ENG LVL LETTER 04/23/2018 9:31AM FAX X0001/0001 "h : v1+ �Lrrock JCJENKINS 1582 McArthur Rd Fayetteville, NC 28311 810.822,1724 CONSULTING ENGINEERS,PAmi 910.8224845(FAX) Professional Corporation License Number Ca070 ‘75->b4 3Ct9 co 19 April 2018 David Nepstad $'19 Vic Keith Road. Sanford, NC Re: LVL sizing Mr. Nepstad: Jenkins Consulting Engineers performed a site visit on April 12,2018 to the subject location. There is a 10' section of an existing 8" CMU wall that is to be removed. This letter is a recommendation of how to accomplish the removal of that wall. There is a porch roof that is supported by this section of the wall, and a double 11 7/8" x 1 V/ LVL will need to be installed. JCE recommends using a Simpson Strong-Tie Masonry Beam Hanger(Model No. MBHU3.56/9.25KT) on each end of the LVLs. Please see the attached submittal and follow all manufacturers'instructions. It should be noted that the blocks that the brackets are Installed to are to be solid filled with grout or concrete(see attached submittal for installation instructions). All existing 2x6 ceiling joists that support the porch roof shall be installed on the LVLs using Simpson U26 2x6 Face Mount Joist Hanger—G90 Galvanized (see attached product guide). • JCE uses the generally accepted practices and principles of the profession. JCE expresses its opinion based on visual observation of the current condition of the structure as It relates to the condition as it was originally constructed. If any other conditions other than those assumed by this report are discovered,the recommendations of this report will no longer be valid until the conditions are reviewed and changes verified in Writing. Please contact us with any and all questions. Respectfully, Jenkins Consulting Engineers, PA 1440I • l 1 \.(tht Kelly J. Dodson, PE,Vice-President Jenkins Consulting Engineers,PA Fayetteville,North, Carolina