MMF-300 DATA SHEETdf-52121:b • 11/13/08 — Page 1 of 4 MMF-300(A) Series, MDF-300(A) Addressable Monitor Modules Addressable Devices df-52121:b • E-325 General Four different monitor modules are available for Fire•Lite’s intelligent control panels to suit a variety of applications. Moni- tor modules are used to supervise a circuit of dry-contact input devices, such as conventional heat detectors and pull stations, or monitor and power a circuit of two-wire smoke detectors (MMF-302). MMF-300 is a standard-sized module (typically mounts to a 4" [10.16 cm] square box) that supervises either a Class A (Style D) or Class B (Style B) circuit of dry-contact input devices. MMF-301 is a miniature monitor module (a mere 1.3" (3.302 cm) H x 2.75" (6.985 cm) W x 0.5" (1.270 cm) D) used to supervise a Class B (Style B) circuit of dry-contact input devices. Its compact design allows the MMF-301 to often be mounted in a single-gang box behind the device it monitors. MMF-302 is a standard-sized module used to monitor and supervise compatible two-wire, 24 volt, smoke detectors on a Class A (Style D) or Class B (Style B) circuit. MDF-300 is a standard-sized dual monitor module used to monitor and supervise two independent two-wire Style B (Class B) dry-contact initiating device circuits (IDCs) at two separate, consecutive addresses in intelligent, two-wire systems. LiteSpeed™ is a communication protocol developed by Fire•Lite Engineering that greatly enhances the speed of com- munication between analog intelligent devices. Intelligent devices communicate in a grouped fashion. If one of the devices within the group has new information, the panel CPU stops the group poll and concentrates on single points. The net effect is response speed greater than five times that of other designs. MMF-300 Monitor Module • Built-in type identification automatically identifies this device as a monitor module to the control panel. • Powered directly by two-wire SLC loop. No additional power required. • High noise (EMF/RFI) immunity. • SEMS screws with clamping plates for ease of wiring. • Direct-dial entry of address: 01 – 159 on MS-9600 series panels, 01 – 99 on other compatible systems. • LED flashes during normal operation and latches on steady to indicate alarm. The MMF-300 Monitor Module is intended for use in intelligent, two-wire systems, where the individual address of each mod- ule is selected using the built-in rotary switches. It provides either a two-wire or four-wire fault-tolerant Initiating Device Cir- cuit (IDC) for normally-open-contact fire alarm and supervisory devices. The module has a panel-controlled LED indicator. The MMF-300 can be used to replace M300 modules in existing systems. MMF-300 APPLICATIONS Use to monitor a zone of four-wire smoke detectors, manual fire alarm pull stations, waterflow devices, or other normally- open dry-contact alarm activation devices. May also be used to monitor normally-open supervisory devices with special supervisory indication at the control panel. Monitored circuit may be wired as an NFPA Style B (Class B) or Style D (Class A) Initiating Device Circuit. A 47K ohm End-of-Line Resistor (provided) terminates the Style B circuit. No resistor is required for supervision of the Style D circuit. MMF-300 OPERATION Each MMF-300 uses one of the available module addresses on an SLC loop. It responds to regular polls from the control panel and reports its type and the status (open/normal/short) of its Initiating Device Circuit (IDC). A flashing LED indicates that the module is in communication with the control panel. The LED latches steady on alarm (subject to current limita- tions on the loop). MMF-300 SPECIFICATIONS Nominal operating voltage: 15 to 32 VDC. Maximum current draw: 5.0 mA (LED on). Maximum operating current: 375 µA (LED flashing). Maximum IDC wiring resistance: 1,500 ohms. EOL resistance: 47K ohms. Temperature range: 32°F to 120°F (0°C to 49°C). Humidity range: 10% to 93% noncondensing. Dimensions: 4.5" (11.43 cm) high x 4" (10.16 cm) wide x 1.25" (3.175 cm) deep. Mounts to a 4" (10.16 cm) square x 2.125" (5.398 cm) deep box. MMF-301 Mini Monitor Module • Built-in type identification automatically identifies this device as a monitor module to the panel. • Powered directly by two-wire SLC loop. No additional power required. • High noise (EMF/RFI) immunity. • Tinned, stripped leads for ease of wiring. • Direct-dial entry of address: 01 – 159 on MS-9600 series panels, 01 – 99 on other compatible systems. MMF-300 (Type H)6999cov.jpg Page 2 of 4 — df-52121:b • 11/13/08 The MMF-301 Mini Monitor Module can be installed in a sin- gle-gang junction directly behind the monitored unit. Its small size and light weight allow it to be installed without rigid mount- ing. The MMF-301 is intended for use in intelligent, two-wire systems where the individual address of each module is selected using rotary switches. It provides a two-wire initiating device circuit for normally-open-contact fire alarm devices. The MMF-301 can be used to replace M301 modules in exist- ing systems. MMF-301 APPLICATIONS Use to monitor a single device or a zone of four-wire smoke detectors, manual fire alarm pull stations, waterflow devices, or other normally-open dry-contact devices. May also be used to monitor normally-open supervisory devices with special super- visory indication at the control panel. Monitored circuit/device is wired as an NFPA Style B (Class B) Initiating Device Circuit. A 47K ohm End-of-Line Resistor (provided) terminates the cir- cuit. MMF-301 OPERATION Each MMF-301 uses one of the available module addresses on an SLC loop. It responds to regular polls from the control panel and reports its type and the status (open/normal/short) of its Initiating Device Circuit (IDC). MMF-301 SPECIFICATIONS Nominal operating voltage: 15 to 32 VDC. Maximum operating current: 375 µA. Maximum IDC wiring resistance: 1,500 ohms. EOL resistance: 47K ohms. Temperature range: 32°F to 120°F (0°C to 49°C). Humidity range: 10% to 93% noncondensing. Dimensions: 1.3" (3.302 cm) high x 2.75" (6.985 cm) wide x 0.65" (1.651 cm) deep. Wire length: 6" (15.24 cm) minimum. MMF-302 Interface Module • Supports compatible two-wire smoke detectors. • Supervises IDC wiring and connection of external power source. • High noise (EMF/RFI) immunity. • SEMS screws with clamping plates for ease of wiring. • Direct-dial entry of address: 01 – 159 on MS-9600 series panels, 01 – 99 on other compatible systems. • LED flashes during normal operation. • LED latches steady to indicate alarm on command from control panel. The MMF-302 Interface Module is intended for use in intelli- gent, addressable systems, where the individual address of each module is selected using built-in rotary switches. This module allows intelligent panels to interface and monitor two- wire conventional smoke detectors. It transmits the status (nor- mal, open, or alarm) of one full zone of conventional detectors back to the control panel. All two-wire detectors being moni- tored must be UL compatible with the module. The MMF-302 can be used to replace M302 modules in existing systems. MMF-302 APPLICATIONS Use the MMF-302 to monitor a zone of two-wire smoke detec- tors. The monitored circuit may be wired as an NFPA Style B (Class B) or Style D (Class A) Initiating Device Circuit. A 3.9 K ohm End-of-Line Resistor (provided) terminates the end of the Style B or D (class B or A) circuit (maximum IDC loop resis- tance is 25 ohms). Install ELR across terminals 8 and 9 for Style D application. MMF-302 OPERATION Each MMF-302 uses one of the available module addresses on an SLC loop. It responds to regular polls from the control panel and reports its type and the status (open/normal/short) of its Initiating Device Circuit (IDC). A flashing LED indicates that the module is in communication with the control panel. The LED latches steady on alarm (subject to current limita- tions on the loop). MMF-302 SPECIFICATIONS Nominal operating voltage: 15 to 32 VDC. Maximum current draw: 5.1 mA (LED on). Maximum IDC wiring resistance: 25 ohms. Maximum operating current: 270 µA (LED flashing). EOL resistance: 3.9K ohms. External supply voltage (between Terminals T3 and T4): DC voltage: 24 volts power limited. Ripple voltage: 0.1 Vrms maximum. Current: 90 mA per module maximum. Temperature range: 32°F to 120°F (0°C to 49°C). Humidity range: 10% to 93% noncondensing. Dimensions: 4.5" (11.43 cm) high x 4" (10.16 cm) wide x 1.25" (3.175 cm) deep. Mounts to a 4" (10.16 cm) square x 2.125" (5.398 cm) deep box. MDF-300 Dual Monitor Module The MDF-300 Dual Monitor Module is intended for use in intel- ligent, two-wire systems. It provides two independent two-wire initiating device circuits (IDCs) at two separate, consecutive addresses. It is capable of monitoring normally open contact fire alarm and supervisory devices. The module has a single panel-controlled LED. NOTE: The MDF-300 provides two Class B (Style B) IDC circuits ONLY. Class A (Style D) IDC circuits are NOT supported in any application. MDF-300 SPECIFICATIONS Normal operating voltage range: 15 to 32 VDC. Maximum current draw: 6.4 mA (LED on). Maximum operating current: 750 µA (LED flashing). Maximum IDC wiring resistance: 1,500 ohms. EOL resistance: 47K ohms. Temperature range: 32° to 120°F (0° to 49°C). Humidity range: 10% to 93% (non-condensing).6720m101.wmf df-52121:b • 11/13/08 — Page 3 of 4 Dimensions: 4.5" (11.43 cm) high x 4" (10.16 cm) wide x 2.125" (5.398 cm) deep. MDF-300 AUTOMATIC ADDRESSING The MDF-300 automatically assigns itself to two addressable points, starting with the original address. For example, if the MDF-300 is set to address “26”, then it will automatically assign itself to addresses “26” and “27”. NOTE: “Ones” addresses on the MDF-300 are 0, 2, 4, 6, or 8 only. Terminals 6 and 7 use the first address, and terminals 8 and 9 use the second address. Installation MMF-300, MMF-302, and MDF-300 modules mount directly to a standard 4" (10.16 cm) square, 2.125" (5.398 cm) deep, electrical box. They may also be mounted to the SMB500 sur- face-mount box. Mounting hardware and installation instruc- tions are provided with each module. All wiring must conform to applicable local codes, ordinances, and regulations. These modules are intended for power-limited wiring only. The MMF-301 module is intended to be wired and mounted without rigid connections inside a standard electrical box. All wiring must conform to applicable local codes, ordinances, and regulations. Agency Listings and Approvals In some cases, certain modules may not be listed by certain approval agencies, or listing may be in process. Consult fac- tory for latest listing status. •UL: S2424 •ULC: S3705 (“A” suffix models) • FM Approved •CSFM: 7300-0075-185 •MEA: 72-01-E Product Line Information NOTE: “A” suffix indicates ULC Listed model. MMF-300(A): Monitor module. MMF-301(A): Monitor module, miniature. MMF-302(A): Monitor module, two-wire detectors. MDF-300(A): Monitor module, dual, two independent Class B circuits. SMB500: Optional surface-mount backbox. NOTE: See installation instructions and refer to the SLC Wiring Manual, PN 51309. Architects’/Engineers’ Specifications Specifications of these devices and all FireLite products are available from FireLite. !CAUTION: Avoid duplicating addresses on the system. Page 4 of 4 — df-52121:b • 11/13/08 This document is not intended to be used for installation purposes. We try to keep our product information up-to-date and accurate. We cannot cover all specific applications or anticipate all requirements. All specifications are subject to change without notice. For more information, contact Fire•Lite Alarms. Phone: (800) 627-3473, FAX: (877) 699-4105. www.firelite.com Fire·Lite® and LiteSpeed® are registered trademarks of Honeywell International Inc. ©2008 by Honeywell International Inc. All rights reserved. Unauthorized use of this document is strictly prohibited. Made in the U.S. A.