The site plan that was submitted for the Vandercroft Farms SD, has been reviewed.
Below you will fine the changes to be made to the site plan to be compliance with the
N.C Fire Prevention Code and the County Ordinances.
Ingress is approved pending the clearance between the median and the shoulder is
20’. The median to be recessed off Hwy 210, or the street at Hwy 210 be beveled
out.
Egress is approved as drawn
Vertical clearance to comply with IFC of 13’ 6”
Utilities not approved, will co-review utility construction documents with Tim
Payseur, HCPU
503.1.1 Fire Access Roads.
Approved fire apparatus access roads shall be provided for every facility,
o
building or portion of a building hereafter constructed or moved into or
within the jurisdiction. The fire apparatus access road shall comply with
the requirements of this section and shall extend to within 150 feet (45 720
mm) of all portions of the facility or all portions of the exterior wall of the
first story of the building as measured by an approved route around the
exterior of the building or facility
This shall apply to the following lots: 56,57,60,61,284,285,288,289, the driveway for
these lots shall be 20’ in width
Teddy Joe McLamb
T.J. McLamb, CFI
Chief Deputy Fire Marshal