Loading...
HomeMy WebLinkAboutFinal Purlife Outreach Decision PacketDRAFT DRB DECISION PACKET Harnett County, North Carolina Planning Department 108 E. Front Street, Lillington, NC 27546 Phone: (910) 893-7525 Fax: (910) 893-2793 Development Name: PURLIFE OUTREACH Development Type: COMMERCIAL SITE PLAN REVIEW Date: DECEMBER 11, 2013 The above referenced application  SHORT TERM CONDITIONS, COMMENTS, OR JUSTIFICATIONS The following conditions are to be rectified prior to obtaining DRB signature and are subject to change during the course of the meeting. : : Show existing fire hydrant locations. Fire hydrants are to be installed where the building is going to measure 400 feet (from its farthest point) to an existing hydrant. Measurements are to be made along vehicular access roads and not by a straight line.  : :   : : Note total lot size. Add note that states “Hwy 24-27 is on the Harnett County Comprehensive Transportation Plan” Add note that states “This development is within one mile of a Voluntary Agricultural District.” Add note that states “This development is within the five mile Military Corridor Overlay Zone, and may be subject to military training activities.” Note who will be responsible for maintenance of the parking areas, drive aisles, and all landscape buffering. Will there be a dedicated play area? If so, fence shall be at least 5’ tall, and the gate shall be self-closing and self-latching. Show location of ground sign, if applicable. Sign should be at least 10’ from NCDOT right-of-way, and shall require an additional permit. Is an NCDOT driveway permit required? If so, certification from NCDOT that all driveway permits have received approval should be submitted with the site plan Add owner cert. example: As the owner of record, I hereby formally consent to the proposed development shown on this site plan and all regulations and requirements of the Harnett County ordinances. ______________________________________ Date Owner Signature   : : -The commercial property must include water and sewer daily usage on site plan. -The existing water mains must be included on the site plan. -The water and sewer capacity fees must be paid prior to services being installed for the site. -The commercial site plan must include approved RPZ locations and services with sizes.  : : No soils report required. property to be addressed during permitting phase.  Engineering (910)893-7555 : This development does not meet the thresholds for stormwater requirements. It is recommended that a drainage plan be developed.   LONG RANGE CONDITIONS The following conditions must be satisfied Must meet all requirements set forth by NC DENR. Contact at (910)433-3300.  : Please visit www.harnett.org/utilities for more information on the approval process.  :   :   :   :     Development Review Board Chairman   A FINAL copy, consisting of any corrections, etc., will be sent after the meeting. Upon resubmittal, additional comments/ corrections may be required. **Please remember all applicable fee’s** If APPROVED, your signed plat/plan may be picked up at the Planning Department or will be mailed to you within two (2) business days. If APPROVED WITH CONDITIONS, you must submit 5 copies of the plat/plan to the Planning Department showing that all items listed under Short Term Conditions have been rectified. Please be aware that review will not be done while you wait, as all DRB members will have to review the plat/plan for compliance. If HELD, you must submit 5 copies of the plat/plan showing that all items listed under Short Term Conditions have been rectified. To attend the next DRB meeting, revised plat/plans must be submitted by noon on Wednesday following the meeting the application was put on hold. If DENIED, you may appeal the Board’s Decision to the Harnett County Planning Board within 30 days or meet with Planning Staff to discuss other potential options.