FM REVIEW /` Harnett
"'�('"'� COUNTY * A (F M) tomilleicr
Plan Review, Inspection, and Permit Fees
Application Number : 18-50044037
$100.00 0 DRB Major Sub Division Prelim Site Plans $ -
$200.00 0 Explosive Material (90 Days) $ -
$100.00 0 Explosive Materials (72 Hours) $ -
$100.00 0 Fireworks Public Display $ -
$50.00 El Final Inspection $ 50.00
$35.00 +$2.00per device ❑ Fire Alarm Testing $ -
$35.00 +$2.00 per nozzle ❑ Fixed Fire Suppression $ -
$75.00 ❑ Insecticide Fog/Fumigation $ -
$100.00 ❑ Pipe Test/UST/AGST $ -
$50.00 0 Plans up to 5000 sq ft $ -
$100.00 o Plans 5001 sq ft to 10,000 sq ft $ ioo.00
$150.00 0 Plans 10,001 sq ft to 25,000 sq ft $ -
$250.00 ❑ Plans 25,001 sq ft and over $ -
$35.00 +2.00 per head In Sprinkler Certification Test $ -
$50.00 ❑ Standpipe Testing $ -
Moo
❑ Special Assembly
(ie.amusement buildings,carnivals,fairs) $ -
$75.00 0 Tents/Canopies/Air Supported Structure $ -
$100.00 ❑ Tank Installation (charge for each tank) $ -
$100.00 ❑ Tank Removal (charge for each tank) $ -
Total Devices/Heads $ -
Total Cost $ 150.00
Code Enforcement Official D. Banks Wallace 5/21/2018
,: , [lamed
--4 •,s a.s:wo '.ro..ur
BMNTY IX= �J{4s
NOM CAROLINA
C�17�( y�y�ry,Ry
Rfy�j{ D FOR Cpp fft
M OM��Y
SfRIti
Application for Plan Revi NCE
Coo "pPj/
Application# \ k -SCl.� -f yo rJ ANCEOFFICfRATzy t
Date Received:_ 5 I IUD I ) Received By: r7 f
Name of Project: l CU Svden4- ll—cEc 1�.e novq on
Physical Address of Project: 1.14, ',at gel
ic!
yr)(�nn , NC r�-75'`f 6L,
Plans Submitted By: S Aecs- c^t �o, y�{r'retemn of 1J�,e5 Crczk7 Lt-
Project Phone: (R t Brett- )- )5_ OF+6.1
1
B
Contact Person/Address: rt Sfit(Ck .t
aB As/or {- RA.
Fri..., , Nc a-853R
Contact Email b't*s 5 t -n c. Con
Contact Phone: ( 41 R )- 105-
ote tt
Contractors Name/Info: 50 LA-Leas-it., 04- .,[, Cvee IL) 1.2C
cL ti Ater{ (I .
jn P.c. ag33q
Contractors Phone: ( 4$OS 666L)
• Plans that are submitted will be reviewed as quickly as possible with an average time of review
between 7-10 working days.
• Status checks may be conducted on plan reviews by visiting the website
hripl/hteweb.hamett.om/Click2GovBP/lndex.isp or by calling the Harnett County Central Permitting
Office(910-893-7525,Option#2), or the Hamett County Fire Marshal's Office(910-893-7580).
• Approved plans must be picked up from the Central Permitting Office and all fees paid before any
required inspections can be conducted.
®Hrnett
COUNTY * ® OM1 1..'.. .o
rs. oermatu .
Fire Marshal Division
May 21, 2018 $
Mr. Brett Strickland
Re: Student Life Renovation
Campbell University
Ullington, NC 27546
Application Number 18-50044037
Mr. Strickland,
Thank you for submitting the plans for the building alterations. The plans have been
carefully reviewed by a qualified code enforcement official to examine for compliance
with the North Carolina Fire Prevention Code and all other fire protection regulatory
documents. There are some items that were found during the plan review process that
need to be addressed before a final inspection of the facility can be given. These items
are outlined and described below.
• 901.2.1 State of Compliance.
o Before requesting final approval of the installation, where required by
the fire code official, the installing contactor shall furnish a written
statement to the fire code official that the subject fire protection system
has been installed in accordance with the manufacture's specifications
and the appropriate installation standard. Any deviations from the design
standards shall be noted and copies of the approvals for such deviations
shall be attached to the written statement.
o All work shall be performed in accordance with NFPA 13 and the NCSFC.
• 906.1 Fire Extinguishers
o Minimum of(1) 2A10:BC fire extinguisher shall be installed not to exceed
75' distance of travel.
o All Fire extinguishers shall be properly mounted and tagged by a fire
extinguisher company.
• 1006.1 Means of Egress Illumination
o The means of egress, including the exit discharge, shall be illuminated at
all time the building space is served by the means of egress is occupied.
=Harnett
COUNTY * A ^margama•Santis o••..w.a
o Means of egress consist of three separate and distinct parts: the
exit access,the exit and the exit discharge.
o The means of egress illumination shall not be less than 1 foot-candle at
the walking surface.
• Penetrations
o All penetrations in fire rated construction must be UL listed and
inspected.
• Smoke Detectors
o A smoke detector shall be located in each office space. This may occur by
relocating or adding additional detectors as required for coverage.
o The detectors shall be compatible with existing detectors and alarm
system.
o All equipment and work shall be conducted per NFPA 72.
o A certification of completion,from the alarm company and an acceptance
test shall be provide at final inspection.
• Notes
o All additions to existing systems shall properly communicate to existing
fire panel.
o A fire alarm construction permit is required.
o Please schedule all inspections through the Fire Marshal's Office.
910-984-4003.
Thank you again for submitting the plans for the building alterations. Please review the
plans and adhere to any notes and alterations that were made in addition to the original
drawings. If you have any questions, please do not hesitate to call this office.
Again,thank you and we look forward to working with you during the construction
period!