FA1This drawing and the design shown are the property of THE
The reproduction, copying or other use of this drawing without
their written consent is prohibited.
THE PYROCADD COMPANY, LLC 2016
PYROCADD COMPANY.Addition to Fire Alarm System for:ANGIER, NCOAK HILL LIVING CENTER ADDITION9767 NC 210ALARM
FIRE
FA1
PLAN
SYSTEM INPUTS
SYSTEM OUTPUTSFIRE ALARM SYSTEM INPUT/OUTPUT MATRIX
HS
S
5'-0" MAXIMUM
3'-8"
(3'-6" MINIMUM,
4'-0" MAXIMUM)
MOUNT ON
SINGLE-GANG
BOX
CONTROL PANEL
GRAPHIC
ANNUNCIATOR
MANUAL PULL STATION
5'-6"
6'-8" MINIMUM
8'-0" MAXIMUM
0'-6" MINIMUM
SMOKE / HEAT
DETECTOR
0'-4" MINIMUM
1'-0" MAXIMUM
HORN
HORN / STROBE
AIR SUPPLY OR RETURN
AIR OPENING
SMOKE / HEAT
DETECTOR
3'-0" MINIMUM0'-4" MINIMUM
MOUNT AUDIBLE &
VISUAL DEVICES ON 4"
SQUARE DEEP BOX
MOUNT ON A 4" SQUARE OR
OCTAGON BOX
INSTALL PER NATIONAL ELECTRIC CODE
CONDUIT
FINISHED
FLOOR
NFPA 72 AND ADA DEVICE INSTALLATION REQUIREMENTS
7'-6" MINIMUM
TOP OF HORN
STROBE