AP FM DOCUMENTS / Harnett
ZrCOUNTY * A ro l..e..,salmon oopowboamr
Plan Review, Inspection, and Permit Fees
Application Number . 18-soo43529
$100.00 0 DRB Major Sub Division Prelim Site Plans $ -
$200.00 ❑ Explosive Material (90 Days) $ -
$100.00 0 Explosive Materials (72 Hours) $ -
$100.00 0 Fireworks Public Display $ -
$50.00 o Final Inspection $ so.00
$35.00 +$2.00 per device 0 Fire Alarm Testing $ -
$35.00 +$2.00 per nozzle 0 Fixed Fire Suppression $ -
$75.00 0 Insecticide Fog/Fumigation $ -
$100.00 0 Pipe Test/UST/AGST $ -
$50.00 El Plans up to 5000 sq ft $ so.00
$100.00 0 Plans 5001 sq ft to 10,000 sq ft $ -
$150.00 0 Plans 10,001 sq ft to 25,000 sq ft $ -
$250.00 0 Plans 25,001 sq ft and over $ -
$35.00 +2.00 per head 0 Sprinkler Certification Test $ -
$50.00 0 Standpipe Testing $ -
$50 00
0 Special Assembly
(ie.amusement buildings,carnivals,fairs) $ -
$75.00 0 Tents/Canopies/Air Supported Structure $ -
$100.00 ❑ Tank Installation (charge for each tank) $ -
$100.00 0 Tank Removal (charge for each tank) $ -
Total Devices/Heads $ -
Total Cost S 100.00
Code Enforcement Official D. Banks Wallace 6/13/2018
,N Harnett
O .r .
CUNTY * A. M1 e.q..rs.w.so•M.a•.M
NI) ..du.w.�
Fire Marshal Division
June 13,2018
Terri McNeill
Competitive Cycles
81 Hollies Pines Rd.
Broadway,NC 27505
Application Number 16-50037930
Mr. McNeill,
Thank you for submitting the plans for the Competitive Cycles. The plans have been
carefiilly reviewed by a qualified code enforcement official to examine for full
compliance with the North Carolina Fire Prevention Code and all other fire protection
regulatory documents. There are some items that were found during the plan review
process that need to be addressed before a final inspection of the new facility can be
given. These items are outlined and described below.
• 505.1 Physical Address
o The physical address of the building shall be posted in a conspicuous
place so that it can be seen on approach from the road,access road,and/or
parking lot.
o The numbers used to make up the physical address shall be at least 6
inches in height.
• 506.1 Knox Box
o A secure key box shall be installed on the new building that houses all
keys to all the doors within the building in which the fire department
would need access to in the event of an emergency.
o Knox Box ID stickers shall be placed on all exterior doors in which entry
to the building may be gained.
o The box shall be mounted not to exceed 48—60 inches in height.
o The basic model for the buildings should be at least a selection from the
3200 Series listed on the order form.
• Fire Extinguishers
o Fire Extinguishers shall be 2A:10BC and shall be placed with a travel
distance to not exceed 75'
o Fire extinguishers are to be mounted no higher than 5' above the finished
floor.
Harnett
C O U N T r * 0rvo infters••:..a. tans
• 1006.1 Illumination Required
o The exit discharge shall be illuminated at all times the building
spaces served by the means of egress is occupied
o Illumination level in all areas of the means of egress shall not be
less than I foot-candle at the walking surface and shall have
emergency power supply.
Thank you again for submitting the plans for the Competitive Cycles. Please review the
plans and adhere to any notes and alterations that were made in addition to the original
drawings. These remarks are for the plans that were submitted and its original intent.
These remarks do not apply if the original intent changes or what was submitted on the
above date changes. If you have any questions,please do not hesitate to call this office
Again,thank you and we look forward to working with you during the construction
period!
Sincerely,
D. Banks Wallace
Chief Deputy Fire Marshal
Harnett �A ,,.•�,,,,,..,„,
I (� COUNTY A CFrfY'�
NORTH CAROLINA
vnins
cki
Application for Plan Review dg t-dq
Application# ICJ - son 4S520 y"litt '
Date Received: 'I Receivve-dlBByy:''I�7- ,/ (9
Name of Project: - /nJ v , ,(/1.1(Path
th
Physical Address of Project n I- ( I��� 4 V CS LQ .
qq NC
•
Plena Submitted By:
iX i.-I0.12 Q Lf t ' EMERGP C'(SERVICES
Project Phone: ( I /"1 )-Z.5 &( KKNET(coOR CODE COMPLIANCE
REVIEWE (1 f3
Contact Person/Address: ,A- ' i.e
• aO Mb% DA E
COO
Contact Email:
Contact Phone: ( )- - ( )- -
Contractor's Name/Info:
Contractor's Phone: -
• Plans that are submitted will be reviewed as quickly as possible with an average time of review
between 7-10 working days.
• Status checks may be conducted on plan reviews by visiting the website
htto://hteweb.hamett.om/Click2GovBP/Index.iso or by calling the Hamett County Central Permitting
Office(910-893-7525, Option#2),or the Hamett County Fire Marshal's Office(910-893-7580).
• Approved plans must be picked up from the Central Permitting Office and all fees paid before any
required inspections can be conducted.