATE CONDUIT
FOR ANNUNCIATOR.
3
RL1M094
1B,1C
F1.0 FIRE ALARM PLANDRAWING NO 3 OF 3
DEVICE LEGEND
SYMBOL DESCRIPTION
DEVICE LEGEND NOTES:
1.SEE DETAIL 1/F0.1 FOR TYPICAL MOUNTING HEIGHTS.
2.SEE F0.1 FOR STANDARD WIRING & INSTALLATION DETAILS.
3.ALL VISUAL NOTIFICATION DEVICES SHALL HAVE A 15 CANDELA RATING UNLESS SHOWN
OTHERWISE ON PLANS (i.e. 30cd, 75cd, etc...).
4."XX" SHOWN ON NOTIFICATION APPLIANCES NOTATES NAC CIRCUIT, SEE WIRE LEGEND
FOR LIST OF CIRCUITS.
FACP
SD
F
XX
M T,F,P
J
FAAP
HD
DD
A V
V
FIRE ALARM CONTROL PANEL
SMOKE DETECTOR
HEAT DETECTOR
DUCT DETECTOR
PULL STATION
AUDIO / VISUAL INDICATING DEVICE - WALL MOUNT
VISUAL ONLY INDICATING DEVICE - WALL MOUNT
MONITOR MODULE (T = TAMPER, F = FLOW, P = PRESSURE)
FIRE ALARM ANNUNCIATOR PANEL
AUDIO / VISUAL INDICATING DEVICE - CEILING MOUNT
VISUAL ONLY INDICATING DEVICE - CEILING MOUNT
JUNCTION BOX (HORIZONTAL WIRING)
RELAY MODULE
REMOTE INDICATOR WITH TEST STATION (KEYED) FOR DUCT DETECTORT
XX
XX
XX
C CONTROL MODULE
R
DH
NAC FIRE ALARM REMOTE POWER SUPPLY PANEL
DOOR HOLDER
J JUNCTION BOX (VERTICAL WIRING / RISER)
END OF LINE (EOL) RESISTOR
I ISOLATION MODULE
REPRESENTS WIRE OR CIRCUIT COMING "IN"
REPRESENTS WIRE OR CIRCUIT GOING "OUT"
REMOTE INDICATOR FOR DUCT DETECTORI
WIRE LEGEND
LABEL DESCRIPTION PANEL LOCATION
A 18-02 UNS SOL FPLR (SLC)FACP 1ST FLOOR
B 2#14 THHN, Solid (24VDC)FAAP 1ST FLOOR
C #18-02 Shielded, FPLR, Solid FAAP 1ST FLOOR
D #18-02 UNS SOL FPLR duct det.SEE PLAN
AA (2) #14 THHN, Solid 1ST FLOOR
AB 1ST FLOOR(2) #14 THHN, Solid
FACP
FACP
FACP NFW2-100
PANEL SCHEDULE
PANEL DESCRIPTION LOCATION
FAAP N-ANN-80
ELEC/DATA 105
LOBBY 108
DATE
ES
CHECKED BY:
JA
DRAWN BY:CCCC AUTO RESTORATION220 OLIVE FARM DRIVESANFORD, NORTH CAROLINA 27332PROJECT NUMBER:TheIntegrationofTechnologyandLifeSafetyFire, Security & CommunicationsA Subsidiary of TriTek Fire & Security, LLCREVISIONNO.BYDATEFOR CONSTRUCTIONCURRENT PHASE:SUBMITTALROUGH-ININSTALLPROGRAMMINGPUNCH LISTAS BUILTINSPECTIONPRINTED:TECHNICIAN:RETURNED:XX/XX/XXXX/XX/XXXXSCHEDULES / LEGENDS
KEYPLAN
02-12-18
13499
SCALE:
PLAN
NORTH
1
F1.0
FIRE ALARM PLAN
1/8" = 1'-0"
FACP 1
BACKBOX SCHEDULE
DEVICE TYPE PART #QTY.BACKBOX
BACKBOX NOTES:
= PROVIDE PLASTER RING
= PROVIDE WITH EXTENSION OR 218" BOX***
MOUNT
NFW2-100 INCLUDED
FAAP 1N-ANN-80
HORN/STROBE 12GEC3-24WR 4"x4"x112"
STROBE 6GES3-24WR
SMOKE DETECTOR 6NP-100 3.5" OCTAGON
PULL STATION 6NOT-BG12LX SINGLE GANG
4"x4"x112"
SURFACE
SURFACE
WALL
WALL
SURFACE
SURFACE
INDICATOR LIGHT 2RA-100Z
INCLUDED
SINGLE GANG
RELAY MODULE 3NC-100R 4"x4"x112"SURFACE **
KEY NOTE SCHEDULE
SYMBOL DESCRIPTION
PROVIDE SURGE PROTECTION ON 120VAC TO FACP. INSTALL GUTTER ABOVE
FACP. SEE RISER F0.0.1
2 DETERMINE LOCATION OF DUCT DETECTOR INDICATION LIGHTS PRIOR TO
INSTALLATION. SEE F0.1 DETAIL 3 FOR WIRING.
VERIFY DUCT DETECTOR LOCATIONS PRIOR TO INSTALLATION.
RELAY MODULE FOR ACCESS CONTROL TIE-IN. VERIFY LOCATION PRIOR TO
INSTALLATION.
3
4