HomeMy WebLinkAboutPU-SR-P-02
PUBLIC UTILITIES STAFF REPORT
Harnett County, North Carolina
Planning Department
108 E. Front Street, Lillington, NC 27546
Phone: (910) 893-7525 Fax: (910) 893-2793
Development Name: Prime Time Subdivision -Preliminary
Property Description
PIN(s): 9691-58-0057.000 Acreage: 7.70 acres
Address/SR No.: Lawrence Road (SR1272)
Water
Public water is available for this development (via Harnett County)
Water capacity is available for this development
Nearest water line location (Road name & SR#): Holly Springs Church Road (SR 1273)
Nearest water line size: 4"
NOTE: Harnett County has an existing four (4") inch water distribution line located on the north side of
Lawrence Road (SR 1272) that can provide domestic (potable) drinking water only. This four (4") inch
water main cannot support fire flow for fire hydrants or fire protection for this proposed subdivision.
The Harnett County Fire Marshal must provide a written variance for this subdivision to be served by a
four
(4") inch water line without fire hydrants or the subdivision must be reduced to six (6) lots or less which
would be classified as a minor subdivision.
The nearest water line that could provide fire flow for fire hydrants is located on Holly Springs Church
Road (SR 1273). The only other alternative would be to extend a new six (6") inch water line from the
existing six (6") inch water line located on the north side of Holly Springs Church Road (SR 1273) along
Hollies Pines Road and Lawrence Road (SR 1272) to serve this proposed development. This will require
that the developer hire a Professional Engineer (P.E.) to design the proposed water line extension and
the P.E. must submit utility plans to HCDPU for review and subsequent approval of the proposed six (6")
inch
water line extension in accordance with the established Approval Process for New Water Line Extensions
as
described on the Harnett County website www.harnett.org under the Public utilities page.
NOTE: HCDPU provides this information as a curteousy to the developer and professional engineer for
design purposes. However, HCDPU cannot be held liable for errors, mistakes, ommissions, and
inaccurate
information provided through this preliminary and/or final plat approval process. It is therefore
recommended that the professional engineer or developer "field verify" the information provided by
HCDPU. 6"
Fire flow is available for this development
Lines permitted under DENR Permit: (DEH Serial Number)
Sewer
Public sewer is not available for this development (via Harnett County)
Sewer capacity is not available for this development
Nearest sewer line location (Road name & SR#):
Nearest sewer line size:
Lines permitted under DENR Permit: (DWQ Serial Number)
Page 1 of 2 PUBLIC UTILITIES STAFF REPORT
Additional Requirements
As-Built Record Drawings Yes No N/A
Cost Statement for water improvements Yes No N/A
Cost Statement for sewer improvements Yes No N/A
Professional Engineer’s Certifications for water/sewer extension Yes No
N/A
Final Plat & As-Built Record Drawings are identical Yes No N/A
DOT Encroachment Agreement Yes No N/A
Distance to nearest water/sewer lines noted (Site Plan Only) Yes No N/A
Master Plan submitted for additional phases if intended Yes No N/A
Ballot
REVIEWER: Tim Payseur Date: Aug. 22, 2007
VOTE: Conditionally Approve
CONDITIONS:
SHORT TERM:
Conditional Approval is given based upon the use of the exisitn 4" water line for 6 lots or less
or the developer must extend the 6" water line from Holly Springs Church Road (SR 1273)
along Hollies Pines Road and Lawrence Road (SR 1272) to serve this proposed development.
LONGE RANGE:
Please visit www.harnett.org/utilities for more information on the approval process.
Page 2 of 2 PUBLIC UTILITIES STAFF REPORT