FM PLAN REVIEW sHarnett ,�
-} C 0 U H T Y _ 01) ^tm..ymn<r somas oswnrmat
w.+J,wMn.ay
Plan Review, Inspection, and Permit Fees
Application Number . 18-50043695
$200.00 ❑ Explosive Material (90 Days) $ -
$100.00 ❑ Explosive Materials (72 Hours) $ -
$100.00 D Fireworks Public Display $ -
$50.00 E Final Inspection $ 50.00
$35.00 +$2.00 per device D Fire Alarm Testing $ -
$35.00 +$2.00 per nozzle ❑ Fixed Fire Suppression $ .
$75.00 ❑ Insecticide Fog/Fumigation $ -
$100.00 ❑ Pipe Test/UST/AGST $ -
$50.00 ❑ Plans up to 5000 sq ft $
$100.00 0 Plans 5001 sq ft to 10,000 sq ft $ 100.00
$150.00 ❑ Plans 10,001 sq ft to 25,000 sq ft $ -
$250.00 ❑ Plans 25,001 sq ft and over $ -
$35.00 +2.00 per head ❑ Sprinkler Certification Test $ -
$50.00 ❑ Standpipe Testing $ -
$50.00 ❑ Special Assembly
(ie.amusement buildings,carnivals,fairs) $ -
$75.00 Tents/Canopies/Air Supported Structure
$ -
$100.00 Tank Installation (charge for each tank) $
$100.00 ❑ Tank Removal (charge for each tank) $ -
Total Devices/Heads $ -
Total Cost $ 150.00
Code Enforcement Official Banks Wallace 5/2/2018
,Iy Harnett
„t ' COUNTY A opr�'r em.ry.nryrtN
far Department
f 'H
Air” Overt haiMt.ay
Fire Marshal Division
May 1, 2018
Mr. Pedro Nunoz
2291 NC Hwy 55 E
Dunn, NC 28334
Re: Gospel Tabernacle Hispanic Church
2291 Hwy 55 E
Dunn, NC 28334
Application Number 18-50043695
Mr. Nunoz,
Thank you for submitting the plans for the Gospel Tabernacle. The plans have been
carefully reviewed by a qualified code enforcement official to examine for compliance
with the North Carolina Fire Prevention Code and all other fire protection regulatory
documents. There are some items that were found during the plan review process that
need to be addressed before a final inspection of the new facility can be given. These
items are outlined and described below.
• 906.1 Fire Extinguishers
o Minimum of (1) 2A10:BC fire extinguisher shall be installed per 75'
distance of travel.
o All Fire extinguishers shall be properly mounted and tagged by a fire
extinguisher company.
• 1008.1.10 Panic Hardware
o UL 305 listed panic hardware is required on exit doors serving a
room/space with an occupant load >50, also indicated on Building code
summary. Panic hardware is not included on door schedule sheet B8 of
Drawings.
• 1004.3 Occupant Load Posting
o The occupant load posting shall be provided by the Fire Marshal's Office
at fire final inspection.
• 1006.1 Means of Egress Illumination
- Harnett
°`:�. COUNTY
10.041,
10)
r.mergency Straus nepnrtm•nt
illis i * A '.Mr
wwwlIanuttwg
o The means of egress, including the exit discharge, shall be illuminated at
all time the building space is served by the means of egress is occupied.
o Means of egress consist of three separate and distinct parts: the
exit access,the exit and the exit discharge.
o The means of egress illumination shall not be less than 1 foot-candle at
the walking surface.
• 703.5 Rated Wall Identification
o Rated walls shall be permanently identified with signs or stenciling.
o Example: "1 Hour Fire Barrier Protect All Openings"
• Notes
o A final fire inspection is required.
o Place key to building in existing Knox Box to allow access any locked
doors
o Schedule all fire inspections through the Fire Marshal's Office.
(919)893-0743
Thank you again for submitting the plans for the Gospel Tabernacle. Please review the
plans and adhere to any notes and alterations that were made in addition to the original
drawings. These remarks are for the plans that were submitted and its original intent.
These remarks do not apply if the original intent changes or what was submitted on the
above date changes. If you have any questions, please do not hesitate to call this office.
Sincerely, afro Ly(
D. Banks Wallace
Chief Deputy Fire Marshal