APPROVED FM PLANSPlan Review, Inspection, and Permit Fees
Application Number :18-50043307
$200.00 Explosive Material (90 Days)
$100.00 Explosive Materials (72 Hours)
$100.00 Fireworks Public Display
$50.00 Final Inspection
$35.00 + $2.00 per device Fire Alarm Testing
$35.00 + $2.00 per nozzle Fixed Fire Suppression
$75.00 Insecticide Fog/Fumigation
$100.00 Pipe Test/UST/AGST
$50.00 Plans up to 5000 sq ft
$100.00 Plans 5001 sq ft to 10,000 sq ft
$150.00 Plans 10,001 sq ft to 25,000 sq ft
$250.00 Plans 25,001 sq ft and over
$35.00 + 2.00 per head Sprinkler Certification Test
$50.00 Standpipe Testing
$50.00 Special Assembly
(ie. amusement buildings, carnivals, fairs)$75.00 Tents/Canopies/Air Supported Structure
$100.00 Tank Installation (charge for each tank)
$100.00 Tank Removal (charge for each tank)
62 Total Devices/Heads
Total Cost
Code Enforcement Official D. Banks Wallace
$ -
$ -
$ -
$ 50.00
$ 35.00
$ -
$ -
$ -
$ -
$ -
$ 150.00
$ -
$ -
$ -
$ -
$ -
$ -
$ -
$ 124.00
$ 359.00
5/11/2018
Plan Review, Inspection, and Permit Fees
Fire Marshal Division
May 10, 2018
Amy Labadie
814 Developments, LLC
3221 W. Big Beaver
Suite 111
Troy, MI 48084
RE: Rainbow Child Care Center
95 Centennial Parkway
Spout Springs, NC 28326
Application Number: 18-50043307
Ms. Labadie,
Thank you for submitting plans for the new day care facility. The plans have been
reviewed by a qualified code enforcement official for compliance with the North
Carolina Fire Prevention code and all other fire protection regulations. The following are
items that will need to be addressed before a final inspection of this project can be
completed. The items are listed and described below.
503 Fire Department Access
o The fire department access shall extend to within 150 feet of all portions
of the facility (current driveway and parking lot may suffice).
o The fire department access road shall be of an unobstructed width of not
less than 20 feet and shall have an unobstructed vertical clearance of not
less the 13 feet 6 inches.
505.1 Physical Address
o The physical address of the building shall be posted in a conspicuous
place so that it can be seen on approach from the road, access road,
and/or parking lot.
o The numbers used to make up the physical address shall be at least 5
inches in height.
906.1 Fire Extinguishers
o Fire extinguishers shall be placed in approved locations and may be field
verified on final inspection. The fire extinguishers provided shall have a
minimum rating of 2A 10 B: C.
1006.1 / 1006.2 Emergency Illumination
o Emergency illumination is required to meet minimum foot candle
illumination.
o Emergency lighting is required. Please show locations
506.1 Knox Box
o A Knox box is required to be installed on the building.
o An application /order form has been attached to the review comments.
901.2 Fire Alarm System
o Fire alarm system design is required to be sealed by a North Carolina
Professional Engineer.
907.1.2 Fire Alarm Construction Drawings
o Provide fire alarm system shop drawings. This submittal should be
completed by the installing fire alarm contractor.
o These plans are to be submitted before fire alarm work begins.
1008.1.10 Panic Hardware
o If occupant load exceeds 50 panic hardware is required on all exit doors.
Notes
o Please contact the Fire marshal’s office to schedule both fire alarm
system testing and fire final inspection when work is complete.
Please review the plans and adhere to any notes and alterations that were made in
addition to the original designed plans. These remarks are for the plans that were
submitted and its original intent. If you have any questions please do not hesitate to
contact me. We look forward to working with you during the construction period.
Sincerely,
D. Banks Wallace
Chief Deputy Fire Marshal
HARNETT COUNTY CHILD CARE CENTER PLAN REVIEW
APPLICATION
* The application will be reviewed using 15A NCAC 18A .2800 “Rules Governing the
Sanitation of Child Care Facilities.”
Plans must be submitted and approved prior to construction, renovation, modification, or upon
the change of ownership of such facilities. Submit plans to the Harnett County Central
Permitting Office located at 108 East Front St., Lillington, NC 27546 or by mail at PO Box 65,
Lillington, NC 27546. You may contact the Central Permitting Office at 910-893-7525, Ext. 2. If
you have questions regarding this application, contact one of the following people listed below at
910-893-7547
Gale Violette Greene, RS Jamie Turlington, RS
Food and Lodging Program Specialist Environmental Health Specialist
Cindy Pierce, RS
Environmental Health Specialist
_____ Plans must include drawings showing placement of equipment in the facility,
including storage, food service areas, diaper changing areas, can wash facilities,
along with general plumbing, electrical, mechanical, and lighting plans. You
must also submit equipment and finish schedules.
_____ Each child care classroom should be identified by age group(s) that will be using
the room.
_____ Plans must have a proposed menu provided listing the foods to be served at the
child care center
_____ Plans must include a site plan locating exterior equipment such as dumpsters or
compactors and indicating the proposed connections to approved sewer and water.
In addition, please complete the following information to identify the child care facility and
who to contact about questions regarding the review of this establishment:
______NEW _____REMODEL ____CONVERSION/ADDITION
NAME OF CHILD CARE CENTER: _________________________________________
CHILD CARE CENTER’S ADDRESS: _________________________________________
PHONE: ______________________________ FAX: _____________________________
NAME OF OWNER: _________________________________
MAILING ADDRESS: ______________________________________________________
PHONE: ______________________________ EMAIL: ___________________________
X
Rainbow Child Care Center
95 Centennial Parkway Spout Springs, NC 28326
EIG14T RCCC 213 NC-SPOUT SPRINGS LLC - Amy Labadie
1742 Crooks Road, Troy MI 48084
Amy@814cre.com(258) 519-9281
X
X
X
X
APPLICANT’S NAME: _______________________________
MAILING ADDRESS: ______________________________________________________
PHONE: ______________________________ EMAIL: ___________________________
TITLE (MANAGER, ARCHITECT, DIRECTOR): ________________________________
NUMBER OF CHILDREN FOR WHICH FACILITY WILL BE LICENSED: __________
If this is a remodel or a change of ownership, what is the age of the building? _____________
Main Food Service
Meals prepared on site or catered meals? (With catered meals you are still required to have the
minimum requirements in the kitchen) ______________________________________
Where will the children eat meals? (Family style, tables in classrooms, dining area, etc…)
______________________________________________________________________________
Will multi-use utensils, silverware, sippy cups, etc… be used or disposable utensils?
______________________________________________________________________________
Can the kitchen door be locked? Is there a barrier to keep children out of the kitchen?
______________________________________________________________________________
Please list all equipment to be used in the kitchen and include specification sheets: ___________
______________________________________________________________________________
______________________________________________________________________________
Do you have a thermometer available to monitor food temperatures? ______________ Do you
have thermometers in the refrigerators? __________________
Will leftovers be served? ______ Will meals be prepared 12 or more hours in advance? _______
Infant Food Service
Will bottles be stored, prepared, warmed, served, etc… in the infant room or in the kitchen?
______________________________________________________________________________
Describe your procedures for handling breast milk: ____________________________________
______________________________________________________________________________
______________________________________________________________________________
Does the infant room have countertop space for warming bottles? ________________________
What method will be used to warm bottles? _________________________________________
Alexia Taylor
604 Courtland Street STE 100
(407) 645-5008 ataylor@interplanllc.com
Permit Coordinator
150
N/A
Meals Prepared on-site
Family Style in classrooms
Both will be used
Yes and yes
Refrigeration equipment, cooking equipment, at least 2-compartment sink, drainboards, adequate countertop
space, seperate hand wash lavatory.
Infant room
Yes
Bottle warmers
Is there a refrigerator for bottle storage? __________ Is there a thermometer? _______________
Is there a separate sink used exclusively for bottle/food preparation? ______________________
Diaper Changing
Are diaper changing stations in each age appropriate room? _____________________________
Where will diaper changing supplies be kept? ________________________________________
Is there a dirty diaper receptacle with a lid? __________________________________________
Can the caregiver view the children while changing diapers? _____________________________
Where and how will soapy water, sanitizers and disinfectants be stored?
______________________________________________________________________________
______________________________________________________________________________
Is there a separate hand wash lavatory used exclusively for diaper changing hand washing?
_____________________________________________________________________________
Are diaper changing signs provided? _______________________________________________
Cubbies and Storage
How and where will cubbies be arranged? ___________________________________________
_____________________________________________________________________________
Are coat hooks spaced at least 12” apart? ____________________________________________
Is all storage in all closets stored off floor (recommend 12”) to facilitate cleaning? ___________
Will toothbrushes be used at the center? _________ Will they be labeled? ______________
Beds, Cots, Mats, Cribs, and Linens
Will cribs have the capability of being spaced 18” apart while in use? (if not, crib dividers and
partitions are acceptable) ______________________________________________________
How and where will cots and/or mats be stored? _____________________________________
Where will crib, cot, and mat sheets be stored? ______________________________________
Where is there a designated sick area with cot/mat? ___________________________________
Is linen being provided by the center or the parents? ___________________________________
How often will infant sheets be changed? ___________________________________________
How often will sheets be laundered? _______________________________________________
Yes
Yes
Yes
On the diaper changing stations in cabinets out of children's reach
Yes
Locked in upper cabinets
Yes
Mounted to walls, near entrance doors to classroom
Yes
Yes
In the classroom where a designated cot storage area is made for the purpose
Center will have a washer and dryer and clean items
will be stored in the cabiners inside the classrooms.
In the Director's office
Cleaning, Sanitizing and Disinfecting
Is all furniture in the center of a smooth, washable finish? _______________________________
How will toys in infant and toddler rooms be washed and sanitized? Where? How often?
______________________________________________________________________________
______________________________________________________________________________
Please explain what type of sanitizer will be used to sanitize toys, food areas, furniture, etc.:
______________________________________________________________________________
Please explain what type of disinfectant will be used to sanitize toilets, lavatories and diaper
changing tables: _______________________________________________________________
Do you have appropriate test strips for the types of sanitizer and disinfectant you are using?
_________________________________
Where is the can wash facility for cleaning trash cans, dumping mop water, etc…?
______________________________________________________________________________
Will water play centers be used? ____________________
Hand wash lavatories
Does each toilet area have a hand wash lavatory? ______________________________________
Does the diaper changing station have a hand wash lavatory exclusively for diaper changing?
______________________________________________________________________________
Does the food service area in the infant and toddler room have a lavatory exclusively for food
service? ______________________________________________________________________
Does the kitchen have a hand sink that is separate from the 2 or 3 compartment sink for hand
washing only? _________________________________________________________________
What types of faucets are at all hand wash lavatories (please note that metering type is not
allowed unless they can retain warm water for at least 20 seconds at the first pressing):
______________________________________________________________________________
Are handwashing signs provided? ________________________________
Locked Items
Please indicate where the following type of locked items will be stored and what type of lock:
Medicines (both refrigerated and non refrigerated)
______________________________________________________________________________
Yes
Daily toys will be washed using 3 step process (soapy-clean-let air dry) mouthed toys are put in a bucket and washed
using the 3 step process (soapy-clean-let air dry).
3 step process (wash, clean water rinse, bleach water) bleach water is 50 to 200 parts per Chlorine.
Yes
Laundry room - Utility mop sink
Yes
Yes
Yes
Yes
Chicago # 1017 Faucet
In lock boxes in kitchen (refrigerated medicines) and in lock boxes in management office (non-refrigerated)
Cleaning supplies and all types of chemicals
______________________________________________________________________________
Personal belongings (purses, keys, employee items)
______________________________________________________________________________
Aerosols and all other toxic products
______________________________________________________________________________
Mildly Ill Children
Will you be licensed to care for mildly ill children pursuant to 10A NCAC 09 .2400? _________
Please include your protocols for this type of care.
Water Supply
Is the child care center on a well or provided with county water? _________________________
Sewage Disposal
Is disposal through an onsite septic system or county sewer? _____________________
Grease trap provided? ________________
Hot Water Supply
The kitchen hot water temperature will need to be a minimum of 120 degrees Fahrenheit. All
other sinks that are accessible to children and the can wash facility must be maintained between
80-110’Fahrenheit. Using two separate water heaters may be the best option since it is often
difficult to obtain two separate temperatures with one water heater. Mixing valves installed on
sinks have a high failure rate and are not very dependable.
Explain what the specifications of your water heater(s) are. (For example, if you are using two
water heaters, indicate which one is for the kitchen and which one if for the classrooms). It
is recommended that the minimum water heater size be 50 gallons.
Tank Manufacturer and Model # ___________________________________________________
Storage tank size__________ GPH recovery__________ Additional tank size___________
Lighting
Do all light fixtures have shatterproof or shielded bulbs? ________________________________
Will lighting illuminate 50 ft. candles at all work areas? ________________________________
and 10 ft. candles at all other areas, including storage closets? ___________________________
Finishes
Please describe the finishes/construction material in the following areas:
County Water
County Sewer
No
No aerosol dispenser. All placed in storage room outside of the kitchen, the door stays locked at all times.
All placed in upper cabinets, which are locked.
All placed in upper cabinets, which are locked.
Floors Walls Baseboards Ceilings
Kitchen
Bathrooms
Infant Room
Toddler Room
Other Rooms
Staff Room/Office
Storeroom
Other
*Wall to wall carpets must be cleaned at least every six months
Animals
What type of animals will be on the premises? ________________________________________
Outside premises
Please describe the playground area (size, type of play equipment, type of fence, water activities,
etc…) ________________________________________________________________________
_____________________________________________________________________________
Is there chromated copper arsenate (CCA) pressure-treated wood in the play ground area?
_____________________________________________________________________________
What methods will you use to make this inaccessible to the children? ______________________
______________________________________________________________________________
Is the can wash facility located outside? _____________________________________________
If yes, is there a fence and lock around it so it is not accessible to children? _________________
Is the HVAC, mechanical equipment, etc… locked with a fence around it so it is not accessible
to children? ___________________________________________________________________
Attach additional sheets if necessary.
gg
8/06
Vinyl Composit Tile Vinyl Composit TileDrywall Drywall
Diaper Changing Counters:Plastic Laminate
Sheet Vinyl
Sheet Vinyl
Drywall
Backsplash: Plastic Laminate
Backsplash: Plastic Laminate
Cabinetry: Thermofoil
Drywall
Drywall
Drywall
Drywall
Drywall
Size is approx. 10,000 sq feet; Fences - commerical grade/chain link; Playground surface is turf & pour & play;
Equipment - Inf. Tod - Inf. maze & fun umbrella (for shade); YPSTPS - Climbing unit & fun umbrella; Ball drop hoop; Pk - school-age - climbing unit & fun umbrella
No
N/A
Yes, there will be a fence around the unit(s) that have a locking mechanism and it will not be accessible to children.
Project Title: Rainbow Child Care Center Report date: 04/23/18
Data filename: P:\R\RainbowChildCare\2017.0643 - 95 Centennial Parkway, Spout Springs, NC\4 Support Documents\5 Calculations\2 Energy
and Load Calcs\17.0643 Rainbow Child Care Cameron, NC - 2012 NCECC Bldg. Envelope Only.cck Page 1 of 2
COMcheck Software Version 4.0.8.1
Envelope Compliance Certificate
Section 1: Project Information
Energy Code: 2012 North Carolina Energy Conservation Code
Project Title: Rainbow Child Care Center
Project Type: New Construction
Construction Site:Owner/Agent:Designer/Contractor:
95 Centennial Parkway
Cameron, NC 28326
Amy Labadie
814 Development, LLC
3221 W. Big Beaver
Suite 111
Troy, MI 48084
Louise Craver
Interplan, LLC
604 Courtland Street
Orlando, FL 32804
407.645.5008
LCraver@interplanllc.com
Building Location (for weather data):Cameron, North Carolina
Climate Zone:3a
Vertical Glazing / Wall Area Pct.:22%
Building Use: Area Type Floor Area
1-Corporate Office (School/University) : Nonresidential 11992
Section 2: Envelope Assemblies and Requirements Checklist
Envelope PASSES: Design 5% better than code.
Envelope Assemblies:
Component Name/Description Gross
Area or
Perimeter
Cavity
R-Value
Cont.
R-Value
Proposed
U-Factor
Budget
U-Factor(a)
Orientation: NORTH
Right Wall: Wood-Framed, 16" o.c., [Bldg. Use 1 - Corporate Office]1381 21.0 0.0 0.062 0.064
Fixed windows (7): Vinyl/Fiberglass Frame:Fixed, Perf. Specs.:
Product ID Windgate picture, SHGC 0.30, PF 0.04, VT 0.57,
[Bldg. Use 1 - Corporate Office] (b)
56 ------0.270 0.320
Windows (7): Vinyl/Fiberglass Frame:Operable, Perf. Specs.:
Product ID Windgate Single hung, SHGC 0.29, PF 0.04, VT
0.56, [Bldg. Use 1 - Corporate Office] (b)
175 ------0.270 0.320
Service door: Insulated Metal, Swinging, [Bldg. Use 1 - Corporate
Office]
20 ------0.600 0.700
Doors (4): Glass (> 50% glazing):Metal Frame, Non-Entrance Door,
Perf. Specs.: Product ID unknown, SHGC 0.40, PF 0.04, VT
0.80, [Bldg. Use 1 - Corporate Office] (b)
80 ------0.650 0.450
Orientation: EAST
Front Wall: Wood-Framed, 16" o.c., [Bldg. Use 1 - Corporate Office]993 21.0 0.0 0.062 0.064
Fixed Windows (10): Vinyl/Fiberglass Frame:Fixed, Perf. Specs.:
Product ID windgate picture window, SHGC 0.30, PF 0.04, VT
0.57, [Bldg. Use 1 - Corporate Office] (b)
87 ------0.270 0.320
Windows (7): Vinyl/Fiberglass Frame:Fixed, Perf. Specs.: Product
ID windgate picture window, SHGC 0.29, PF 0.04, VT 0.56,
[Bldg. Use 1 - Corporate Office] (b)
123 ------0.270 0.320
Outdoor entry door, transom and sidelights: Glass (> 50%
glazing):Metal Frame, Entrance Door, Perf. Specs.: Product
ID unknown, SHGC 0.40, PF 0.04, VT 0.80, [Bldg. Use 1 -
Corporate Office] (b)
66 ------0.650 0.770
Orientation: SOUTH
Left Wall: Wood-Framed, 16" o.c., [Bldg. Use 1 - Corporate Office]1256 21.0 0.0 0.062 0.064
Windows (6): Vinyl/Fiberglass Frame:Operable, Perf. Specs.:
Product ID Windgate single-hung, SHGC 0.29, PF 0.04, VT
0.56, [Bldg. Use 1 - Corporate Office] (b)
150 ------0.270 0.320
Project Title: Rainbow Child Care Center Report date: 04/23/18
Data filename: P:\R\RainbowChildCare\2017.0643 - 95 Centennial Parkway, Spout Springs, NC\4 Support Documents\5 Calculations\2 Energy
and Load Calcs\17.0643 Rainbow Child Care Cameron, NC - 2012 NCECC Bldg. Envelope Only.cck Page 2 of 2
Doors (4): Glass (> 50% glazing):Metal Frame, Non-Entrance Door,
Perf. Specs.: Product ID unknown, SHGC 0.40, PF 0.04, VT
0.80, [Bldg. Use 1 - Corporate Office] (b)
80 ------0.650 0.450
Orientation: WEST
Rear Wall: Wood-Framed, 16" o.c., [Bldg. Use 1 - Corporate Office]728 21.0 0.0 0.062 0.064
Windows (2): Vinyl/Fiberglass Frame:Operable, Perf. Specs.:
Product ID Windgate single hung, SHGC 0.29, PF 0.04, VT 0.56,
[Bldg. Use 1 - Corporate Office] (b)
50 ------0.270 0.320
Doors (5): Glass (> 50% glazing):Metal Frame, Non-Entrance Door,
Perf. Specs.: Product ID unkown, SHGC 0.40, PF 0.04, VT 0.80,
[Bldg. Use 1 - Corporate Office] (b)
100 ------0.650 0.450
Orientation: UNSPECIFIED ORIENTATION
Roof 1: Attic Roof with Wood Joists, [Bldg. Use 1 - Corporate Office]12000 38.0 0.0 0.027 0.027
Floor 1: Slab-On-Grade:Unheated, Vertical 4 ft., [Bldg. Use 1 -
Corporate Office]
491 ---10.0 ------
(a) Budget U-factors are used for software baseline calculations ONLY, and are not code requirements.
(b) Fenestration product performance must be certified in accordance with NFRC and requires supporting documentation.
Air Leakage, Component Certification, and Vapor Retarder Requirements:
q 1.All joints and penetrations are caulked, gasketed or covered with a moisture vapor-permeable wrapping material installed in accordance
with the manufacturer's installation instructions.
q 2.Windows, doors, and skylights certified as meeting leakage requirements.
q 3.Component R-values & U-factors labeled as certified.
q 4.No roof insulation is installed on a suspended ceiling with removable ceiling panels.
q 5.'Other' components have supporting documentation for proposed U-Factors.
q 6.Insulation installed according to manufacturer's instructions, in substantial contact with the surface being insulated, and in a manner that
achieves the rated R-value without compressing the insulation.
q 7.Shaft vents serving stairs and elevators integral to the building envelope are equipped with motorized dampers.
Exceptions:
q Buildings without fire alarm system.
q Stairway vents open to the exterior.
q 8.Cargo doors and loading dock doors are weather sealed.
q 9.Recessed lighting fixtures installed in the building envelope are Type IC rated as meeting ASTM E283, are sealed with gasket or caulk.
q 10.Building entrance doors have a vestibule equipped with self-closing devices.
Exceptions:
q Building entrances with revolving doors.
q Doors not intended to be used as a building entrance.
q Doors that open directly from a space less than 3000 sq. ft. in area.
q Doors used primarily to facilitate vehicular movement or materials handling and adjacent personnel doors.
q Doors opening directly from a sleeping/dwelling unit.
q Buildings less than four stories above grade and less than 10,000 ft2 in area.
Additional Efficiency Package Requirements:
q 1.The high efficiency HVAC option has been selected as the additional efficiency package required by this energy code. Systems that do
not meet the performance requirement will be identified in the mechanical requirements checklist report.
Section 3: Compliance Statement
Compliance Statement: The proposed envelope design represented in this document is consistent with the building plans, specifications and
other calculations submitted with this permit application. The proposed envelope system has been designed to meet the 2012 North Carolina
Energy Conservation Code requirements in COMcheck Version 4.0.8.1 and to comply with the mandatory requirements in the Requirements
Checklist.
Name - Title Signature Date
Project Title: Rainbow Child Care Center Report date: 04/18/18
Data filename: G:\MEP\06 MECHANICAL DESIGN\HVAC Energy Calcs\Rainbow Child Care Center\17.0643 Rainbow Child Care Cameron,
NC - 2012 NCECC.cck Page 3 of 11
COMcheck Software Version 4.0.8.1
Interior Lighting Compliance
Certificate
Section 1: Project Information
Energy Code: 2012 North Carolina Energy Conservation Code
Project Title: Rainbow Child Care Center
Project Type: New Construction
Construction Site:Owner/Agent:Designer/Contractor:
95 Centennial Parkway
Cameron, NC 28326
Amy Labadie
814 Developments, LLC
3221 W. Big Beaver
Suite 111
Troy, MI 48084
Stacy Henson
Interplan, LCC
604 Courtland Street
Orlando, FL 32804
407.645.5008
shenson@interplanllc.com
Section 2: Interior Lighting and Power Calculation
A
Area Category
B
Floor Area
(ft2)
C
Allowed
Watts / ft2
D
Allowed Watts
(B x C)
Vestibule (Common Space Types:Corridor/Transition)69 0.65 45
Lobby (Common Space Types:Lobby)207 0.6 124
Reception (Common Space Types:Education Laboratory)255 1.28 326
Director's Office (Office:Enclosed)138 1.11 153
Hallway (Common Space Types:Corridor/Transition)112 0.65 73
Kitchen (Common Space Types:Food Preparation)250 0.99 248
Conference Room (Common Space Types:Conference/Meeting/Multipurpose)74 1.29 95
Infant 1/2 (Common Space Types:Education Laboratory)1123 1.28 1437
Young Pre-School (Common Space Types:Education Laboratory)580 1.28 742
Varsity (Common Space Types:Education Laboratory)910 1.28 1165
Pre-School 1/2 (Common Space Types:Education Laboratory)1301 1.28 1665
Pre-K 1/2 (Common Space Types:Education Laboratory)1392 1.28 1782
Toddler 1/2 (Common Space Types:Education Laboratory)1329 1.28 1701
Gym (Gymnasium:Playing Area)910 1.35 1229
Corridor 1/Central Corridor (Common Space Types:Corridor/Transition)1143 0.65 743
Laundry (Common Space Types:Education Laboratory)68 1.28 87
Stairs (Common Space Types:Stairway)59 0.69 41
Storage/Pantry/Utility/Closet/Gym Equipment/IT Closet (Common Space
Types:Active Storage)
559 0.63 352
Staff Lounge (Common Space Types:Conference/Meeting/Multipurpose)89 1.29 115
Restrooms (Common Space Types:Restroom)669 0.84 562
Total Allowed Watts =12685
Section 3: Interior Lighting Fixture Schedule
A
Fixture ID : Description / Lamp / Wattage Per Lamp / Ballast
B
Lamps/
Fixture
C
# of
Fixtures
D
Fixture
Watt.
E
(C X D)
Vestibule ( Common Space Types:Corridor/Transition 69 sq.ft.)
Linear Fluorescent 1: E: Other: Electronic:1 2 54 108
Linear Fluorescent 2: K: Other: Electronic:3 1 54 54
Lobby ( Common Space Types:Lobby 207 sq.ft.)
Linear Fluorescent 3: B: 48" T8 32W: Electronic:2 4 64 256
Reception ( Common Space Types:Education Laboratory 255 sq.ft.)
Linear Fluorescent 3 copy 1: B: 48" T8 32W: Electronic:2 4 64 256
Project Title: Rainbow Child Care Center Report date: 04/18/18
Data filename: G:\MEP\06 MECHANICAL DESIGN\HVAC Energy Calcs\Rainbow Child Care Center\17.0643 Rainbow Child Care Cameron,
NC - 2012 NCECC.cck Page 4 of 11
Compact Fluorescent 1: J: Triple 4-pin 18W: Electronic:1 3 18 54
Director's Office ( Office:Enclosed 138 sq.ft.)
Linear Fluorescent 5: A: 48" T8 32W: Electronic:3 2 87 174
Hallway ( Common Space Types:Corridor/Transition 112 sq.ft.)
Linear Fluorescent 3 copy 1: B: 48" T8 32W: Electronic:2 2 64 128
Kitchen ( Common Space Types:Food Preparation 250 sq.ft.)
Linear Fluorescent 5 copy 1: A: 48" T8 32W: Electronic:3 3 87 261
Conference Room ( Common Space Types:Conference/Meeting/Multipurpose 74 sq.ft.)
Linear Fluorescent 5 copy 2: A: 48" T8 32W: Electronic:3 1 87 87
Infant 1/2 ( Common Space Types:Education Laboratory 1123 sq.ft.)
Linear Fluorescent 5 copy 3: A: 48" T8 32W: Electronic:3 12 87 1044
Linear Fluorescent 11: H: 36" T8 25W: Electronic:2 2 25 50
Young Pre-School ( Common Space Types:Education Laboratory 580 sq.ft.)
Linear Fluorescent 5 copy 4: A: 48" T8 32W: Electronic:3 7 87 609
Varsity ( Common Space Types:Education Laboratory 910 sq.ft.)
Linear Fluorescent 5 copy 5: A: 48" T8 32W: Electronic:3 10 87 870
Pre-School 1/2 ( Common Space Types:Education Laboratory 1301 sq.ft.)
Linear Fluorescent 5 copy 6: A: 48" T8 32W: Electronic:3 20 87 1740
Pre-K 1/2 ( Common Space Types:Education Laboratory 1392 sq.ft.)
Linear Fluorescent 5 copy 7: A: 48" T8 32W: Electronic:3 18 87 1566
Toddler 1/2 ( Common Space Types:Education Laboratory 1329 sq.ft.)
Linear Fluorescent 5 copy 8: A: 48" T8 32W: Electronic:3 16 87 1392
Linear Fluorescent 11 copy 1: H: 36" T8 25W: Electronic:2 2 25 50
Gym ( Gymnasium:Playing Area 910 sq.ft.)
Linear Fluorescent 18: C: 48" T8 32W: Electronic:4 8 128 1024
Corridor 1/Central Corridor ( Common Space Types:Corridor/Transition 1143 sq.ft.)
Linear Fluorescent 3 copy 2: B: 48" T8 32W: Electronic:2 13 64 832
Laundry ( Common Space Types:Education Laboratory 68 sq.ft.)
Linear Fluorescent 3 copy 3: B: 48" T8 32W: Electronic:2 1 64 64
Stairs ( Common Space Types:Stairway 59 sq.ft.)
Linear Fluorescent 21: D: 48" T8 32W: Electronic:2 1 64 64
Storage/Pantry/Utility/Closet/Gym Equipment/IT Closet ( Common Space Types:Active Storage 559 sq.ft.)
Linear Fluorescent 21 copy 1: D: 48" T8 32W: Electronic:2 7 64 448
Linear Fluorescent 18 copy 1: C: 48" T8 32W: Electronic:4 1 128 128
Staff Lounge ( Common Space Types:Conference/Meeting/Multipurpose 89 sq.ft.)
Linear Fluorescent 5 copy 3: A: 48" T8 32W: Electronic:3 1 87 87
Restrooms ( Common Space Types:Restroom 669 sq.ft.)
Linear Fluorescent 3 copy 3: B: 48" T8 32W: Electronic:2 10 64 640
Total Proposed Watts =11986
Section 4: Requirements Checklist
Interior Lighting PASSES: Design 6% better than code.
Lighting Wattage:
q 1.Total proposed watts must be less than or equal to total allowed watts.
Allowed Watts Proposed Watts Complies 12685 11986 YES
Controls, Switching, and Wiring:
q 2.Separate lighting controls present for: Display/Accent Lighting, Case Lighting, lighting for nonvisual applications (e.g., such as plant
growth and food warming), lighting equipment that is for sale or for demonstrations in lighting education.
q 3.Hotel and motel guest rooms and guest suites have a master control device at the main room entry that controls all permanently
installed luminaires and switched receptacles.
q 4.Supplemental task lighting has a control device integral to the luminaires or be controlled by a wall-mounted control device provided the
control device is readily accessible and located so that the occupant can see the controlled lighting..
q 5.Independent controls for each space (switch/occupancy sensor).
Exceptions:
q Areas designated as security or emergency areas that must be continuously illuminated.
Project Title: Rainbow Child Care Center Report date: 04/18/18
Data filename: G:\MEP\06 MECHANICAL DESIGN\HVAC Energy Calcs\Rainbow Child Care Center\17.0643 Rainbow Child Care Cameron,
NC - 2012 NCECC.cck Page 5 of 11
q Lighting in stairways or corridors that are elements of the means of egress.
q 6.Individual dwelling units separately metered.
q 7.Medical task lighting or art/history display lighting claimed to be exempt from compliance has a control device independent of the control
of the nonexempt lighting.
q 8.Each space required to have a manual control also allows for reducing the connected lighting load by at least 50 percent by either
controlling all luminaires, dual switching of alternate rows of luminaires, alternate luminaires, or alternate lamps, switching the middle
lamp luminaires independently of other lamps, or switching each luminaire or each lamp.
Exceptions:
q Only one luminaire in space.
q An occupant-sensing device controls the area.
q The area is a corridor, storeroom, restroom, public lobby or sleeping unit.
q Areas that use less than 0.6 Watts/sq.ft.
q 9.Automatic lighting shutoff control in buildings larger than 5,000 sq.ft.
Exceptions:
q Sleeping units, patient care areas; and spaces where automatic shutoff would endanger safety or security.
q 10.Photocell/astronomical time switch on exterior lights.
Exceptions:
q Lighting intended for 24 hour use.
q 11.Tandem wired one-lamp and three-lamp ballasted luminaires (No single-lamp ballasts).
Exceptions:
q Electronic high-frequency ballasts; Luminaires on emergency circuits or with no available pair.
q 12.Lighting controls are tested to ensure that control devices, components, equipment, and systems are calibrated, adjusted and operate
in accordance with approved plans and specifications. Sequences of operation shall be functionally tested to ensure they operate in
accordance with approved plans and specifications.
Section 5: Compliance Statement
Compliance Statement: The proposed lighting design represented in this document is consistent with the building plans, specifications and
other calculations submitted with this permit application. The proposed lighting system has been designed to meet the 2012 North Carolina
Energy Conservation Code requirements in COMcheck Version 4.0.8.1 and to comply with the mandatory requirements in the Requirements
Checklist.
Stacy Henson
Name - Title Signature Date
Project Title: Rainbow Child Care Center Report date: 04/18/18
Data filename: G:\MEP\06 MECHANICAL DESIGN\HVAC Energy Calcs\Rainbow Child Care Center\17.0643 Rainbow Child Care Cameron,
NC - 2012 NCECC.cck Page 6 of 11
COMcheck Software Version 4.0.8.1
Exterior Lighting Compliance
Certificate
Section 1: Project Information
Energy Code: 2012 North Carolina Energy Conservation Code
Project Title: Rainbow Child Care Center
Project Type: New Construction
Exterior Lighting Zone: 2 (Neighborhood business district)
Construction Site:Owner/Agent:Designer/Contractor:
95 Centennial Parkway
Cameron, NC 28326
Amy Labadie
814 Developments, LLC
3221 W. Big Beaver
Suite 111
Troy, MI 48084
Stacy Henson
Interplan, LCC
604 Courtland Street
Orlando, FL 32804
407.645.5008
shenson@interplanllc.com
Section 2: Exterior Lighting Area/Surface Power Calculation
A
Exterior Area/Surface
B
Quantity
C
Allowed
Watts
/ Unit
D
Tradable
Wattage
E
Allowed
Watts
(B x C)
F
Proposed
Watts
Front Door (Main entry)16 ft of door width 20 Yes 320 52
Building Facade (Illuminated length of facade wall or
surface)
467 ft 2.5 No 1168 840
Total Tradable Watts* =320 52
Total Allowed Watts =1488
Total Allowed Supplemental Watts** =600
* Wattage tradeoffs are only allowed between tradable areas/surfaces.
** A supplemental allowance equal to 600 watts may be applied toward compliance of both non-tradable and tradable areas/surfaces.
Section 3: Exterior Lighting Fixture Schedule
A
Fixture ID : Description / Lamp / Wattage Per Lamp / Ballast
B
Lamps/
Fixture
C
# of
Fixtures
D
Fixture
Watt.
E
(C X D)
Front Door ( Main entry 16 ft of door width): Tradable Wattage
Compact Fluorescent 1: Twin Tube 13W: Electronic:2 2 26 52
Building Facade ( Illuminated length of facade wall or surface 467 ft): Non-tradable Wattage
Compact Fluorescent 2: Triple 4-pin 42W: Electronic:1 20 42 840
Total Tradable Proposed Watts =52
Section 4: Requirements Checklist
Lighting Wattage:
q 1.Within each non-tradable area/surface, total proposed watts must be less than or equal to total allowed watts. Across all tradable
areas/surfaces, total proposed watts must be less than or equal to total allowed watts.
Compliance:Passes.
Controls, Switching, and Wiring:
q 2.All exemption claims are associated with fixtures that have a control device independent of the control of the nonexempt lighting.
q 3.Lighting not designated for dusk-to-dawn operation is controlled by either a a photosensor (with time switch), or an astronomical time
switch.
q 4.Lighting designated for dusk-to-dawn operation is controlled by an astronomical time switch or photosensor.
Project Title: Rainbow Child Care Center Report date: 04/18/18
Data filename: G:\MEP\06 MECHANICAL DESIGN\HVAC Energy Calcs\Rainbow Child Care Center\17.0643 Rainbow Child Care Cameron,
NC - 2012 NCECC.cck Page 7 of 11
q 5.All time switches are capable of retaining programming and the time setting during loss of power for a period of at least 10 hours.
q 6.Lighting controls are tested to ensure that control devices, components, equipment, and systems are calibrated, adjusted and operate
in accordance with approved plans and specifications. Sequences of operation shall be functionally tested to ensure they operate in
accordance with approved plans and specifications.
Exterior Lighting Efficacy and Application:
q 7.All exterior building grounds luminaires that operate at greater than 100W have minimum efficacy of 60 lumen/watt.
Exceptions:
q Lighting that has been claimed as exempt and is identified as such in Section 3 table above.
q Lighting that is specifically designated as required by a health or life safety statue, ordinance, or regulation.
q Emergency lighting that is automatically off during normal building operation.
q Lighting that is controlled by motion sensor.
q 8.Exterior lighting fixtures are fully shielded fixtures unless a lighting plan is submitted showing that the use of alternative fixtures would
provide greater energy efficiency.
Exceptions:
q Luminaires with an output of 150 Watts or less, or the equivalent light output.
q Luminaires intended to illuminate the facade of buildings or to illuminate other objects including but not limited to flagpoles,
landscape and water features, statuary and works of art.
q Luminaires for historic lighting on the premises of an historic building as defined in the or within a designated historic district.
q Outdoor sports facility lighting of the participant sport area.
q Emergency exit discharge lighting.
q Sign illumination, festoon lighting, low voltage landscape lighting.
q Temporary lighting for emergency, repair, construction, special events or similar activities.
Section 5: Compliance Statement
Compliance Statement: The proposed exterior lighting design represented in this document is consistent with the building plans, specifications
and other calculations submitted with this permit application. The proposed lighting system has been designed to meet the 2012 North
Carolina Energy Conservation Code requirements in COMcheck Version 4.0.8.1 and to comply with the mandatory requirements in the
Requirements Checklist.
Stacy Henson
Name - Title Signature Date
Project Title: Rainbow Child Care Center Report date: 04/18/18
Data filename: G:\MEP\06 MECHANICAL DESIGN\HVAC Energy Calcs\Rainbow Child Care Center\17.0643 Rainbow Child Care Cameron,
NC - 2012 NCECC.cck Page 8 of 11
COMcheck Software Version 4.0.8.1
Mechanical Compliance Certificate
Section 1: Project Information
Energy Code: 2012 North Carolina Energy Conservation Code
Project Title: Rainbow Child Care Center
Project Type: New Construction
Construction Site:Owner/Agent:Designer/Contractor:
95 Centennial Parkway
Cameron, NC 28326
Amy Labadie
814 Developments, LLC
3221 W. Big Beaver
Suite 111
Troy, MI 48084
Stacy Henson
Interplan, LCC
604 Courtland Street
Orlando, FL 32804
407.645.5008
shenson@interplanllc.com
Section 2: General Information
Building Location (for weather data):Cameron, North Carolina
Climate Zone:3a
Section 3: Mechanical Systems List
Quantity System Type & Description
1 GF-1 (Single Zone) :
Heating: 1 each - Central Furnace, Gas, Capacity = 126 kBtu/h
Proposed Efficiency = 95.00% Et, Required Efficiency = 92.00% Et
Cooling: 1 each - Split System, Capacity = 57 kBtu/h, Air-Cooled Condenser, Air Economizer
Proposed Efficiency = 15.00 SEER, Required Efficiency: 15.00 SEER + 12.5 EER
Fan System: None
1 GF-2 (Single Zone) :
Heating: 1 each - Central Furnace, Gas, Capacity = 126 kBtu/h
Proposed Efficiency = 95.00% Et, Required Efficiency = 92.00% Et
Cooling: 1 each - Split System, Capacity = 57 kBtu/h, Air-Cooled Condenser, Air Economizer
Proposed Efficiency = 15.00 SEER, Required Efficiency: 15.00 SEER + 12.5 EER
Fan System: None
1 GF-3 (Single Zone) :
Heating: 1 each - Central Furnace, Gas, Capacity = 126 kBtu/h
Proposed Efficiency = 95.00% Et, Required Efficiency = 92.00% Et
Cooling: 1 each - Split System, Capacity = 57 kBtu/h, Air-Cooled Condenser, Air Economizer
Proposed Efficiency = 15.00 SEER, Required Efficiency: 15.00 SEER + 12.5 EER
Fan System: None
1 GF-4 (Single Zone) :
Heating: 1 each - Central Furnace, Gas, Capacity = 126 kBtu/h
Proposed Efficiency = 95.00% Et, Required Efficiency = 92.00% Et
Cooling: 1 each - Split System, Capacity = 57 kBtu/h, Air-Cooled Condenser, Air Economizer
Proposed Efficiency = 15.00 SEER, Required Efficiency: 15.00 SEER + 12.5 EER
Fan System: None
1 GF-5 (Single Zone) :
Heating: 1 each - Central Furnace, Gas, Capacity = 126 kBtu/h
Proposed Efficiency = 95.00% Et, Required Efficiency = 92.00% Et
Cooling: 1 each - Split System, Capacity = 57 kBtu/h, Air-Cooled Condenser, Air Economizer
Proposed Efficiency = 15.00 SEER, Required Efficiency: 15.00 SEER + 12.5 EER
Fan System: None
1 GF-6 (Single Zone) :
Heating: 1 each - Central Furnace, Gas, Capacity = 126 kBtu/h
Proposed Efficiency = 95.00% Et, Required Efficiency = 92.00% Et
Project Title: Rainbow Child Care Center Report date: 04/18/18
Data filename: G:\MEP\06 MECHANICAL DESIGN\HVAC Energy Calcs\Rainbow Child Care Center\17.0643 Rainbow Child Care Cameron,
NC - 2012 NCECC.cck Page 9 of 11
Cooling: 1 each - Split System, Capacity = 57 kBtu/h, Air-Cooled Condenser, Air Economizer
Proposed Efficiency = 15.00 SEER, Required Efficiency: 15.00 SEER + 12.5 EER
Fan System: None
1 GF-7 (Single Zone) :
Heating: 1 each - Central Furnace, Gas, Capacity = 126 kBtu/h
Proposed Efficiency = 95.00% Et, Required Efficiency = 92.00% Et
Cooling: 1 each - Split System, Capacity = 57 kBtu/h, Air-Cooled Condenser, No Economizer, Economizer
exception: None
Proposed Efficiency = 15.00 SEER, Required Efficiency: 15.00 SEER + 12.5 EER
Fan System: None
1 Water Heater 1:
Gas Storage Water Heater, Capacity: 100 gallons, Input Rating: 120 kBtu/h w/ Circulation Pump
Proposed Efficiency: 90.00 % Et, Required Efficiency: 80.00 % Et
Section 4: Requirements Checklist
Additional Efficiency Package Requirements:
q 1.The high efficiency HVAC option has been selected as the additional efficiency package required by this energy code. Systems not
satisfying the performance requirement are identified in the specific system requirement section below. Full compliance with this
efficiency option requires inspection and verification that each system meets the required performance criteria.
Requirements Specific To: GF-1 :
q 1.Equipment minimum efficiency: Central Furnace (Gas): 92.00 % Et (or 92% AFUE)
q 2.Equipment minimum efficiency: Split System: 15.00 SEER + 12.5 EER
Requirements Specific To: GF-2 :
q 1.Equipment minimum efficiency: Central Furnace (Gas): 92.00 % Et (or 92% AFUE)
q 2.Equipment minimum efficiency: Split System: 15.00 SEER + 12.5 EER
Requirements Specific To: GF-3 :
q 1.Equipment minimum efficiency: Central Furnace (Gas): 92.00 % Et (or 92% AFUE)
q 2.Equipment minimum efficiency: Split System: 15.00 SEER + 12.5 EER
Requirements Specific To: GF-4 :
q 1.Equipment minimum efficiency: Central Furnace (Gas): 92.00 % Et (or 92% AFUE)
q 2.Equipment minimum efficiency: Split System: 15.00 SEER + 12.5 EER
Requirements Specific To: GF-5 :
q 1.Equipment minimum efficiency: Central Furnace (Gas): 92.00 % Et (or 92% AFUE)
q 2.Equipment minimum efficiency: Split System: 15.00 SEER + 12.5 EER
Requirements Specific To: GF-6 :
q 1.Equipment minimum efficiency: Central Furnace (Gas): 92.00 % Et (or 92% AFUE)
q 2.Equipment minimum efficiency: Split System: 15.00 SEER + 12.5 EER
Requirements Specific To: GF-7 :
q 1.Equipment minimum efficiency: Central Furnace (Gas): 92.00 % Et (or 92% AFUE)
q 2.Equipment minimum efficiency: Split System: 15.00 SEER + 12.5 EER
Requirements Specific To: Water Heater 1 :
q 1.Water heating equipment meets minimum efficiency requirements: Gas Storage Water Heater efficiency: 80.00 % Et (161 SL,
kBtu/h)
q 2.All piping in circulating system insulated
q 3.Hot water storage temperature controls that allow setpoint of 90°F for non-dwelling units and 110°F for dwelling units.
q 4.Automatic time control of heat tapes and recirculating systems present
q 5.Controls will shut off operation of circulating pump between water heater/boiler and storage tanks within 5 minutes after end of heating
cycle
Generic Requirements: Must be met by all systems to which the requirement is applicable:
q 1.Plant equipment and system capacity no greater than needed to meet loads
Exception(s):
q Standby equipment automatically off when primary system is operating
q Multiple units controlled to sequence operation as a function of load
q 2.Minimum one temperature control device per system
q 3.Minimum one humidity control device per installed humidification/dehumidification system
Project Title: Rainbow Child Care Center Report date: 04/18/18
Data filename: G:\MEP\06 MECHANICAL DESIGN\HVAC Energy Calcs\Rainbow Child Care Center\17.0643 Rainbow Child Care Cameron,
NC - 2012 NCECC.cck Page 10 of 11
q 4.Load calculations per ASHRAE/ACCA Standard 183.
q 5.Automatic Controls: Setback to 55°F (heat) and 85°F (cool); 7-day clock, 2-hour occupant override, 10-hour backup
Exception(s):
q Continuously operating zones
q 6.Outside-air source for ventilation; system capable of reducing OSA to required minimum
q 7.R-5 supply and return air duct insulation in unconditioned spaces
R-8 supply and return air duct insulation outside the building
R-8 insulation between ducts and the building exterior when ducts are part of a building assembly
Exception(s):
q Ducts located within equipment
q Ducts with interior and exterior temperature difference not exceeding 15°F.
q 8.Mechanical fasteners and sealants used to connect ducts and air distribution equipment
q 9.Ducts sealed - longitudinal seams on rigid ducts; transverse seams on all ducts; UL 181A or 181B tapes and mastics
q 10.Hot water pipe insulation: 1.5 in. for pipes <=1.5 in. and 2 in. for pipes >1.5 in.
Chilled water/refrigerant/brine pipe insulation: 1.5 in. for pipes <=1.5 in. and 1.5 in. for pipes >1.5 in.
Steam pipe insulation: 1.5 in. for pipes <=1.5 in. and 3 in. for pipes >1.5 in.
Exception(s):
q Piping within HVAC equipment.
q Fluid temperatures between 55 and 105°F.
q Fluid not heated or cooled with renewable energy.
q Piping within room fan-coil (with AHRI440 rating) and unit ventilators (with AHRI840 rating).
q Runouts <4 ft in length.
q 11.Operation and maintenance manual provided to building owner
q 12.Thermostatic controls have 5°F deadband
Exception(s):
q Thermostats requiring manual changeover between heating and cooling
q Special occupancy or special applications where wide temperature ranges are not acceptable and are approved by the authority
having jurisdiction.
q 13.Balancing devices provided in accordance with IMC 603.17
q 14.Ventilation systems in buildings over 10,000 ft2 of conditioned area have demand controls. DCV systems are capable of reducing
outside supply air to at least 50% below design ventilation rates. In all buildings, spaces larger than 500 ft2 with a maximum occupant
load of 40 or more people per 1,000 ft2 of floor area control ventilation supply air flow by monitoring indoor air quality conditions.
Exception(s):
q Systems with heat recovery.
q Building spaces where the primary ventilation needs are for process loads, including laboratories and hospital.
q Individual units with less than 65 kBtu/h of cooling capacity.
q 15.Motorized, automatic shutoff dampers required on exhaust and outdoor air supply openings
Exception(s):
q Gravity dampers acceptable in buildings <3 stories
q 16.Automatic controls for freeze protection systems present
q 17.Exhaust air heat recovery included for systems 5,000 cfm or greater with more than 70% outside air fraction or specifically exempted
Exception(s):
q Hazardous exhaust systems, commercial kitchen and clothes dryer exhaust systems that the International Mechanical Code
prohibits the use of energy recovery systems.
q Systems serving spaces that are heated and not cooled to less than 60°F.
q Where more than 60 percent of the outdoor heating energy is provided from site-recovered or site solar energy.
q Heating systems in climates with less than 3600 HDD.
q Cooling systems in climates with a 1 percent cooling design wet-bulb temperature less than 64°F.
q Systems requiring dehumidification that employ energy recovery in series with the cooling coil.
q Laboratory fume hood exhaust systems that have either a variable air volume system capable of reducing exhaust and makeup air
volume to 50 percent or less of design values or, a separate make up air supply meeting the following makeup air requirements:
a) at least 75 percent of exhaust flow rate, b) heated to no more than 2°F below room setpoint temperature, c) cooled to no lower
than 3°F above room setpoint temperature, d) no humidification added, e) no simultaneous heating and cooling.
Section 5: Compliance Statement
Compliance Statement: The proposed mechanical design represented in this document is consistent with the building plans, specifications
and other calculations submitted with this permit application. The proposed mechanical systems have been designed to meet the 2012 North
Project Title: Rainbow Child Care Center Report date: 04/18/18
Data filename: G:\MEP\06 MECHANICAL DESIGN\HVAC Energy Calcs\Rainbow Child Care Center\17.0643 Rainbow Child Care Cameron,
NC - 2012 NCECC.cck Page 11 of 11
Carolina Energy Conservation Code requirements in COMcheck Version 4.0.8.1 and to comply with the mandatory requirements in the
Requirements Checklist.
Stacy Henson
Name - Title Signature Date
Section 6: Post Construction Compliance Statement
q HVAC record drawings of the actual installation, system capacities, calibration information, and performance data for each equipment
provided to the owner.
q HVAC O&M documents for all mechanical equipment and system provided to the owner by the mechanical contractor.
q Written HVAC balancing and operations report provided to the owner.
The above post construction requirements have been completed.
Principal Mechanical Designer-Name Signature Date
04/20/18
T.100
COVER SHEET
JCRCCHECKED:
PROJECT NO:
DATE:
REVISIONS
NO DATE REMARKS
CORPORATE SEAL:
DRAWN:
SEAL:
THIS DOCUMENT IS "NOT FOR CONSTRUCTION"
UNLESS THE ARCHITECT OR ENGINEER'S
SIGNATURE AND SEAL APPEAR BELOW.
RAINBOW CHILD
CARE CENTER
C-PROTOTYPE
95 CENTENNIAL PARKWAY
SPOUT SPRINGS, NC 28326
2017.0643
COPYRIGHT cP-0215
2018 INTERPLAN PLLC RESERVES COPYRIGHT & OTHER RIGHTS RESTRICTING THESE DOCUMENTS TO THE ORIGINAL SITE OR PURPOSE FOR WHICH THEY WERE PREPARED. REPRODUCTIONS, CHANGES OR ASSIGNMENTS ARE PROHIBITED.604 COURTLAND STREET
SUITE 100
ORLANDO, FLORIDA 32804
PH 407.645.5008
FX 407.629.9124
ARCHITECTURE
ENGINEERING
INTERIOR DESIGN
PROJECT MANAGEMENT
Rainbow Child
Care Center
Code InformationInterior Finish Flame
FROM TABLE 803.5 (GROUP E)
1. EXIT ENCLOSURES AND EXIT PASSAGEWAYS: CLASS
A, FLAME SPREAD 0-25; SMOKE DEVELOPED 0-450
2. CORRIDORS: CLASS B, FLAME SPREAD 26-75; SMOKE
DEVELOPED 0-450
3. ROOMS AND ENCLOSED SPACES: CLASS C, FLAME
SPREAD 76-200; SMOKE DEVELOPED 0-450
Building Code Note:
Deferred Submittal Note:
Type of Construction
Type V-B, Unsprinklered
Building Occupancy
E (Educational)
Per Sections 305.2 & 308.5.2 Exception.
Occupant Loads
1. Per Building Code
Table 1004.1.1
Maximum Floor Area Allowances per Occupant Daycare:
35 net sq. ft. / occupant
Classrooms: 6,303 s.f. / 35 = 180
Exercise (Gym): 943 s.f. / 50 = 19
Business (Office/Reception)= 240 s.f. /100 = 3
Kitchen: 253 s.f. / 200 = 2
Maximum Occupant Load for Egress = 204
2. Actual Occupant Load
(Maximum operational occupancy per state of North Carolina
Childcare licensing) Refer to Sheet A.102 for complete Licensing
Chart.
Children: 149 children
Director, Teachers, Staff: 23 occupants
Total Number of Occupants:172 occupants
Height and Area Limitations for E:
Maximum Height:1 Story (40'-0")
Proposed Height: 1 Story 25'-6 3/4"
Building Area:9,500 s.f.
Building Area Modifications:
Per section 506.2 (NCSBC 2012)
- Frontage Increase Calculation
If = (F/P - 0.25)W/30
If = 100 [491/491 - 0.25] 30/30 = 75% Increase
9,500 Sq. Ft. (.75) = 7,125 Sq. Ft. Increase
9,500 Sq. Ft. + 7,125 Sq. Ft. = 16,625 Allowable Sq. Ft.
Maximum Area Allowed:16,625 Sq. Ft.
Total Building Gross Area:11,992 Sq. Ft.
First Floor Gross Area:11,992 Sq. Ft.
Equipment Platform Area *: 514 Sq. Ft.
* Per Section 505.5, Equipment Platforms are excluded from the
Fire Area calculation.
Fire Protection:
Automatic Fire Sprinkler System: NO
Per Section 903.2.3, an Automatic Fire Sprinkler system is not
required for Fire Areas less than 12,000 s.f. in Group E.
Corridor Protection:
Fire Resistance Rating is not required according to NCSBC & FPC
Section 1018.1 g for Group E.
Protection of Incidental Accessory Occupancies (Section 508.2.5):
Laundry: no separation required (area is less than 100 s.f.)
Separation of Accessory Occupancies (Section 508.2):
General Closets, Gym Equipment Closets, IT Closet, Kitchen,
Pantry, Utility Room, Staff Lounge & Conference Rm.
Total Area of Accessories = 1,003 s.f.
10% of Total Building Area= 11,992 x .10= 1,199 s.f.
1,003s.f. < 1,199 s.f.
Separation of Accessory Spaces is not required according to
508.2.3 & 508.2.4.
Stair Enclosure (Section 505.5)
Equipment platforms shall not be a part of any mezzanine and
such platforms and the walkways, stairs, alternating tread devices
and ladders providing access to an equipment platform shall not
serve as a part of the means of egress from the building.
ALL WORK IS TO COMPLY WITH THE BUILDING CODES
MENTIONED IN THE "CODE INFORMATION" SECTION IN THIS
SHEET.
THE REGISTERED DESIGN PROFESSIONAL IS:
LOUISE CRAVER.
THESE CONSTRUCTION DOCUMENTS WERE PRODUCED
FOR COMPLIANCE WITH THE CONSTRUCTION CODES IN
EFFECT AT TIME OF PERMIT SUBMITTAL. ALL ENGINEERS,
CONTRACTORS AND SUPPLIERS INVOLVED WITH THIS
PROJECT SHALL COMPLY WITH THE SAME CODES.
ISSUED AND APPROVED CODE MODIFICATIONS
AND/OR BOARDS OF APPEALS RULING AND WHENEVER
REQUIRED SHALL PROVIDE SHOP DRAWINGS AND
SUBMITTALS CLEARLY DESCRIBING COMPLIANCE TO THE
REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE
CHARGE FOR REVIEW AND APPROVAL
Sheet Index:
T.100 Cover Sheet
APPX-B Appendix B (NC)
T.101 Fire & Life Safety Plan
A.100 First Floor Wall Framing Plan
A.101 First Floor Plan
A.102 First Floor Key Plan
A.102.1 Enlarged Floor Plans
A.103 Attic Plan
A.104 Roof Plan
A.105 Finish Plan
A.200 Exterior Elevations
A.201 Exterior Elevations
A.300 Building Sections
A.301 Building Sections
A.302 Building Sections
A.302.1 Building Sections
A.303 Wall Sections
A.304 Wall Sections
A.305 Section Details
A.400 Interior Elevations
A.401 Interior Elevations
A.402 Interior Elevations
A.500 Schedules
S.000 General Structural Notes
S.100 Foundation Plan
S.101 Roof Framing Plan
S.102 Equipment Platform Framing Plan
S.200 Typical Schedules & Details
S.300 Sections and Details
S.301 Sections and Details
M.001 Mechanical Cover Sheet
M.100 Main Level Mechanical Plan
M.200 Upper Level Mechanical Plan
M.300 Mechanical Schedules
M.400 Mechanical Details
M.500 Mechanical Specifications
P.001 Plumbing Cover Sheet
P.002 Slab Dimension Plan
P.100 Underground Piping Plan
P.101 Main Level Piping Plan
P.200 Upper Level Piping Plan & Riser Diagrams
P.300 Plumbing Schedules
P.400 Plumbing Details
P.401 Plumbing Details
E.000 Electrical Cover Sheet
E.010 Electrical Site Plan
E.100 Electrical Plan - Lighting
E.101 Electrical Plan - Power
E.102 Electrical Plan - Fire Alarm
E.103 Electrical Plan - Equipment Platform
E.201 Electrical Details
E.202 Panel Schedules
E.204 Electrical Specifications
Design Professionals:
ARCHITECT CIVIL ENGINEER
SHEET TO BE FOUND ON
A.C.T.ACOUSTICAL CEILING TILE
A.F.F.ABOVE FINISHED FLOOR
ALUM.ALUMINUM
ANOD.ANODIZED
APA AMERICAN PLYWOOD ASSOCIATION
A.T.ALUMINUM THRESHOLD
BRD.BOARD
C. TILE CERAMIC TILE
CLG.CEILING
CPT.CARPET
COORD.COORDINATE
CONC.CONCRETE
DIA.DIAMETER
ELEC.ELECTRICAL
EXIST.EXISTING
EXT.EXTERIOR
FND.FOUNDATION
Abbreviations
Symbols Legend:
X
X.X
A
CL
SECTION OR
ELEVATION NUMBER
DIRECTION OF VIEW
KEYED NOTE
CENTER LINE
ELEVATION MARKER
START OF WORK
A DOOR SYMBOL
WALL TYPEA
A FINISH NOTE
ADDENDUM
BULLETIN
1
1
Government
Agencies:
Schedule Ratings:
C- PROTOTYPE
Location Map:Vicinity Map:
STRUCTURAL ENGINEER
N
Plumbing Code Analysis:
Children Restrooms:
Water Closets = 1 per 15 Occupants (NCSPC Section 403)
Required: 149 / 15 = 9.93 = 10 Provided: 15 water closets
Lavatories = 1 per 25 Occupants (NCSPC Section 403)
Required: 149 / 25 = 5.96 = 6 Provided: 17 lavatories
Adult Restrooms:
Water Closets = 1 per 25 Occupants (NCSPC Section 403)
Required: 23 / 25 = 0.92 = 1 Provided: 1 water closet
Lavatories = 1 per 35 Occupants (NCSPC Section 403)
Required: 23 / 35 = 0.66 = 1 Provided: 1 lavatory
Drinking Fountains: 1 per 100 Occupants (NCSPC Section 403)
Required: 172 / 100 = 1.72 = 2 Provided: 2 (1 high + 1 low)
Effective Codes:
Revision Issue Log:
N
95 CENTENNIAL PARKWAY
CAMERON, NC 28326
SITE SITE
MECHANICAL ENGINEER
PLUMBING ENGINEER
ELECTRICAL ENGINEER
BUILDING CODE: North Carolina State Building Code, EDITION: 2012
PLUMBING CODE: North Carolina Plumbing Code, EDITION: 2012
MECHANICAL CODE: North Carolina Mechanical Code, EDITION: 2012
ELECTRIC CODE: National Electric Code, EDITION: 2014
ACCESSIBILITY CODE: North Carolina Building Code, Ch.11, EDITION: 2012
ENERGY CODE: North Carolina Energy Code, EDITION: 2012
FIRE CODE: North Carolina Fire Prevention Code, EDITION: 2012
FLUOR.FLUORESCENT
FTG.FOOTING
G.C.GENERAL CONTRACTOR
GALV.GALVANIZED
GYP. BRD.GYPSUM BOARD
HGT.HEIGHT
INSUL.INSULATION
JST.JOIST
LAM.LAMINATE
L.V.L.LAMINATED VENEER LUMBER
MAT'L MATERIAL
MAX.MAXIMUM
MECH.MECHANICAL
MIN.MINIMUM
MTD.MOUNTED
MTG.MOUNTING
MTL.METAL
NOM.NOMINAL
OPNG.OPENING
O.C.ON CENTER
PLYWD PLYWOOD
PLA POINT LOAD FROM ABOVE
RAD.RADIUS
REQ'D REQUIRED
SIM.SIMILAR
S.S.STAINLESS STEEL
STL.STEEL
T.G. TEMPERED GLASS
TYP.TYPICAL
U.N.O.UNLESS NOTED OTHERWISE
V.C.T.VINYL COMPOSITION TILE
W.F.WIDE FLANGE
WD.WOOD
04/20/18
APPX-B
APPENDIX B
JCRCCHECKED:
PROJECT NO:
DATE:
REVISIONS
NO DATE REMARKS
CORPORATE SEAL:
DRAWN:
SEAL:
THIS DOCUMENT IS "NOT FOR CONSTRUCTION"
UNLESS THE ARCHITECT OR ENGINEER'S
SIGNATURE AND SEAL APPEAR BELOW.
RAINBOW CHILD
CARE CENTER
C-PROTOTYPE
95 CENTENNIAL PARKWAY
SPOUT SPRINGS, NC 28326
2017.0643
COPYRIGHT cP-0215
2018 INTERPLAN PLLC RESERVES COPYRIGHT & OTHER RIGHTS RESTRICTING THESE DOCUMENTS TO THE ORIGINAL SITE OR PURPOSE FOR WHICH THEY WERE PREPARED. REPRODUCTIONS, CHANGES OR ASSIGNMENTS ARE PROHIBITED.604 COURTLAND STREET
SUITE 100
ORLANDO, FLORIDA 32804
PH 407.645.5008
FX 407.629.9124
ARCHITECTURE
ENGINEERING
INTERIOR DESIGN
PROJECT MANAGEMENT
BUILDING CODE SUMMARY FOR ALL COMMERCIAL PROJECTS (APPENDIX B)
Total Number of Occupants: 172 occupants
04/20/18
T.101
FIRE & LIFE SAFETY PLAN
JCRCCHECKED:
PROJECT NO:
DATE:
REVISIONS
NO DATE REMARKS
CORPORATE SEAL:
DRAWN:
SEAL:
THIS DOCUMENT IS "NOT FOR CONSTRUCTION"
UNLESS THE ARCHITECT OR ENGINEER'S
SIGNATURE AND SEAL APPEAR BELOW.
RAINBOW CHILD
CARE CENTER
C-PROTOTYPE
95 CENTENNIAL PARKWAY
SPOUT SPRINGS, NC 28326
2017.0643
COPYRIGHT cP-0215
2018 INTERPLAN PLLC RESERVES COPYRIGHT & OTHER RIGHTS RESTRICTING THESE DOCUMENTS TO THE ORIGINAL SITE OR PURPOSE FOR WHICH THEY WERE PREPARED. REPRODUCTIONS, CHANGES OR ASSIGNMENTS ARE PROHIBITED.604 COURTLAND STREET
SUITE 100
ORLANDO, FLORIDA 32804
PH 407.645.5008
FX 407.629.9124
ARCHITECTURE
ENGINEERING
INTERIOR DESIGN
PROJECT MANAGEMENT
Pre-School 2
Pre-K 2
Staff
Lounge
Pre-K 1
Pre-School 1 Laundry
Rm.
Varsity
Room
Corridor 1
Toddler 1
Gym
Infant 1Infant 2
Young
Pre-School
Central Corridor
Vestibule
Childs
Toilet 4
Childs
Toilet 3
Child
Toilet 5
Childs
Toilet 7
Childs
Toilet 9
Childs
Toilet 8
Toddler 2
Childs
Toilet 6
Gym Child ToiletCloset
Gym Equip.Gym
Equip.
Directors
Office
Car
Seat
Sto.
Utility Rm.
Kitchen
Pantry
Kitchen
Outdoor Toy
Storage
Closet
Adult B.F.
Toilet 1
Stair
Child
Toilet 2
Lobby
Reception
Conf.Rm.
Closet
109
110
134 135
136
138
113
112
132
128
106 108
104
125 124
122
118
102
126
129123
101
100111
117
116
115
114
121
120
127 133
103
105107
119
137
140
Hall
131
I.T. Closet
130
141
PREP
SINK
HAND
SINK
FIRE & LIFE SAFETY PLAN 3/16"=1'-0"
EGRESS
DOOR #1
EGRESS
DOOR #2
EGRESS
DOOR #3
EGRESS
DOOR #4
EGRESS
DOOR #5EGRESS
DOOR #6
EGRESS
DOOR #7
EGRESS
DOOR #8EGRESS
DOOR #9
EGRESS
DOOR #10
EGRESS
DOOR #11
EGRESS
DOOR #12
EGRESS
DOOR #13
EGRESS
DOOR #14
Egress Width
Per table 1005.1: 0.2 inches per occupant required.
Minimum width of one exit is 36"
Total Occupant Load:172 Occupants (per T.100)
Required Width of Egress:35 Inches
Egress Width Provided:504 InchesEQUIPMENT PLATFORM LIFE SAFETY PLAN 3/16"=1'-0"
Equipment
Platform
TRAVEL DISTANCE (T.D.)
Legend
EXIT SIGN
EMERGENCY LIGHTS TRAVEL DISTANCE = 44'-0" TRAVAL DISTANCE = 7'-8"TRAVEL DISTANCE = 41'-0"TRAVEL
D
ISTANCE
=
39
'
-0
"TRAVEL DISTANCE = 43'-0"TRAVEL DISTANCE = 36'-0"TRAVEL DISTANCE = 33'-6"TRA
V
E
L
D
I
S
T
A
N
C
E
=
3
2
'
-
0
"
TRAVEL DISTANCE = 81'-0"
T.
D
.
=
1
4
'
-
0
"
TRAVEL DISTANCE = 12'-
6
"
TRAVEL DISTANCE = 17'-0"
T
RAV
E
L
D
I
S
TANC
E
=
2
1
'
-
6
"
TR
A
V
E
L
D
I
S
T
A
N
C
E
=
4
0
'
-
0
"TRAVEL DISTANCE = 37'-0"TRAVEL DISTANCE = 42'-0"TRAVEL DISTANCE = 35'-6"TRAVEL
D
IS
TANCE
=
35
'
-6
"
TRAVEL DISTANCE = 44'-6"
TRAVEL DISTANCE = 64'-0"TRAVEL DISTANCE = 13'-0"TRAVEL DISTANCE = 16'-0"T.D. = 31'-6"General Contractor to provide Access to a Public Way from the fenced playground areas in (1) of the
following methods;
1.Provide an 'Area of Safe Dispersal' within the fenced Playground area that is a minimum of
50'-0” away from the building, sized to fit five (5) SF per occupant of the building, provide
signage designating 'Safe Dispersal Area', and have a safe and unobstructed path from the
building. Refer to “MAXIMUM OCCUPANT LOAD FOR EGRESS” within the code Information on
sheet T.100 for the number of occupants.
2.If the criteria for an 'Area of Safe Dispersal' cannot be provided; General Contractor to
coordinate with Owner and provide either A) Panic Hardware on all gates leading to a Public
Way or B) Ensure all gates enclosing the playground have spring loaded hinges and ensure
that there are no closers, latches, locking mechanisms, magnalatches, or any other device
installed on the gates in order to ensure free and unobstructed egress from the playground
area.
ACCESS TO PUBLIC WAY
04/20/18
A.100
FIRST FLOOR WALL
FRAMING PLAN
JCRCCHECKED:
PROJECT NO:
DATE:
REVISIONS
NO DATE REMARKS
CORPORATE SEAL:
DRAWN:
SEAL:
THIS DOCUMENT IS "NOT FOR CONSTRUCTION"
UNLESS THE ARCHITECT OR ENGINEER'S
SIGNATURE AND SEAL APPEAR BELOW.
RAINBOW CHILD
CARE CENTER
C-PROTOTYPE
95 CENTENNIAL PARKWAY
SPOUT SPRINGS, NC 28326
2017.0643
COPYRIGHT cP-0215
2018 INTERPLAN PLLC RESERVES COPYRIGHT & OTHER RIGHTS RESTRICTING THESE DOCUMENTS TO THE ORIGINAL SITE OR PURPOSE FOR WHICH THEY WERE PREPARED. REPRODUCTIONS, CHANGES OR ASSIGNMENTS ARE PROHIBITED.604 COURTLAND STREET
SUITE 100
ORLANDO, FLORIDA 32804
PH 407.645.5008
FX 407.629.9124
ARCHITECTURE
ENGINEERING
INTERIOR DESIGN
PROJECT MANAGEMENT
Floor Plan Height Notes:
1.ALL FIRST FLOOR DOOR, WINDOW, AND HEADER HEIGHTS ARE TO BE 6'-8" UNLESS OTHERWISE
NOTED. (NOTE: WINDOWS AND DOORS ARE TO LINE-UP IN THE FINISH. ALL ROUGH FRAMING
HEIGHTS ARE TO MATCH)
2.ALL FIRST FLOOR CEILING HEIGHTS ARE TO BE 8'-0" EXCEPT FOR OPEN STAIRWELL, GYM & KITCHEN.
KITCHEN TO RECEIVE 9'-0" CEILING HEIGHT, GYM TO RECEIVE 12'-0" CEILING HEIGHT
3.MECHANICAL EQUIPMENT PLATFORM CEILING HEIGHTS ARE TO BE 8'-0" UNLESS NOTED OTHERWISE
(ATTIC FLOOR PLAN)
4.UNLESS NOTED OTHERWISE ON THE CONSTRUCTION DOCUMENTS, LOCATE ALL DOORS MINIMUM 4"
FROM ADJACENT WALLS ON HINGE SIDE. IF A CASING LARGER THEN 2 1/4" IS SELECTED, ADJUST
AS NECESSARY. IF DOORS ARE NOT LOCATED NEXT TO ADJACENT WALL, CENTER ON SPACE THEY
ENTER INTO.
6.ALL WOOD AND WOOD BASED PRODUCTS WITHIN 8" OF GRADE AND IN
CONTACT W/ CONC. OR MASONRY MUST BE PRESSURE TREATED AS
REQUIRED PER CODE
7.PROVIDE INTERIOR AND/OR EXTERIOR JAMB EXTENSIONS AS REQ'D FOR
ALL WINDOWS VER. W/DESIGNER.
8.PROVIDE MAGNETIC CHILD LOCKS ON ALL CABINET DOORS AND
DRAWERS
9. GC TO COORDINATE ALL ROUGH CARPENTRY WITH MEP
10.GC TO COORDINATE CONTROL JOINTS IN DRYWALL WITH
MANUFACTURERS RECOMMENDATION TO PREVENT CRACKING.
1.ALL EXTERIOR WALLS ARE TO BE 2X6 WOOD FRAMING U.N.O.
2.INSULATION IN CONCEALED AND EXPOSED SPACES MUST HAVE A FLAME SPREAD
RATING OF 25 OR LESS AND SMOKE DEVELOPED INDEX 450 OR LESS PER CODE.
3.ANY OCCUPANT SUSPECTED OF HAVING AN ILLNESS OR DISEASE SHALL BE TAKEN TO
THE DIRECTOR'S OFFICE WHERE THEY CAN BE ISOLATED FROM THE OTHER
OCCUPANTS AND CARED FOR. IN THE DIRECTOR'S OFFICE THERE SHALL BE A COT
FOR THIS PURPOSE.
4.PROVIDE EXTERIOR FROST FREE HOSE BIBS @ LOCATIONS DIRECTED BY M.E.P.
5.PROVIDE SOLID BLOCKING IN WALLS FOR ALL WALL MOUNTED ITEMS NOT LIMITED TO
THE FOLLOWING:
5.1.DOOR STOPS
5.2.TOWEL BARS
5.3.TOILET TISSUE DISPENSER
5.4.MISC. WALL MOUNTED ACCESSORIES
5.5.MIRRORS
General Floor Plan Notes:
ALL DIMENSIONS ON FRAMING PLANS ARE
TAKEN FROM STUD TO STUD AND DO NOT
INCORPORATE THE DRYWALL.
Pre-School 2
Pre-K 2
Staff
Lounge
Pre-K 1
Pre-School 1
Laundry
Rm.
Varsity
Room
Corridor 1
Toddler 1
Gym
Infant 1Infant 2
Young
Pre-School
Central Corridor
Vestibule
Childs
Toilet 4
Childs
Toilet 3
Child
Toilet 5
Childs
Toilet 7
Childs
Toilet 9
Childs
Toilet 8
Toddler 2
Childs
Toilet 6
Gym Child ToiletCloset
Gym Equip.Gym
Equip.
Directors
Office
Car
Seat
Sto.
Utility Rm.Kitchen
Pantry
Kitchen
Outdoor Toy
Storage
Closet
Adult B.F.
Toilet 1
Stair
Child
Toilet 2
Lobby
Reception
Conf.Rm.
Closet6'-7 1/2"5'-8"11'-5"11'-5"3'-5 1/4"16'-10 3/4"
26'-9"
153'-0"
28'-0"11'-5 1/2"5'-8"15'-3"2'-9"3'-11"4'-1"2'-1"10'-6"58'-11"15'-4"14'-0"15'-4"21'-7 1/2"24'-0 1/2"5'-8"5'-8"2'-8"90'-4"2'-8"
7'-0"
12'-1 1/2"6'-9 1/2"9'-2"5'-10"
8"
51'-7"46'-8"28'-0"2'-0"3'-6 1/2"6'-2"46'-8"78'-4"5'-4 1/2"2'-9"11'-0 7/8"4'-5"2'-0"4'-0 1/8"3'-8"39'-1"11'-4"4'-4"
27'-8 1/2"8'-2"28'-1 3/8"6'-1 1/4"6'-1 1/4"2'-5 1/4"27'-8 1/8"8'-7 1/2"2'-5 1/4"5'-0"5'-0"
3'-11 3/4"
2'-5 1/4"2'-5 1/4"12'-1 1/8"
18'-0"16'-5 1/2"29'-5 1/8"32'-5 1/4"14'-2 1/2"7'-3 1/8"5'-4"
4'-11 1/2"EQ.8'-2"8'-0"7'-10"9'-8 1/8"9'-8 1/4"10'-9 7/8"33'-4 3/8"8'-0 1/8"19'-5 3/8"
2'-6"
7'-7 1/8"21'-0 5/8"21'-6"6'-1 1/4"8'-4 1/4"5'-1 1/2"
3'-0"22'-5 3/8"27'-8 3/8"2'-0"
9'-1 7/8"
5'-0 7/8"
8'-10 1/4"
8'-0"
8'-0"MIN. 18"9 7/8"
9'-7 1/8"
10'-7"10'-3 1/2"4'-6 1/2"11'-3 1/2"10'-0"8'-3 1/8"6'-1 1/4"
5'-0"
9'-8 1/2"
60" MIN.
2'-6" MIN.
2'-5 1/4"5'-0"4'-0 1/4"27'-0"4'-0 1/4"4'-0 1/4"A
B
B
B
D
B
B
D
D
DD
BD
D
A
A
B
B
B B
B
B
B
BD
D
B
B
B
B
B
B
B
B
A
A
B
B
D
D
D
D
B B
D
D
D
B
B
BB
D
B
D
D
B B
B
D
B
D
B
D
D
B
DD
B B
B
H
H
D
H
D
B
B
BB
A
A
B
8'-1 3/8"13'-11 7/8"10'-5"23'-11 1/8"
6'-11 1/4"
109
110
134
135
136
138
113
112
132
128
106
108
104
125 124
122
118
102
126
129123
101
100
111
117
116
115
114
121
120
127
133
103
105
107
119
139
137
140
21'-7"28'-1 3/8"5'-3 3/4"6'-1 1/4"2'-5 1/4"5'-0"
29'-4"10'-5"5'-4 1/2"5'-0"35'-2 7/8"8'-0 1/8"4'-1 1/4"13'-9 1/2"EQ.EQ.8'-2"10'-9 7/8"
23'-1 1/4"
21'-6"8'-4 1/4"8'-7 1/2"8'-0 1/8"5'-0 5/8"9'-11"8'-2 3/8"
3'-0"1'-8"2'-1 3/4"8'-2 3/8"MIN. 18"5'-6"9'-5 3/8"6'-1 3/4"9'-7 1/8"12'-4 1/2"8'-3 1/8"25'-0"
9'-1 7/8"
9'-5 3/8"
2'-6" MIN.2'-5 1/4"11'-3 1/8"6'-11 1/4"6'-11 1/4"
CEILING HGT.
9'-0" A.F.F.
VAULT. CEILING HGT.
12'-0" A.F.F.
CEILING HGT.
12'-0" A.F.F.CEILING HGT.
8'-0" A.F.F.
Hall
131
2'-5 1/4"5'-0"2'-5 1/4"
17'-11"30'-0 1/4"32'-5 3/4"9'-6 5/8"16'-5 3/8"
B
11 1/8"6'-11 7/8"45°3'-6 1/2"45°7'-11 3/4"7'
-
1
1
3
/
4
"5'-1 1/4"6'-1 1/4"4'-0 1/4"4'-0 1/4"3'-0"
I.T. Closet
130
141
D
B
D
D
D
A A
A
A
A
A
B
A
DD
B
D
D
H
A
B
D
B
A
A A
REF.FREEZ.FUTURE
REF.
COMBO
OVEN
UNIT
3'-0 3/4"3'-1 7/8"
CEILING HGT.
12'-0" A.F.F.4'-0 1/4"7'-5 1/4"9'-3 1/8"9'-3 1/8"7'-5 1/4"BB9'-7 7/8"2'-2"11'-5 1/2"TYP.15'-6"6'-3"14'-3"10'-9"18'-4 1/2"4'-5 1/2"8'-2 1/2"17'-6"
2'-11"11'-7 3/4"20'-6 1/4"4'-1"11'-10 1/4"14'-3 1/2"4'-3 1/2"8'-2 1/2"17'-6"5'-2"3'-4"3'-4"3'-4"5'-2"5'-2"5'-2"1'-5"3'-4"5'-2"3'-4"3'-4"5'-2"5'-2"3'-4"5'-2"2'-10 1/2"3'-4"2'-10 1/2"5'-2"3'-8"5'-2"5'-2"7'-0"9'-3"5'-2"4'-5"3'-6 1/2"2'-10"3'-2"2'-10"3'-2"2'-10"3'-3"23'-4"3'-4"3'-10 1/2"3'-4"2'-6"5'-2"7'-8"5'-2"2'-5 1/4"3'-4"7'-10"5'-2"5'-2 1/2"8'-0"3'-4"3'-1 1/2"5'-2"10'-7 1/2"5'-2"11'-3"11'-5"5'-2"11'-5"9'-3"PREP
SINK
HAND
SINK
FIRST FLOOR WALL FRAMING PLAN
3/16"=1'-0"3'-4"2'-10 1/2"20'-10 5/8"
D
5'-3 3/8"4'-4 5/8"4'-4 5/8"B9'-0 7/8"B13'-5 1/4"11'-5 1/2"6'-7 1/2"D
Wall Legend X
2X6 INTERIOR PARTITION WALL:
5/8" GYPSUM BOARD EACH SIDE OF
2X6 WOOD STUDS @ 16" O.C.
PROVIDE ACOUSTICAL SOUND BATT
INSULATION @ ALL INTERIOR WALLS
AS DIRECTED BY OWNER
INTERIOR PARTITION WALL:
1 LAYER TYPE 'X' 5/8" GYPSUM
BOARD EACH SIDE OF 2X4 WOOD
STUDS @ 16" O.C. PROVIDE
ACOUSTICAL SOUND BATT
INSULATION @ ALL INTERIOR WALLS
AS DIRECTED BY OWNER
NOTE:
ALL OPENINGS, DOORS AND
WINDOW FRAMES ARE TO BE FIRE
CAULKED
A
B
C
INTERIOR EQUIPMENT ENCLOSURE WALL:
PROVIDE (1) LAYER OF 5/8" GYPSUM
BOARD ON THE INSIDE AND 2X WOOD
STUD AS REQUIRED TO PROVIDE CAVITY
FOR A TOTAL INSULATION OF R-38. SEE
DETAIL 5/A.303
F
EXTERIOR WALL (BRICK):
EXTERIOR BEARING WALL: BRICK
VENEER EXTERIOR FINISH W/ 1" AIR
SPACE ON TYVEK AIR INFILTRATION
BARRIER ON 1/2" APA RATED
PLYWOOD SHEATHING ON 2X6
WOOD STUDS @ 16" O.C. W/ R-19
KRAFT FACED BATT INSUL. W/ 5/8"
GYPSUM BOARD FINISH
General Wall Type Notes:
1.ALL INTERIOR WALLS ARE ASSUMED WALL TYPE "D" U.N.O.
2.ALL EXTERIOR WALLS ARE ASSUMED WALL TYPE "A" U.N.O.
DRAFTSTOPPING WALL:
3/8" PLYWOOD ON ONE SIDE OF
PRE-ENG. ROOF TRUSS. RUN UP TO
UNDER SIDE OF ROOF SHEATHING (SEE
TYPICAL DETAIL ON SHEET A.305 FOR
ADDITIONAL INFORMATION)
GINTERIOR PARTITION WALL:
1 LAYER TYPE 'X' 5/8" GYPSUM
BOARD EACH SIDE OF 2X6 WOOD
STUDS @ 16" O.C. PROVIDE
ACOUSTICAL SOUND BATT
INSULATION @ ALL INTERIOR WALLS
AS DIRECTED BY OWNER
NOTE:
ALL OPENINGS, DOORS AND
WINDOW FRAMES ARE TO BE FIRE
CAULKED
E
TYPICAL INTERIOR PARTITION WALL:
2X4 STUDS @ 16" O.C. WITH 5/8" GYP.
BOARD EACH SIDE. PROVIDE
ACOUSTICAL SOUND BATT
INSULATION @ ALL INTERIOR WALLS
AS DIRECTED BY OWNER
D
1-HR. RATED 1-HR. RATED
NOT
U
S
E
D
NOT
U
S
E
D
TYPICAL INTERIOR PARTITION WALL:
2X4 STUDS @ 12" O.C. WITH 5/8" GYP.
BOARD EACH SIDE. PROVIDE
ACOUSTICAL SOUND BATT
INSULATION @ ALL INTERIOR WALLS
AS DIRECTED BY OWNER
H 5'-2"F.E.
F.E.
F.E.F.E.
COMBO
OVEN
UNIT8'-0 1/2"2'-2"2'-2"4'-2 5/8"2'-4"
04/20/18
A.101
FIRST FLOOR PLAN
JCRCCHECKED:
PROJECT NO:
DATE:
REVISIONS
NO DATE REMARKS
CORPORATE SEAL:
DRAWN:
SEAL:
THIS DOCUMENT IS "NOT FOR CONSTRUCTION"
UNLESS THE ARCHITECT OR ENGINEER'S
SIGNATURE AND SEAL APPEAR BELOW.
RAINBOW CHILD
CARE CENTER
C-PROTOTYPE
95 CENTENNIAL PARKWAY
SPOUT SPRINGS, NC 28326
2017.0643
COPYRIGHT cP-0215
2018 INTERPLAN PLLC RESERVES COPYRIGHT & OTHER RIGHTS RESTRICTING THESE DOCUMENTS TO THE ORIGINAL SITE OR PURPOSE FOR WHICH THEY WERE PREPARED. REPRODUCTIONS, CHANGES OR ASSIGNMENTS ARE PROHIBITED.604 COURTLAND STREET
SUITE 100
ORLANDO, FLORIDA 32804
PH 407.645.5008
FX 407.629.9124
ARCHITECTURE
ENGINEERING
INTERIOR DESIGN
PROJECT MANAGEMENT
W1
W1 W1
W1 W1 W1
W1W1
W1W1
W1W1
W1
W1
W1
27'-7 1/4"8'-0 11/16"21'-5 11/16"28'-0 1/8"6'-0"5'-2 1/2"6'-0"2'-4"5'-0"
29'-2 11/16"
27'-7 1/4"8'-6 3/16"10'-3 3/4"2'-4 1/8"5'-3 1/4"5'-0"5'-0"5'-0"
13'-7 1/4"
2'-4"2'-4"12'-0 1/2"
17'-10 3/4"16'-4 3/16"29'-3 7/8"32'-4"7'-10 13/16"14'-1 1/4"3'-11 15/16"7'-1 3/4"5'-4"13'-7 1/4"
4'-10 1/4"EQ.EQ.8'-1 13/16"4'-10 1/8"7'-8 3/4"9'-6 13/16"9'-6 15/16"10'-9 5/16"33'-3 1/8"7'-10 3/4"19'-4 1/8"
2'-6"
22'-11 15/16"
7'-5 15/16"20'-11 3/16"21'-4 9/16"6'-0"8'-2 7/8"8'-7 1/2"7'-10 7/8"5'-0"9'-11"5'-0 3/16"
8'-1"
3'-0"22'-4 1/8"27'-7 1/8"18"
2'-0"
9'-0 5/8"
5'-0 7/8"
8'-9 15/16"
7'-10 3/4"
8'-1 1/8"MIN. 18"MIN. 18"11 1/8"5'-4 3/4"6'-0 1/2"9'-5 13/16"
10'-5 3/4"10'-2 1/4"4'-5 1/4"11'-2 1/4"12'-3 1/4"9'-10 3/4"8'-3 1/8"9'-0 5/8"
5'-0"
9'-7 1/4"
60" MIN.
2'-6" MIN.
2'-3 15/16"5'-0"3'-10 15/16"26'-10 3/4"3'-10 15/16"8'-0 1/16"13'-10 5/8"10'-3 11/16"2'-4 3/4"23'-9 7/8"11'-2"6'-10"6'-10"
7'-10 3/4"8'-1 1/16"4'-0"24'-10 3/4"
W4 W2
W2
W2 W2 W2
W2
W2
W2
2'-4"5'-0"8'-11 5/8"11'-3 5/16"5'-0 3/16"45°3'-6 1/2"2'-8 1/8"
7'-0 15/16"3'-11"3'-11"3'-0"
(TYP)(TYP)(TYP)(TYP)(TYP)
7'-
1
1
3
/
4
"8'-0 1/16"3
17
17
16
15
2
73
12
11
3
3
6
6
19
17
6
4
6
6
15
8
8
9
9
24
2424
24
24
24
24
24
24
6
24
6
9'-10 15/16"10'-2 7/8"7'-5 3/4"7'-5 3/4"8'-2 13/16"4'-0 5/16"6'-0"2'-7 3/16"11 3/8"3
14'-7 3/8"9'-0 1/4"W5
W5
W5
W5
W5
W5
W5
W5
W5W6W5 WINDOWS ABOVE IN CLEARSTORY
SEE SHEET A.102.1 FOR INFO.
CLEARSTORY
ABOVE
U.C. REF.
(TYP.)1'-8"4'-0"3'-0 3/4"3'-1 7/8"3'-11"(TYP)(TYP)17'-5 3/8"8'-2 1/2"4'-3 1/2"14'-3 9/16"11'-10 1/4"4'-0 7/8"27'-11 15/16"11'-5 1/2"Floor Plan Height Notes:
1.ALL FIRST FLOOR DOOR, WINDOW, AND HEADER HEIGHTS ARE TO BE 6'-8" UNLESS OTHERWISE
NOTED. (NOTE: WINDOWS AND DOORS ARE TO LINE-UP IN THE FINISH. ALL ROUGH FRAMING
HEIGHTS ARE TO MATCH)
2.ALL FIRST FLOOR CEILING HEIGHTS ARE TO BE 8'-0" EXCEPT FOR OPEN STAIRWELL, GYM & KITCHEN.
KITCHEN TO RECEIVE 9'-0" CEILING HEIGHT, GYM TO RECEIVE 12'-0" CEILING HEIGHT
3.MECHANICAL EQUIPMENT PLATFORM CEILING HEIGHTS ARE TO BE 8'-0" UNLESS NOTED OTHERWISE
(ATTIC FLOOR PLAN)
4.UNLESS NOTED OTHERWISE ON THE CONSTRUCTION DOCUMENTS, LOCATE ALL DOORS MINIMUM 4"
FROM ADJACENT WALLS ON HINGE SIDE. IF A CASING LARGER THEN 2 1/4" IS SELECTED, ADJUST
AS NECESSARY. IF DOORS ARE NOT LOCATED NEXT TO ADJACENT WALL, CENTER ON SPACE THEY
ENTER INTO.
General Floor Plan Notes:
FIRST FLOOR PLAN
3/16"=1'-0"ALL DIMENSIONS ON FLOOR PLANS ARE TAKEN
FROM FINISH TO FINISH & INCLUDE THE 5/8"
GYP. BOARD
1.NOT USED.
2.PROVIDE F.R.P. (WHITE OR AS DIRECTED BY OWNER) TO A 60" A.F.F. BEHIND MOP
SINK
3.PROVIDE 16" DEEP WIRE SHELVING OVER TO OWNER SPECIFICATION
4.BUILT-IN CAR SEAT CUBBIES
5.PARTITIONED STORAGE UNITS (BY OWNER)
6.COT STORAGE AREA - PROVIDE FULL HEIGHT F.R.P. WITH OS CORNER PROTECTION.
REFER TO SHEET A.105 FOR TYP. LOCATION.
7.LOCATE DRYER VENT IN WALL CAVITY
8.PROVIDE 2X6 BLOCKING IN WALLS @ 42" A.F.F. TO CENTER @ ENTIRE PERIMETER OF
GYM
9.MASONRY PIER. REFER TO STRUCTURAL DRAWINGS FOR DETAIL - STRUCTURAL STEEL
IS TO BE LOCATED WITHIN COLUMN
10.KNOX-BOX RAPID ENTRY SYSTEM, OR APPROVED EQUAL. COORDINATE EXACT
LOCATION AND TYPE WITH FIRE MARSHAL. COORDINATE WITH FIRE MARSHAL IF A
TRUSS SIGN IS REQUIRED, AND IF SO PROVIDE THE TYPE, LOCATION, AND
DESIGNATION AS REQUIRED.
11.PROVIDE BLOCKING IN WALL FOR T.V. MOUNT - 72" WIDE @ 65" A.F.F. TO MID
POINT 14'-4" FROM ADJACENT VESTIBULE WALL (VERIFY EXACT LOCATION WITH
OWNER)
12.PROVIDE 12" X 12" HORIZONTAL BLOCKING, FINISHED TO ACCOMMODATE
CEILING MOUNTED LIGHT FIXTURE
13.PROVIDE BLOCKING AS REQ'D 54"-78" A.F.F. FOR WALL MOUNTED BASKETBALL
HOOP - EXACT LOCATION TO BE VERIFIED BY OWNER
14.PROVIDE WALL MOUNTED MOP HOOKS AND SHELVING
15.DOOR TO BE LOCKED AND INACCESSIBLE TO CHILDREN
16.ADA COMPLIANT HIGH/LOW DRINKING FOUNTAIN
17.CHANGING LOCATION
18.CONDENSING UNIT PAD
19.AREA OF EQUIPMENT PLATFORM (ABOVE)
20.LOCATION OF FUTURE WALL
21.SEE CIVIL DRAWINGS BY OTHERS FOR EXTERIOR WALK LOCATIONS & DETAILS
22.FUTURE DOOR - FRAME IN OPENING
23.LINE OF STAIRS & SLOPED CEILING (ABOVE) - PROVIDE STORAGE SPACE UNDER
STAIRS
24.PROVIDE BLOCKING FOR 4' W. X 15" X 20"
CUBBIES TO BE INSTALLED @ (SEE BELOW)
24.1 ROOMS 109,112,117,119, & 121 @ 36" A.F.F
24.2 ROOM 106 @ 47 1/2"
24.3 ROOM 104 @ 39 1/2"
25.CHAINLINK FENCE, GATES, LATCH & PAD LOCK
26.GC SHALL PROVIDE AND INSTALL FIRE EXTINGUISHER CABINET 1 10LB ABC FIRE
EXTINGUISHER AT LOCATION SHOWN. CABINET SHALL BE ELITE SERIES
SEMI-RECESSED VERTICAL DUO EXTINGUISHER CABINET, 8"W X 16-3/4"H X 5"D OR
APPROVED EQUAL. FIRE EXTINGUISHER CABINETS ARE REQUIRED TO BE IDENTIFIED
PER SECTION 905.7.1.
27.GC SHALL PROVIDE AND INSTALL 1 WALL MOUNTED 10LB K TYPE FIRE
EXTINGUISHER.
28.TACTILE EXIT SIGNAGE IS REQUIRED TO BE INSTALLED ADJACENT TO EACH
STAIRWAY EXIT DOOR AND EACH EXTERIOR EXIT DOOR.
Keyed First Floor Plan Notes:X
Pre-School 2
Pre-K 2
Staff
Lounge
Pre-K 1
Pre-School 1
Laundry
Rm.
Varsity
Room
Corridor 1
Toddler 1 Gym
Infant 1Infant 2
Young
Pre-School
Central Corridor
Vestibule
Childs
Toilet 4
Childs
Toilet 3
Child
Toilet 5
Childs
Toilet 7
Childs
Toilet 9
Childs
Toilet 8
Toddler 2
Childs
Toilet 6
Gym Child ToiletCloset
Gym Equip.
Directors
Office
Car
Seat
Sto.
Utility Rm.Kitchen
Pantry
Kitchen
Outdoor Toy
Storage
Closet
Adult B.F.
Toilet 1
Stair
Child
Toilet 2
Lobby
Reception
Conf.Rm.
Closet
109
110
134
135
136
138
113
112
132
128
106
108
104
125 124
122
118
102
126
129
123
101
100111
117
116
114
121
120
127
133
103
105
107
119
139
137
140
Hall
131
I.T. Closet
130
141
REF.FREEZ.FUTURE
REF.
118
105
110
135
123
137
104128
134 140
109-A
134-A
136
112
106
138
113
112-A
119-A
119
127139
103
125 124
122
116
100-B
100-A
101
131-A124-A
106-A
108
107
109
137-A
121-A
114
115
116-A
121
117
100
125-A
104-A
132
120
120-A
131
141
130
PREP
SINK
HAND
SINK
14 21
21
6.ALL WOOD AND WOOD BASED PRODUCTS WITHIN 8" OF GRADE AND IN
CONTACT W/ CONC. OR MASONRY MUST BE PRESSURE TREATED AS
REQUIRED PER CODE
7.PROVIDE INTERIOR AND/OR EXTERIOR JAMB EXTENSIONS AS REQ'D FOR
ALL WINDOWS VER. W/DESIGNER.
8.PROVIDE MAGNETIC CHILD LOCKS ON ALL CABINET DOORS AND
DRAWERS
9. GC TO COORDINATE ALL ROUGH CARPENTRY WITH MEP
10.GC TO COORDINATE CONTROL JOINTS IN DRYWALL WITH
MANUFACTURERS RECOMMENDATION TO PREVENT CRACKING.
1.ALL EXTERIOR WALLS ARE TO BE 2X6 WOOD FRAMING U.N.O.
2.INSULATION IN CONCEALED AND EXPOSED SPACES MUST HAVE A FLAME SPREAD
RATING OF 25 OR LESS AND SMOKE DEVELOPED INDEX 450 OR LESS PER CODE.
3.ANY OCCUPANT SUSPECTED OF HAVING AN ILLNESS OR DISEASE SHALL BE TAKEN TO
THE DIRECTOR'S OFFICE WHERE THEY CAN BE ISOLATED FROM THE OTHER
OCCUPANTS AND CARED FOR. IN THE DIRECTOR'S OFFICE THERE SHALL BE A COT
FOR THIS PURPOSE.
4.PROVIDE EXTERIOR FROST FREE HOSE BIBS @ LOCATIONS DIRECTED BY M.E.P.
5.PROVIDE SOLID BLOCKING IN WALLS FOR ALL WALL MOUNTED ITEMS NOT LIMITED TO
THE FOLLOWING:
5.1.DOOR STOPS
5.2.TOWEL BARS
5.3.TOILET TISSUE DISPENSER
5.4.MISC. WALL MOUNTED ACCESSORIES
5.5.MIRRORS
212518
13
8 8
1717
1717
21
8
W7 W8
W7
W7
W8 W8
25
W3
W3
W3
W9 W9
W1 W8
4'-5 1/4"
10
3'-5"
27
26
26
NOTE: DOOR DIMENSIONS THIS
ROOM ARE TO OUTSIDE EDGE OF
DOOR FRAMES.19'-6 3/8"3'-4"2 1/4"1'-11 3/4"3'-4"1"Gym Equip.
115
6'-0"9'-5 3/8"9'-5 3/8"
COMBO
OVEN
UNIT
COMBO
OVEN
UNIT
28 26 28 28
T.G.T.G.
T.G.
T.G.2'-2"7'-11 5/16"2'-1 15/16"2'-4"4'-1 3/8"
04/20/18
A.102
FIRST FLOOR KEY PLAN
JCRCCHECKED:
PROJECT NO:
DATE:
REVISIONS
NO DATE REMARKS
CORPORATE SEAL:
DRAWN:
SEAL:
THIS DOCUMENT IS "NOT FOR CONSTRUCTION"
UNLESS THE ARCHITECT OR ENGINEER'S
SIGNATURE AND SEAL APPEAR BELOW.
RAINBOW CHILD
CARE CENTER
C-PROTOTYPE
95 CENTENNIAL PARKWAY
SPOUT SPRINGS, NC 28326
2017.0643
COPYRIGHT cP-0215
2018 INTERPLAN PLLC RESERVES COPYRIGHT & OTHER RIGHTS RESTRICTING THESE DOCUMENTS TO THE ORIGINAL SITE OR PURPOSE FOR WHICH THEY WERE PREPARED. REPRODUCTIONS, CHANGES OR ASSIGNMENTS ARE PROHIBITED.604 COURTLAND STREET
SUITE 100
ORLANDO, FLORIDA 32804
PH 407.645.5008
FX 407.629.9124
ARCHITECTURE
ENGINEERING
INTERIOR DESIGN
PROJECT MANAGEMENT
FIRST FLOOR KEY PLAN 3/16"=1'-0"
Pre-School 2
Pre-K 2
Staff
Lounge
Pre-K 1
Pre-School 1
Laundry
Rm.
Varsity
Room
Corridor 1
Toddler 1 Gym
Infant 1Infant 2
Young
Pre-School
Central Corridor Vestibule
Childs
Toilet 4
Childs
Toilet 3
Child
Toilet 5
Childs
Toilet 7
Childs
Toilet 9
Childs
Toilet 8
Toddler 2
Childs
Toilet 6
Gym Child ToiletCloset
Gym Equip.
Directors
Office
Car
Seat
Sto.
Utility Rm.
Kitchen
Pantry
Kitchen
Outdoor Toy
Storage
Closet
Adult B.F.
Toilet 1
Stair
Child
Toilet 2
Lobby
Reception
Conf.Rm.
Closet
20
A.401
109 110
134
135
136
138
113
112
132
128
106
108 104
125 124
122
118
102
126
129123
101
100111
117
116
114
121
120
127
133
103
105
107
119
139
137
140
Hall
131
9
A.400
23
A.401
27
A.401
23
A.401
23
A.401
30
A.401
9
A.400
25
A.401
26
A.401
31
A.402
22
A.401
33
A.402
4
A.400
15
A.400
32
A.402
36
A.402
37
A.402
35
A.402
24
A.401
1
A.402
24
A.401
30
A.401
8
A.402
13
A.400
34
A.402
38
A.402
21
A.401
9
A.400
29
A.401
24
A.402
26
A.401
28
A.401
12
A.400
11
A.400
9
A.400
E.9
A.400
2
A.400
EP-7
A.102.1
EP-6
A.102.1
EP-2
A.102.1
EP-4
A.102.1
EP-3
A.102.1
I.T. Closet
130
141
EP-2
A.102.1
EP-5
A.102.1
EP-1
A.102.1
REF.FREEZ.FUTURE
REF.
5
A.400
4
A.304
PREP
SINK
HAND
SINK
9
A.400
SIM.
E
A.301
E
A.301
C
A.300
C
A.300
A
A.300
A
A.300
H
A.302
H
A.302
F
A.301
F
A.301
OPP.
OPP.
SIM.
OPP.
SIM.
G
A.302
G
A.302
B
A.300
TOILET HEIGHT LEGEND
39
A.402
40
A.402
41
A.402
1
A.200
2
A.200
1
A.201
2
A.201
J
A.305
D
A.301
D
A.301
10
A.400
5
A.305
Gym Equip.
115
COMBO
OVEN
UNIT
COMBO
OVEN
UNIT
04/20/18
A.102.1
ENLARGED FLOOR PLANS
JCRC
Gym Clearstory PlanEP-1
A.102.1 Scale: 1/2" = 1'-0"
Enlarged Floor Plan @ Reception AreaChild B.F. Restroom PlanEP-5
A.102.1 Scale: 1/2" = 1'-0"
Child B.F. Restroom PlanEP-4
A.102.1 Scale: 1/2" = 1'-0"
Child B.F. & Adult Restroom PlanEP-6
A.102.1 Scale: 1/2" = 1'-0"
EP-7
A.102.1 Scale: 1/2" = 1'-0"
Child B.F. Restroom PlanEP-3
A.102.1 Scale: 1/2" = 1'-0"
Child B.F. Restroom PlanEP-2
A.102.1 Scale: 1/2" = 1'-0"
CHECKED:
PROJECT NO:
DATE:
REVISIONS
NO DATE REMARKS
CORPORATE SEAL:
DRAWN:
SEAL:
THIS DOCUMENT IS "NOT FOR CONSTRUCTION"
UNLESS THE ARCHITECT OR ENGINEER'S
SIGNATURE AND SEAL APPEAR BELOW.
RAINBOW CHILD
CARE CENTER
C-PROTOTYPE
95 CENTENNIAL PARKWAY
SPOUT SPRINGS, NC 28326
2017.0643
COPYRIGHT cP-0215
2018 INTERPLAN PLLC RESERVES COPYRIGHT & OTHER RIGHTS RESTRICTING THESE DOCUMENTS TO THE ORIGINAL SITE OR PURPOSE FOR WHICH THEY WERE PREPARED. REPRODUCTIONS, CHANGES OR ASSIGNMENTS ARE PROHIBITED.604 COURTLAND STREET
SUITE 100
ORLANDO, FLORIDA 32804
PH 407.645.5008
FX 407.629.9124
ARCHITECTURE
ENGINEERING
INTERIOR DESIGN
PROJECT MANAGEMENT
W5
W5
W5
W5
W5
W5
W5
W5
W5W8W6W5
2
A.304
NOTE:
SEE WINDOW SCHEDULE
SHEET A.500
7 1/2"2'-6"23'-6 1/2"4"2'-6"4"2'-6"4"2'-6"4"2'-6"4"2'-6"4"2'-6"4"2'-6"7"7 1/4"2'-6"4"5'-0"4"2'-3 1/2"4"3'-4"4"2'-3 1/2"4"5'-0"4"2'-6"6 3/4"
W8 W9 W9
1'-0"CL
5'-0 1/4"12"(MAX)42"(MIN)34" - 36"54"(MIN)9'-6 3/4"Child Toilet 4
108
CL
2'-6"
2'-0"2'-0"1'-3 1/2"CL
Child Toilet 7
138
Child Toilet 8
113
12"CL
42"(MIN)
34" - 36"
54"(MIN)
6'-10"U 6'-10"11'-2"3'-0"5'-0"1'-3 1/2"1'-0"4'-10 1/2"CL
CL
34" - 36"5'-0 1/2"CL
CL
CL
CL
3'-0"2'-0"2'-0"2'-0"2'-0"5'-3 1/2"2'-10"5'-9 3/8"5'-0"8'-9 1/2"1'-0"7'-4 3/4"2'-0"10 1/2"5'-7"4'-3 3/4"Reception
102
1'-6"
LINE OF BASE WALL BELOW
(DASHED)
PROVIDE (2) 1-1/2"
GROMETS IN C. TOP (VERIFY
EXACT LOCATION W/
OWNER) - TYPICAL
30" HIGH COUNTER TOP
LINE OF RECEPTION AREA BUILT-IN
BOOKCASE (SEE A.401 FOR
ADDITIONAL INFORMATION)
30" COUNTER TOP
42" HIGH COUNTER TOP
TO PROJECT PAST BASE
A MAX. OF 2" (V.I.F.)R3'-3 3/4"48" (MIN)30" (MIN)9'-7"1'-0"16"-18"
12"(MIN)24"(MIN)
36"(MIN)
CL CL
12"(MAX)42"(MIN)39"-41"54"(MIN)8'-11 3/4"5'-7"
3'-2"
8'-1"
8'
-
0
1
/
2
"
Adult B.F.
Toilet 1
103
Child Toilet 2
105
34" - 36"4'-7"48" (MIN.)30" (MIN.)3'-0"1'-8"12"(MAX)42"(MIN)39"-41"54"(MIN)1'-6"CL
2'-0 1/2"
CL
CL
2'-0"2'-0"
3'-0 1/2"
1'-0"
CL12"(MAX)42"(MIN)34" - 36"54"(MIN)8'-2 3/4"8'-1"
30" (MIN)48" (MIN)Child Toilet 9
120 3'-0"CL 1'-3"
1'-6"
CL
3'-0 1/2"
2'-0"2'-0"
Child Toilet 6
135
1'-0"CL
12"(MAX)42"(MIN)34"-36"54"(MIN)CL
1'-3"
7'-10 3/4"10'-3 3/4"3'-0"1'-5 1/2"CL
2'-9 3/4"CL
2'-0"2'-0"
04/20/18
A.103
ATTIC PLAN
JCRC
Scale: 3/16" = 1'-0"
Attic Floor Plan
Scale: 3/16" = 1'-0"
Attic Framing Plan
514 SQ. FT.
CHECKED:
PROJECT NO:
DATE:
REVISIONS
NO DATE REMARKS
CORPORATE SEAL:
DRAWN:
SEAL:
THIS DOCUMENT IS "NOT FOR CONSTRUCTION"
UNLESS THE ARCHITECT OR ENGINEER'S
SIGNATURE AND SEAL APPEAR BELOW.
RAINBOW CHILD
CARE CENTER
C-PROTOTYPE
95 CENTENNIAL PARKWAY
SPOUT SPRINGS, NC 28326
2017.0643
COPYRIGHT cP-0215
2018 INTERPLAN PLLC RESERVES COPYRIGHT & OTHER RIGHTS RESTRICTING THESE DOCUMENTS TO THE ORIGINAL SITE OR PURPOSE FOR WHICH THEY WERE PREPARED. REPRODUCTIONS, CHANGES OR ASSIGNMENTS ARE PROHIBITED.604 COURTLAND STREET
SUITE 100
ORLANDO, FLORIDA 32804
PH 407.645.5008
FX 407.629.9124
ARCHITECTURE
ENGINEERING
INTERIOR DESIGN
PROJECT MANAGEMENT
Mechanical Equip.
Platform
201
Attic 'B'
Attic 'D'
31'-3 5/8"13'-7 7/8"10'-8 3/4"
16 RISERS
DOWN 5'-6"3'-3 1/2"9'-11 1/2"F
D
F
F
G
GG
F
18'-11 3/4"F
F11'-8 3/4"
G
200
Attic 'C'
Attic 'B'
G
F
3'-0"ATTIC PLAN
3/16"=1'-0"1.SEE SHEET MECHANICAL DRAWINGS FOR EXACT
LOCATION OF FURNACES
2.SEE SHEET A-101 FOR LOCATION OF
MECHANICAL EQUIPMENT PLATFORM IN
RELATION TO FIRST FLOOR-INDICATED BY
DASHED LINE
General Attic Plan Notes:
1.3/4" FIRE RETARDANT TREATED PLYWOOD FLOOR
DECKING
2.PROVIDE (1) LAYER OF 5/8" GYP. BRD. @
CEILING
3.PRE-FIN BREAK MTL. CAP W/DRIP EDGE
4.PRIMARY ROOF SUMP (VER. EXACT LOCATION
W/ MEP ENGINEER)
5.EMERGENCY OVERFLOW ROOF SUMP (VER.
EXACT LOCATION W/MEP ENGINEER)
6.SINGLE PLY - 60 MIL. EPDM ROOF ON TAPERED
INSULATION
7.PITCHED TO DRAIN (TYP.)
8.A/C CONDENSER (VER. EXACT LOCATION
W/MEP ENGINEER)
9.NOTE: THESE WALLS ARE TO BE DETERMINED BY
TRUSS MANUF. INTENT IS TO HAVE SIMILAR
CONSTRUCTION TO WALL TYPE "F" (NOTIFY
ARCHITECT OF ANY DISCREPANCIES)
10.FLOOR DRAIN (VER. EXACT LOCATION W/MEP
ENGINEER)
11.34" HIGH HANDRAIL PER CODE EACH SIDE
12.PROVIDE METAIL NOSING ON STAIR W/PAINTED
TREADS & RISERS (GREY)
13.R-38 KRAFT FACE BATTS BELOW LANDINGS &
CATWALK
14.PROVIDE LANDING THAT IS FLUSH W/
MECHANICAL ENCLOSURE LEVEL
15.3'-0" X 6'-8" SELF-CLOSING ACCESS DOOR TO
EACH DRAFTSTOPPING ATTIC AREA -
COORDINATE EXACT LOCATION IN FIELD
W/MECHANICAL, ELECTRICAL AND PLUMBING
TRADES TO AVOID INTERFERENCE WITH MECH.
EQUIP., WATER HEATERS, ETC.
16.SCAB ON 2X FRAMING TO BOT. CHORD OF
TRUSS TO BRING VATWALK TO SAME ELEV. AS
EQUIPMENT PLATFORM FLOOR
17.LIMESTONE SILL (BELOW)
18.WATER HEATER (VER. EXACT SIZE, LOCATION &
CLEARANCES REQ'D. W/MEP ENGINEER) -
PROVIDE METAL DRAIN PAN @ EACH W.H. (TYP.)
19.MECH. EQUIP. (VER. EXACT SIZE, LOCATION
AND CLEARANCES REQ'D. W/ MEP ENGINEER)
20.LINE OF FIRST FLOOR WALL (BELOW)
21.LINE OF DRAFTSTOPPING - VER. LOCATION
W/TRUSS MANUF.
22.PROVIDE SELF-CLOSING ACCESS DOOR TO
EACH DRAFT STOPPING AREA W/AUTOMATIC
LATCHES - REFER TO SHT. A.305
23.GC SHALL PROVIDE AND INSTALL 1 WALL
MOUNTED 10LB ABC FIRE EXTINGUISHER IN THE
MECH. EQ. PLATFORM.
Keyed Attic Plan Notes:X Wall Legend X
2X6 INTERIOR PARTITION WALL:
5/8" GYPSUM BOARD EACH SIDE OF
2X6 WOOD STUDS @ 16" O.C.
PROVIDE ACOUSTICAL SOUND BATT
INSULATION @ ALL INTERIOR WALLS
AS DIRECTED BY OWNER
INTERIOR PARTITION WALL:
1 LAYER TYPE 'X' 5/8" GYPSUM
BOARD EACH SIDE OF 2X4 WOOD
STUDS @ 16" O.C. PROVIDE
ACOUSTICAL SOUND BATT
INSULATION @ ALL INTERIOR WALLS
AS DIRECTED BY OWNER
NOTE:
ALL OPENINGS, DOORS AND
WINDOW FRAMES ARE TO BE FIRE
CAULKED
A
B
C
INTERIOR EQUIPMENT ENCLOSURE WALL:
PROVIDE (1) LAYER OF 5/8" GYPSUM
BOARD ON THE INSIDE AND 2X WOOD
STUD AS REQUIRED TO PROVIDE CAVITY
FOR A TOTAL INSULATION OF R-38. SEE
DETAIL 5/A.303
F
EXTERIOR WALL (BRICK):
EXTERIOR BEARING WALL: BRICK
VENEER EXTERIOR FINISH W/ 1" AIR
SPACE ON TYVEK AIR INFILTRATION
BARRIER ON 1/2" APA RATED
PLYWOOD SHEATHING ON 2X6
WOOD STUDS @ 16" O.C. W/ R-19
KRAFT FACED BATT INSUL. W/ 5/8"
GYPSUM BOARD FINISH
General Wall Type Notes:
1.ALL INTERIOR WALLS ARE ASSUMED WALL TYPE "D" U.N.O.
2.ALL EXTERIOR WALLS ARE ASSUMED WALL TYPE "A" U.N.O.
DRAFTSTOPPING WALL:
3/8" PLYWOOD ON ONE SIDE OF
PRE-ENG. ROOF TRUSS. RUN UP TO
UNDER SIDE OF ROOF SHEATHING (SEE
TYPICAL DETAIL ON SHEET A.305 FOR
ADDITIONAL INFORMATION)
GINTERIOR PARTITION WALL:
1 LAYER TYPE 'X' 5/8" GYPSUM
BOARD EACH SIDE OF 2X6 WOOD
STUDS @ 16" O.C. PROVIDE
ACOUSTICAL SOUND BATT
INSULATION @ ALL INTERIOR WALLS
AS DIRECTED BY OWNER
NOTE:
ALL OPENINGS, DOORS AND
WINDOW FRAMES ARE TO BE FIRE
CAULKED
E
TYPICAL INTERIOR PARTITION WALL:
2X4 STUDS @ 16" O.C. WITH 5/8" GYP.
BOARD EACH SIDE. PROVIDE
ACOUSTICAL SOUND BATT
INSULATION @ ALL INTERIOR WALLS
AS DIRECTED BY OWNER
D
1-HR. RATED 1-HR. RATED
NOT
U
S
E
D
TYPICAL INTERIOR PARTITION WALL:
2X4 STUDS @ 12" O.C. WITH 5/8" GYP.
BOARD EACH SIDE. PROVIDE
ACOUSTICAL SOUND BATT
INSULATION @ ALL INTERIOR WALLS
AS DIRECTED BY OWNER
H
NOT
U
S
E
D
1819
19
19
19
Mechanical Equip.
Platform
11
12
201
Attic 'B'
Attic 'D'
21
99
1616
15
1515
21
21
200
14
Attic 'C'
Attic 'B'
19
2
14
13
23
04/20/18
A.104
ROOF PLAN
JCRCCHECKED:
PROJECT NO:
DATE:
REVISIONS
NO DATE REMARKS
CORPORATE SEAL:
DRAWN:
SEAL:
THIS DOCUMENT IS "NOT FOR CONSTRUCTION"
UNLESS THE ARCHITECT OR ENGINEER'S
SIGNATURE AND SEAL APPEAR BELOW.
RAINBOW CHILD
CARE CENTER
C-PROTOTYPE
95 CENTENNIAL PARKWAY
SPOUT SPRINGS, NC 28326
2017.0643
COPYRIGHT cP-0215
2018 INTERPLAN PLLC RESERVES COPYRIGHT & OTHER RIGHTS RESTRICTING THESE DOCUMENTS TO THE ORIGINAL SITE OR PURPOSE FOR WHICH THEY WERE PREPARED. REPRODUCTIONS, CHANGES OR ASSIGNMENTS ARE PROHIBITED.604 COURTLAND STREET
SUITE 100
ORLANDO, FLORIDA 32804
PH 407.645.5008
FX 407.629.9124
ARCHITECTURE
ENGINEERING
INTERIOR DESIGN
PROJECT MANAGEMENT
ROOF PLAN
3/16"=1'-0"
Attic Space A
2506 Sq. Ft.
Attic Space B
2973 Sq. Ft.
Attic Space C
2014 Sq. Ft.
6
6
8
8
8
8
8
8 12
5
7
7
7
.
9
.
9
9 .9
..
9
4
4
4
4
4
4
4
12
12
1212
1
1
1
1
1
1
1
Attic Space D
2206 Sq. Ft.
Attic Space E
2241 Sq. Ft.
13
7
7
Attic 'A' Ventilation Calculation:
1 SQ. FT. OF ATTIC VENT PER 300 SQ. FT. OF ATTIC FLOOR
SPACE (OVER ALL PERIMETER OF ROOF)
TOTAL ATTIC SPACE: 2,506 SQ. FT
2,506 SQ. FT. / 300 SQ. FT. = 8.4 SQ. FT.
8.4 SQ. FT. / 2 (INTAKE/EXHAUST) = 4.1 SQ. FT.
4.1 SQ. FT. X 144 IN. = 590.4 SQ. IN. (NET FREE AREA REQUIRED)
VENTILATION EXHAUST CALCULATIONS:
ROOF LOUVER: B-144 ROUND METAL DOME VENT BY AIR
VENT EQUALS 144 NFA PER PIECE: 590.4 SQ. IN / 144 NFA = 4.1
STATIC VENTS REQ'D.
PROPOSED VENTILATION EXHAUST:
4 STATIC ROOF VENTS PROVIDED
VENTILATION INTAKE CALCULATIONS:
590.4 SQ.IN. (NET FREE AREA REQUIRED - SEE ABOVE)
AIR VENT UNDER EAVE VENT 16"X6" EQUALS 42 SQ.IN. NFA PER
PIECE: 590.4 SQ.IN. / 42 NFA = 14.1 = 14 VENTS REQ'D.
PROPOSED VENTILATION INTAKE:
14 VENTS PROVIDED
VENTILATION DIAGRAM PLAN
Attic 'B' Ventilation Calculation:
1 SQ. FT. OF ATTIC VENT PER 300 SQ. FT. OF ATTIC FLOOR
SPACE (OVER ALL PERIMETER OF ROOF)
TOTAL ATTIC SPACE: 2,973 SQ. FT
2,973 SQ. FT. / 300 SQ. FT. = 10.0 SQ. FT.
10.0 SQ. FT. / 2 (INTAKE/EXHAUST) = 5 SQ. FT.
5 SQ. FT. X 144 IN. = 720 SQ. IN. (NET FREE AREA REQUIRED)
VENTILATION EXHAUST OPTIONS:
ROOF LOUVER: B-144 ROUND METAL DOME VENT BY AIR
VENT EQUALS 144 NFA PER PIECE: 720 SQ. IN / 144 NFA = 5
STATIC VENTS REQ'D.
PROPOSED VENTILATION EXHAUST:
5 STATIC ROOF VENTS PROVIDED
VENTILATION INTAKE CALCULATIONS:
720 SQ.IN. (NET FREE AREA REQUIRED - SEE ABOVE)
AIR VENT UNDER EAVE VENT 16"X6" EQUALS 42 SQ.IN. NFA PER
PIECE: 720 SQ.IN. / 42 NFA = 17.14 = 17 VENTS REQ'D.
PROPOSED VENTILATION INTAKE:
17 VENTS PROVIDED
Attic 'C' Ventilation Calculation:
1 SQ. FT. OF ATTIC VENT PER 300 SQ. FT. OF ATTIC FLOOR
SPACE (OVER ALL PERIMETER OF ROOF)
TOTAL ATTIC SPACE:12,162 SQ. FT
2,014 SQ. FT. / 300 SQ. FT. = 6.7 SQ. FT.
6.7 SQ. FT. / 2 (INTAKE/EXHAUST) = 3.35 SQ. FT.
3.35 SQ. FT. X 144 IN. = 482.4 SQ. IN. (NET FREE AREA
REQUIRED)
VENTILATION EXHAUST OPTIONS:
ROOF LOUVER: B-144 ROUND METAL DOME VENT BY AIR
VENT EQUALS 144 NFA PER PIECE: 482.4 SQ. IN / 144 NFA =
3.35
STATIC VENTS REQ'D.
PROPOSED VENTILATION EXHAUST:
3 STATIC ROOF VENTS PROVIDED
VENTILATION INTAKE CALCULATIONS:
482.4 SQ.IN. (NET FREE AREA REQUIRED - SEE ABOVE)
AIR VENT UNDER EAVE VENT 16"X6" EQUALS 42 SQ.IN. NFA PER
PIECE: 482.4 SQ.IN. / 42 NFA = 11.48 = 11 VENTS REQ'D.
PROPOSED VENTILATION INTAKE:
11 VENTS PROVIDED
Attic 'D' Ventilation Calculation:
1 SQ. FT. OF ATTIC VENT PER 300 SQ. FT. OF ATTIC FLOOR
SPACE (OVER ALL PERIMETER OF ROOF)
TOTAL ATTIC SPACE: 8,720 SQ. FT
2,206 SQ. FT. / 300 SQ. FT. = 7.35 SQ. FT.
7.35 SQ. FT. / 2 (INTAKE/EXHAUST) = 3.67 SQ. FT
3.67 SQ. FT. X 144 IN. = 529.2 SQ. IN. (NET FREE AREA
REQUIRED)
VENTILATION EXHAUST OPTIONS:
ROOF LOUVER: B-144 ROUND METAL DOME VENT BY AIR
VENT EQUALS 144 NFA PER PIECE: 529.2 SQ. IN / 144 NFA =
3.67 STATIC VENTS REQ'D.
PROPOSED VENTILATION EXHAUST:
4 STATIC ROOF VENTS PROVIDED
VENTILATION INTAKE CALCULATIONS:
529.2 SQ.IN. (NET FREE AREA REQUIRED - SEE ABOVE)
AIR VENT UNDER EAVE VENT 16"X6" EQUALS 42 SQ.IN. NFA PER
PIECE: 529.2 SQ.IN. / 42 NFA = 12.6 = 13 VENTS REQ'D.
PROPOSED VENTILATION INTAKE:
13 VENTS PROVIDED
Attic 'E' Ventilation Calculation:
1 SQ. FT. OF ATTIC VENT PER 300 SQ. FT. OF ATTIC FLOOR
SPACE (OVER ALL PERIMETER OF ROOF)
TOTAL ATTIC SPACE: 2,241 SQ. FT
2,241 SQ. FT. / 300 SQ. FT. = 7.47 SQ. FT.
7.47 SQ. FT. / 2 (INTAKE/EXHAUST) = 3.73 SQ. FT.
3.73 SQ. FT. X 144 IN. = 537.8 SQ. IN. (NET FREE AREA
REQUIRED)
VENTILATION EXHAUST OPTIONS:
ROOF LOUVER: B-144 ROUND METAL DOME VENT BY AIR
VENT EQUALS 144 NFA PER PIECE: 537.8 SQ. IN / 144 NFA =
3.73 STATIC VENTS REQ'D.
PROPOSED VENTILATION EXHAUST:
4 STATIC ROOF VENTS PROVIDED
VENTILATION INTAKE CALCULATIONS:
537.8 SQ.IN. (NET FREE AREA REQUIRED - SEE ABOVE)
AIR VENT UNDER EAVE VENT 16"X6" EQUALS 42 SQ.IN. NFA PER
PIECE: 537.8 SQ.IN. / 42 NFA = 12.8 = 13 VENTS REQ'D.
PROPOSED VENTILATION INTAKE:
13 VENTS PROVIDED
General Roof Plan Notes:
1. SEE CONSTRUCTION SPECIFICATIONS FOR
FLASHING NOTES
2. FLASH ALL ROOF PENETRATIONS AS
REQUIRED AND PER CODE
3. LOCATE ALL PLUMBING STACKS AT REAR
ROOF PLANE. VERIFY THAT NO VENTS ARE
VISIBLE FROM THE STREET
4.PROVIDE PRE-FIN. MTL. DRIP EDGE @ ALL
ROOF EAVES AND RAKES
5.PROVIDE PRE-FIN. 6" ALUM. GUTTERS &
DOWNSPOUTS (MECH. FASTENED) - COORD.
DOWNSPOUT LOCATIONS W/OWNER &
CIVIL ENG. IN FIELD
1.LOCATION OF DRAFTSTOPPING - VER. W/TRUSS MANUF.
NOTE: DO NOT EXCEED 3,000 SQ.FT. OF ATTIC SPACE WITHOUT
DRAFTSTOPPING - SEE DETAIL ON SHEET A.305 FOR ADDITIONAL
INFORMATION
2.IF ROOF ABOVE GYM IS NOT OPEN TO MAIN ROOF STRUCTURE (ROOF
#3) PROVIDE RIDGE VENT. OTHERWISE ALLOW VENTILATION TO PASS
THROUGH TO MAIN ROOF ATTIC AND OUT THROUGH EXHAUST VENTS
3.A/C CONDENSING UNIT - VER. EXACT SIZE, LOCATION AND
CLEARANCES W/MEP ENGINEER
4.LINE OF EXTERIOR WALL BELOW (TYP.)
5.PROVIDE GRACE ICE & WATER SHIELD @ ALL EAVES & VALLEYS 36" PAST
THE INTERIOR OF THE EXTERIOR WALL AND UP EACH VALLEY SIDE 18"
(MIN.)
6.ASPHALT SHINGLES ROOF (TYP.)
7.PROVIDE FULL GRACE ICE & WATER SHIELD @ ALL DORMERS (TYP.)
8.EXTEND GRACE ICE & WATER SHIELD UP ADJACENT WALL 18" (MIN.)
9.TYP. O.H. FOR ALL HIPS (U.N.O.) - SEE WALL SECTIONS
10.TYP. RAKE PROJECTION (U.N.O.)
11.TYP. O.H. FOR ALL DORMERS (U.N.O.)
12.AIRVENT: B-144 METAL DOME VENT - INSTALL PER MANUF. SPECS. VENTS
MUST BE INSTALLED PER IBC 1203.2 (TYP.) - PAINT TO MATCH ROOF
13.SINGLE-PLY 60 MIL. EPDM W/PREFIN. METAL EDGE FLASHING W/DRIP
EDGE - INSTALL IN STRICT COMPLIANCE W/MANUF. INSTALLATION
SPECS. MIN. SLOPE 1/4" PER FOOT
14.OUTLINE OF MECHANICAL EQUIPMENT PLATFORM- RM. 201
Keyed Roof Plan Notes:X
ATTIC AATTIC 'B'ATTIC 'D'ATTIC 'E'ATTIC 'C'
14
1
04/20/18
A.105
FINISH PLAN
JCRCScale: 3/16" = 1'-0"
Equipment Platform Finish Plan
Scale: 1-1/2" = 1'-0"
Chair Rail Detail
Scale: 1/4" = 1'-0"
Typ. Int. Elev. @ Infant
Scale: 1/4" = 1'-0"
Typ. Int. Elev. @ Classrooms
CHECKED:
PROJECT NO:
DATE:
REVISIONS
NO DATE REMARKS
CORPORATE SEAL:
DRAWN:
SEAL:
THIS DOCUMENT IS "NOT FOR CONSTRUCTION"
UNLESS THE ARCHITECT OR ENGINEER'S
SIGNATURE AND SEAL APPEAR BELOW.
RAINBOW CHILD
CARE CENTER
C-PROTOTYPE
95 CENTENNIAL PARKWAY
SPOUT SPRINGS, NC 28326
2017.0643
COPYRIGHT cP-0215
2018 INTERPLAN PLLC RESERVES COPYRIGHT & OTHER RIGHTS RESTRICTING THESE DOCUMENTS TO THE ORIGINAL SITE OR PURPOSE FOR WHICH THEY WERE PREPARED. REPRODUCTIONS, CHANGES OR ASSIGNMENTS ARE PROHIBITED.604 COURTLAND STREET
SUITE 100
ORLANDO, FLORIDA 32804
PH 407.645.5008
FX 407.629.9124
ARCHITECTURE
ENGINEERING
INTERIOR DESIGN
PROJECT MANAGEMENT
FINISH PLAN
3/16"=1'-0"
Pre-School 2
Pre-K 2
Staff
Lounge
Pre-K 1
Pre-School 1
Laundry
Rm.
Varsity
Room
Corridor 1
Toddler 1
Gym
Infant 1Infant 2
Young
Pre-School
Central Corridor
Vestibule
Childs
Toilet 4
Childs
Toilet 3
Child
Toilet 5
Childs
Toilet 7
Childs
Toilet 9
Childs
Toilet 8
Toddler 2
Childs
Toilet 6
Gym Child ToiletCloset
Gym Equip.Gym
Equip.
Directors
Office
Car
Seat
Sto.
Utility Rm.
Kitchen
Pantry
Kitchen
Outdoor Toy
Storage
Closet
Adult B.F.
Toilet 1
Stair
Child
Toilet 2
Lobby
Reception
Conf.Rm.
Closet
109
110
134
135
136
138
113
112
132
128
106
108
104
125 124
122
118
102
126
129123
101
100111
117
116
115
114
121
120
127
133
103
105
107
119
139
137
140
Hall
131
I.T. Closet
130
141
REF.FREEZ.FUTURE
REF.
PREP
SINK
HAND
SINK
D1
D4
D1
D1 F1
B2
P11
F3
F3
WJ1
WJ1
F3 B2 P6
D3 D2
CT4C2 CT4C2
F1 B2 P11
F1 B2 P11
WF2D1
F1 B2 P11
B2
CT2
CT1
F3
WJ1
WJ2
F3
F5
WJ1
P10
ABOVE
CHAIR RAIL
P10
ABOVE
CHAIR RAIL
P11
BELOW
CHAIR RAIL
F3
F2
F3
F2
B1
P1
P1
TYP.
F2 F4
C1
CT3
F4
F3
D1D1
F4
F3
F4 F2
C1
CT3
B1
P1
P1
TYP.
P11
C2 CT4
B2 F1
WF2
D1
C2 CT4
WF2
B2
D1
P11F1
C2
CT4 C2 CT4
WF2
B2
D1
P11F1
C2
CT4
F3 F1
F3
F1
C2
CT4
C2
CT4
F1
F1
WF2
B2
D1
P11F1
WF1 WF1
D1D1D1
D1 D1 D1 D1 D1
D1
D1
D1
D6
D1
C1
CT3
C1
CT3
C2
CT4
C2
CT4F3
B2
F3 F1
F4
F2
F4
F2
F1
F3
F1
F3
C2 CT4 C2 CT4
WJ1
WJ1
F1
F3
F1
F3
F3F3
F1
WF2
D1
P11 F1
D1
WF2
B2P11F1
D1
WF2
B2 P11F1
P11
B2
F4 F2 F2 F4
F2
F4
C1
CT3
C1
CT3
C1
CT3
C1
CT3
C1
CT3
D3D2D3D2
D3 D2
D3 D3
D6 D6
B3
F5
P11
B1
P1 B2
WF2
B1 P11 F2
F3
F1 D1
F3 B2
F6
C2
CT4
WF1
D2 D3
D2
D3
D3D2
D3
D2
D2
WJ1
WJ2B1P11F1
WF2
D3 D2
P8 B2
P3 B1
P7
B2
B2
P7
F1
B2
WF1
B2F2P11B2F2P11
F1 B2 P11
F1 B2 P11
D5
F3 B2 P11
WJ1 WJ1
WJ1
WJ1
P11B2 F1
C2
CT4
P6B2 F1
D1
C3
C3
P11
BELOW
CHAIR RAIL
P4
D1
D1
B2
P6
P10
ABOVE
CHAIR RAIL
P11
BELOW
CHAIR RAIL
F3 F3
F3 F3
B2 P1
F3
WJ1
WJ1
WJ1
C1
CT3
WJ1
D1
B2
F3
P11
WJ1
F3B2P6F1F3
DESCRIPTION
F3
F2
BEHR 560C-3 HOLIDAY ROAD
SHERWIN WILLIAMS: CUSTOM MATCH
B20W2651- COLORANT: Y1 Y3P1
SHERWIN WILLIAMS
B20W2651
BEHR 580-3 IMPRESSION SKY
MANUFACTURER
P8 SW 1206 MOON RIVER
SHERWIN WILLIAMS: CUSTOM MATCH
B20W2651 - COLORANT: W1 L1 R3 Y1
SHERWIN WILLIAMS
B2W2651
P7
WJ2
D1
D6
DOOR JAMB = WHITE (H.M.)
SHERWIN WILLIAMS
SAFETY BLUE
DOOR JAMB = RED (H.M.)
F
SYMBOL FINISH / COLOR
WJ1
WJ
WHITE JAMB
WINDOW JAMBS
(1) COAT PRIMER W/ (2) COATS PAINT
RED JAMB
FLOORS
F1
P PAINTS
BEHR 340E-2 COTTONSEED
P2
F4
SHERWIN WILLIAMS: CUSTOM MATCH
B20W2651 - COLORANT: L1 R3 Y1
MANUFACTURER
P4
P3
SHERWIN WILLIAMS
B20W2651
SHERWIN WILLIAMS: CUSTOM MATCH
B20W2651 - COLORANT: L1 N1 R3
FINISH / COLORDESCRIPTIONSYMBOL
(1) COAT PRIMER W/ (2) COATS PAINT
SW-2234 MEMORY LANE
P5
SW-6519 HINTING BLUE
P9
SHERWIN WILLIAMS
B20W2651
WHITE WALL
PACKAGE EXTRA WHITE
UL 220-2 VOYAGE
P6
RAINBOW WHITE
P10 SW 6520 HONEST BLUE
D5
F6
F5
DOOR EXTERIOR = BLUE
D4
DOOR INTERIOR = WHITE
D3
DOOR JAMB = RED (H.M.)
DOORS & DOOR JAMBS COLORS
DOOR JAMB INT. = WHITE
DOOR INTERIOR = RED
D2
D
EXTERIOR DOOR
DOOR WOOD PRE-FINISHED (MAPLE)
SHERWIN WILLIAMS
PRO CLASSIC WATER BORN SEMI-GLOSS
DOOR WOOD PRE-FINISHED (MAPLE)
DOOR JAMB EXT. = BLUE
DOOR WOOD PRE-FINISHED (MAPLE)INTERIOR DOOR
EXTERIOR DOOR
INTERIOR DOOR
EXTERIOR DOOR
DOOR JAMB = BLUE (H.M.)
SHERWIN WILLIAMS
SAFETY BLUE
SHERWIN WILLIAMS
INTERIOR DOOR
INTERIOR WINDOW JAMBS
B
SHERWIN WILLIAMS
NATURAL MAPLE
BASE
C1
B1
PL
INTERIOR WINDOW JAMBS
CABINETSC
(APPROVED BY OWNER)
C3
MAPLE FINISH CABINETS
C2
PL1
FINISH SCHEDULE
SHERWIN WILLIAMS
SAFETY BLUE
SHERWIN WILLIAMS
SAFETY BLUE
B3
B2
NATURAL MAPLE
WHITE THERMOFOIL
NO BASE
(APPROVED BY OWNER)
WHITE FINISH CABINETS
CUSTOM CABINETS
(APPROVED BY OWNER)
F.R.P.: MARLITE (OR EQUAL)
WF WALL FINISHES
F.R.P. WALL FINISH TO CEILING F.R.P.: S100 G WHITE (CLASS A)WF1
NOTE: ALL INTERIOR WALLS TO RECEIVE EGGSHELL PAINT FINISH. ALL CEILINGS TO RECEIVE FLAT PAINT FINISH. PAINT ALL EXPOSED DUCT WORK TO MATCH CEILINGS
(1) COAT PRIMER W/ (2) COATS PAINT
(1) COAT PRIMER W/ (2) COATS PAINT
(1) COAT PRIMER W/ (2) COATS PAINT
(1) COAT PRIMER W/ (2) COATS PAINT
(1) COAT PRIMER W/ (2) COATS PAINT
(1) COAT PRIMER W/ (2) COATS PAINT
(1) COAT PRIMER W/ (2) COATS PAINT
(1) COAT PRIMER W/ (2) COATS PAINT
(1) COAT PRIMER W/ (2) COATS PAINT SHERWIN WILLIAMS: CUSTOM MATCH
B34W851 - COLORANT: L1 R3
P11
PLASTIC LAMINATE
SHERWIN WILLIAMS
B20W2651
SHERWIN WILLIAMS
B20W2651
PLAS. LAM. HALF WALL @ RECEPTION AREA 7012-58 AMBER MAPLE OR
10734-60 LIMBER MAPLEFORMICA OR WILSON
7811 VERVE
COLOR 18103 (ACADEMY)
TOLI
CPT (INSTALLED BY GC)
MASLAND
ROPPE 4" VINYL BASE - 1/8"
V.C.T.
SHEET VINYL (INSTALLED BY GC)
STANDARD EXCELON IMPERIAL TEXTURE
COLOR 51933 (BLUE CLOUD)ARMSTRONG
FLOOR PAINT
CLASSIC VERMONT MAPLE #772
GREY
VINYL COVE BASE/TRANSITION MLDG
PADDED SHEET VINYL (INSTALLED BY GC)
CPT. (INSTALLED BY GC)
MASLAND
SIGNAFLEX MAPLE
COLOR 139 (DEEP NAVY)VINYL COVE BASE/TRANSITION MLDG-S
7811 VERVE
COLOR 18111 (BLUE RIBBON)
ROPPE 4" VINYL BASE - 1/8"
COLOR 632 (FLAX)
SW-6190 FILMY GREEN
F.R.P.: MARLITE (OR EQUAL)F.R.P. WALL FINISH TO 4'-0" A.F.F.F.R.P.: S100 G WHITE (CLASS C)WF2
X
D2
D3
D2
D3
D2
D3
D6
5'-11 1/4"10'-3 7/8"8'-1 11/16"5'-11 1/4"21'-6 7/8"23'-9 7/8"21'-5 11/16"9'-11 3/8"8'-0 11/16"14'-11 3/8"7'-7 3/4"6'-4 3/4"8'-0"19'-2 1/4"11'-3 1/4"
19'-0 3/8"16'-11 1/4"16'-11 1/4"6'-10 3/8"
10'-6 3/8"10'-2 1/4"
6'-10 3/8"
10'-10 3/8"
11'-11 3/8"
P11 1 COAT
12" PASTTYP.P10 BELOW
CHAIR RAIL12"PASTTYP.12" PAST
TYP.
P11 ABOVE
CHAIR RAIL
12" PAST
TYP.
WF1
WF112" PASTTYP.12" PAST
TYP.
WF1
WF1
12" PASTTYP.ZODIAQ BOREALIS BLUE
CT2
CT COUNTER TOPS
PLAS. LAM. COUNTER
CT1 SOLID SURFACE COUNTER
PLAS. LAM. COUNTER
PLAS. LAM. COUNTERCT3
CT4 FORMICA LAMINATE
WILSONART LAMINATE
FINISH - 58 (MATTE)
COLOR - 459 (BRITE WHITE)
POST FORMED ROLL DRIP EDGE
FINISH - 60 (MATTE)
COLOR - 4166 (PAMPAS)
POST FORMED ROLL DRIP EDGE
WILSONART LAMINATE FINISH - 60 (MATTE)
COLOR - 4142 (GREY GLACE)
POST FORMED ROLL DRIP EDGE
WF1
F.E.
F.E.
F.E.F.E.
COMBO
OVEN
UNIT
COMBO
OVEN
UNIT
B2F3
B2F3B2F3
B3
NOTES:
1.CHAIR RAIL IS TO RUN ENTIRE
PERIMETER OF CORRIDOR &
ROOMS 100, 102, 124, & 125
2.FLOORING LEAD TIME IS 7 WEEKS
FROM APPROVED OVER FORM
AND TAKE OFF
3.G.C. TO PROVIDE THE GYM PAD
MEASUREMENTS TO THE OWNER
NO LATER THAN SEVEN (7) WEEKS
BEFORE C/O.
WF1
ULTRALITE SUPERCOAT MOULDING
956WWM (1/2" X 4-1/4")
(SEE FINSIH SCHEDULE - P9)39" A.F.F. @INFANT RMS.ULTRALITE SUPERCOAT MOULDING
300M (1" X 3")
(SEE FINISH SCHEDULE - P9)34.5" A.F.F. @CORRIDORULTRALITE SUPERCOAT MOULDING
956WWM (1/2" X 4-1/4")
(SEE FINSIH SCHEDULE - P9)39" A.F.F. @INFANT RMS.ULTRALITE SUPERCOAT MOULDING
300M (1" X 3")
(SEE FINISH SCHEDULE - P9)34.5" A.F.F. @CORRIDOR8'-0" CEILING HEIGHT56" A.F.F.GYP. BRD. (PAINT)
4" VINYL COVE BASE
GYP. BRD. CLG. (PAINT)
CHAIR RAIL - 39" A.F.F.
INFANT 9" WALLPAPER
BOARDS
GYP. BRD. (PAINT)
NOTES:
SEE FINISH SCHEDULE & FINISH
PLAN ON SHEET A.500
(1) PHONE JACK
(2) LIGHT SWITCH
39"Equipment
Platform
201
Attic 'B'
F6 P11
2018'-0" CEILING HEIGHT56" A.F.F.GYP. BRD. (PAINT)
4" VINYL COVE BASE
GYP. BRD. CLG. (PAINT)
GYP. BRD. (PAINT)
NOTES:
SEE FINISH SCHEDULE & FINISH
PLAN ON SHEET A.500
(1) PHONE JACK
(2) LIGHT SWITCH
CHECKED:
PROJECT NO:
DATE:
REVISIONS
NO DATE REMARKS
CORPORATE SEAL:
DRAWN:
SEAL:
THIS DOCUMENT IS "NOT FOR CONSTRUCTION"
UNLESS THE ARCHITECT OR ENGINEER'S
SIGNATURE AND SEAL APPEAR BELOW.
RAINBOW CHILD
CARE CENTER
C-PROTOTYPE
95 CENTENNIAL PARKWAY
SPOUT SPRINGS, NC 28326
2017.0643
COPYRIGHT cP-0215
2018 INTERPLAN PLLC RESERVES COPYRIGHT & OTHER RIGHTS RESTRICTING THESE DOCUMENTS TO THE ORIGINAL SITE OR PURPOSE FOR WHICH THEY WERE PREPARED. REPRODUCTIONS, CHANGES OR ASSIGNMENTS ARE PROHIBITED.604 COURTLAND STREET
SUITE 100
ORLANDO, FLORIDA 32804
PH 407.645.5008
FX 407.629.9124
ARCHITECTURE
ENGINEERING
INTERIOR DESIGN
PROJECT MANAGEMENT
04/20/18
A.200
EXTERIOR ELEVATIONS
JCRC
3'-0"
D
A.301
G
A.302
1 FRONT (EAST) ELEVATION 3/16"= 1'-0"
2
1
6
2
3
3
6 6
M-1 M-1
M-1
M-2
M-4
M-2
M-9 M-9
M-6
M-5
M-8 M-8
5
12
5
12
5
12
M-2
12
E
A.301
C
A.300
F
A.301
A
A.300
H
A.302
2 LEFT (SOUTH) ELEVATION 3/16"= 1'-0"
1 1
222
33
44
6 6
M-1M-1M-1
M-9M-9M-9M-9
M-4
M-6
M-8
5
12
5
12
5
12
5
12
M-5
7
M-2
8888
3
7
General Elevation Notes:
1). ALL TRIM BOARDS (U.N.O.) WILL BE CLAD IN PRE-FIN.
ALUM. - DETERMINE GAUGE PER RAINBOW CHILD CARE
CENTER SPEC'S.
2). EXTERIOR BRICK IS TO BE STANDARD SIZE - COURSE
OUT QUOIN CORNERS
3). EXTERIOR WINDOWS ARE JELDWEN. THEY ARE
OPERABLE AND HAVE SCREENS. SCREENS ARE TO BE 16
MESH OR BETTER.
4). DO NOT SCALE HATCHING. REFER TO BUILDING
SECTIONS & WALL SECTIONS FOR PROPER
CONSTRUCTION METHODS. A.300 - A.305
5). SIGNAGE TO BE INSTALLED BY G.C. AS DIRECTED BY
OWNER
Exterior Elevation Materials
ITEM MANUFACTURER MODEL COLOR / FINISH NOTES
BRICK
ASPHALT SHINGLES
BREAK METAL TRIM COLOR - 807 (CLAY)
BRAMPTON BRICK
NOTE:
JELD-WEN WINDOWS TO BE PRE-FINISHED W/DESERT SAND
STONE VENEER
COLOR - JASPER
IF BRICK IS NOT READILY
AVAILABLE PROVIDE OPTIONS
FOR OWNER TO APPROVE
VINYL SIDING CERTAINTEED
CORPORATION
DOUBLE 5" CLAPBOARD
CROSSROADS SERIES
MIST -
QUALITY EDGE TRULINE EMBOSSED TRIM COIL -
GAF ROOFING COLOR - WEATHERED WOOD -TIMBERLINE HD - LIFETIME SHINGLES
-
-
PRE-FIN ALUMINUM GUTTER MASTIC HOME EXTERIORS 6" GUTTER COIL - 27 GAUGE COLOR - PEBBLESTONE CLAY
(VERIFY W/OWNER)
VER. W/ OWNER FOR
MANUFACTURER, MODEL,
AND COLOR
SILLS T.B.D.LIMESTONE VARIEGATED
SYMBOL
M-1
M-2
M-3
M-4
M-5
M-6
M-7
X-x
-CEDAR TRIM BOARD CEDAR NATURAL & SEALEDM-8 -
---
SPLITFACE C.M.U.MICHIGAN CERTIFIED
CONCRETE SPLIT FACED VAOLS
IF BLOCK IS NOT READILY
AVAILABLE PROVIDE OPTIONS
FOR OWNER TO APPROVE
M-9
1.TYPICAL EAVE - SEE DETAIL FOR MORE INFORMATION
2.BRICK SOLDIER COURSE (TYP.)
3.SILL SLOPED TO ALLOW WATER RUNOFF WITH DRIP EDGE
4.1X2 TRIM BRD. ON 1X6 RAKE BRD. ON 1X6 SUB-RAKE
BRD. WITH PRE-FINISHED ALUMINUM WRAP
5.1/2" AZTEK PANEL (PAINT)
6.PRE-FINISHED ALUMINUM GUTTER AND DOWNSPOUT -
VERIFY CONNECTION DETAIL AND LOCATION WITH
CIVIL ENGINEER
7.PROVIDE LOUVERED DORMERS FOR MECHANICAL
INTAKE(VER. W/ MECH. DRAWINGS)
8.LINE OF DRAFT STOPPING
9.LINE OF BUILDING BEYOND
10.CONDENSING UNIT. SEE MECH. DRAWINGS FOR EXACT
LOCATIONS
11.60MIL EPDM ROOF FULLY ADHERED
12.PROPOSED 81" X 30" SIGN SHOWN. SIGN TO BE
PERMITTED UNDER SEPARATE SUBMITTAL BY SIGN
VENDOR.
Keyed Elevation Notes:X
CHECKED:
PROJECT NO:
DATE:
REVISIONS
NO DATE REMARKS
CORPORATE SEAL:
DRAWN:
SEAL:
THIS DOCUMENT IS "NOT FOR CONSTRUCTION"
UNLESS THE ARCHITECT OR ENGINEER'S
SIGNATURE AND SEAL APPEAR BELOW.
RAINBOW CHILD
CARE CENTER
C-PROTOTYPE
95 CENTENNIAL PARKWAY
SPOUT SPRINGS, NC 28326
2017.0643
COPYRIGHT cP-0215
2018 INTERPLAN PLLC RESERVES COPYRIGHT & OTHER RIGHTS RESTRICTING THESE DOCUMENTS TO THE ORIGINAL SITE OR PURPOSE FOR WHICH THEY WERE PREPARED. REPRODUCTIONS, CHANGES OR ASSIGNMENTS ARE PROHIBITED.604 COURTLAND STREET
SUITE 100
ORLANDO, FLORIDA 32804
PH 407.645.5008
FX 407.629.9124
ARCHITECTURE
ENGINEERING
INTERIOR DESIGN
PROJECT MANAGEMENT
04/20/18
A.201
EXTERIOR ELEVATIONS
JCRC
3'-0"
2'-10"
E
A.301
C
A.300
F
A.301
A
A.300
H
A.302
2 RIGHT (NORTH) ELEVATION 3/16"= 1'-0"
2
1
2
3
6
6
3
4 4
M-1
M-1
M-1
M-1
M-2
M-2M-2
M-4
M-4
M-9 M-9 M-9
M-5
2
M-8
1010
5
12
5
12
5
12
5
12
M-2
11
8
88
8
M-4
3'-0"
G
A.302
D
A.301
1 REAR (WEST) ELEVATION 3/16"= 1'-0"
1
11
2 2
3 3
4
6
M-1 M-1
M-5 M-5M-5
M-2
M-2
M-4
M-6
10
5
5
12
5
12
M-2
General Elevation Notes:
1). ALL TRIM BOARDS (U.N.O.) WILL BE CLAD IN PRE-FIN.
ALUM. - DETERMINE GAUGE PER RAINBOW CHILD CARE
CENTER SPEC'S.
2). EXTERIOR BRICK IS TO BE STANDARD SIZE - COURSE
OUT QUOIN CORNERS
3). EXTERIOR WINDOWS ARE JELDWEN. THEY ARE
OPERABLE AND HAVE SCREENS. SCREENS ARE TO BE 16
MESH OR BETTER.
4). DO NOT SCALE HATCHING. REFER TO BUILDING
SECTIONS & WALL SECTIONS FOR PROPER
CONSTRUCTION METHODS. A.300 - A.305
5). SIGNAGE TO BE INSTALLED BY G.C. AS DIRECTED BY
OWNER
Exterior Elevation Materials
ITEM MANUFACTURER MODEL COLOR / FINISH NOTES
BRICK
ASPHALT SHINGLES
BREAK METAL TRIM COLOR - 807 (CLAY)
BRAMPTON BRICK
NOTE:
JELD-WEN WINDOWS TO BE PRE-FINISHED W/DESERT SAND
STONE VENEER
COLOR - JASPER
IF BRICK IS NOT READILY
AVAILABLE PROVIDE OPTIONS
FOR OWNER TO APPROVE
VINYL SIDING CERTAINTEED
CORPORATION
DOUBLE 5" CLAPBOARD
CROSSROADS SERIES
MIST -
QUALITY EDGE TRULINE EMBOSSED TRIM COIL -
GAF ROOFING COLOR - WEATHERED WOOD -TIMBERLINE HD - LIFETIME SHINGLES
-
-
PRE-FIN ALUMINUM GUTTER MASTIC HOME EXTERIORS 6" GUTTER COIL - 27 GAUGE COLOR - PEBBLESTONE CLAY
(VERIFY W/OWNER)
VER. W/ OWNER FOR
MANUFACTURER, MODEL,
AND COLOR
SILLS T.B.D.LIMESTONE VARIEGATED
SYMBOL
M-1
M-2
M-3
M-4
M-5
M-6
M-7
X-x
-CEDAR TRIM BOARD CEDAR NATURAL & SEALEDM-8 -
---
SPLITFACE C.M.U.MICHIGAN CERTIFIED
CONCRETE SPLIT FACED VAOLS
IF BLOCK IS NOT READILY
AVAILABLE PROVIDE OPTIONS
FOR OWNER TO APPROVE
M-9
1.TYPICAL EAVE - SEE DETAIL FOR MORE INFORMATION
2.BRICK SOLDIER COURSE (TYP.)
3.SILL SLOPED TO ALLOW WATER RUNOFF WITH DRIP EDGE
4.1X2 TRIM BRD. ON 1X6 RAKE BRD. ON 1X6 SUB-RAKE
BRD. WITH PRE-FINISHED ALUMINUM WRAP
5.1/2" AZTEK PANEL (PAINT)
6.PRE-FINISHED ALUMINUM GUTTER AND DOWNSPOUT -
VERIFY CONNECTION DETAIL AND LOCATION WITH
CIVIL ENGINEER
7.PROVIDE LOUVERED DORMERS FOR MECHANICAL
INTAKE(VER. W/ MECH. DRAWINGS)
8.LINE OF DRAFT STOPPING
9.LINE OF BUILDING BEYOND
10.CONDENSING UNIT. SEE MECH. DRAWINGS FOR EXACT
LOCATIONS
11.60MIL EPDM ROOF FULLY ADHERED
12.PROPOSED 81" X 30" SIGN SHOWN. SIGN TO BE
PERMITTED UNDER SEPARATE SUBMITTAL BY SIGN
VENDOR.
Keyed Elevation Notes:X
Partial Building Section
Scale: 1/4" = 1'-0"
C
A.300
NOTE:
1. PROVIDE DRAFTSTOPPING AS REQUIRED BY CODE
IN ATTIC SPACE
(SEE ROOF PLAN SHEET A-104 & DETAIL SHEET A-305).
2. FIRESTOPPING SHALL BE INSTALLED PER CODE
3. THE INTEGRITY OF ALL FIRESTOPPING AND
DRAFTSTOPPING SHALL BE CONTINUOUSLY
MAINTAINED.
4. FIRESTOPPING SHALL OCCUR AT ALL
INTERSECTIONS BETWEEN VERTICAL AND HORIZONTAL
SPACES PER CODE
Building Section
Scale: 1/4" = 1'-0"
A
A.300
CHECKED:
PROJECT NO:
DATE:
REVISIONS
NO DATE REMARKS
CORPORATE SEAL:
DRAWN:
SEAL:
THIS DOCUMENT IS "NOT FOR CONSTRUCTION"
UNLESS THE ARCHITECT OR ENGINEER'S
SIGNATURE AND SEAL APPEAR BELOW.
RAINBOW CHILD
CARE CENTER
C-PROTOTYPE
95 CENTENNIAL PARKWAY
SPOUT SPRINGS, NC 28326
2017.0643
COPYRIGHT cP-0215
2018 INTERPLAN PLLC RESERVES COPYRIGHT & OTHER RIGHTS RESTRICTING THESE DOCUMENTS TO THE ORIGINAL SITE OR PURPOSE FOR WHICH THEY WERE PREPARED. REPRODUCTIONS, CHANGES OR ASSIGNMENTS ARE PROHIBITED.604 COURTLAND STREET
SUITE 100
ORLANDO, FLORIDA 32804
PH 407.645.5008
FX 407.629.9124
ARCHITECTURE
ENGINEERING
INTERIOR DESIGN
PROJECT MANAGEMENT
04/20/18
A.300
BUILDING SECTIONS
JCRC
Partial Building Section
Scale: 1/4" = 1'-0"
B
A.300
CONCRETE SLAB
(SEE STRUCT.)
GIRDER TRUSS
GIRDER TRUSS
Utility. Rm.
Attic
Kitchen
Attic
Reception
Gym
Lobby
CONC.FOUND. WALL
(SEE STRUCT.)
8'-0"
ROOF LINE IN
FOREGROUND
5/8" DRYWALL
(3) LVL BEAM
SEE STRUCTURALLVL BEAM (FLUSH)
SEE STRUCTURAL.
JOISTS W/ HANGERS
2X6 @ 16" 0.C. JOISTS W/
HANGERS
HEADER
SEE STRUCTURAL
CEILING @ DIRECTOR'S OFFICE
BEYOND
FOUNDATION BEYOND.
SEE FOUNDATION PLAN.
GIRDER TRUSS
(1) LAYER 5/8" TYPE -X
GYPSUM BD.
(1) LAYER 5/8" TYPE -X GYPSUM
(TYPICAL)
44'-8"
3'-0"9'-0"12'-0"12'-0"Gym
Equip.
(R-38) BLOWN-IN
INSULATION
(R-38) BLOWN-IN
INSULATION
(R-38) BLOWN-IN
INSULATION
6'-10 3/8" ±COORDINATE W/ WINDOWSCONSTRUCTION OF
LID OVER STORAGE
TO SLOPE TO THE FRONT
FOUNDATION BEYOND.
SEE FOUNDATION PLAN.6'-8 3/8" ±(R-38) BATT
INSULATION
(R-38) BATT INSULATION8'-1 1/8"CONCRETE SLAB
(SEE STRUCT.)
CONC. FOUND.
(SEE STRUCT.)
Pre-K 2Varsity Room
3/4" F.R.T. PLYWD. SUBFLOOR
(SEE STRUCTURAL)
1 LAYER OF 5/8" GYP. BD.
Attic
Attic
Attic
12
5
12
5
Equipment Platform
PLATE HGT.(TYPICAL)(1) LAYER 5/8" TYPE -X GYP. BD.
INTERIOR WALL:
5/8" GYP. BD.. (EACH SIDE) ON
2X4 WOOD STUDS @ 16" O.C. U.N.O.
3'-3 5/8"
9'-5 7/8"9'-5 7/8"
5 1/2"
6'-0"
5 1/2"
DORMER BEYOND (TYPICAL)
METAL FLASHING
8'-6"8'-6"
Corridor 1
PRE-ENG. GIRDER
TRUSS. W/ HIGH
BOTTOM CHORD.
(SEE STRUCT.)9'-2"11 1/4"8'-2 3/4"8'-1 1/8" PLATE HGT.'QUIET BATT' SOUNDPROOFING INSULATION
(TYP. BELOW MECH. ROOM FLOOR)
(R-38) BLOWN-IN
INSULATION
PRE-ENG ROOF
TRUSSES (SEE STRUCT.)
PRE-ENG ROOF
TRUSSES (SEE STRUCT.)
PRE-ENG ROOF
TRUSSES (SEE STRUCT.)
(R-38) BLOWN-IN
INSULATION
(R-38) BLOWN-IN
INSULATION
5 1/2"
Child Toilet 7
8'-6 5/8"
DOOR LANDING
BEYOND
5
A.303
INSULATION BAFFLE
8'-1 1/8"CONCRETE SLAB
(SEE STRUCT.)
Pre-School 2
3/4" F.R.T. PLYWD. SUBFLOOR
(SEE STRUCTURAL)
1 LAYER OF 5/8" GYP. BD.
Attic
Attic
12
5
Equipment Platform
(1) LAYER 5/8"
TYPE -X GYP. BD.
INTERIOR WALL: 5/8" GYP. BD.
(EACH SIDE) ON 2X4 WOOD
STUDS @ 16" O.C. U.N.O.
3'-3 5/8"
9'-5 7/8"4'-0 7/8"
5 1/2"
6'-0"
3 5/8"
STAIRS TO EQUIPMENT PLATFORM.
REFER TO SHEET A-305.
Corridor 1
PRE-ENG. GIRDER
TRUSS. W/ HIGH
BOTTOM CHORD.
(SEE STRUCT.)9'-2"11 1/4"8'-2 3/4" PLATE HGT.'QUIET BATT'
SOUNDPROOFING
INSULATION (TYP. BELOW
MECH. ROOM FLOOR)
PRE-ENG ROOF
TRUSSES (SEE STRUCT.)9'-1 1/4"16 RISERS AT 6-13/16" EACHPRE-ENG ROOF
TRUSSES (SEE STRUCT.)
PRE-ENG ROOF
TRUSSES (SEE STRUCT.)
(R-38) BLOWN-IN
INSULATION
(R-38) BLOWN-IN
INSULATION
Attic
Young Pre-School
DOOR LANDING
(R-38) BLOWN-IN
INSULATION
Building Section
Scale: 1/4" = 1'-0"
F
A.301
Partial Building Section
Scale: 1/4" = 1'-0"
D
A.301
Partial Building Section
Scale: 1/4" = 1'-0"
E
A.301
NOTE:
1. PROVIDE DRAFTSTOPPING AS REQUIRED BY CODE
IN ATTIC SPACE
(SEE ROOF PLAN SHEET A-104 & DETAIL SHEET A-305).
2. FIRESTOPPING SHALL BE INSTALLED PER CODE
3. THE INTEGRITY OF ALL FIRESTOPPING AND
DRAFTSTOPPING SHALL BE CONTINUOUSLY
MAINTAINED.
4. FIRESTOPPING SHALL OCCUR AT ALL
INTERSECTIONS BETWEEN VERTICAL AND HORIZONTAL
SPACES PER CODE
CHECKED:
PROJECT NO:
DATE:
REVISIONS
NO DATE REMARKS
CORPORATE SEAL:
DRAWN:
SEAL:
THIS DOCUMENT IS "NOT FOR CONSTRUCTION"
UNLESS THE ARCHITECT OR ENGINEER'S
SIGNATURE AND SEAL APPEAR BELOW.
RAINBOW CHILD
CARE CENTER
C-PROTOTYPE
95 CENTENNIAL PARKWAY
SPOUT SPRINGS, NC 28326
2017.0643
COPYRIGHT cP-0215
2018 INTERPLAN PLLC RESERVES COPYRIGHT & OTHER RIGHTS RESTRICTING THESE DOCUMENTS TO THE ORIGINAL SITE OR PURPOSE FOR WHICH THEY WERE PREPARED. REPRODUCTIONS, CHANGES OR ASSIGNMENTS ARE PROHIBITED.604 COURTLAND STREET
SUITE 100
ORLANDO, FLORIDA 32804
PH 407.645.5008
FX 407.629.9124
ARCHITECTURE
ENGINEERING
INTERIOR DESIGN
PROJECT MANAGEMENT
04/20/18
A.301
BUILDING SECTIONS
JCRC8'-1 1/8"CONCRETE SLAB
(SEE STRUCT.)
12
12
5
5
Toddler 1Infant 1
Attic
Central Corridor
PLATE HGT.(TYPICAL)12'-0" CEILING HGT.(TYPICAL THRU-OUT CENTRALCORRIDOR "OCTAGON")INTERIOR WALL W/
5/8" GYPSUM BD.
SEE STRUCTURAL PLANS
FOR BEARING POINTS
87'-6" (OUTSIDE TO OUTSIDE OF 2x6 WOOD STUD WALLS)
33'-10 5/8"34'-3 5/8"19'-3 3/4" (WOOD STUD TO WOOD STUD)8'-1 1/8"PLATE HGT. (TYPICAL)8'-6"8'-6"
(1) LAYER 5/8" TYPE -X GYPSUM BD.
'STO' STO GUARD
DAMP PROOFING
MINIMUM 6" BELOW
TOP OF FOOTING.
TYPICAL @ ALL C.M.U.
BELOW GRADE
CONC. FOUND.
(SEE STRUCT.)CONC. FOUND.
(SEE STRUCT.)9'-0"SPRING POINT FOR CATHEDRALCEILING IN LOBBY ONLYLINE OF CATHEDRAL
CEILING IN LOBBY ONLY
4068 OPENING
TO CORRIDOR
(R-38) BLOWN-IN
INSULATION
(R-38) BLOWN-IN
INSULATION
(R-38) BLOWN-IN
INSULATION
PRE-ENG ROOF
TRUSSES (SEE STRUCT.)
PRE-ENG ROOF
TRUSSES (SEE STRUCT.)
PRE-ENG ROOF
TRUSSES (SEE STRUCT.)
(R-21) BATT INSULATION
W/ 3" ALUMINUM FOIL FACE
POLYISO. RIGID INSULATION
ALTERNATIVE: PROVIDE
BATT INSULATION TO A
TOTAL OF R-38.
ALTERNATIVE: PROVIDE
BATT INSULATION TO A
TOTAL OF R-38.
(R-21) BATT INSULATION
W/ 3" ALUMINUM FOIL
FACE POLYISO. RIGID
INSULATION12'-0"8'-1 1/8"8"EXISTING GRADE
Attic
Gym PLATE HGT.
PLATE HGT.
CONCRETE SLAB
(SEE STRUCT.)
2x6 STUD WALL
INBETWEEN
WOOD TRUSSES3'-10 7/8"EXTEND TRUSS
TOP CHORD
2x CONTINUOUS
WD. PLATES AS REQID.
60 MIL E.P.D.M ROOFING W/
PREFINISHED METAL EDGE FLASHING W/
DRIP EDGE (SEE ROOF PLAN, SHEET A.104) ON
3/4" ISO 3 RIGID ROOF INSULATION
(INSTALLED PER MANUF. INSTALLATION & DETAILS) ON
3/4" APA RATED EXTERIOR PLYWOOD SHEATHING ON
2x6 @ 16" O.C. FRAMING.
2x12 CONTINUOUS
PLATE NAILED TO
TRUSSES
FLASHING ON
ALL SIDES OF SADDLE
PER ROOF'G MANUF.
DETAILS & SPEC.
CONC. FOUNDATION
(SEE STRUCT.)
CONC. FOUND.
(SEE STRUCT.)
'GRACE' PERMA-BARRIER
THRU-WALL FLASHING W/
WEEP HOLES @ 32" O.C.
& MIN. 3" LAYER PEA GRAVEL ON
TOP OF FLASH'G. GROUT AIR SPACE
SOLID BELOW FLASH'G
VARIES(R-38) BLOWN-IN
INSULATION
12
5
ASPHALT ROOF SHINGLES ON
MIN. 30 # FELT PAPER ON
1/2 APA RATED EXT. PLYWOOD SHEATHING ON
PRE-ENGINEERED ROOF TRUSSES
4'-0"
INSULATION BAFFLE
(2" MIN.)
VENEER STONE ON
1" AIRSPACE ON
1/2" PLYWOOD ON
2X6 STUD ON
STEEL COLUMN
(SEE STRUCTURAL DWGS)
ADD BLOCKING AS REQUIRED
TO PACK OUT TO SPEC'D DIM.2'-8"9'-0 3/4" ± V.I.F.1'-8"2" LIMESTONE CAP
SLOPE FOR WATER
RUN OFF
3/4" CEDAR TRIM ON
WOOD BLOCKING
ON STEEL COLUMN
1'-6"
SEE STRUCTURAL
DETAIL.
FULLY VENTED ALUM.
SOFFIT ON BOTTOM
CHORD OF TRUSSES
Building Section
Scale: 1/4" = 1'-0"
H
Building Section
Scale: 1/4" = 1'-0"
G
A.302
A.302
CHECKED:
PROJECT NO:
DATE:
REVISIONS
NO DATE REMARKS
CORPORATE SEAL:
DRAWN:
SEAL:
THIS DOCUMENT IS "NOT FOR CONSTRUCTION"
UNLESS THE ARCHITECT OR ENGINEER'S
SIGNATURE AND SEAL APPEAR BELOW.
RAINBOW CHILD
CARE CENTER
C-PROTOTYPE
95 CENTENNIAL PARKWAY
SPOUT SPRINGS, NC 28326
2017.0643
COPYRIGHT cP-0215
2018 INTERPLAN PLLC RESERVES COPYRIGHT & OTHER RIGHTS RESTRICTING THESE DOCUMENTS TO THE ORIGINAL SITE OR PURPOSE FOR WHICH THEY WERE PREPARED. REPRODUCTIONS, CHANGES OR ASSIGNMENTS ARE PROHIBITED.604 COURTLAND STREET
SUITE 100
ORLANDO, FLORIDA 32804
PH 407.645.5008
FX 407.629.9124
ARCHITECTURE
ENGINEERING
INTERIOR DESIGN
PROJECT MANAGEMENT
04/20/18
A.302
BUILDING SECTIONS
JCRC
NOTE:
1. PROVIDE DRAFTSTOPPING AS REQUIRED BY CODE
IN ATTIC SPACE
(SEE ROOF PLAN SHEET A-104 & DETAIL SHEET A-305).
2. FIRESTOPPING SHALL BE INSTALLED PER CODE
3. THE INTEGRITY OF ALL FIRESTOPPING AND
DRAFTSTOPPING SHALL BE CONTINUOUSLY
MAINTAINED.
4. FIRESTOPPING SHALL OCCUR AT ALL
INTERSECTIONS BETWEEN VERTICAL AND HORIZONTAL
SPACES PER CODE
8'-1 1/8"ASPHALT ROOF SHINGLES ON MIN. 30 # FELT
PAPER ON 1/2 APA RATED EXT. PLYWOOD
SHEATHING ON PRE-ENGINEERED ROOF
TRUSSES
CONCRETE SLAB
(SEE STRUCT.)
CONC. FOUND.
(SEE STRUCT.)
Pre - K1
Attic
12
5
12
5
(1) LAYER 5/8" TYPE - X GYPSUM BD
Pre-School 1
58'-1" (OUTSIDE TO OUTSIDE OF 2X6 WOOD STUD WALLS)
Corridor 1INTERIOR WALL: 5/8" TYPE X
GYPSUM BD. (EACH SIDE) ON 2X4
WOOD STUD FRAMING @ 16" O.C.
UNLESS NOTED OTHERWISEPLATE HGT. (TYPICAL)PRE-ENG ROOF
TRUSSES (SEE STRUCT.)
PRE-ENG ROOF
TRUSSES (SEE STRUCT.)
THICKENED SLAB
(SEE STRUCT.)12'-0"9'-0"Lobby
CONC.FOUND.
(SEE STRUCT.)
Vestibule
Central Corridor
12'-0"8'-0"132 101111
133
12
5
12
5
12
5
11'-5"ASPHALT ROOF SHINGLES
SPRING POINT FOR CATHEDRAL
CEILING - REFER TO SECTION 3
7'-2"4068 OPENING
(R-38) BLOWN-IN
INSULATIONPRE-ENG ROOF
TRUSSES (SEE STRUCT.)
PRE-ENG ROOF
TRUSSES (SEE STRUCT.)
(R-38) BLOWN-IN
INSULATION
Corridor
EXTERIOR
GRADE
12
5
ASPHALT ROOF SHINGLES ON MIN. 30 # FELT
PAPER ON 5/8" APA RATED EXT. PLYWOOD
SHEATHING ON PRE-ENGINEERED ROOF TRUSSES
3'-0"
(R-38) BLOWN-IN
INSULATION
CHECKED:
PROJECT NO:
DATE:
REVISIONS
NO DATE REMARKS
CORPORATE SEAL:
DRAWN:
SEAL:
THIS DOCUMENT IS "NOT FOR CONSTRUCTION"
UNLESS THE ARCHITECT OR ENGINEER'S
SIGNATURE AND SEAL APPEAR BELOW.
RAINBOW CHILD
CARE CENTER
C-PROTOTYPE
95 CENTENNIAL PARKWAY
SPOUT SPRINGS, NC 28326
2017.0643
COPYRIGHT cP-0215
2018 INTERPLAN PLLC RESERVES COPYRIGHT & OTHER RIGHTS RESTRICTING THESE DOCUMENTS TO THE ORIGINAL SITE OR PURPOSE FOR WHICH THEY WERE PREPARED. REPRODUCTIONS, CHANGES OR ASSIGNMENTS ARE PROHIBITED.604 COURTLAND STREET
SUITE 100
ORLANDO, FLORIDA 32804
PH 407.645.5008
FX 407.629.9124
ARCHITECTURE
ENGINEERING
INTERIOR DESIGN
PROJECT MANAGEMENT
04/20/18
A.302.1
BUILDING SECTIONS
JCRC
Wall Mat Detail at Gym
Scale: 1 1/2" = 1'-0"
Typ. Single-hung Window Head2
A.302.1
Typ. Single-hung Window Jamb
Scale: 3" = 1'-0"
Typ. Single-hung Window Sill
Scale: 3" = 1'-0"
4
A.302.1
1
A.302.1
3
A.302.1
2 X 10 SOLID BLOCKING
BETWEEN STUDS
F/A PULL BOXES SWITCHES,
OUTLETS BOT @ 46" A.F.F.
(NOTCH BLOCKING AS REQUIRED)
NOTE:
POTENTIAL CONFLICT WITH
SWITCHES OUTLETS AND
PULL STATIONS AND ADA HT.
42" or 46" WALL MATS
BY OWNER
BRICK ROWLOCK COURSE BEYOND
SINGLE HUNG VINYL WINDOW WITH 1"
INSULATING GLASING AND NAILING FIN.
BRICK STACK BOND BEYOND
PRE-FINISHED BRAKE METAL FLASHING
UP AND IN FRONT OF NAILING FIN
PRE-FINISHED BRAKE METAL TRIM
PRE-FINISHED BRAKE METAL TRIM
2X SOFFIT FRAMING
1X4 TRIM BOARD
1X10 FRIEZE BOARD
2X FRAMING RIPPED FROM 2X6 TO
FLUSH-OUT WITH FACE OF BRICK.
TRUSS ANCHOR SEE STRUCTURAL
1/2" EXTERIOR SHEATHING - EXTEND TO
U/S OF TRUSS TOP CHORD.
2X HEADER SEE STRUCTURAL
2X6 WALL FRAMING WITH DBL. TOP
PLATE.
5/8" GYP. BOARD
BACKER ROD AND SEALANT FULL-ROUND
2X6 WALL FRAMING WITH DBL. TOP
PLATE. REFER TO STRUCTURAL FOR
MULTIPLE STUD PACK LOCATIONS
5/8" GYP. BOARD
BRICK STACK BOND RETURNS AT
WINDOWS
BRICK VENEER - RUNNING BOND IN
FIELD.
BACKER ROD AND SEALANT FULL ROUND
SINGLE HUNG VINYL WINDOW W/
1"INSULATING GLASS
CAST STONE SILL/WATERTABLE BELOW
SEALANT FULL ROUND
CORIAN WINDOW SILL WITH RADIUSED
NOSE AND CORNERS - CONFIRM WITH
OWNER
BATT INSULATION REFER TO WALL TYPE
SINGLE HUNG VINYL WINDOW W/
1"INSULATING GLASS
CORIAN WINDOW SILL WITH RADIUSED
NOSE AND CORNERS - CONFIRM WITH
OWNER
SEALANT FULL ROUND
BRICK STACK BOND RETURNS AT
WINDOWS
PRE-FINISHED BREAK METAL FLASHING
SET IN FULL BED OF SEALANT ON PT
WOOD CANT SHIM, HEM FLASHING END
BACKER ROD AND SEALANT
THRU WALL METAL FLASHING UP AND IN
FRONT OF FIN. HEM FLASHING END
MORTAR NET
WEEPS AT 16" O.C.
FLEXIBLE THRU WALL FLASHING
SPLIT-FACE CMU REFER TO ELEVATIONS
FOR MATERIAL AND COLOR DESCRIPTION.
SEE WALL TYPES FOR TYPICAL MATERIALS.
NOMINAL 4" CAST STONE SILL/WATERTABLE
WITH MFR'S RECOMMENDED ANCHORS
INSTALL PER MFR'S INSTRUCTIONS
BACKER ROD AND SEALANT FULL ROUND
Section Thru H.M. Door Jamb
Scale: 1-1/2" = 1'-0"
Typical Wall Section
Scale: 3/4" = 1'-0"
Typical Wall Section Thru Window
Scale: 3/4" = 1'-0"
Typical Wall Section Thru Exterior Door
Scale: 3/4" = 1'-0"
1 2 3
A.303
4
A.303
A.303 CHECKED:
PROJECT NO:
DATE:
REVISIONS
NO DATE REMARKS
CORPORATE SEAL:
DRAWN:
SEAL:
THIS DOCUMENT IS "NOT FOR CONSTRUCTION"
UNLESS THE ARCHITECT OR ENGINEER'S
SIGNATURE AND SEAL APPEAR BELOW.
RAINBOW CHILD
CARE CENTER
C-PROTOTYPE
95 CENTENNIAL PARKWAY
SPOUT SPRINGS, NC 28326
2017.0643
COPYRIGHT cP-0215
2018 INTERPLAN PLLC RESERVES COPYRIGHT & OTHER RIGHTS RESTRICTING THESE DOCUMENTS TO THE ORIGINAL SITE OR PURPOSE FOR WHICH THEY WERE PREPARED. REPRODUCTIONS, CHANGES OR ASSIGNMENTS ARE PROHIBITED.604 COURTLAND STREET
SUITE 100
ORLANDO, FLORIDA 32804
PH 407.645.5008
FX 407.629.9124
ARCHITECTURE
ENGINEERING
INTERIOR DESIGN
PROJECT MANAGEMENT
04/20/18
A.303
WALL SECTIONS
JCRC
Typical Equipment Platform Wall Section
Scale: 3/4" = 1'-0"
5
A.303
A.303
Typical Equipment Platform Wall Plan
Scale: 1 1/2" = 1'-0"
6
A.303
1/2" EXPANSION JOINT
MATERIAL
(2) 2X HEADER.
SEE STRUCT.
H.M. JAMB (BEYOND-PAINT)
ALUMINUM THRESHOLD
H.M. DOOR (PAINT)
H.M. JAMB (BEYOND-PAINT)
BACKER ROD / CAULK
LINE OF BRICK (BEYOND)6'-10" R.O.1/4 : 12
PITCH
3'-0"8'-1 1/4"CONC. SLAB
RIGID INSUL.
(SEE STRUCT.)
(R-38) BLOWN-IN
INSULATION4
A.303
FULLY VENTED ALUMINUM
SOFFIT ON 2x4 FRAMING
@ 24" O.C.
(3) #5 CONT. (BOTTOM)
6"
3"3"CARDBOARD INSULATION BAFFLE
BEYOND @ 48" O.C. TURN OUT FLANGES
AND NAIL TO U/S OF TOP CHORD AND
HORIZONTAL 2X6 BLOCKING NOTE:
MINIMUM FREE AIR AREA - 3 12" X 2 2 12" @
48" O.C.
2'-9"
12
5
SHEATHING STOPS AT U/S OF TOP CHORD
BRICK VENEER W/ BRICK
TIES PER CODE ON MIN.
1" AIR SPACE
1/2" APA RATED
PLYWOOD SHEATHING
ON 2X6 WOOD STUDS
BACKER ROD/CAULK
H.M. DOOR
H.M. DOOR
JAMB-ANCHOR TO
WOOD FRAMING PER
MANUF. INSTRUCTION
5/8" GYPSUM BD.
ALUMINUM THRESHOLD
(BELOW)
4" THK. LIMESTONE SILL
W/ SLOPED TOP BELOW.
PRE-FIN. ALUM. CLAD
2x8 (CUT TOP) FASCIA
FULLY VENTED ALUMINUM
SOFFIT ON 2x4 FRAMING
@ 24" O.C.
PRE-FINISHED METAL DRIP EDGE
PRE-FIN. 1x8 ALUM. CLAD
FRIEZE BD. ON WOOD BLOCKING
VINYL COVE BASE
4" SPLIT FACE VENEER
GRADE (VARIES)
WINDOW HEADER W/
BATT INSULATION INBETWEEN
'AZEK' 5/4 WINDOW STOOL W/
BULL NOSE
4" HIGH CAST STONE SILL W/ SLOPED TOP
6'-10" R.O.1'-8"5'-2" WINDOW R. O. HEIGHTPERMA-BARRIER THRU-WALL FLASHING
(TO START @ WOOD PLATE & EXTENT
UNDERSIDE OF STONE SILL)
W/ WEEP HOLES @ 24" O.C. BELOW.( 5'-4" WINDOW BRICK OPENINGWIDTH )PRE-FIN. 1X6 (CUT) ALUM. CLAD SOFFIT
5/8" GYP. BD. (PAINTED)2'-0"12
5
1"
'GRACE' PERMA-BARRIER THRU-WALL
FLASHING W/ DRAINAGE MAT, DRAINAGE
WEEPS @ 24" O.C. & MIN. 3" LAYER PEA
GRAVEL ON TOP OF FLASH'G. GROUT AIR
SPACE SOLID BELOW FLASH'G
FINISH FLOOR
1 LAYER OF 5/8" GYP. BD. (PAINTED)8'-1 1/4"8"EL. = 100'-0"
CONC.FOUND.
(SEE STRUCT.)FIRST FLOOR PLATE HEIGHT(4" SPLIT FACE VENEER)PRE-FINISHED ALUM.
GUTTER ON ALUM. CLAD
2X8 FRIEZE BD. W/ CUT TOP
(R-38) BLOWN-IN
INSULATION
3'-0"
2X6 BLOCKING SEE STRUCT.
ASPHALT SHINGLES ON 30# ROOF FELT ON APA
RATED SHEATHING W/ EDGE SUPPORT (24/16
RATING) ON PRE-ENGINEERED ROOF TRUSSES
CARDBOARD INSULATION BAFFLE @ 48" O.C.
TURN OUT FLANGES AND NAIL TO U/S OF TOP
CHORD AND HORIZONTAL 2X6 BLOCKING
NOTE: MINIMUM FREE AIR AREA - 3 12" X 2 2 12"
@ 48" O.C.
2'-9"
SHEATHING STOPS AT U/S OF TOP CHORD
NOTE:
INSULATION SHALL BE FSK TYPE
BATTS (CLASS A) W/ FLAME
SPREAD OF 25 OR LESS AND
SMOKE DEVELOPMENT OF 450
OR LESS
SLAB ON GRADE -
SEE STRUCTURAL SHEETS FOR
DETAILS
PRE-FINISHED ALUM.
GUTTER ON ALUM.
CLAD 2X8 FRIEZE BD.
W/ CUT TOP
2X4 WOOD FRAMING @ 24" O.C.
FULLY VENTED ALUMINUM
SOFFIT PANELS
PRE-FIN. METAL DRIP EDGE
1X8 ALUM. CLAD FRIEZE
WOOD BLOCKING
2X6 BLOCKING SEE STRUCT.
VINYL COVE BASE
4" SPLIT FACE VENEER
GROUT VOID FULL BELOW GRADE
'GRACE'PERMA-BARRIER THRU-WALL
FLASHING W/ DRAINAGE MAT, DRAINAGE
WEEPS @ 24" O.C. & MIN. 3" LAYER PEA
GRAVEL ON TOP OF FLASH'G. GROUT AIR
SPACE SOLID BELOWFLASH'G
GRADE (VARIES)8'-1 1/8"FIRST FLOOR PLATE HEIGHT5/8" GYPSUM BD. (PAINTED).2'-0"(4" SPLIT FACE VENEER)12
5
1 LAYER OF 5/8" GYP. BD.
(PAINTED)
4" BRICK ON
1" MIN. AIR SPACE ON
TYVEK AIR/MOISTURE BARRIER (OR EQUAL)
(LAP OVER THRU-WALL FLASH'G IN SHINGLE
FASHION) ON
1/2" SHEATHING ON
2X6 STUDS AT 16" O.C. W/ 6" (R-19) FSK BATT
INSULATION.
(ONE HOUR RATED, SEE UL # U356, SHT. A16).
ASPHALT SHINGLES ON 30# ROOF FELT ON APA
RATED SHEATHING W/ EDGE SUPPORT (24/16
RATING) ON PRE-ENGINEERED ROOF TRUSSES
CONC.FOUND.
(SEE STRUCT.)
(R-38) BLOWN-IN
INSULATION
3'-1 1/2"
2X BLOCKING VERT. @ 48" O.C. SEE STRUCTURAL.
2'-9"
CARDBOARD INSULATION BAFFLE BEYOND @ 48"
O.C. TURN OUT FLANGES AND NAIL TO U/S OF
TOP CHORD AND HORIZONTAL 2X6 BLOCKING
NOTE: MINIMUM FREE AIR AREA - 3 12" X 2 2 12" @
48" O.C.
SHEATHING STOPS AT U/S OF TOP CHORD
5/8" GYPSUM BD.
(R-21) BATT INSULATION EXTENDED
INTO THE OPEN SPACE OF THE TRUSS
WEB MEMBERS
INSULATION BAFFLE(R-38) BLOWN-IN
INSULATION
VERTICAL TRUSS MEMBER
PRE-ENG. GIRDER
TRUSS. W/ HIGH
BOTTOM CHORD.
(SEE STRUCT.)
2X4 STUDS @ 24" O.C. AS REQ'D.
ALUMINUM FOIL FACE POLYISO. RIGID
INSULATION (LTTR = 5.7/ INCH) ASTM C1289
LIKE JOHNS MANVILLE CIMAX BOARD
TOTAL LTTR VALUE = 17.4 OR 3" BOARD
(R-21) BATT INSULATION EXTENDED
INTO THE OPEN SPACE OF THE TRUSS
WEB MEMBERS
2X4 STUDS @ 24" O.C. AS REQ'D.
5/8" GYPSUM BD.
PRE-ENG. GIRDER
TRUSS. W/ HIGH
BOTTOM CHORD.
(SEE STRUCT.)
ALUMINUM FOIL FACE POLYISO. RIGID
INSULATION (LTTR = 5.7/ INCH) ASTM C1289
LIKE JOHNS MANVILLE CIMAX BOARD
TOTAL LTTR VALUE = 17.4 OR 3" BOARD
Upper Window Plan Details @ Gym
Scale: 1 1/2" = 1'-0"
Typ. Outside Corner DetailInside Corner Detail
Typ. Lower Window Plan Detail @ Front
Elevation - Gym
Typ. Jamb Detail
2
A.304
3
A.304
5'-2" WINDOW R. O. (VERIFY)2'-10" WINDOWR. O. (VERIFY)A.304
2
A.3043
Wall Section @ Gym
Scale: 1 1/2" = 1'-0"
1
A.304
Column Plan Detail
Scale: 1" = 1'-0"
4
A.304Scale: 1 1/2" = 1'-0"
CHECKED:
PROJECT NO:
DATE:
REVISIONS
NO DATE REMARKS
CORPORATE SEAL:
DRAWN:
SEAL:
THIS DOCUMENT IS "NOT FOR CONSTRUCTION"
UNLESS THE ARCHITECT OR ENGINEER'S
SIGNATURE AND SEAL APPEAR BELOW.
RAINBOW CHILD
CARE CENTER
C-PROTOTYPE
95 CENTENNIAL PARKWAY
SPOUT SPRINGS, NC 28326
2017.0643
COPYRIGHT cP-0215
2018 INTERPLAN PLLC RESERVES COPYRIGHT & OTHER RIGHTS RESTRICTING THESE DOCUMENTS TO THE ORIGINAL SITE OR PURPOSE FOR WHICH THEY WERE PREPARED. REPRODUCTIONS, CHANGES OR ASSIGNMENTS ARE PROHIBITED.604 COURTLAND STREET
SUITE 100
ORLANDO, FLORIDA 32804
PH 407.645.5008
FX 407.629.9124
ARCHITECTURE
ENGINEERING
INTERIOR DESIGN
PROJECT MANAGEMENT
04/20/18
A.304
WALL SECTIONS
JCRC
(2) 2x12 CONTINUOUS BOX BEAM
W/ SPACERS. SEE STRUCTURAL
DRAW'GS
2 1/2" BATT INSULATION W/
KRAFT PAPER ON WARM SIDE
Attic
4"7 1/2"3 1/4"4 1/2"
3'-3"1 1/2"
5" OGEE ALUM. GUTTER ON
ALUM. CLAD 2x8 FASCIA
W/ CUT TOP
FULLY VENTED ALUMINUM SOFFIT ON
2x4 @ 24" O.C. FRAMING.
PRE-FINISHED METAL DRIP EDGE
1x10 (CUT) ALUM. CLAD ON 1x8
ALUM. CLAD FRIEZE ON TYVEK
COMMERCIAL WRAP ON
1/2" SHEATHING
2'-9"
CAULKING
25 1/4"2 6
6
2 6
2 6
DOUBLE 2x6 PLATE
STRAP TIE BEYOND & FOREGROUND -
BETWEEN EACH WINDOW.
(SEE STRUCTURAL)
(R-38) CLOSED CELL
BLOWN-IN INSULATION
ANCHOR STRAPS @ EACH TRUSS.
SEE STRUC.
2 6
CARDBOARD INSULATION BAFFLE BEYOND
@ 48" O.C. TURN OUT FLANGES AND NAIL
TO U/S OF TOP CHORD AND HORIZONTAL
2X6 BLOCKING NOTE: MINIMUM FREE AIR
AREA - 3 12" X 2 2 12" @ 48" O.C.
2X6 BLOCKING SEE STRUCT.
2X BLOCKING VERT. @ 48" O.C. SEE
STRUCTURAL.
STOP SHEATING AT U/S OF TOP CHORD
2 6
2 X 4 FRAMING AS REQUIRED
W/ 3 1/2" (R-11 MIN.) BATT INSULATION
W/ KRAFT PAPER ON WARM SIDE)
DOUBLE HUNG PICTURE WINDOW
W/ OBSCURE GLASS & CENTER RAIL TO
SIMULATE DOUBLE HUNG APPEARANCE.
SEE WINDOW SCHEDULE.7 3/4"8"
10 1/2"
WOOD COLUMN.
(SEE STRUCTURAL). PROVIDE
1/4" PLYWD. SPACERS.
CONTINUOUS 2 X 6 COLUMN
TO UNDERSIDE OF BOXED BM. ABOVE.
TYP EA. SIDE OF WINDOW
(SEE STRUCT.)
1/4" APA RATED PLYWD.
PAINTED ON BOTH SIDES.
(LIGHT GRAY COLOR ON WINDOW SIDE).
ALUM. CLAD 1x8 (CUT)
CORNER BD'S
ALUM. CLAD 1x6 (CUT) TRIM ON
TYVEK COMMERCIAL WRAP ON
1/2" SHEATHING ON CONTINUOUS
VERTICAL (2) 2 X 6 STUDS W/
1/2" PLYWD. SPACER (SEE STRUCT.)
ALUM. CLAD
1x10 (CUT) TRIM
PICTURE WINDOW.
(SEE WINDOW SCHEDULE)
CAULKING TYP.
2 X 6 STUDS W/ 12 PLYWOOD
SPACER TO UNDERSIDE OF BOXED
BM. ABOVE
2'-6" R. O.4"4"2'-6" R.O.10 1/2"7 1/2"
6 3/4"6 3/4"3 3/4"3 3/4"7 3/4"SEE STRUCTURAL FOR
COLUMN
PROVIDE 1/4 PLYWD.
SPACERS
7 3/4"STRAP TIE @ EACH (2) 1 3/4 X 5 1/2 LVL
(SEE STRUCT)
1
2" AZEK PANEL
℄ GIRDER TRUSS ABOVE.
SEE STRUCTURAL 9 3/4"2 3/4"
4" VERIFY CLEARANCE
WINDOW MANUF.
4 3/8"
GALV. LINTEL (REFER TO STRUCTURAL)
8" BRICK SOLDIER COURSE
GRACE PERMA-BARRIER THROUGH WALL
FLASHING W/ WEEP HOLES @ 24" O.C ON
1/2" SHEATHING ON HEADER W/ HANGERS W/
2 1/2" BATT INSUL. W/ KRAFT PAPER
ON WARM SIDE.
BREAK METAL SILL W/
DRIP EDGE ON P.T. 2x6 (CUT)
BLOCKING W/ SLOPED TOP.12'-0" PLATE HGT.CAULKING
1/4" APA RATED PLYWD. PAINTED ON
BOTH SIDES. (LIGHT GRAY COLOR ON
WINDOW SIDE).
3/4" PLYWOOD ON
2 X 8'S @ 16"OC FOR
PLATFORM IN GYM.
EQUIP. RM
THRU-WALL FLASHIN W/ DRAINAGE MAT
DRAINAGE WEEPS @ 24" O.C.
BLOCKING AS
REQ'D.10'-6"1'-8"GRADE (VARIES)
4" SPLIT FACE VENEER
1" AIR SPACE ON TYVEK AIR/MOISTURE
BARRIER (OR EQUAL) ON 1/2" SHEATHING
ON 2X6 WD. STUDS AT 16" O.C. W/
MIN. R-21 FSK BATT INSULATION
2 3/8" HIGH x 5" DP. SLOPED
LIMESTONE SILL W/ DRIP ON
PERMA-BARRIER THRU-WALL FLASHING
(TO START @ WOOD PLATE & EXTEND
UNDERSIDE OF STONE SILL)
W/ WEEP HOLES @ 24" O.C. BELOW.
DOUBLE HUNG PICTURE WINDOW
W/ OBSCURE GLASS. SEE WINDOW
SCHEDULE
DAMPPROOFING. LAP OVER
FOUNDATION MIN. 6"
VINYL
COVE
BASE
5 1/2"GROUT SOLID BELOW FLASHING 8"CONT. P.T. SILL PLATE
THRU-WALL FLASHIN W/ DRAINAGE MAT
DRAINAGE WEEPS @ 24" O.C.
ANCHOR BOLTS. REFER TO STRUC. FOR
SPACING & SIZE
CONCRETE FOUNDATIONS &
SLABS OVER COMPACTED,
TERMITE TREATED FILL
10 MIL VAPOR BARRIER
2'-1 1/2"2'-1 1/2"PRE-MANUFACTURED
STONE VENEER OVER
CORROSION
RESISTANT WIRE LATH
OVER 3/4" P.T.
PLYWOOD OVER STUD
FRAMING
POST (SEE STRUCT.)
2 X 6 STUDS
@ 16" OC
ALL DIMENSIONS ON FRAMING PLANS
ARE TAKEN FROM STUD TO STUD AND
DO NOT INCORPORATE THE DRYWALL.
Stair SectionJ
A.305 Scale: 1/2" = 1'-0"
Typ. Draft Stop Sec. Detail
Scale: 1-1/2" = 1'-0"
Typ. Draft. Stop Access Plan Detail
Scale: 1-1/2" = 1'-0"
CHECKED:
PROJECT NO:
DATE:
REVISIONS
NO DATE REMARKS
CORPORATE SEAL:
DRAWN:
SEAL:
THIS DOCUMENT IS "NOT FOR CONSTRUCTION"
UNLESS THE ARCHITECT OR ENGINEER'S
SIGNATURE AND SEAL APPEAR BELOW.
RAINBOW CHILD
CARE CENTER
C-PROTOTYPE
95 CENTENNIAL PARKWAY
SPOUT SPRINGS, NC 28326
2017.0643
COPYRIGHT cP-0215
2018 INTERPLAN PLLC RESERVES COPYRIGHT & OTHER RIGHTS RESTRICTING THESE DOCUMENTS TO THE ORIGINAL SITE OR PURPOSE FOR WHICH THEY WERE PREPARED. REPRODUCTIONS, CHANGES OR ASSIGNMENTS ARE PROHIBITED.604 COURTLAND STREET
SUITE 100
ORLANDO, FLORIDA 32804
PH 407.645.5008
FX 407.629.9124
ARCHITECTURE
ENGINEERING
INTERIOR DESIGN
PROJECT MANAGEMENT
04/20/18
A.305
SECTION DETAILS
JCRC
Typ. Fence Detail
Scale: 3/4" = 1'-0"
Typ. Fence Post Detail
Scale: 1" = 1'-0"
1
A.305
2
A.305
3
A.305
4
A.305
Typ. Sidewalk @ Ext. Door5
A.305 Scale: 1/2" = 1'-0"
11"9'-1 1/8"6 7/8"2'-10"16 RISERS AT 6-13/16" EACH1 X _RISER
2X12 TREAD STOCK
2X12 STAIR STRINGER
3/4" F.R.T. PLYWOOD FLR
SHEATHING ON 2X12 JOISTS
@ 16" O.C.
1-1/2" WOOD
HANDRAIL
PER CODE
1'-0"
1'-0"
FIRST FLOOR
3'-4 7/8"1" NOSING
5'-4 5/8"13'-10 3/4"3 1/2"5 1/2"
15 T. @ 11" EACH = 13'-9"
1 3/4"
PRE-ENG. WOOD
TRUSSES @ 24" O.C.
2x6 @ 24"O.C. BRIDGING
W/ HANGERS AS REQ'D.8'-0"8'-0"DROPPED 2X
CEILING FRAMING
OVER STAIR WELL
GYP. WALLS
& CEILING IN
STAIRWELL
ASPHALT SHINGLES ON ROOF FELT
ON 1/2" ROOF SHEATHING
DESIGN TRUSSES FOR
DRAFT STOP LOAD
2-LAYERS OF TYPE "X"
GYP. BRD. (CEILING)
3/8" PLYWOOD
NOTE:
OPENINGS IN PARTITIONS SHALL BE PROTECTED BY SELF-CLOSING DOORS WITH
AUTOMATIC LATCHES CONSTRUCTED AS REQUIRED FOR THE PARTITIONS
PNEUMATIC HEAVY-DUTY DOOR
CLOSER - OR APPROVED EQUAL
(3) HEAVY-DUTY
DOOR HINGE
2X4 DOOR FRAME
1X3 DOOR FRAME
OVERLAP DOOR W/ WALL
TO PROVIDE CONTINUOUS
DRAFT STOPPING
1/2" PLYWOOD ONE SIDE
44"44"MINIMUM36"
MINIMUM3'-4"
MASONRY OPENING
36"
MINIMUM
28"6'-0"CONC.
SIDEWALK
REFER TO CIVIL
DWGS.
ADA DOOR
APPROACH
Scale: 1/2" = 1'-0"
Gym Wall Elev.
Rm. 116
Cubby Section
Rm. 102
Car Seat Cubby Elev.
Rm. 102
Stair Wall Elev.
Rm. 112
5
A.400
2
A.400
3
A.400
4
A.400
Recep. Desk Elev.
Rm. 102
11
A.400
Corridor Window Elev.
Rm. 132
9
A.400
Recep. Desk Elev.
Rm. 102
13
A.400
Recep. Desk Elev.
Rm. 102
10
A.400
Scale: 1/2" = 1'-0"Scale: 1/2" = 1'-0"Scale: 1/2" = 1'-0"
Scale: 1/2" = 1'-0"Scale: 1/2" = 1'-0"Scale: 1/2" = 1'-0"Scale: 1/2" = 1'-0"
CHECKED:
PROJECT NO:
DATE:
REVISIONS
NO DATE REMARKS
CORPORATE SEAL:
DRAWN:
SEAL:
THIS DOCUMENT IS "NOT FOR CONSTRUCTION"
UNLESS THE ARCHITECT OR ENGINEER'S
SIGNATURE AND SEAL APPEAR BELOW.
RAINBOW CHILD
CARE CENTER
C-PROTOTYPE
95 CENTENNIAL PARKWAY
SPOUT SPRINGS, NC 28326
2017.0643
COPYRIGHT cP-0215
2018 INTERPLAN PLLC RESERVES COPYRIGHT & OTHER RIGHTS RESTRICTING THESE DOCUMENTS TO THE ORIGINAL SITE OR PURPOSE FOR WHICH THEY WERE PREPARED. REPRODUCTIONS, CHANGES OR ASSIGNMENTS ARE PROHIBITED.604 COURTLAND STREET
SUITE 100
ORLANDO, FLORIDA 32804
PH 407.645.5008
FX 407.629.9124
ARCHITECTURE
ENGINEERING
INTERIOR DESIGN
PROJECT MANAGEMENT
04/20/18
A.400
INTERIOR ELEVATIONS
JCRC
Crib Cubby Elev.7
A.400
Recep. Desk Elev.
Rm. 102
12
A.400
Recep. Desk Elev.
Rm. 102
14
A.400
Lobby Door Elev.
Rm. 111
15
A.400Scale: 1/2" = 1'-0"Scale: 1/2" = 1'-0"Scale: 1/2" = 1'-0"Scale: 1/2" = 1'-0"
Fire Extinguisher Detail1
A.400 Scale: 1/2" = 1'-0"
PROVIDE CLEAR AREA
FOR OWNER PROVIDED
ART SEE BRANDING
BOOK PROVIDED BY
OWNER FOR EXACT
SIZING & PLACEMENT
MOUNT FIRE ALARM
HORN/STROBE/EMER.
LIGHT PER ELEC. PLANS 1'-0"PROVIDE CONDUIT
THROUGH WALL FOR
OUTLET & CABLE IN
CLOSET 130
2'-4"2"2"2"3'-0"2"2"2'-4"2"2'-4"2"2'-4"2"3'-0"3'-10"2'-10 1/2"6'-10"CHAIR RAIL
WHITE
GYP. BD.
(PAINT)
4" VINYL
BASE
2" H.M. FRAME
(PAINT- WHITE IN
HALLWAY -RED IN ROOM)TEMPERED
GLASS
P.LAM.
ADJUSTABLE
SHELVES
1/2" P. LAM
BACK
PANEL
2'-6"
2'-4 3/4"
P.LAM.
ADJUSTABLE
SHELVES
3
A.400
8'-0"2'-4 1/4"2'-4 1/2"2'-5 1/4"EQ.EQ.EQ.EQ.EQ.
DOOR
SLAB
LINE OF STAIRS
BEYOND
COT AREA -
FULL HEIGHT FRP
FULL HEIGHT
DIVIDING WALL
P. LAM COUNTER
SOLID SURFACE
COUNTER
SUPPORT
BRACKET
(2) 24" FILE CAB.
ALL CABINETS TO
MATCH - MAPLE
OPEN KNEE SPACE BELOW
P.LAM C.TOP
4" VINYL BASE2'-6"3'-0"3'-0"3'-8"6'-8"GYP. BD.
(PAINT)
4" VINYL
COVERBASE
2" H.M.
FRAME
(PAINT)
FIXED SAFETY GLASS
PENCIL DRAWER
P. LAM COUNTER
SOLID SURFACE
COUNTER
SUPPORT BRACKET
OPEN KNEE SPACE
BELOW
P.LAM C.TOP
NOTE: ALL OF RECEPTION
COUNTER SHALL BE
STANDARD P. LAM TOPS
WALL AT INFANT
CRIB CUBBY
CHAIR RAIL RETURN
BOTH SIDES ON
BACKER BOARD
BACKER BOARD
ONLY
GYP. BRD. (PAINT)
4" VINYL
COVERBASE
45" MIN. CLEARANCE FOR CRIB
9" WALL-PAPER
BORDERR. 1'-5 1/4"4" CROWN MLDG.
MAPLE WOOD
VENEER W/ NATURAL
FINISH-COORD. W/
OWNER
WOOD VENEER
COLUMN W/ FLUTE
4" TOE KICK
ARCH TOP
2" MLDG.
3/4" ADJ. SHELVES
1 1/2" P. LAM
COUNTER
2'-11 1/4"
3 3/4"
2'-11 1/4"2'-11 1/4"6"3'-0"1'-0"2'-2"4"4 1/2"1'-6"1'-6"3"1'-6"1'-6"3"2'-6"14
A.400
3 3/4"3 3/4"3 3/4"5 1/4"DECORATIVE
WOOD PILASTER
6" WOOD BASE6"3"3/8"3/8"3 3/4"ALL CAB'T AS
SPEC'D BY OWNER
MAPLE WD. VENEER W/
NATURAL STAIN FINISH -
COORD. W/ OWNER
4" CROWN MLDG.
4" TOE KICK
1-1/2" P.LAM C. TOP
3/4" ADJ. SHELVES
1'-6"1"
SCHED. PARTITION
EXIT
9'-0"ACCENT DOOR
CHAIR RAIL
(SEE SHEET
A.500 & A.501
KEEP AREA
CLEAR OF
DEVICES
EXIT/EMER.
LIGHT (VERIFY
W/ MECH.
DOCS.
WALL MOUNTED 10LB TYPE
ABC FIRE EXTINGUISHER AT
MECH. EQUIP. PLATFORM OR
10LB TYPE K FIRE EXTINGUISHER
AT KITCHEN, SUPPLIED &
INSTALLED BY G.C.48" MAX TO EXTINGUISHERHANDLE (MAX.)F.F.27" MAX.48" TO HIGHEST DEMOUNTING POINTG.C. SHALL PROVIDE AND INSTALL FIRE EXTINGUISHER
CABINET, (1)10LB ABC FIRE EXTINGUISHER, AND ALL
REQUIRED MOUNTING HANGER EQUIPMENT. CABINET
SHALL BE ELITE SERIES SEMI-RECESSED VERTICAL DUO
FIRE EXTINGUISHER CABINET, OR APPROVED EQUAL.
Kitchen Elev
Rm. 126
20
A.401
21
A.401
22
A.401
Infant Changing Station Elev23
A.401
Sink Base Elev24
A.401Rms. 104, 124 & 125
Built-in Elev.25
A.401 Rm. 109
Built-in Elev.26
A.401 Rms. 137 & 112
Scale: 1/2" = 1'-0"
Built-in Elev.27
A.401 Rm. 106
Built-in Elev.28
A.401 Rm. 109 & 134
Built-in Elev.29
A.401 Rm.134
Infant Changing Station Elev30
A.401 Rms. 119 & 121Scale: 1/2" = 1'-0"Scale: 1/2" = 1'-0"Scale: 1/2" = 1'-0"
Scale: 1/2" = 1'-0"Scale: 1/2" = 1'-0"Scale: 1/2" = 1'-0"Scale: 1/2" = 1'-0"
Scale: 1/2" = 1'-0"
CHECKED:
PROJECT NO:
DATE:
REVISIONS
NO DATE REMARKS
CORPORATE SEAL:
DRAWN:
SEAL:
THIS DOCUMENT IS "NOT FOR CONSTRUCTION"
UNLESS THE ARCHITECT OR ENGINEER'S
SIGNATURE AND SEAL APPEAR BELOW.
RAINBOW CHILD
CARE CENTER
C-PROTOTYPE
95 CENTENNIAL PARKWAY
SPOUT SPRINGS, NC 28326
2017.0643
COPYRIGHT cP-0215
2018 INTERPLAN PLLC RESERVES COPYRIGHT & OTHER RIGHTS RESTRICTING THESE DOCUMENTS TO THE ORIGINAL SITE OR PURPOSE FOR WHICH THEY WERE PREPARED. REPRODUCTIONS, CHANGES OR ASSIGNMENTS ARE PROHIBITED.604 COURTLAND STREET
SUITE 100
ORLANDO, FLORIDA 32804
PH 407.645.5008
FX 407.629.9124
ARCHITECTURE
ENGINEERING
INTERIOR DESIGN
PROJECT MANAGEMENT
04/20/18
A.401
INTERIOR ELEVATIONS
JCRC
PAPER TOWEL DISPENSER
PROVIDED BY OWNER
INSTALLED BY G.C.S.S. WIRE SHELVING
PROVIDED & INSTALLED
BY G.C.
SOAP DISPENSER
PROVIDED BY OWNER
INSTALLED BY G.C.WALL MTD. BARRIER TO
PROTECT HAND SIND FROM
3 COMP. SINK TO COMPLY
W/ HEALTH DEPT. STDS.
(INSTALLED BY G.C.)
F.R.P. FULL HEIGHT
PROVIDE CODE APPROVED THERMOMETER
IN EACH COMPARTMENT OF EACH REFR.
AND FREEQER WHERE FOOR IS STORED
NOTE:
PROVIDE WALL MTD. PAPER
TOWER DISPENSER & WASTE
RECEPTACLE @ HAND SINK5'-0"FREEZERREFR. FUTURE REFR.
1'-3"1'-3"
HOLD CLEAR EA. SIDE
OF CENTERLINE OF SINK34" MAX29" MIN.4'-0" MAX. REACH HT.HT AS REQUIRED TO SERVICEPAPERTOWEL DISPENSERGYP. BD. (PAINT)
(2) MICROWAVE/OVEN
COMBOS SEARS COMMERCIAL
KENMORE 49613 30" (INSTALLED
BY G.C. PER MANUF. SPECS.)
COUNTERTOP
COUNTERTOP
34" MAX4" P. LAM.
BACKSPLASH
36" MAXF.R.P. FULL HEIGHT GYP. BD. (PAINT)
1 1/2" P. LAM
COUNTER TOP
PROVIDE CODE APPROVED
THERMOMETER IN EACH
COMPARTMENT OF EACH REFR. &
FREEZER WHERE FOOD IS STORED
U.C. REFR.
4" TOE KICK
(VINYL BASE)
4" P. LAM. BACK
SPLASH
3/4" P. LAM. ADJ.
SHELF (TYP.)
TOWEL & SOAP
DISPENSER
VERIFY LOCATION
W/ OWNER
(OPEN)(OPEN)2'-8"1'-6"2'-10"AS REQUIRED TO REACH
CONTROLS 48" MAX.48" MAX. TO OPERABLEELEMENTSPAPER TOWEL DISP.
(BY OWNER)
SOAP DISPENSER
(BY OWNER)
4" BACKSPLASH
SINK (BEYOND)
FIN. FLOOR2'-6"36" MAX. TO OPERABLEDEVICESCL
3/4" P. LAM ADJ.
SHELF (TYP)
4" P. LAM.
BACKSPLASH
SINK
(BEYOND)
FIN. FLOOR4" TOE KICK 2'-0"3'-0" MAX REACH HTFOR OPERABLE PORTIONOF DISPENSERSCL
3/4" P. LAM
ADJ. SHELF (TYP)
4" P. LAM.
BACKSPLASH
SINK (BEYOND)
4" TOEKICK2'-0"2'-10"1'-8"2'-6"3/4" P. LAM
ADJ. SHELF (TYP)
5'-0"
2'-6"2'-6"
5'-0"
2'-6"2'-6"
7'-9"2'-10" MAX.3/4" P. LAM ADJ.
SHELF (TYP)
4" P. LAM.
BACKSPLASH
SINK (BEYOND)
4" TOEKICK
PROVIDE WALL
MOUNTED PAPER
TOWEL DISPENSER &
WASTE RECEPTACLE
MICROWAVE SHELF
2'-10"AS REQUIRED TO REACH
MICROWAVE CONTROLS 48" MAX.
3/4" P. LAM ADJ.
SHELF (TYP)
4" P. LAM.
BACKSPLASH
SINK (BEYOND)
FIN. FLOOR 4" TOE KICK2'-0"3'-0" MAX REACH HTFOR OPERABLE PORTIONOF DISPENSERSCL
1 1/2" P. LAM COUNTER TOP
4" TOE KICK (VINYL BASE)
4" P. LAM. BACK SPLASH
OPEN SHELF TO
MATCH CABINETS
3/4" P. LAM. ADJ.
SHELF (TYP.)
TOWEL & SOAP DISPENSER
VERIFY LOCATION W/
OWNER
(OPEN)(OPEN)2'-8"1'-6"2'-10"NOTE: ALL COUNTERTOPS IN CHILDREN'S
ROOMS, RESTROOMS, AND LOUNGE SHALL
BE POST FORMED, ROLL TOP - NO DRIP EDGES
AS REQUIRED TO REACH
CONTROLS 48" MAX.48" MAX. TO OPERABLEELEMENTSNOTE: ALL KITCHEN COUNTERS
SHALL BE STANDARD P. LAM TOPS
NOTE: ALL COUNTERTOPS IN CHILDREN'S
ROOMS, RESTROOMS, AND LOUNGE SHALL
BE POST FORMED, ROLL TOP - NO DRIP EDGES
Scale: 1/2" = 1'-0"
Typ. Adult B.F. Restroom Elevs.
31
A.402
Rm. 103
32
A.402
33
A.402
34
A.402
Typ. Child Cab. Lav. Elevs.
37
A.402
39
A.402
Scale: 1/2" = 1'-0"
Drinking Fountain Elev
Rm. 132
1
A.402
Mop Sink Elev.
Rm. 132
8
A.402 Scale: 1/2" = 1'-0"Scale: 1/2" = 1'-0"
Conference Room Elev.
Rm. 132
6
A.402
CHECKED:
PROJECT NO:
DATE:
REVISIONS
NO DATE REMARKS
CORPORATE SEAL:
DRAWN:
SEAL:
THIS DOCUMENT IS "NOT FOR CONSTRUCTION"
UNLESS THE ARCHITECT OR ENGINEER'S
SIGNATURE AND SEAL APPEAR BELOW.
RAINBOW CHILD
CARE CENTER
C-PROTOTYPE
95 CENTENNIAL PARKWAY
SPOUT SPRINGS, NC 28326
2017.0643
COPYRIGHT cP-0215
2018 INTERPLAN PLLC RESERVES COPYRIGHT & OTHER RIGHTS RESTRICTING THESE DOCUMENTS TO THE ORIGINAL SITE OR PURPOSE FOR WHICH THEY WERE PREPARED. REPRODUCTIONS, CHANGES OR ASSIGNMENTS ARE PROHIBITED.604 COURTLAND STREET
SUITE 100
ORLANDO, FLORIDA 32804
PH 407.645.5008
FX 407.629.9124
ARCHITECTURE
ENGINEERING
INTERIOR DESIGN
PROJECT MANAGEMENT
04/20/18
A.402
INTERIOR ELEVATIONS
JCRC
Scale: 1" = 1'-0"
Adult Roll-Under Sink7
A.402
9
A.402 Scale: 1" = 1'-0"
Child Roll-Under Sink
Typ. Child B.F. Wall Mount Sink
40
A.402
41
A.402
38
A.402
Typ. Child B.F. Restroom Elevs.
Rm. 103 Scale: 1/2" = 1'-0"
35
A.402
36
A.402
Scale: 1/2" = 1'-0"Scale: 1/2" = 1'-0"
Six Years & Up
33"-36"17"-19"36"
16 "-18"
12" MIN.
12"33"- 36"42"
39" - 41"39"- 41"18" MIN.(Rm. 114 ONLY)6"34" max.9" min.29" min.17" min.
3" max.48" MAX.32" MIN.40" MAX.29" MIN.34" MAX.WALL-HUNG LAVATORY
TO BE BY AMERICAN
STANDARD-LUCERNE.
LAVATORY MEETS ADA
GUIDLINES. INSTALL
WITH TOP OF FRONT RIM
AT 34" A.F.F. (PER
MANUF. SPECS.).
PROVIDE NECESSARY
BACKING AS REQ'D.24" TO 25" AT P1, 26" TO 30" AT P218" TO 20" AT P1, 20" TO 25" AT P248" (MIN.) F.R.P.14" AT P1, 14 TO 17" AT P211" TO 12" AT P1, 12" TO 15" AT P214" AT P1, 14"TO 17" AT P212"42"
TOILET PAPER
DISPENSER
7"-9"24" TO 25" AT P1,26" TO 30" AT P218"34" - 36"
24" (MIN.) F.R.P.
RUN F.R.P. WALL FINISH
MIN. 24" PAST THE EDGE
OF THE WC. (TYP.)GYP. BRD. (PAINT)
PAPER TOWEL
DISPENSER
G.F.I.C.
RECEPT.48"TO OPENINGA.5/8" HIGH BY 1/32" RAISED LETTERING (UNLESS NOTED
OTHERWISE)
B.GRADE 2 BRAILLE POSITIONED DIRECTLY BELOW TEXT
C.1/32" RAISED PICTOGRAM WITH 70% CONTRASTING BETWEEN
BACKGROUND AND TEXT. FINISH TO BE EGGSHELL.
D.COLOR TO BE BLUE BACKGROUND WITH WHITE LETTERS.
ROOM NAME2"VARIES
6" MIN.8" MIN.9"
ADA
TACTILE
SIGN
48" MIN. TO LOWEST TACTILE CHAR.60" MAX TO HIGHEST TACTILE CHAR.SIGNAGE NOTES:
PROVIDE AND INSTALL
PLUMBING INSULATION/
SHIELDS AT DRAINS
VALVES AND PIPING NO
SHARP HAZARDS ARE
ACCEPTABLE 11" TO 12" AT P1, 12" TO 15" AT P218" TO 20" AT P1, 20 TO 25 AT P2SIGNS TO BE PROVIDED
AND INSTALLED BY G.C.
OPPOSITE 4"48" (MIN.) F.R.P.4"TOILET PAPER
DISPENSER
1'-0"1 1
2"
MIN.48" (MIN.) F.R.P.1'-0"FROM TOPOF GRAB BARTO BOT. OFDISPENSER24"
12" AT P1 AND P2
24"1'-3"B.O. DISP.2'-0"
TOILET
PAPER DISP.
(SIDEVIEW)15" (MIN.)TOILET PAPER
DISPENSER
7"-9"
WIRE SHELVING
GYP. BD.
(PAINT)
16" X 20"
MIRROR
BOT AT 35"
TOWEL
DISPENSER
VERIFY
LOCATION
WITH OWNER
4" PLASTIC LAM.
BACKSPLASH
4" TOEKICK
1 1
2" COUNTER
TOP 5'-6"WIRE SHELVING
GYP. BD.
(PAINT)5'-6"16" X 20"
MIRROR
BOT AT 34"30" MAX3'-0" MAX REACH HTFOR OPERABLE PORTIONOF DISPENSERS31"MAX3'-0" MAX REACH HTFOR OPERABLE PORTIONOF DISPENSERS24"MIN.30" MIN
KNEE SPACE 30" MAX.9" MIN.24" MIN.17" MIN.
3" MAX.32" MIN.36" MAX.24" MIN.30" MAX.WALL-HUNG LAVATORY
TO BE BY AMERICAN
STANDARD-LUCERNE.
LAVATORY MEETS ADA
GUIDLINES. INSTALL WITH
TOP OF FRONT RIM AT 30"
A.F.F. FOR CHILDREN
PROVIDE NECESSARY
BACKING AS REQ'D.
PROVIDE AND INSTALL
PLUMBING INSULATION/
SHIELDS AT DRAINS
VALVES AND PIPING NO
SHARP HAZARDS ARE
ACCEPTABLE
1'-3"
MIN.
16" X 20" MIRROR
TOWEL DISPENSER
VERIFY LOCATION
WITH OWNER
4" TOEKICK
1 12" COUNTER
TOP
4" P.LAM BACK
SPLASH
SIDEWALL MNT
SOAP DISPENSER
BOT AT 27" AFF
MAX
2'-0"
GENERAL NOTES:
1. PROVIDE FILLERS AS REQ'D @
CABINET/WALL INTERSECTIONS TO ALLOW
FOR PROPER DOOR/DRAWER SWING
CLEARANCES
2. ALL PAPER TOWEL, TOILET PAPER AND
SOAP DISPENSERS ARE TO BE PROVIDED BY
OWNER AND INSTALLED BY G.C.
3. G.C. TO INSTALL ALL OWNER PROVIDED
EQUIP. PER MANUF. SPECS.
4. G.C. TO PROVIDE SHOP DRAWINGS PRIOR
TO FABRICATION FOR OWNER APPROVAL.
G.C. ALSO TO PROVIDE AND INSTALL ALL
CABINETS, COUNTERTOPS, AND HARDWARE.
5. ALL BUILT-INS TO BE COORDINATED WITH
M.E.P. TO DETERMINE EMERGENCY FIRE AND
LIGHTING REQS.
NEW ELKAY #EZSTL8 WALL MOUNT
DRINKING FOUNTAINS. DRINKING
FOUNTAINS MEET A.D.A. GUIDELINES36" MAX.27" (MIN.)8"
6 1/4"9" (MIN)15" (MIN)5" (MAX)36" MAX - WHEELCHAIR38" - 43" - STANDINGLINE OF SOFFIT
DUE TO STAIR
6'-8"LINE OF WALL
MOP SINK
WALL MOUNTED
SERVICE SINK
FAUCET-TO
SPECIFICATIONS
FRP ON WALL
2 SIDES
3'-4"4'-0"2'-1"
1'-5" MIN9" MIN3/4"2'-10"MAX.2'-3"MIN.5 1/2"1 1/2"8"
MIN.
P-LAM COVERED
POST FORMED COUNTERTOP
WITH "NO-DRIP" EDGE
SST DROP IN SINK WITH OFFSET
DRAIN FOR ADA CLEARANCE
SEE PLUMBING
ADA COMPLIANT FAUCET
FIXTURES SEE PLUMBING
30"MAX.2'-0"MIN.4 1/2"P-LAM COVERED
POST FORMED COUNTERTOP
WITH "NO-DRIP" EDGE
SST DROP IN SINK WITH OFFSET
DRAIN FOR ADA CLEARANCE
SEE PLUMBING
ADA COMPLIANT FAUCET
FIXTURES SEE PLUMBING
P-LAM COVERED
REMOVABLE PANEL
SECURED TO
CLEATSWITH ST.
STL. FINISH WASHERS
AND SCREWS.
PROVIDE ADA
CLEARANCES
DIMENSIONED.
2'-1"
1'-5" MIN
3/4"
8"
MIN.1 1/2"PLAM-1 9" MINPLAM-1
P-LAM COVERED
REMOVABLE PANEL
SECURED TO
CLEATSWITH ST.
STL. FINISH WASHERS
AND SCREWS.
PROVIDE ADA
CLEARANCES
DIMENSIONED.
CHECKED:
PROJECT NO:
DATE:
REVISIONS
NO DATE REMARKS
CORPORATE SEAL:
DRAWN:
SEAL:
THIS DOCUMENT IS "NOT FOR CONSTRUCTION"
UNLESS THE ARCHITECT OR ENGINEER'S
SIGNATURE AND SEAL APPEAR BELOW.
RAINBOW CHILD
CARE CENTER
C-PROTOTYPE
95 CENTENNIAL PARKWAY
SPOUT SPRINGS, NC 28326
2017.0643
COPYRIGHT cP-0215
2018 INTERPLAN PLLC RESERVES COPYRIGHT & OTHER RIGHTS RESTRICTING THESE DOCUMENTS TO THE ORIGINAL SITE OR PURPOSE FOR WHICH THEY WERE PREPARED. REPRODUCTIONS, CHANGES OR ASSIGNMENTS ARE PROHIBITED.604 COURTLAND STREET
SUITE 100
ORLANDO, FLORIDA 32804
PH 407.645.5008
FX 407.629.9124
ARCHITECTURE
ENGINEERING
INTERIOR DESIGN
PROJECT MANAGEMENT
04/20/18
A.500
SCHEDULES
JCRC
INSULATED
SAFETY
GLASS
PRE-FIN. ALUM.9'-4 1/4"6'-8"1'-10"FLUSH H.M. OR
WOOD SLAB
12"X12" SAFETY
GLASS WINDOW
A B C D E F G H I
OPEN
FLUSH H.M. OR
WOOD SLAB
HALF DOOR
CENTER
DOOR
HANDLE
R.O. HEIGHT =
HEIGHT = 1"
R.O. WIDTH =
WIDTH = 1"
ROUGH FRAMING DIAGRAM
INTERIOR DOORS
ROUGH FRAMING DIAGRAM
INTERIOR WINDOWS
INSULATED
SAFETY GLASS
INSULATED SAFETY
GLASS
10"INTERNAL BLINDS
10"HARDWARE SET 1
ITEM:
HINGES
LOCKSET
CLOSERS
EXIT PANIC DEVICES
- PADDLE
FLAT GOODS
MODEL NUMBER:
SPEC:
HAGER
SCHLAGE
LCN
VON DUPRIN
ROCKWOOD
STYLE/FINISH:
ACCEPTABLE SUBSTITUTE:
BOMMER, STANLEY, MCKINNEY
YALE, SARGENT
NO SUBSTITUTION
PRECISION, SARGENT
ANY BHMA MEMBER
HARDWARE SCHEDULE
HARDWARE SPECIFICATIONS:
HARDWARE SET 11
2 HINGE
1 PASSAGE SET
1 KICK PLATE
HARDWARE SET 12
3 HINGE
1 LOCKSET
1 KICK PLATE
HARDWARE SET 13
1 HINGE
2 SPRING HINGE
1 PASSAGE SET
1 O.H. HOLDER
1 WALL BUMPER
1 KICK PLATE
1 CLOSER
HARDWARE SET 14
2 HINGE
1 PASSAGE SET
1 KICK PLATE
1 FLOOR STOP
HARDWARE SET 15
3 HINGE
1 PRIVACY
1 WALL BUMPER
1 KICK PLATE
1 O.H. HOLDER
HARDWARE SET 16
1 HINGE
2 SPRING HINGE
1 LOCKSET
1 O.H. HOLDER
1 WALL BUMPER
1 KICK PLATE
HARDWARE SET 17
4 HINGE
1 PRIVACY
1 DUTCH BOLT
1 WALL BUMPER
1 KICK PLATE
1 MAG CATCH
HARDWARE SET 18
3 HINGE
1 LOCKSET
1 CLOSER
1 WALL BUMPER
1 KICKPLATE
NOTE: DOOR AND HARDWARE SHALL NOT PROJECT INTO PATH OF EGRESS
MORE THAN 7" WHEN FULLY OPEN.
HARDWARE SET 19
3 HINGE
1 LOCKSET
1 CLOSER
1 WALL BUMPER
1 KICK PLATE
1 W/S
1 THRESHOLD
1 SWEEP
HARDWARE SET 20
3 HINGE
1 EXIT PANIC DEVICE
W/ LEVER TRIM
1 CLOSER
1 W/S
1 THRESHOLD
1 SWEEP
1 DRIP CAP
1 KICK PLATE
BB1279 4-1/2"
W101S - DANE
10" X 34"
BB1279 4-1/2"
10" X 34"
BB1279 4-1/2" NRP
1250 4'1/2"
W101S - DANE
454H
409
10" X 34"
1461 (SLIM COVER)
BB1279 4-1/2"
W101S - DANE
10" X 34"
FS13 DOME STOP
BB1279 4-1/2"
W301S - DANE
409
10" X 34"
454H
BB1279 4-1/2" NRP
1250 4'1/2"
W581PD - DANE
454H
409
10" X 34"
BB1279 4-1/2"
W301S - DANE
409
10" X 34"
180 DEGREE HINGES
W581PD DANE
180 DEGREE CLOSER
409
10" X 34"
BB1279 4-1/2"
W581PD - DANE
1461 (SLIM COVER)
409
10" X 34"
160V (3070)
613 36"
102VA 36"
BB1279 4-1/2" NRP
1461 - H - CUSH (SLIM COVER)
160V (3070)
613 36"
102VA 36"
16AD 40"
10" X 34"
26D
626
32D
26D
626
32D
(CENTER)
(TOP BOTTOM)
626
32D
32D
32D
ALUM.
26D
626
32D
26D
26D
626
32D
32D
32D
(CENTER)
(TOP BOTTOM)
626
32D
32D
32D
26D
626
32D
32D
26D
626
ALUM
32D
32D
26D
626
ALUM.
32D
32D
ALUM.
ALUM.
ALUM.
26D
ALUM.
ALUM.
ALUM.
ALUM.
ALUM.
32D
HARDWARE SET 2
3 HINGE
1 LOCK
1 CLOSER
1 W/S
1 THRESHOLD
1 SWEEP
1 DRIP CAP
1 KICK PLATE
HARDWARE SET 4
2 HINGE
1 LOCKSET
1 WALL BUMPER
1 KICK PLATE
HARDWARE SET 5
1 HINGE
2 SPRING HINGE
1 PASSAGE SET
1 O.H. HOLDER
1 WALL BUMPER
1 KICK PLATE
HARDWARE SET 6
3 HINGE
1 LOCKSET
1 CLOSER
1 WALL BUMPER
1 KICK PLATE
HARDWARE SET 7
3 HINGE
1 PASSAGE
1 WALL BUMPER
1 KICK PLATE
HARDWARE SET 8
3 HINGE
1 LOCKSET
1 WALL BUMPER
1 KICK PLATE
HARDWARE SET 9
3 HINGE
1 PASSAGE
1 CLOSER
1 WALL BUMPER
1 KICK PLATE
BB1279 4-1/2" NRP
W511PD - DANE
1461- H - CUSH (SLIM COVER)
160V (3070)
613 36"
102VA 36"
16AD 40"
10" X 34"
BA1279 4-1/2"
W581PD - DANE
409
10" X 22"
BB1279 4-1/2" NRP
1250 4'1/2"
W101S - DANE
454H
409
10" X 34"
BB1279 4-1/2"
W581PD - DANE
1461 (SLIM COVER)
409
10" X 34"
BB1279 4-1/2"
W101S - DANE
409
10" X 34"
BB1279 4-1/2"
W101S - DANE
409
10" X 34"
BB1279 4-1/2"
W101S - DANE
1461 (SLIM COVER)
409
10" X 34"
26D
626D
ALUM.
ALUM.
ALUM.
ALUM.
ALUM.
32D
26D
626
32D
32D
(CENTER)
(TOP BOTTOM)
626
32D
32D
32D
26D
626
ALUM.
32D
32D
26D
626
32D
32D
26D
626
32D
32D
26D
626
ALUM.
32D
32D
3 HINGE
1 LOCK
1 CLOSER
1 W/S
1 THRESHOLD
1 SWEEP
by ALUM. DOOR SUPPLIER
W511PD - DANE
1461- H - CUSH (SLIM COVER)
160V (3070)
BRONZE
626D
ALUM.
ALUM.
ALUM.
ALUM.
MODEL NUMBER:STYLE/FINISH:
1 EXIT PANIC DEVICE V99 (or by ALUM. Door Supplier)
by ALUM. DOOR SUPPLIER
by ALUM. DOOR SUPPLIER
HARDWARE SET 3
3 HINGE
1 ALARM LOCK TRILOGY
1 ELEC. STK.
1 RECTIFIER
1 CLOSER
1 WALL BUMPER
1 KICK PLATE
BA1279 4-1/2"
VD 6111
SO-24 VAC
1461 (SLIM COVER)
409
10" X 34"
26D
26D
ALUM
ALUM
32D
32D
W/ EXIT PANIC DEVICE
ETDL27-S1G-V99
HARDWARE SET 10
3 HINGE
1 PRIVACY
1 WALL BUMPER
1 KICK PLATE
BB1279 4-1/2"
W301S - DANE
409
10" X 34"
26D
626
32D
32D
NOTE: WHEN PANIC DEVICE IS REQ'D, SEE NOTE 4.
NOTES:
1.PROVIDE HEAVY DUTY COMMERCIAL EXIT PANIC DEVICE, IN LIEU OF LOCKSET, AS
REQ'D PER STATE CODE AT DOORS 100, 100A & 132.
2.ALL INTERIOR WINDOW SILLS ARE TO BE SOLID SURFACE - SPECIFICATION BY OWNER
3.PROVIDE CLOSER AT ALL 1 HOUR RATED DOORS.
4.ALL DOORS IN THE GYM TO BE ONE PIECE WELDED HOLLOW MTL. FRAME. INSTALL
FRAME DURING ROUGH WALL FRAMING.
1 TYP. EXT. DOOR THRESHOLD 3"=1'-0"
NOTES
MAT'L
FRAME
FINISHFINISHMAT'L
DOOR
TYPE
DOOR SIZEDOOR
NO.
Door Schedule
HDWR.
SET
131 3068 E
FIRE
RATING
100 3068 B AL/INSUL BRZ AL BRZ 1 +PANIC FULL LITE
100-A
100-B
3068
2636
E
D
WD PREF PTDHM 3 +PANIC
2
HALF LITE
12 X 12 LITEWDPREFPTDHM
101 3068 E 4 HALF LITEWDPREFPTDHM
103 3068 C
105 3036 F
106 3068 E
107 3068 C
108 3068 C
109 3068 E
110 3036 F
113
109-A 3068 G
106-A 3068 G
112-A 3068 G
114 3068 C
119 3068 E
120 3036 F
123
124
125
3068
3068
3068
E
E
C
126 NOT USED
127 3068 E
128 3068 A
124-A 3068 G
125-A 3068 G
121-A 3068 G
116-A 3068 G
120-A 3036 F
130 3068 C
134-A 3068 G
135 3036
137-A 3068 G
131-A 3068 G
137
139 3068 H
104-A 3068 G
104 3068 E
115 3068 C
118 3068 E
117 3068 C
116 3068 E
112 3068 E
132 3068 G 20
134 3068 E
138
122 3068 H
136 3068 C
3068 E
3036 F
3036 F
140 3068 C
119-A 3068 G
WD PREF PTDHM
WD PREF PTDHM
WD PREF PTDHM
WD PREF PTDHM
WD PREF PTDHMWDPREFPTDHM
WD PREF PTDHM
WD PREF PTDHM
WD PREF PTDHM
WD PREF PTDHM
WD PREF PTDHM
HALF LITEWDPREFPTDHM
HALF LITEWDPREFPTDHM
HALF LITEWDPREFPTDHM
HALF LITEWDPREFPTDHM
HALF LITEWDPREFPTDHM
HALF LITEWDPREFPTDHM
HALF LITEWDPREFPTDHM
HALF LITEWDPREFPTDHM
HALF LITEWDPREFPTDHM
HALF LITEWDPREFPTDHM
HALF LITEWDPREFPTDHM
HALF LITEWDPREFPTDHM
FULL LITEHM/INSUL PTD HM PTD
FULL LITEHM/INSUL PTD HM PTD
FULL LITEHM/INSUL PTD HM PTD
FULL LITEHM/INSUL PTD HM PTD
FULL LITEHM/INSUL PTD HM PTD
FULL LITEHM/INSUL PTD HM PTD
FULL LITEHM/INSUL PTD HM PTD
FULL LITEHM/INSUL PTD HM PTD
FULL LITEHM/INSUL PTD HM PTD
FULL LITEHM/INSUL PTD HM PTD
FULL LITEHM/INSUL PTD HM PTD
7 X 22 LITEWDPREFPTDHM
7 X 22 LITEWDPREFPTDHM
7 X 22 LITEWDPREFPTDHM
WD PREF PTDHM
WD PREF PTDHM
WD PREF PTDHM
WD PREF PTDHM
WD PREF PTDHM
WD PREF PTDHM
FULL LITEHM/INSUL PTD HM PTD
FULL LITEHM/INSUL PTD HM PTD
HALF LITEWDPREFPTDHM
9
5
14
5
5
6
7
6
2
2
2
14
12
2
2
2
18
5
12
5
14
12
2
2
8
11
5
10
10
5
11
2
2
2
6
2
2
12
6
83
6
7
5
14
121 3068 E HALF LITEWDPREFPTDHM5
F WD PREF PTDHM 14
200 3068 C HM/INSUL PTD HM PTD 19
NOTE:
1.NATIONAL ACCOUNT PROVIDER: ALL HOLLOW METAL FRAMES, DOORS, WOOD DOORS, AND FINISH HARDWARE TO BE
SUPPLIED BY GIRTMAN & ASSOCIATES. CONTACT MATT RODRIGUEZ AT MRODRIGUEZ@GIRTMAN.COM FOR PRICING.
DOOR THERMAL PERFORMANCE CRITERIA
GC SHALL PROVIDE DOORS THAT MEET THE THERMAL PERFORMANCE CRITERIA
OF THE FOLLOWING DOORS:
DOOR 112A, 116A,121A, 119A,113A,137A 134A,132, 109A, 106A,104A, 125A, 126A, 131A -
U Factor : 0.65, SHGC: 0.40, PF: 0.04, VT: .80
DOOR 136 - U Factor: 0.130
DOOR 100 STORE-FRONT - U Factor : 0.65, SHGC: 0.40, PF: 0.04, VT: .80
DOOR 200 - U Factor: 0.130
WIN.
NO.
GREEN
WHITE
W2-8
HALL SIDE COLOR
Interior Window Schedule
W2-1
ROOM SIDE COLOR
WHITE
WHITE
WHITE
WHITE
W2-3
W2-6
W2-2
W2-10
W2-11
W2-4
W2-5
W2-7
W2-9
W2-13
W2-12
GREEN
RED
RED
BLUE
BLUE
YELLOW
YELLOW
WHITE
WHITE
WHITE
WHITE
WHITE
WHITE
WHITE
WHITE
WHITE
WHITE
WHITE
WHITE
GLASS
WHITE
W2-14 WHITE
W2-15 WHITE
RED
RED
MAT'L
FRAME
H.M.
MAT'L
TEMP.
Window Legend
W1
W2
SINGLE HUNG VINYL WINDOWS (2 WIDE) W/ 1"
INSULATED GLASS. UPPER OPERABLE - SASH TO
HAVE SCREEN APPROXIMATE SIZE: 5'-2" WIDE
(OVERALL) X 5'-2" HIGH - MANUFACTURER TO USE
STANDARD SIZES. VERIFY ARCHITECT OF ANY
DISCREPANCIES. TEMPERED GLAZING WHEN
WITHIN 24IN OF DOOR OR WITHIN 18IN OF THE
FLOOR.
36" x 36" SAFETY GLASS (TEMP.) LAMINATED
WINDOW IN HOLLOW METAL PAINTED FRAME.
REFER TO 9/A.400
30" X 36" VINYL WINDOW W/ 1" INSULATED CLEAR
GLASS.
32" x 36" SAFETY GLASS (TEMP.) LAMINATED
WINDOW IN HOLLOW METAL PAINTED FRAME @
GYMNASIUM. REFER TO 2/A.400
30" X 35" VINYL WINDOW W/ 1" INSULATED CLEAR
GLASS.
40" X 35" VINYL WINDOW W/ 1" INSULATED CLEAR
GLASS.
62" X 62" NON-OPERABLE PICTURE WINDOW W/
APPLIED MUNTINS.
60" X 35" VINYL WINDOW W/ 1" INSULATED CLEAR
GLASS.
27 1/2" X 35" VINYL WINDOW W/ 1" INSULATED
CLEAR GLASS.
W4
W3
W5
W6
W7
W8
NOTES:
1.EXTERIOR WINDOWS TO BE PRE-FINISHED , COLOR: DESERT SAND
2.BLACK OUT GLASS IN WINDOWS IN GYM EQUIP. #114 & #115
3.WINDOW MANUFACTURER:
ALLIANCE OR OWNER APPROVED EQUAL
W9
04/23/18
04/23/18
04/23/18
04/23/18
04/23/18
04/23/18
04/23/18
04/20/18
M.001
MECHANICAL COVER SHEET
ROHASCHECKED:
PROJECT NO:
DATE:
REVISIONS
NO DATE REMARKS
CORPORATE SEAL:
DRAWN:
SEAL:
THIS DOCUMENT IS "NOT FOR CONSTRUCTION"
UNLESS THE ARCHITECT OR ENGINEER'S
SIGNATURE AND SEAL APPEAR BELOW.
RAINBOW CHILD
CARE CENTER
C-PROTOTYPE
95 CENTENNIAL PARKWAY
SPOUT SPRINGS, NC 28326
2017.0643
COPYRIGHT cP-0215
2018 INTERPLAN PLLC RESERVES COPYRIGHT & OTHER RIGHTS RESTRICTING THESE DOCUMENTS TO THE ORIGINAL SITE OR PURPOSE FOR WHICH THEY WERE PREPARED. REPRODUCTIONS, CHANGES OR ASSIGNMENTS ARE PROHIBITED.604 COURTLAND STREET
SUITE 100
ORLANDO, FLORIDA 32804
PH 407.645.5008
FX 407.629.9124
ARCHITECTURE
ENGINEERING
INTERIOR DESIGN
PROJECT MANAGEMENT
HVAC SYMBOLS LEGENDHVAC GENERAL NOTES
FIELD VERIFY ALL CONDITIONS
HVAC ABBREVIATIONS
CHECKED:
PROJECT NO:
DATE:
REVISIONS
NO DATE REMARKS
CORPORATE SEAL:
DRAWN:
SEAL:
THIS DOCUMENT IS "NOT FOR CONSTRUCTION"
UNLESS THE ARCHITECT OR ENGINEER'S
SIGNATURE AND SEAL APPEAR BELOW.
RAINBOW CHILD
CARE CENTER
C-PROTOTYPE
95 CENTENNIAL PARKWAY
SPOUT SPRINGS, NC 28326
2017.0643
COPYRIGHT cP-0215
2018 INTERPLAN PLLC RESERVES COPYRIGHT & OTHER RIGHTS RESTRICTING THESE DOCUMENTS TO THE ORIGINAL SITE OR PURPOSE FOR WHICH THEY WERE PREPARED. REPRODUCTIONS, CHANGES OR ASSIGNMENTS ARE PROHIBITED.604 COURTLAND STREET
SUITE 100
ORLANDO, FLORIDA 32804
PH 407.645.5008
FX 407.629.9124
ARCHITECTURE
ENGINEERING
INTERIOR DESIGN
PROJECT MANAGEMENT
04/20/18
M.100
MAIN LEVEL MECHANICAL
PLAN
ROHAS
Kitchen
Pantry
129
Utility Rm
123
Kitchen
126
Closet
140
Director's
Office
101
Vestibule
100
Gym
116Toddler 1
121
Toddler 2
119
Central Corridor
133
Lobby
111
Reception
102Conf.
Room.
118
Closet
122
Infant 1
124
Infant 2
125
Adult B.F.
Toilet 1
103
Child
Toilet 2
105
Gym
Childs Toilet
117
Childs
Toilet 7
138
Pre-School 2
112
Pre-K 2
137
Outdoor Toy
Storage
136
Childs Toilet 6
135
Pre-K 1
134 Closet
139
Corridor 1
132
Pre-School 1
109
Laundry
Room
128
Childs
Toilet 5
110
Varsity
Pre-Shool
106
Childs
Toilet 4
108
Car
Seat
Sto.
I.T.
Closet
130
Childs Toilet 9
120
Childs B.F.
Toilet 8
113
Staff Lounge
127
Young
Pre-School
104
Childs
Toilet 3
107
Stairs
Gym Equip.
114
Gym Equip.
115
PLAN KEYED NOTES
MAIN LEVEL MECHANICAL PLAN 3/16" = 1'-0"
04/20/18
M.200
UPPER LEVEL MECHANICAL
PLAN
ROHASCHECKED:
PROJECT NO:
DATE:
REVISIONS
NO DATE REMARKS
CORPORATE SEAL:
DRAWN:
SEAL:
THIS DOCUMENT IS "NOT FOR CONSTRUCTION"
UNLESS THE ARCHITECT OR ENGINEER'S
SIGNATURE AND SEAL APPEAR BELOW.
RAINBOW CHILD
CARE CENTER
C-PROTOTYPE
95 CENTENNIAL PARKWAY
SPOUT SPRINGS, NC 28326
2017.0643
COPYRIGHT cP-0215
2018 INTERPLAN PLLC RESERVES COPYRIGHT & OTHER RIGHTS RESTRICTING THESE DOCUMENTS TO THE ORIGINAL SITE OR PURPOSE FOR WHICH THEY WERE PREPARED. REPRODUCTIONS, CHANGES OR ASSIGNMENTS ARE PROHIBITED.604 COURTLAND STREET
SUITE 100
ORLANDO, FLORIDA 32804
PH 407.645.5008
FX 407.629.9124
ARCHITECTURE
ENGINEERING
INTERIOR DESIGN
PROJECT MANAGEMENT
EQUIPMENT PLATFORM
Attic Space #1
Attic Space #2
Attic Space #3
Attic Space #4
Attic Space #5
PLAN KEYED NOTES
UPPER LEVEL MECHANICAL PLAN 3/16" = 1'-0"
04/20/18
M.300
MECHANICAL SCHEDULES
ROHASCHECKED:
PROJECT NO:
DATE:
REVISIONS
NO DATE REMARKS
CORPORATE SEAL:
DRAWN:
SEAL:
THIS DOCUMENT IS "NOT FOR CONSTRUCTION"
UNLESS THE ARCHITECT OR ENGINEER'S
SIGNATURE AND SEAL APPEAR BELOW.
RAINBOW CHILD
CARE CENTER
C-PROTOTYPE
95 CENTENNIAL PARKWAY
SPOUT SPRINGS, NC 28326
2017.0643
COPYRIGHT cP-0215
2018 INTERPLAN PLLC RESERVES COPYRIGHT & OTHER RIGHTS RESTRICTING THESE DOCUMENTS TO THE ORIGINAL SITE OR PURPOSE FOR WHICH THEY WERE PREPARED. REPRODUCTIONS, CHANGES OR ASSIGNMENTS ARE PROHIBITED.604 COURTLAND STREET
SUITE 100
ORLANDO, FLORIDA 32804
PH 407.645.5008
FX 407.629.9124
ARCHITECTURE
ENGINEERING
INTERIOR DESIGN
PROJECT MANAGEMENT
EXHAUST FAN SCHEDULE
DIFFUSER / REGISTER / GRILLE SCHEDULE GAS FIRED FURNACE SCHEDULE
HEAT PUMP UNIT SCHEDULE
LOUVER / INTAKE SCHEDULE
COOLING COIL SCHEDULE
FLEX DUCT SIZE
BUILDING AIR BALANCE SCHEDULE
THERMOSTAT SCHEDULE
04/20/18
M.400
MECHANICAL DETAILS
ROHASCHECKED:
PROJECT NO:
DATE:
REVISIONS
NO DATE REMARKS
CORPORATE SEAL:
DRAWN:
SEAL:
THIS DOCUMENT IS "NOT FOR CONSTRUCTION"
UNLESS THE ARCHITECT OR ENGINEER'S
SIGNATURE AND SEAL APPEAR BELOW.
RAINBOW CHILD
CARE CENTER
C-PROTOTYPE
95 CENTENNIAL PARKWAY
SPOUT SPRINGS, NC 28326
2017.0643
COPYRIGHT cP-0215
2018 INTERPLAN PLLC RESERVES COPYRIGHT & OTHER RIGHTS RESTRICTING THESE DOCUMENTS TO THE ORIGINAL SITE OR PURPOSE FOR WHICH THEY WERE PREPARED. REPRODUCTIONS, CHANGES OR ASSIGNMENTS ARE PROHIBITED.604 COURTLAND STREET
SUITE 100
ORLANDO, FLORIDA 32804
PH 407.645.5008
FX 407.629.9124
ARCHITECTURE
ENGINEERING
INTERIOR DESIGN
PROJECT MANAGEMENT
9 RECTANGULAR BRANCH CONNECT NTS 10 ROUND BRANCH CONNECTION NTS
2 LOUVER- MOUNTING DETAIL NTS
4 TYPICAL AIR HANDLING UNIT DETAIL NTS 5 CONDENSER TIE-DOWN DETAIL NTS
3 TYPICAL SQUARE VANED DUCT DETAIL NTS
6 TYPICAL DUCT TRANSITION DETAIL NTS
8 TYPICAL DUCT STRAP HANGER DETAIL NTS7TYPICAL DUCT RADIUS DETAIL NTS
1 AHU CONDENSATE DRAIN DETAIL NTS
11 ROOF CAP DETAIL NTS 12 DRYER EXHAUST VENT DETAIL NTS 13 REFRIGERANT LINES DETAIL NTS 14 CONCENTRIC VENT DETAIL NTS
04/20/18
M.500
MECHANICAL
SPECIFICATIONS
ROHASCHECKED:
PROJECT NO:
DATE:
REVISIONS
NO DATE REMARKS
CORPORATE SEAL:
DRAWN:
SEAL:
THIS DOCUMENT IS "NOT FOR CONSTRUCTION"
UNLESS THE ARCHITECT OR ENGINEER'S
SIGNATURE AND SEAL APPEAR BELOW.
RAINBOW CHILD
CARE CENTER
C-PROTOTYPE
95 CENTENNIAL PARKWAY
SPOUT SPRINGS, NC 28326
2017.0643
COPYRIGHT cP-0215
2018 INTERPLAN PLLC RESERVES COPYRIGHT & OTHER RIGHTS RESTRICTING THESE DOCUMENTS TO THE ORIGINAL SITE OR PURPOSE FOR WHICH THEY WERE PREPARED. REPRODUCTIONS, CHANGES OR ASSIGNMENTS ARE PROHIBITED.604 COURTLAND STREET
SUITE 100
ORLANDO, FLORIDA 32804
PH 407.645.5008
FX 407.629.9124
ARCHITECTURE
ENGINEERING
INTERIOR DESIGN
PROJECT MANAGEMENT
SECTION 23 0000 - HVAC
“”“”
”
CHECKED:
PROJECT NO:
DATE:
REVISIONS
NO DATE REMARKS
CORPORATE SEAL:
DRAWN:
SEAL:
THIS DOCUMENT IS "NOT FOR CONSTRUCTION"
UNLESS THE ARCHITECT OR ENGINEER'S
SIGNATURE AND SEAL APPEAR BELOW.
RAINBOW CHILD
CARE CENTER
C-PROTOTYPE
95 CENTENNIAL PARKWAY
SPOUT SPRINGS, NC 28326
2017.0643
COPYRIGHT cP-0215
2018 INTERPLAN PLLC RESERVES COPYRIGHT & OTHER RIGHTS RESTRICTING THESE DOCUMENTS TO THE ORIGINAL SITE OR PURPOSE FOR WHICH THEY WERE PREPARED. REPRODUCTIONS, CHANGES OR ASSIGNMENTS ARE PROHIBITED.604 COURTLAND STREET
SUITE 100
ORLANDO, FLORIDA 32804
PH 407.645.5008
FX 407.629.9124
ARCHITECTURE
ENGINEERING
INTERIOR DESIGN
PROJECT MANAGEMENT
04/20/18
P.001
PLUMBING COVER SHEET
PHROH
GENERAL PLUMBING NOTESPLUMBING SYMBOLSPLUMBING ABBREVIATIONS
CHECKED:
PROJECT NO:
DATE:
REVISIONS
NO DATE REMARKS
CORPORATE SEAL:
DRAWN:
SEAL:
THIS DOCUMENT IS "NOT FOR CONSTRUCTION"
UNLESS THE ARCHITECT OR ENGINEER'S
SIGNATURE AND SEAL APPEAR BELOW.
RAINBOW CHILD
CARE CENTER
C-PROTOTYPE
95 CENTENNIAL PARKWAY
SPOUT SPRINGS, NC 28326
2017.0643
COPYRIGHT cP-0215
2018 INTERPLAN PLLC RESERVES COPYRIGHT & OTHER RIGHTS RESTRICTING THESE DOCUMENTS TO THE ORIGINAL SITE OR PURPOSE FOR WHICH THEY WERE PREPARED. REPRODUCTIONS, CHANGES OR ASSIGNMENTS ARE PROHIBITED.604 COURTLAND STREET
SUITE 100
ORLANDO, FLORIDA 32804
PH 407.645.5008
FX 407.629.9124
ARCHITECTURE
ENGINEERING
INTERIOR DESIGN
PROJECT MANAGEMENT
04/20/18
P.002
SLAB DIMENSION PLAN
PHROHSLAB DIMENSION PLAN 1/8" = 1'-0"
Kitchen
Pantry
129
Utility Rm
123
Kitchen
126
Closet
140
Director's
Office
101
Vestibule
100
Gym
116
Gym Equip.
114
Toddler 1
121Toddler 2
119
Central Corridor
133
Lobby
111
Reception
102Conference Rm.
118Closet
122
Infant 1
124
Infant 2
125
Adult B.F.
Toilet 1
103
Child Toilet 2
105
Gym Childs Toilet
117
Childs
Toilet 7
138
Pre-School 2
112
Pre-K 2
137
Outdoor Toy
Storage
136
Childs
Toilet 6
135
Pre-K 1
134
Closet
139
Corridor 1
132
Pre-School 1
109
Laundry
Room
128
Childs
Toilet 5
110
Varsity
Pre-School
106
Young Pre-School
104
Childs
Toilet 4
108
Childs
Toilet 3
107
I.T.
Closet
130
Childs B.F.
Toilet 8
113
Childs Toilet 9
120
Gym Equip.
115
Car
Seat
Sto.
Staff Lounge
127
Stairs
CHECKED:
PROJECT NO:
DATE:
REVISIONS
NO DATE REMARKS
CORPORATE SEAL:
DRAWN:
SEAL:
THIS DOCUMENT IS "NOT FOR CONSTRUCTION"
UNLESS THE ARCHITECT OR ENGINEER'S
SIGNATURE AND SEAL APPEAR BELOW.
RAINBOW CHILD
CARE CENTER
C-PROTOTYPE
95 CENTENNIAL PARKWAY
SPOUT SPRINGS, NC 28326
2017.0643
COPYRIGHT cP-0215
2018 INTERPLAN PLLC RESERVES COPYRIGHT & OTHER RIGHTS RESTRICTING THESE DOCUMENTS TO THE ORIGINAL SITE OR PURPOSE FOR WHICH THEY WERE PREPARED. REPRODUCTIONS, CHANGES OR ASSIGNMENTS ARE PROHIBITED.604 COURTLAND STREET
SUITE 100
ORLANDO, FLORIDA 32804
PH 407.645.5008
FX 407.629.9124
ARCHITECTURE
ENGINEERING
INTERIOR DESIGN
PROJECT MANAGEMENT
04/20/18
P.100
UNDERGROUND PIPING
PLAN
PHROH
Kitchen
Pantry
129
Utility Rm
123
Kitchen
126
Closet
140
Director's
Office
101
Vestibule
100
Gym
116
Gym Equip.
114
Toddler 1
121Toddler 2
119
Central Corridor
133
Lobby
111
Reception
102Conference Rm.
118Closet
122
Infant 1
124
Infant 2
125
Adult B.F.
Toilet 1
103
Child Toilet 2
105
Gym Childs Toilet
117
Childs
Toilet 7
138
Pre-School 2
112
Pre-K 2
137
Outdoor Toy
Storage
136
Childs
Toilet 6
135
Pre-K 1
134
Closet
140
Corridor 1
132
Pre-School 1
109
Laundry
Room
128
Childs
Toilet 5
110
Varsity
Pre-School
106
Young Pre-School
104
Childs
Toilet 4
108
Childs
Toilet 3
107
I.T.
Closet
130
Childs B.F.
Toilet 8
113
Childs Toilet 9
120
Gym Equip.
115
Car
Seat
Sto.
Staff Lounge
127
KEY NOTES
UNDERGROUND PIPING PLAN 3/16" = 1'-0"
Stairs
139
Hall
131
CHECKED:
PROJECT NO:
DATE:
REVISIONS
NO DATE REMARKS
CORPORATE SEAL:
DRAWN:
SEAL:
THIS DOCUMENT IS "NOT FOR CONSTRUCTION"
UNLESS THE ARCHITECT OR ENGINEER'S
SIGNATURE AND SEAL APPEAR BELOW.
RAINBOW CHILD
CARE CENTER
C-PROTOTYPE
95 CENTENNIAL PARKWAY
SPOUT SPRINGS, NC 28326
2017.0643
COPYRIGHT cP-0215
2018 INTERPLAN PLLC RESERVES COPYRIGHT & OTHER RIGHTS RESTRICTING THESE DOCUMENTS TO THE ORIGINAL SITE OR PURPOSE FOR WHICH THEY WERE PREPARED. REPRODUCTIONS, CHANGES OR ASSIGNMENTS ARE PROHIBITED.604 COURTLAND STREET
SUITE 100
ORLANDO, FLORIDA 32804
PH 407.645.5008
FX 407.629.9124
ARCHITECTURE
ENGINEERING
INTERIOR DESIGN
PROJECT MANAGEMENT
04/20/18
P.101
MAIN LEVEL PIPING PLAN
PHROH
Kitchen
Pantry
129
Utility Rm
123
Kitchen
126
Closet
140
Director's
Office
101
Vestibule
100
Gym
116
Gym Equip.
114
Toddler 1
121Toddler 2
119
Staff Lounge
127
Central Corridor
133
Lobby
111
Reception
102
Conference Rm.
118Closet
122
Infant 1
124
Infant 2
125
Adult B.F.
Toilet 1
103
Child
Toilet 2
105
Gym Childs Toilet
117
Childs
Toilet 7
138
Pre-School 2
112
Pre-K 2
137
Outdoor Toy
Storage
136
Childs Toilet 6
135
Pre-K 1
134
Corridor 1
132
Pre-School 1
109
Laundry
Rm.
128
Childs Toilet 5
110
Varsity
Pre-School
106 Young
Pre-School
104
Childs
Toilet 4
108
Childs
Toilet 3
107 Car
Seat
Sto.
I.T.
Closet
130
Childs B.F.
Toilet 8
113
Childs
Toilet 9
120
Gym Equip.
115
KEY NOTES
MAIN LEVEL PIPING PLAN 3/16" = 1'-0"
Closet
140
Stairs
139
Hall
131
CHECKED:
PROJECT NO:
DATE:
REVISIONS
NO DATE REMARKS
CORPORATE SEAL:
DRAWN:
SEAL:
THIS DOCUMENT IS "NOT FOR CONSTRUCTION"
UNLESS THE ARCHITECT OR ENGINEER'S
SIGNATURE AND SEAL APPEAR BELOW.
RAINBOW CHILD
CARE CENTER
C-PROTOTYPE
95 CENTENNIAL PARKWAY
SPOUT SPRINGS, NC 28326
2017.0643
COPYRIGHT cP-0215
2018 INTERPLAN PLLC RESERVES COPYRIGHT & OTHER RIGHTS RESTRICTING THESE DOCUMENTS TO THE ORIGINAL SITE OR PURPOSE FOR WHICH THEY WERE PREPARED. REPRODUCTIONS, CHANGES OR ASSIGNMENTS ARE PROHIBITED.604 COURTLAND STREET
SUITE 100
ORLANDO, FLORIDA 32804
PH 407.645.5008
FX 407.629.9124
ARCHITECTURE
ENGINEERING
INTERIOR DESIGN
PROJECT MANAGEMENT
04/20/18
P.200
WASTE AND VENT RISER
DIAGRAM
PHROH
KEY NOTES
WASTE AND VENT RISER DIAGRAM NTSUPPER LEVEL PIPING PLAN 1/4" = 1'-0"
CHECKED:
PROJECT NO:
DATE:
REVISIONS
NO DATE REMARKS
CORPORATE SEAL:
DRAWN:
SEAL:
THIS DOCUMENT IS "NOT FOR CONSTRUCTION"
UNLESS THE ARCHITECT OR ENGINEER'S
SIGNATURE AND SEAL APPEAR BELOW.
RAINBOW CHILD
CARE CENTER
C-PROTOTYPE
95 CENTENNIAL PARKWAY
SPOUT SPRINGS, NC 28326
2017.0643
COPYRIGHT cP-0215
2018 INTERPLAN PLLC RESERVES COPYRIGHT & OTHER RIGHTS RESTRICTING THESE DOCUMENTS TO THE ORIGINAL SITE OR PURPOSE FOR WHICH THEY WERE PREPARED. REPRODUCTIONS, CHANGES OR ASSIGNMENTS ARE PROHIBITED.604 COURTLAND STREET
SUITE 100
ORLANDO, FLORIDA 32804
PH 407.645.5008
FX 407.629.9124
ARCHITECTURE
ENGINEERING
INTERIOR DESIGN
PROJECT MANAGEMENT
04/20/18
P.300
PLUMBING SCHEDULES
PHROH
PIPING TYPES:
EXPANSION TANK SCHEDULE
DOMESTIC WATER HEATER SCHEDULE
WATER HEATER SIZING CALCULATION
BACKFLOW DEVICE SCHEDULE
WATER SHOCK ARRESTOR SIZING CHART
DRAINAGE FIXTURE UNITS SCHEDULE
DOMESTIC WATER SUPPLY FIXTURE UNITS
GREASE INTERCEPTOR CALCULATIONS
GREASE INTERCEPTOR
PLUMBING FIXTURE / COMPONENT SCHEDULE
CHECKED:
PROJECT NO:
DATE:
REVISIONS
NO DATE REMARKS
CORPORATE SEAL:
DRAWN:
SEAL:
THIS DOCUMENT IS "NOT FOR CONSTRUCTION"
UNLESS THE ARCHITECT OR ENGINEER'S
SIGNATURE AND SEAL APPEAR BELOW.
RAINBOW CHILD
CARE CENTER
C-PROTOTYPE
95 CENTENNIAL PARKWAY
SPOUT SPRINGS, NC 28326
2017.0643
COPYRIGHT cP-0215
2018 INTERPLAN PLLC RESERVES COPYRIGHT & OTHER RIGHTS RESTRICTING THESE DOCUMENTS TO THE ORIGINAL SITE OR PURPOSE FOR WHICH THEY WERE PREPARED. REPRODUCTIONS, CHANGES OR ASSIGNMENTS ARE PROHIBITED.604 COURTLAND STREET
SUITE 100
ORLANDO, FLORIDA 32804
PH 407.645.5008
FX 407.629.9124
ARCHITECTURE
ENGINEERING
INTERIOR DESIGN
PROJECT MANAGEMENT
04/20/18
P.400
PLUMBING DETAILS
PHROH12WALL HYDRANT INSTALLATION DETAIL NTS
EXTERIOR CLEANOUT (COTG)INTERIOR FLOOR CLEANOUT (FCO)
7 CLEANOUT DETAILS NTS 8 FLOOR DRAIN DETAIL NTS
3 INDIRECT DRAIN DETAIL NTS2SANITARY CLEAN OUT OUTSIDE BUILDING NTS 4 WALL CLEAN OUT DETAIL NTS 5 FLOOR SINK DETAIL NTS
10 GREASE INTERCEPTOR DETAIL NTS
6 THERMAL MIXING VALVE DETAIL NTS
11 FLOOR DRAIN W/ TRAP PRIMER DETAILNTS
1 WATER HAMMER ARRESTORS DETAIL NTS
9 WATER SERVICE ENTRANCE DETAIL NTS
CHECKED:
PROJECT NO:
DATE:
REVISIONS
NO DATE REMARKS
CORPORATE SEAL:
DRAWN:
SEAL:
THIS DOCUMENT IS "NOT FOR CONSTRUCTION"
UNLESS THE ARCHITECT OR ENGINEER'S
SIGNATURE AND SEAL APPEAR BELOW.
RAINBOW CHILD
CARE CENTER
C-PROTOTYPE
95 CENTENNIAL PARKWAY
SPOUT SPRINGS, NC 28326
2017.0643
COPYRIGHT cP-0215
2018 INTERPLAN PLLC RESERVES COPYRIGHT & OTHER RIGHTS RESTRICTING THESE DOCUMENTS TO THE ORIGINAL SITE OR PURPOSE FOR WHICH THEY WERE PREPARED. REPRODUCTIONS, CHANGES OR ASSIGNMENTS ARE PROHIBITED.604 COURTLAND STREET
SUITE 100
ORLANDO, FLORIDA 32804
PH 407.645.5008
FX 407.629.9124
ARCHITECTURE
ENGINEERING
INTERIOR DESIGN
PROJECT MANAGEMENT
04/20/18
P.401
PLUMBING DETAILS
PHROH6WATER HEATER DETAIL NTS
4 WATER MANIFOLD DETAIL NTS
5 WASHING MACHINE HOOK-UP NTS
2 EXPANSION TANK DETAIL NTS1IN-LINE CIRCULATING PUMP DETAIL NTS
3 PIPE HANGER DETAIL NTS
2"CW
04/20/18
E.000
ELECTRICAL COVER SHEET
MSDMSCHECKED:
PROJECT NO:
DATE:
REVISIONS
NO DATE REMARKS
CORPORATE SEAL:
DRAWN:
SEAL:
THIS DOCUMENT IS "NOT FOR CONSTRUCTION"
UNLESS THE ARCHITECT OR ENGINEER'S
SIGNATURE AND SEAL APPEAR BELOW.
RAINBOW CHILD
CARE CENTER
C-PROTOTYPE
95 CENTENNIAL PARKWAY
SPOUT SPRINGS, NC 28326
2017.0643
COPYRIGHT cP-0215
2018 INTERPLAN PLLC RESERVES COPYRIGHT & OTHER RIGHTS RESTRICTING THESE DOCUMENTS TO THE ORIGINAL SITE OR PURPOSE FOR WHICH THEY WERE PREPARED. REPRODUCTIONS, CHANGES OR ASSIGNMENTS ARE PROHIBITED.604 COURTLAND STREET
SUITE 100
ORLANDO, FLORIDA 32804
PH 407.645.5008
FX 407.629.9124
ARCHITECTURE
ENGINEERING
INTERIOR DESIGN
PROJECT MANAGEMENT
)'0'4#.016'5
POWER AND DIAGRAMS
LIGHTING
FIRE DETECTION AND ALARM
TELECOMMUNICATION
SECURITY
ABBREVIATIONS
GENERAL NOTES
·
”
·
·
·
·
·
·
·
·
·
·
·
·
·
·””
”
·
·
·”
·
LOW VOLTAGE NOTES
LIGHTING FIXTURE SCHEDULE
04/20/18
E.010
ELECTRICAL SITE PLAN
MSDMSCHECKED:
PROJECT NO:
DATE:
REVISIONS
NO DATE REMARKS
CORPORATE SEAL:
DRAWN:
SEAL:
THIS DOCUMENT IS "NOT FOR CONSTRUCTION"
UNLESS THE ARCHITECT OR ENGINEER'S
SIGNATURE AND SEAL APPEAR BELOW.
RAINBOW CHILD
CARE CENTER
C-PROTOTYPE
95 CENTENNIAL PARKWAY
SPOUT SPRINGS, NC 28326
2017.0643
COPYRIGHT cP-0215
2018 INTERPLAN PLLC RESERVES COPYRIGHT & OTHER RIGHTS RESTRICTING THESE DOCUMENTS TO THE ORIGINAL SITE OR PURPOSE FOR WHICH THEY WERE PREPARED. REPRODUCTIONS, CHANGES OR ASSIGNMENTS ARE PROHIBITED.604 COURTLAND STREET
SUITE 100
ORLANDO, FLORIDA 32804
PH 407.645.5008
FX 407.629.9124
ARCHITECTURE
ENGINEERING
INTERIOR DESIGN
PROJECT MANAGEMENT
ELECTRICAL SITE PLAN 1" = 20'
KEYED NOTES
·
·
04/20/18
E.100
ELECTRICAL PLAN -
LIGHTING
MSDMSCHECKED:
PROJECT NO:
DATE:
REVISIONS
NO DATE REMARKS
CORPORATE SEAL:
DRAWN:
SEAL:
THIS DOCUMENT IS "NOT FOR CONSTRUCTION"
UNLESS THE ARCHITECT OR ENGINEER'S
SIGNATURE AND SEAL APPEAR BELOW.
RAINBOW CHILD
CARE CENTER
C-PROTOTYPE
95 CENTENNIAL PARKWAY
SPOUT SPRINGS, NC 28326
2017.0643
COPYRIGHT cP-0215
2018 INTERPLAN PLLC RESERVES COPYRIGHT & OTHER RIGHTS RESTRICTING THESE DOCUMENTS TO THE ORIGINAL SITE OR PURPOSE FOR WHICH THEY WERE PREPARED. REPRODUCTIONS, CHANGES OR ASSIGNMENTS ARE PROHIBITED.604 COURTLAND STREET
SUITE 100
ORLANDO, FLORIDA 32804
PH 407.645.5008
FX 407.629.9124
ARCHITECTURE
ENGINEERING
INTERIOR DESIGN
PROJECT MANAGEMENT
ELECTRICAL PLAN - LIGHTING 3/16" = 1'-0"
KEYED NOTES
Pre-School 2Pre-K 2
Staff
Lounge
Pre-K 1
Pre-School 1
Laundry Rm.
Varsity
Corridor 1
Toddler 1
Gym
Infant 1Infant 2
Young
Pre-School
Central Corridor Vestibule
Childs
Toilet 4
Childs
Toilet 3
Child
Toilet 5
Childs
Toilet 7
Childs
Toilet 9
Childs
Toilet 8
Toddler 2
Childs
Toilet 6
Gym Child
Toilet
Closet
Gym Equip.Gym Equip.
Directors
Office
Utility Rm.
Kitchen
Pantry
Kitchen
Outdoor Toy
Storage
Closet
Adult B.F.
Toilet 1
Stair
Child
Toilet 2
Lobby
Reception
Conf.Rm.
Closet
109
110
134
135
136
138
113
112
132
128
106
108
104 125 124
122
118
102
126
129123
101
100111
117
116
115114
121
120
127
133
103
105
107
119
139
137
140
Hall
131
I.T. Closet
130
140
04/20/18
E.101
ELECTRICAL PLAN - POWER
MSDMSCHECKED:
PROJECT NO:
DATE:
REVISIONS
NO DATE REMARKS
CORPORATE SEAL:
DRAWN:
SEAL:
THIS DOCUMENT IS "NOT FOR CONSTRUCTION"
UNLESS THE ARCHITECT OR ENGINEER'S
SIGNATURE AND SEAL APPEAR BELOW.
RAINBOW CHILD
CARE CENTER
C-PROTOTYPE
95 CENTENNIAL PARKWAY
SPOUT SPRINGS, NC 28326
2017.0643
COPYRIGHT cP-0215
2018 INTERPLAN PLLC RESERVES COPYRIGHT & OTHER RIGHTS RESTRICTING THESE DOCUMENTS TO THE ORIGINAL SITE OR PURPOSE FOR WHICH THEY WERE PREPARED. REPRODUCTIONS, CHANGES OR ASSIGNMENTS ARE PROHIBITED.604 COURTLAND STREET
SUITE 100
ORLANDO, FLORIDA 32804
PH 407.645.5008
FX 407.629.9124
ARCHITECTURE
ENGINEERING
INTERIOR DESIGN
PROJECT MANAGEMENT
ELECTRICAL PLAN - POWER 3/16" = 1'-0"
KEYED NOTES
Pre-School 2
Pre-K 2
Staff
Lounge
Pre-K 1
Pre-School 1
Laundry Rm.
Varsity
Pre-School
Corridor 1
Toddler 1
Gym
Infant 1Infant 2
Young
Pre-School
Central Corridor
Vestibule
Childs
Toilet 4
Childs
Toilet 3
Child
Toilet 5
Childs
Toilet 7
Childs
Toilet 9
Childs
Toilet 8
Toddler 2
Childs
Toilet 6
Gym Child
Toilet
Closet
Gym Equip.Gym Equip.
Directors
Office
Utility Rm.
Kitchen
Pantry
Kitchen
Outdoor Toy
Storage
Closet
Adult B.F.
Toilet 1
Stair
Child
Toilet 2
Lobby
Reception
Conf.Rm.
Closet
109
110
134
135
136
138
113
112
132
128
106
108
104 125 124
122
118
102
126
129123
101
100
111
117
116
115114
121
120
127
133
103105
107
119
139
137
140
Hall
131
I.T. Closet
130
140
04/20/18
E.102
ELECTRICAL PLAN - FIRE
ALARM
MSDMSCHECKED:
PROJECT NO:
DATE:
REVISIONS
NO DATE REMARKS
CORPORATE SEAL:
DRAWN:
SEAL:
THIS DOCUMENT IS "NOT FOR CONSTRUCTION"
UNLESS THE ARCHITECT OR ENGINEER'S
SIGNATURE AND SEAL APPEAR BELOW.
RAINBOW CHILD
CARE CENTER
C-PROTOTYPE
95 CENTENNIAL PARKWAY
SPOUT SPRINGS, NC 28326
2017.0643
COPYRIGHT cP-0215
2018 INTERPLAN PLLC RESERVES COPYRIGHT & OTHER RIGHTS RESTRICTING THESE DOCUMENTS TO THE ORIGINAL SITE OR PURPOSE FOR WHICH THEY WERE PREPARED. REPRODUCTIONS, CHANGES OR ASSIGNMENTS ARE PROHIBITED.604 COURTLAND STREET
SUITE 100
ORLANDO, FLORIDA 32804
PH 407.645.5008
FX 407.629.9124
ARCHITECTURE
ENGINEERING
INTERIOR DESIGN
PROJECT MANAGEMENT
ELECTRICAL PLAN - FIRE ALARM 3/16" = 1'-0"1 DETAIL - FIRE ALARM RISER NTS
04/20/18
E.103
ELECTRICAL PLAN -
EQUIPMENT PLATFORM
MSDMSCHECKED:
PROJECT NO:
DATE:
REVISIONS
NO DATE REMARKS
CORPORATE SEAL:
DRAWN:
SEAL:
THIS DOCUMENT IS "NOT FOR CONSTRUCTION"
UNLESS THE ARCHITECT OR ENGINEER'S
SIGNATURE AND SEAL APPEAR BELOW.
RAINBOW CHILD
CARE CENTER
C-PROTOTYPE
95 CENTENNIAL PARKWAY
SPOUT SPRINGS, NC 28326
2017.0643
COPYRIGHT cP-0215
2018 INTERPLAN PLLC RESERVES COPYRIGHT & OTHER RIGHTS RESTRICTING THESE DOCUMENTS TO THE ORIGINAL SITE OR PURPOSE FOR WHICH THEY WERE PREPARED. REPRODUCTIONS, CHANGES OR ASSIGNMENTS ARE PROHIBITED.604 COURTLAND STREET
SUITE 100
ORLANDO, FLORIDA 32804
PH 407.645.5008
FX 407.629.9124
ARCHITECTURE
ENGINEERING
INTERIOR DESIGN
PROJECT MANAGEMENT
ELECTRICAL PLAN - EQUIPMENT PLATFORM 3/16" = 1'-0"
KEYED NOTES
GENERAL NOTES
04/20/18
E.201
ELECTRCIAL DETAILS
MSDMSCHECKED:
PROJECT NO:
DATE:
REVISIONS
NO DATE REMARKS
CORPORATE SEAL:
DRAWN:
SEAL:
THIS DOCUMENT IS "NOT FOR CONSTRUCTION"
UNLESS THE ARCHITECT OR ENGINEER'S
SIGNATURE AND SEAL APPEAR BELOW.
RAINBOW CHILD
CARE CENTER
C-PROTOTYPE
95 CENTENNIAL PARKWAY
SPOUT SPRINGS, NC 28326
2017.0643
COPYRIGHT cP-0215
2018 INTERPLAN PLLC RESERVES COPYRIGHT & OTHER RIGHTS RESTRICTING THESE DOCUMENTS TO THE ORIGINAL SITE OR PURPOSE FOR WHICH THEY WERE PREPARED. REPRODUCTIONS, CHANGES OR ASSIGNMENTS ARE PROHIBITED.604 COURTLAND STREET
SUITE 100
ORLANDO, FLORIDA 32804
PH 407.645.5008
FX 407.629.9124
ARCHITECTURE
ENGINEERING
INTERIOR DESIGN
PROJECT MANAGEMENT
4 COMMUNICATIONS DETAIL NTS
3 MOUNTING HEIGHTS NTS1ONE LINE DIAGRAM NTS
6 DETAIL - CLASSRMN. SWITCH BANK NTS 7 DETAIL - RECEPTION SWITCH BANK NTS
8 LIGHTING CONTROLS - EXTERIOR NTS 9 LIGHTING CONTROLS - INTERIOR NTS
KEYED NOTES
5 MAIN SERVICE ENTRANCE GROUND CONNECTIONS
N.T.S
NOTES
2 COMMS/DATA WIRING DIAGRAM NTS
04/20/18
E.202
PANEL SCHEDULES
MSDMSCHECKED:
PROJECT NO:
DATE:
REVISIONS
NO DATE REMARKS
CORPORATE SEAL:
DRAWN:
SEAL:
THIS DOCUMENT IS "NOT FOR CONSTRUCTION"
UNLESS THE ARCHITECT OR ENGINEER'S
SIGNATURE AND SEAL APPEAR BELOW.
RAINBOW CHILD
CARE CENTER
C-PROTOTYPE
95 CENTENNIAL PARKWAY
SPOUT SPRINGS, NC 28326
2017.0643
COPYRIGHT cP-0215
2018 INTERPLAN PLLC RESERVES COPYRIGHT & OTHER RIGHTS RESTRICTING THESE DOCUMENTS TO THE ORIGINAL SITE OR PURPOSE FOR WHICH THEY WERE PREPARED. REPRODUCTIONS, CHANGES OR ASSIGNMENTS ARE PROHIBITED.604 COURTLAND STREET
SUITE 100
ORLANDO, FLORIDA 32804
PH 407.645.5008
FX 407.629.9124
ARCHITECTURE
ENGINEERING
INTERIOR DESIGN
PROJECT MANAGEMENT
GENERAL NOTES
SHORT CIRCUIT CURRENT RATING
”
Voltage Drop Calculations
04/20/18
E.204
ELECTRICAL
SPECIFICATIONS
MSDMSCHECKED:
PROJECT NO:
DATE:
REVISIONS
NO DATE REMARKS
CORPORATE SEAL:
DRAWN:
SEAL:
THIS DOCUMENT IS "NOT FOR CONSTRUCTION"
UNLESS THE ARCHITECT OR ENGINEER'S
SIGNATURE AND SEAL APPEAR BELOW.
RAINBOW CHILD
CARE CENTER
C-PROTOTYPE
95 CENTENNIAL PARKWAY
SPOUT SPRINGS, NC 28326
2017.0643
COPYRIGHT cP-0215
2018 INTERPLAN PLLC RESERVES COPYRIGHT & OTHER RIGHTS RESTRICTING THESE DOCUMENTS TO THE ORIGINAL SITE OR PURPOSE FOR WHICH THEY WERE PREPARED. REPRODUCTIONS, CHANGES OR ASSIGNMENTS ARE PROHIBITED.604 COURTLAND STREET
SUITE 100
ORLANDO, FLORIDA 32804
PH 407.645.5008
FX 407.629.9124
ARCHITECTURE
ENGINEERING
INTERIOR DESIGN
PROJECT MANAGEMENT
DIVISION 16000 - ELECTRICAL SPECIFICATIONS