Loading...
Flowers - Construction Set IFCLOCATION MAP SCALE N.T.S. EPC CONTRACTOR: 1519 KING ST. CHARLESTON, SC 29405 877.878.SOLAR APPLICABLE SPECIFICATIONS AND CODES -ELECTRICAL: NEC-2014 -BUILDING:ASCE 07-10 -WIND SPEED: 107 mph -SNOW LOAD:10 lbs/sq.ft. COUNTY: PERMIT INFO GC LICENSE #: ELECTRICAL LICENSE #: BUILDING PERMIT #: ELECTRICAL PERMIT #: HARNETT INDEX SHEET TITLE 001 TITLE PAGE 002 GENERAL NOTES 003 TOTAL PV SYSTEM OVERVIEW 004 TRENCH PLAN 005 TRENCH DETAILS 006 DC CIRCUIT PLAN 007 WIRING MANAGEMENT DETAILS 008 ELECTRICAL ONE LINE 009 ELECTRICAL CALCULATIONS 010 MONITORING ONE LINE DIAGRAM 011 GROUNDING DETAILS 012 CONCRETE SLAB DETAILS (PG-1) 013 CONCRETE SLAB DETAILS (PG-2) 014 TRANSFORMER AND JUMPER DETAILS 015 MEDIUM VOLTAGE DETAILS (PG-1) 016 MEDIUM VOLTAGE DETAILS (PG-2) 017 MEDIUM VOLTAGE DETAILS (PG-3) 018 LABEL PLAN 019 GROUND RING AND MONITORING DETAIL FLOWERS SOLAR PV INSTALLATION CONSTRUCTION PLAN SITE ADDRESS: 3188 BAILEYS CROSSROADS ROAD BENSON, NC 27512 LOCATION MAP SCALE: NTS CIVIL: CITED PLANS RACKING: KLEINFELDER RBI T.JONES01/15/20180ISSUED FOR PERMITD.BRUECK1519 King St. Charleston, S.C. 29405 "THIS DOCUMENT CONTAINS INTELLECTUAL, DESIGN, OR COPY WRITE PROPERTY OF SOUTHERN CURRENT LLC WHICH IS PRIVILEGED OR CONFIDENTIAL AND IS NOT TO BE REPRODUCED, DISCLOSED, USED IN ANY MANNER OR DISTRIBUTED WITHOUT WRITTEN PERMISSION OF SOUTHERN CURRENT LLC" "THIS DOCUMENT CONTAINS INTELLECTUAL, DESIGN, OR COPY WRITE PROPERTY OF SOUTHERN CURRENT LLC WHICH IS PRIVILEGED OR CONFIDENTIAL AND IS NOT TO BE REPRODUCED, DISCLOSED, USED IN ANY MANNER OR DISTRIBUTED WITHOUT WRITTEN PERMISSION OF SOUTHERN CURRENT LLC" REVISION DESCRIPTIONAPRV'DNODATEBYFLOWERS SOLAR3188 BAILEYS CROSSROADS ROADBENSON, NC 275124.34 MW AC - SOLAR PV SYSTEMTITLE PAGESITE SITE 77979 31652-U T.JONES01/18/20181ISSUED FOR CONSTRUCTIOND.BRUECK INVERTER 1. INVERTER SHALL BE HANDLED AND INSTALLED IN ACCORDANCE WITH THE MANUFACTURER'S RECOMMENDATIONS AND DOCUMENTATION. ALL INSTRUCTIONS AND REFERENCE DOCUMENTS SHALL BE REVIEWED AND UNDERSTOOD BY THE CONTRACTOR PRIOR TO HANDLING AND UNPACKING THE EQUIPMENT. 2. CONTRACTOR SHALL INSPECT ALL PACKAGES FOR DAMAGE UPON DELIVERY. ANY DAMAGED PACKAGES SHALL BE OPENED SO THE INVERTER AND EQUIPMENT CAN BE INSPECTED. ANY DAMAGE TO THE PACKAGING OR EQUIPMENT SHALL BE DOCUMENTED AND REPORTED TO THE OWNER IMMEDIATELY. INVERTERS TO BE STORED SHALL BE PROPERLY REPLACED IN THE PACKAGING FOR STORAGE. 3. INVERTER SHALL BE STORED IN A SECURE AND CLEAN LOCATION PER THE MANUFACTURER'S RECOMMENDATIONS AND DOCUMENTATION. INVERTERS SHALL BE PROTECTED FROM THE ENVIRONMENT SUCH AS HEAT, COLD, MOISTURE, DUST, SNOW, ETC. 4. REFERENCE THE MANUFACTURER'S INSTRUCTIONS FOR UNPACKING THE EQUIPMENT. INVERTERS SHALL BE TRANSPORTED BY MEANS OUTLINED IN THE MANUFACTURER'S DOCUMENTATION ONLY. 5. THE CONTRACTOR IS TO ENSURE THAT WORKING CLEARANCES MEET THE REQUIREMENTS OF ALL APPLICABLE CODES AND THE MANUFACTURERS REQUIREMENT'S. ANY DISCREPANCIES SHALL BE REPORTED TO THE OWNER IMMEDIATELY. 6. ALL DISCONNECT SWITCHES SHALL BE IN THE OPEN POSITION DURING INSTALLATION AND SHALL REMAIN IN THE OPEN POSITION UNTIL PROPER TESTING, INSPECTION, AND COMMISSIONING HAS BEEN COMPLETED. 7. DO NOT OPEN THE INVERTER OR ELECTRICAL CABINETS WHEN IT IS RAINING OR HUMIDITY EXCEEDS 95%. 8. ALL FASTENERS SHALL BE TORQUED PER THE MANUFACTURER'S DOCUMENTATION. 9. IT IS PROHIBITED TO MODIFY THE INVERTER OR INSTALL EQUIPMENT NOT EXPLICITLY RECOMMENDED BY THE MANUFACTURER. DO NOT STORE DOCUMENTS, INSTRUCTIONS, PLANS, OR ANY OTHER FOREIGN MATERIAL NOT INTENDED TO BE PART OF THE SYSTEM INSIDE THE INVERTER CABINETS. 10. COMPONENTS OF THE INVERTER MAY BE DAMAGED BY ELECTROSTATIC DISCHARGE (ESD). WHEN HANDLING THE ELECTRICAL COMPONENTS, OBSERVE ALL ESD SAFETY REGULATIONS. 11. ALL CONDUCTORS SHALL BE CONNECTED TO THE INVERTER PER THE MANUFACTURER'S DOCUMENTATION, MAKING NOTE OF RECOMMENDED TERMINATIONS, TORQUE VALUES, AND BOLT STACK UP DETAILS IF PROVIDED. ALL BUSS BARS, CONDUCTORS, AND TERMINATIONS SHALL BE CLEAN PRIOR TO MAKING THE CONNECTION. 12. PHOTOVOLTAIC SYSTEM DC GROUNDING CONFIGURATIONS MAY VARY BY MANUFACTURER AND TECHNOLOGY. THE GROUNDING CONFIGURATION SHALL BE NOTED BY THE CONTRACTOR FOR SAFETY AND PROPER INSTALLATION. WIRING AND WIRING METHODS 1. ALL WIRING METHODS AND INSTALLATION PRACTICES SHALL CONFORM TO THE NATIONAL ELECTRIC CODE. 2. EXPOSED PV SOLAR PANEL WIRING WILL BE 'PV WIRE', 90 DEGREE C, 2000V, WET RATED. ALL EXPOSED CABLES, SUCH AS MODULE LEADS SHALL BE SECURED WITH MECHANICAL OR OTHER SUN-LIGHT RESISTANT MEANS. 3. PV PANEL CONDUCTORS SHALL BE COPPER AND HAVE INSULATION RATING 2000 V, 90 DEGREE C, UNLESS OTHERWISE NOTED. 4. USE THE FOLLOWING COLOR CONVENTION FOR DC CONDUCTORS: BLACK - POSITIVE WHITE - NEGATIVE GREEN - GROUND 5. ALL FIELD WIRING THAT IS NOT COLOR CODED SHALL BE TAGGED AT BOTH ENDS WITH PERMANENT WIRE MARKERS TO IDENTIFY POLARITY AND GROUND. FACE TAPE SHALL NOT BE USED. 6. ALL AMPACITIES OF CONDUCTORS ENCLOSED IN CONDUIT SHALL BE CALCULATED AT A MAXIMUM OF 75°C INSULATION RATING OR THE TEMPERATURE RATING OF THE TERMINATION, WHICHEVER IS LOWER AS PER NEC TABLE 310.15(B)(16). 7. ALLOWABLE AMPACITIES OF UNDERGROUND CONDUCTORS SHALL BE BASED ON AN AMBIENT TEMPERATURE 30 DEGREE C, (REFER TO NEC TABLE 310.15(B)(16)). 8THE MAX AND MIN AMBIENT TEMPERATURES USED IN THIS DESIGN ARE 35°C AND (-)10°C AND ARE BASED ON DATA PROVIDED BY ASHRAE FOR FORT BRAGG, NORTH CAROLINA. 9. IF USED, ALL WIRENUTS ARE TO BE SILICONE FILLED, EQUIVALENT TO IDEAL BLUE, AND INSTALLED PER MANUFACTURER'S SPECIFICATIONS BY A QUALIFIED/CERTIFIED PERSON. WIRENUTS SHALL NOT BE INSTALLED ALONG THE PATH OF PV POWER GENERATION, OR FOR ANY EQUIPMENT NECESSARY FOR THE GENERATION OF PV POWER. WIRENUTS ARE ONLY ALLOWED FOR AUXILIARY EQUIPMENT. 10. FUSES AND WIRES SUBJECT TO TRANSFORMER INRUSH CURRENT SHALL BE SIZED ACCORDINGLY. 11. ALL DC MATERIALS SHALL BE UL LISTED FOR 1000VDC MINIMUM. 12. CONNECTORS TO BE TORQUED PER DEVICE LISTING, OR MANUFACTURERS RECOMMENDATIONS. ONLY 60 TON HYDRAULIC CRIMPS WITH HIGH VOLTAGE HEAT-SHRINK INSULATION ARE ACCEPTABLE. 13. SPLIT BOLTS / SPLICES / CONNECTORS SHALL BE INSULATED WITH APPROVED MEANS. UL LISTED ELECTRICAL TAPE ALONE IS NOT SUITABLE AS THE ONLY INSULATION MEANS. FOLLOW MANUFACTURERS INSTRUCTIONS FOR APPLICATION OF INSULATING PRODUCT. GROUNDING 1. SEE ELECTRICAL ONE-LINE DIAGRAM FOR SPECIFIC PLAN. 2. ONLY ONE CONNECTION TO AC CIRCUITS SHALL BE USED FOR SYSTEM GROUNDING. 3. EQUIPMENT GROUNDING CONDUCTORS AND SYSTEM GROUNDING CONDUCTORS SHALL HAVE AS SHORT A DISTANCE TO GROUND AS POSSIBLE AND A MINIMUM NUMBER OF TURNS. 4. NON-CURRENT CARRYING METAL PARTS SHALL BE CHECKED FOR PROPER GROUNDING; NOTING THAT TERMINAL LUGS BOLTED ON AN ENCLOSURE'S FINISHED SURFACE MAY BE INSULATED BECAUSE OF PAINT/FINISH. PAINT/FINISH AT POINT OF CONTACT SHALL BE PROPERLY REMOVED AND TREATED FOR RUST PREVENTION. 5. 'PV' MODULE FRAMES SHALL BE BONDED WITH WEEB'S BONDING WASHERS OR OTHER APPROVED BONDING METHOD TO RACKing StRUCTURE USING A METHOD APPROVED BY THE MODULE MANUFACTURER AND WITH A MEANS OF BONDING LISTED FOR THIS PURPOSE. 6. THE CONNECTION TO THE MODULE OR PANEL OF THIS PROPOSED SOLAR ELECTRIC SYSTEM SHALL BE SO ARRANGED THAT REMOVAL OF A MODULE OR A PANEL FROM THE PHOTOVOLTAIC SOURCE CIRCUIT DOES NOT INTERRUPT A GROUNDED CONDUCTOR TO ANOTHER PHOTOVOLTAIC SOURCE CIRCUIT. SETS OF MODULES INTERCONNECTED AS SYSTEMS RATED AT 50 VOLTS OR HIGHER, WITH OR WITHOUT BLOCKING DIODES, AND HAVING A SINGLE OVER CURRENT DEVICE SHALL BE CONSIDERED AS A SINGLE SOURCE CIRCUIT. 7. GROUNDING SYSTEM COMPONENTS SHALL BE LISTED FOR THEIR PURPOSE, INCLUDING BUT NOT LIMITED TO GROUND RODS, GROUNDING LUGS, GROUNDING CLAMPS, ETC. GROUNDING DEVICES EXPOSED TO THE ENVIRONMENT SHALL BE RATED FOR DIRECT BURIAL. GROUNDING LUGS SHALL BE LISTED FOR DIRECT-BURIAL, ILSCO GBL4-DBT OR EQUAL. 8. ALL FLEXIBLE CONDUITS SHALL HAVE AN EXTERIOR GROUND WIRE BETWEEN THE CONNECTORS AT BOTH ENDS. GROUND WIRE SHALL RUN ALONG THE CONDUIT. 9. ALL GROUNDING SYSTEMS FOR THE SOLAR PV INSTALLATION SHALL COMPLY WITH THE NATIONAL ELECTRIC CODE, AND LOCAL STANDARDS. GROUND FAULT PROTECTION 1. PHOTOVOLTAIC INVERTERS SHALL BE EQUIPPED WITH DC GROUND FAULT PROTECTION TO REDUCE FIRE HAZARDS. INVERTERS ARE ALSO EQUIPPED WITH ANTI-ISLANDING CIRCUITRY. ARC-FAULT PROTECTION 1. PHOTOVOLTAIC SYSTEMS WITH DC SOURCE CIRCUITS, DC OUTPUT CIRCUITS, OR BOTH OPERATING AT A PV SYSTEM MAXIMUM SYSTEM VOLTAGE OF 80 VOLTS OR GREATER, SHALL BE PROTECTED BY A LISTED (DC) ARC-FAULT CIRCUIT INTERRUPTER, PV TYPE, OR OTHER SYSTEM COMPONENTS LISTED TO PROVIDE EQUIVALENT PROTECTION. NEW PHOTOVOLTAIC SYSTEM 1. THE PROPOSED PHOTOVOLTAIC SYSTEM IS INTENDED TO OPERATE IN PARALLEL WITH THE UTILITY DISTRIBUTION SYSTEM. 2. THE PHOTOVOLTAIC SYSTEM IS INTENDED TO CONNECT TO THE EXISTING DUKE ENERGY PROGRESS (DEP) POWER SYSTEM. THIS CONNECTION SHALL BE IN COMPLIANCE WITH THE NEC AND DEP STANDARDS. 3. PHOTOVOLTAIC SYSTEM SHALL MEET DEP SERVICE REQUIREMENTS. 4. PRIOR TO INSTALLATION, THE CONTRACTOR SHALL SUBMIT AN INTERCONNECTION APPLICATION TO DEP AND OBTAIN AN INTERCONNECTION AGREEMENT IN COORDINATION WITH LOCAL STANDARDS. 5. THE CONTRACTOR SHALL SUBMIT ALL DATA SHEETS OF MAJOR COMPONENTS TO THE OWNER. 6. THE INVERTER FOR THE PROPOSED PHOTOVOLTAIC SYSTEM SHALL BE IDENTIFIED FOR USE IN SOLAR PHOTOVOLTAIC SYSTEMS. 7. ALL SOURCE CIRCUITS SHALL HAVE INDIVIDUAL SOURCE CIRCUIT PROTECTION FOR TESTING AND ISOLATION. ALL COMBINER BOXES SHALL HAVE DISCONNECTION MEANS IN OR NEAR THE COMBINER FOR ISOLATION AND TESTING. 8. ALL DISCONNECTS, COMBINERS, PULL/SPLICE BOXES, AND ENCLOSURES SHALL BE UL LISTED FOR ITS PURPOSE. DISCONNECTING MEANS 1. MEANS SHALL BE PROVIDED TO DISCONNECT ALL CURRENT CARRYING CONDUCTORS OF THE PHOTOVOLTAIC POWER SOURCE FROM ALL OTHER CONDUCTORS. 2. WHERE A CIRCUIT GROUNDING CONNECTION IS NOT DESIGNED TO BE AUTOMATICALLY INTERRUPTED AS PART OF THE GROUND-FAULT PROTECTION SYSTEM REQUIRED BY NEC ARTICLE 690-5, A SWITCH OR CIRCUIT BREAKER USED AS A DISCONNECTING MEANS SHALL NOT HAVE A POLE IN THE GROUNDED CONDUCTOR. 3. THE GROUNDED CONDUCTOR MAY HAVE A BOLTED OR TERMINAL DISCONNECTING MEANS TO ALLOW MAINTENANCE OR TROUBLESHOOTING BY QUALIFIED PERSONNEL. 4. THE DISCONNECTING MEANS SHALL NOT BE REQUIRED TO BE SUITABLE AS SERVICE EQUIPMENT AND SHALL BE RATED IN ACCORDANCE WITH NEC ARTICLE 690-17. 5. EQUIPMENT SUCH AS PHOTOVOLTAIC SOURCE CIRCUITS, OVER CURRENT DEVICES, AND BLOCKING DIODES SHALL BE PERMITTED ON THE PHOTOVOLTAIC SIDE OF THE PHOTOVOLTAIC DISCONNECTING MEANS. 6. MEANS SHALL BE PROVIDED TO DISCONNECT EQUIPMENT SUCH AS INVERTERS, BATTERIES, CHARGE CONTROLLERS, AND THE LIKE FROM ALL UNGROUNDED CONDUCTORS OF ALL SOURCES. IF THE EQUIPMENT IS ENERGIZED FROM MORE THAN ONE SOURCE, THE DISCONNECTING MEANS SHALL BE GROUPED AND IDENTIFIED. 7. A SINGLE DISCONNECTING MEANS SHALL BE PERMITTED FOR THE COMBINED AC OUTPUT OF ONE OR MORE INVERTERS IN AN INTERACTIVE SYSTEM. 8. NEC 690-16. FUSES. DISCONNECTING MEANS SHALL BE PROVIDED TO DISCONNECT A FUSE FROM ALL SOURCES OF SUPPLY IF THE FUSE IS ENERGIZED FROM BOTH DIRECTIONS AND IS ACCESSIBLE TO OTHER THAN QUALIFIED PERSONS. SUCH A FUSE IN A PHOTOVOLTAIC SOURCE CIRCUIT SHALL BE CAPABLE OF BEING DISCONNECTED INDEPENDENTLY OF FUSES IN OTHER PHOTOVOLTAIC SOURCE CIRCUITS. REQUIRED SAFETY SIGNS AND LABELS REQUIRED SAFETY SIGNS AND LABELS SHALL BE PERMANENTLY ATTACHED BY ADHESIVE, OR OTHER MECHANICAL MEANS. LABELS SHALL COMPLY WITH ARTICLE 690 OF THE NEC OR OTHER APPLICABLE STATE, AND UTILITY CODES. SEE LABELS AND MARKING PAGE FOR MORE INFORMATION. 1. ANY SWITCH, FUSES, OR CIRCUIT BREAKERS THAT CAN BE ENERGIZED IN EITHER DIRECTION SHALL BE LABELED AS FOLLOWS WARNING: ELECTRICAL SHOCK HAZARD DO NOT TOUCH TERMINALS. TERMINALS ON BOTH THE LINE AND LOAD SIDES MAY BE ENERGIZED IN THE OPEN POSITION 2. THIS PHOTOVOLTAIC SYSTEM WILL BE EQUIPPED WITH A DC DISCONNECT WHICH WILL BE LABELED AS FOLLOWS: DC DISCONNECT SWITCH 3. THIS PHOTOVOLTAIC SYSTEM WILL BE EQUIPPED WITH AN AC DISCONNECT WHICH WILL BE LABELED AS FOLLOWS: PHOTOVOLTAIC AC DISCONNECT 4. A MARKING SPECIFYING THE PHOTOVOLTAIC POWER SOURCE RATED AS FOLLOWS SHALL BE PROVIDED AT AN ACCESSIBLE LOCATION AT THE DISCONNECTION MEANS FOR THE POWER SOURCE: OPERATING CURRENT (##) AMPS OPERATING VOLTAGE (##) VOLTS MAXIMUM SYSTEM VOLTAGE (##) VOLTS SHORT CIRCUIT CURRENT (##) AMPS NOTE:## VALUES TO BE PROVIDED BY CONTRACTOR PER ACTUAL INSTALLATION. 5. ALL MAJOR EQUIPMENT SHALL BE PROPERLY LABELED WITH ARC-FLASH HAZARD SIGNS AS REQUIRED BY NFPA 70E. CONDUIT 1. FLEXIBLE METAL CONDUIT IS GENERALLY SUITABLE FOR INSTALLATION IN DRY LOCATIONS. SHOULD IT BE EMPLOYED, SUPPORTS WILL BE NO MORE THAN 12 INCHES FROM BOXES (JUNCTION BOX, CABINETS OR CONDUIT FITTING) AND NO MORE THAN 54 INCHES APART. 2. LIQUID TIGHT FLEXIBLE NON-METALLIC CONDUIT SHALL NOT BE USED. 3. BURIED CONDUIT SHALL BE SCHD 40 GREY PVC BURIED AT LEAST 24" DEEP FOR CIRCUITS 1,000 VOLTS OR LESS. 4. BURIED CONDUIT SHALL BE SCHD 40 GREY PVC BURIED AT LEAST 48" DEEP FOR CIRCUITS OVER 1,000 VOLTS. 5. RIGID METAL CONDUIT OR SCHD 80 PVC TO BE USED FOR ABOVE GROUND CONDUIT IN AREAS SUBJECT TO VEHICLE DAMAGE. 6. LONG STRAIGHT METALLIC AND/OR PVC CONDUIT RUNS, 100 FEET OR MORE, SHALL HAVE EXPANSION FITTINGS. 7. CONDUIT RUNS WITH OVER 270 DEGREES IN BENDS SHALL HAVE A JUNCTION OR PULL BOX INSTALLED TO REDUCE NUMBER OF BENDS. 8. WIRING SHALL BE INSTALLED IN APPROVED METAL OR PVC CONDUITS OR RACEWAYS WITH LISTED FITTINGS, AS APPLICABLE, ADEQUATELY STRAP AND SUPPORT ALL CONDUIT WORK PER NEC. IN GENERAL SUPPORT ALL CONDUIT WITHIN THREE FEET (3') OF OUTLET BOX, CABINET OR PANEL AND MAXIMUM OF TEN FEET (10') ON CENTER THEREAFTER, EMT CONDUIT IS TO BE LISTED FOR WET LOCATION, IF USED. 9. THE PHOTOVOLTAIC SOURCE CIRCUITS AND PHOTOVOLTAIC OUTPUT CIRCUITS OF THIS PROPOSED SOLAR SYSTEM SHALL NOT BE CONTAINED IN THE SAME RACEWAY CABLE TRAY, CABLE, OUTLET BOX, JUNCTION BOX, OR SIMILAR FITTING AS FEEDERS OR BRANCH CIRCUITS OF OTHER SYSTEMS UNLESS THE CONDUCTORS OF THE DIFFERENT SYSTEMS ARE SEPARATED BY A PARTITION OR ARE CONNECTED TOGETHER. 10. PROVIDE 'PV SOURCE CIRCUIT' LABELS ON CONDUIT EVERY 10 FEET. MEDIUM VOLTAGE THE PRIMARY NEUTRAL OF THE UNDERGROUND SYSTEM IS FORMED BY CONNECTING THE PRIMARY CONCENTRIC NEUTRALS AT EACH TRANSFORMER LOCATION. THIS PRIMARY CONCENTRIC NEUTRAL SHALL BE CONNECTED TO THE OVERHEAD SYSTEM NEUTRAL AT EACH DIP POLE AND SHALL BE TREATED IN THE SAME MANNER AS THE OVERHEAD SYSTEM NEUTRAL. IDENTIFICATION PROCEDURES ONE OF THE MAJOR DIFFERENCES BETWEEN OVERHEAD AND UNDERGROUND DISTRIBUTION IS THAT THE SOURCE OF FEED FOR THE VARIOUS CABLES AND APPARATUS CANNOT BE VISIBLY TRACED IN THE UNDERGROUND SYSTEM. A COMPLETE IDENTIFICATION METHOD MUST BE USED FOR UNDERGROUND PROJECTS. IT MUST BE SIMPLE, PERMANENT, AND EASILY IDENTIFIABLE IN ORDER TO KNOW THE SOURCE, DIRECTION OF FEED, AND TERMINATION POINT OF THE UNDERGROUND CABLES. ALL TERMINAL POLES, PADS, TRANSFORMERS, PEDESTALS, PRIMARY PHASES, AND ANY OTHER APPARATUS SHALL BE NUMBERED OR LETTERED ON LAYOUT MAPS ON THE SYSTEM BY ENGINEERING BEFORE CONSTRUCTION IS STARTED. DURING CONSTRUCTION, ALL CABLE ENDS MUST BE TAGGED BEFORE TRENCHES ARE BACKFILLED. IF TEMPORARY TAGS ARE USED DURING CONSTRUCTION, PERMANENT TAGS MUST BE INSTALLED BEFORE THE SYSTEM IS ENERGIZED. THE LETTERS X, Y AND Z ARE USED TO IDENTIFY DIFFERENT UNDERGROUND CABLES. SYSTEM ARE SWAPPED. IN ADDITION TO CABLE IDENTIFICATION, EACH CABLE SHALL BE TAGGED AT EACH END PROTECTION AND COORDINATION LIGHTNING PROTECTION SHALL BE PROVIDED BY RISER POLE TYPE ARRESTERS INSTALLED ON EACH CABLE AT ALL TERMINAL POLES. PROTECTION AGAINST FAULT CURRENTS SHOULD BE PROVIDED BY A SECTIONALIZING FUSE ON ALL CABLE TERMINAL POLES AS SPECIFIED BY THE ENGINEER. CARE SHOULD BE TAKEN TO ENSURE THAT THE PROTECTIVE DEVICE ON THE TERMINAL POLE PROPERLY COORDINATES WITH THAT IN THE LARGEST TRANSFORMER IN THE LOOP, AS WELL AS THE NEXT OVERHEAD PROTECTIVE DEVICE TOWARD THE SUBSTATION. CABLES PRIMARY CABLES AND REELS ARE MARKED WITH THE SEQUENTIAL FOOTAGE TO FACILITATE MEASURING CABLE USED OR REMAINING ON REEL. STORAGE, INSTALLATION AND WHENEVER CABLE ENDS ARE LEFT EXPOSED. SEALS SHOULD NOT BE REMOVED CAUTION SHOULD BE USED IN THE HANDLING, STORAGE AND INSTALLATION OF THE CABLE TO PREVENT DAMAGE. CABLE SHALL BE INSPECTED AS IT IS INSTALLED, AND IN NO CASE SHALL DAMAGED CABLE BE INSTALLED. A MINIMUM BENDING RADIUS OF 12 TIMES THE CABLE OUTSIDE DIAMETER INCHES SHALL BE MAINTAINED ON ALL CABLE BENDS IN TRENCHES AND ON ALL CABLE LOOPS UP THROUGH TRANSFORMER PADS. TERMINATIONS AND CONNECTIONS IT IS EXTREMELY IMPORTANT THAT PRIMARY CABLES BE PROPERLY TERMINATED. TO ASSURE GOOD, TROUBLE-FREE OPERATION, INSTRUCTIONS FOR TERMINATIONS MUST BE CAREFULLY FOLLOWED. THESE CONNECT PRIMARY CABLES TO DEAD FRONT PAD-MOUNTED TRANSFORMERS WITH LOADBREAK ELBOWS THE CABLE FOR UNDERGROUND PRIMARY DISTRIBUTION IS ALUMINUM. TREE RETARDANT CROSSLINKED INSULATED WITH BARE CABLE CONCENTRIC NEUTRALS, AND AN OVERALL POLYETHYLENE JACKET. THE SECONDARY AND SERVICE LATERAL CABLE IS ALUMINUM, CROSS-LINKED POLYETHYLENE INSULATED. LARGER CABLES ARE LC SHIELD. ALL UNDERGROUND CABLES ARE SUITABLE FOR DIRECT BURIAL. SECONDARY CABLE CONNECTIONS AT LOW-PROFILE TRANSFORMERS SHALL BE INSTALLED USING ALUMINUM ARE DESIGNED FOR USE ON SINGLE-PHASE LOW PROFILE PAD-MOUNTED TRANSFORMERS AND ARE NOT FOR USE ON SPADE TYPE OR THREE-PHASE PAD-MOUNTED TRANSFORMERS. SECONDARY CABLE CONNECTIONS IN THREE-PHASE PAD-MOUNTED TRANSFORMERS SHOULD BE MADE PER DWG. 27.06-12. ELECTRICAL TAPE AS SHOWN ON DWG. 23.02-01 TO PREVENT MOISTURE FROM ENTERING CABLES DURING SEE DWGS. 23.02-02A, 23.02-02B, 23.02-02C AND 23.02-02D FOR CABLE HANDLING AND STORAGE PROCEDURES. ACCORDING TO DWGS. 26.04-02A AND 26.04-02B. SET SCREW CONNECTORS AS SHOWN ON DWG. 27.05-06. THESE SET SCREW CONNECTORS ARE DESIGNED FOR UNTIL READY TO MAKE TERMINATIONS. PROPER CABLE TERMINATIONS AND SPLICES ARE SHOWN IN SECTION 26. GROUNDING DRIVEN GROUND RODS SHALL BE PROVIDED AT EACH CABLE TERMINAL POLE AND AT EACH TRANSFORMER, GROUND LEADS FROM THE DRIVEN GROUNDS SHALL BE SOLIDLY CONNECTED TO THE PRIMARY NEUTRAL, THE SECONDARY NEUTRAL, AND TO THE GROUNDING CONNECTION OF ALL EQUIPMENT AT THE LOCATION. GROUNDING ELECTRODES FOR DISTRIBUTION LINES THE UNDERGROUND DISTRIBUTION LINE DESIGN STANDARD IN THE CAROLINAS AND FLORIDA IS CONSIDERED TO BE A MULTI-GROUNDED SYSTEM PER THE NESC. THE UNDERGROUND SYSTEM NEUTRAL (THE CONCENTRIC NEUTRAL ON THE #1/0 PRIMARY CABLE, THE LC SHIELD ON THE LARGER BULK FEEDER CABLES, AND THE NEUTRAL CABLE OF 600 VOLT SECONDARY AND SERVICE CABLE) MUST HAVE A MINIMUM OF 4 GROUNDS PER MILE OF CABLE. EQUIPMENT GROUNDING/BONDING WHERE EQUIPMENT GROUNDING IS REQUIRED, ALL EQUIPMENT TANKS, HANGERS, AND OTHER HARDWARE MUST BE SOLIDLY BONDED TOGETHER AND THEN CONNECTED TO THE SYSTEM NEUTRAL. EQUIPMENT PROTECTED BY A FUSE (i.e. OH TRANSFORMERS, OH CAPACITOR BANKS) WILL REQUIRE A #6 SD BC GROUND WIRE, CONNECTED TO THE SYSTEM NEUTRAL. THE GROUND WIRE DOWN THE POLE IS ALL #6 SD BC, CONNECTED TO THE SYSTEM NEUTRAL AND THE GROUND RODS. ALL PAD-MOUNTED TRANSFORMERS AND UNDERGROUND PRIMARY ENCLOSURES, SINGLE AND THREE-PHASE, REQUIRE A #4 SD BC LOOPED GROUND TO MATCH THE NEUTRAL OF #1/0 UG PRIMARY CABLE. EQUIPMENT THAT WILL BE SUBJECT TO OPERATING ON THE SUBSTATION BREAKER (i.e. REGULATORS, PAD-MOUNTED SWITCHGEAR, PAD-MOUNTED CAPACITORS, PRIMARY METERING ENCLOSURES, RECLOSERS, ETC.) WILL REQUIRE #2 SD BC GROUND. (THE GROUND WIRE DOWN THE POLE TO THE GROUND RODS IS #6 SD BC.) BULK FEEDER (TERMINAL) POLES REQUIRE THE GROUND BRAID STRAPS (PROVIDED IN THE TERMINATOR KIT) BE RUN TO THE SYSTEM NEUTRAL AND CONNECTED. (THE GROUND WIRE DOWN THE POLE TO THE GROUND GROUND RODS IS #6 SD BC.) DESCRIPTION PHASE/CODE LETTER WIRE COLOR 12KV, 3Ø PHASE A BLACK PHASE B RED PHASE C BLUE 480V, 3Ø PHASE A BROWN PHASE B ORANGE PHASE C YELLOW 240V OR 208V, 3Ø PHASE A BLACK PHASE B RED (ORG. IF HI LEG) PHASE C BLUE 240/120 1Ø L1 BLACK L2 RED AC NEUTRAL N WHITE DC GROUNDED PV SYSTEMS VDC POS +BLACK VDC NEG -WHITE GROUND N GREEN DC UNGROUNDED PV SYSTEMS VDC POS +RED VDC NEG -BLACK GROUND N GREEN EQUIPMENT 1. EQUIPMENT AND COMPONENTS SHALL BE UL LISTED AND LABELED. 2. PROVIDE DANGER, WARNING, AND CAUTION LABELS AS REQUIRED BY NEC, NFPA, OR OSHA STANDARDS ON EQUIPMENT ENCLOSURES, DOORS, ACCESS PLATES, AND BARRIERS AND LABEL ALL LOW VOLTAGE EQUIPMENT WITH THE OPERATING VOLTAGE. 3. EQUIPMENT SHALL BE ANCHORED TO CONCRETE PADS, FOUNDATIONS, OR WALLS PER MANUFACTURER'S INSTRUCTIONS, IF REQUIRED. 4. EQUIPMENT SHALL BE INSTALLED IN APPROPRIATE ENVIRONMENT PER ITS NEMA RATING. MARKINGS 1. ALL INTERACTIVE SYSTEM POINTS OF INTERCONNECTION WITH OTHER SOURCES SHALL BE MARKED AT AN ACCESSIBLE LOCATION AT THE DISCONNECTION MEANS. 2. A PERMANENT PLAQUE OR DIRECTORY SHALL BE PROVIDED IDENTIFYING THE LOCATION OF THE SERVICE DISCONNECTION MEANS AND THE PHOTOVOLTAIC SYSTEM DISCONNECTION MEANS, IF NOT LOCATED AT THE SAME LOCATION. 3. PHOTOVOLTAIC MODULES SHALL BE MARKED TO IDENTIFY LEAD POLARITY, DEVICE RATINGS, AND SPECIFICATIONS FOR VOLTAGES, CURRENTS, AND POWER. GENERAL SYMBOLS SYMBOL DESCRIPTION SECTION ELEVATION DETAIL PG. NUMBER EQUIPMENT CALLOUT SEE NOTE ON SAME SHEET X XXX X XXX XXX X ELECTRICAL SYMBOLS SYMBOL DESCRIPTION CONTINUED ON SAME DWG, X - CONTINUATION REFERENCE NON-FUSED DISCONNECT UTILITY GRADE METER FUSED CUTOUT GROUND BURIED CONDUIT OR DUCT BANK UNDERGROUND PRIMARY CT SOLAR MODULE GROUND FAULT PROTECTION CONDUIT NUMBER SEE AC WIRE AND CONDUIT SPECIFICATION TABLE BREAKER INSTALL POLE EXISTING POLE GFP X M ABBREVIATIONS A or AMP AMPERE KW KILOWATT AC ALTERNATING CURRENT LIGHTNING ARRESTERS AL ALUMINUM NEU NEUTRAL CU COPPER NTS NOT TO SCALE DC DIRECT CURRENT P POLE DISC DISCONNECT PH PHASE EMT ELECTRIC METALLIC TUBING PV PHOTOVOLTAIC GND GROUND PVC POLYVINYL-CHLORIDE Hz HERTZ SWBD SWITCHBOARD INV INVERTER TYP TYPICAL Isc CURRENT, SHORT CIRCUIT W WATT KVA KILOVOLT-AMPERE XXX X XXX T.JONES01/15/20180ISSUED FOR PERMITD.BRUECK"THIS DOCUMENT CONTAINS INTELLECTUAL, DESIGN, OR COPY WRITE PROPERTY OF SOUTHERN CURRENT LLC WHICH IS PRIVILEGED OR CONFIDENTIAL AND IS NOT TO BE REPRODUCED, DISCLOSED, USED IN ANY MANNER OR DISTRIBUTED WITHOUT WRITTEN PERMISSION OF SOUTHERN CURRENT LLC" "THIS DOCUMENT CONTAINS INTELLECTUAL, DESIGN, OR COPY WRITE PROPERTY OF SOUTHERN CURRENT LLC WHICH IS PRIVILEGED OR CONFIDENTIAL AND IS NOT TO BE REPRODUCED, DISCLOSED, USED IN ANY MANNER OR DISTRIBUTED WITHOUT WRITTEN PERMISSION OF SOUTHERN CURRENT LLC" REVISION DESCRIPTIONAPRV'DNODATEBYFLOWERS SOLAR3188 BAILEYS CROSSROADS ROADBENSON, NC 275124.34 MW AC - SOLAR PV SYSTEMGENERAL NOTES1519 King St. Charleston, S.C. 29405 T.JONES01/18/20181ISSUED FOR CONSTRUCTIOND.BRUECK BAILEYS CROSSROADS RD PM PM RCL S E N W N SCALE T.JONES01/15/20180ISSUED FOR PERMITD.BRUECK"THIS DOCUMENT CONTAINS INTELLECTUAL, DESIGN, OR COPY WRITE PROPERTY OF SOUTHERN CURRENT LLC WHICH IS PRIVILEGED OR CONFIDENTIAL AND IS NOT TO BE REPRODUCED, DISCLOSED, USED IN ANY MANNER OR DISTRIBUTED WITHOUT WRITTEN PERMISSION OF SOUTHERN CURRENT LLC" "THIS DOCUMENT CONTAINS INTELLECTUAL, DESIGN, OR COPY WRITE PROPERTY OF SOUTHERN CURRENT LLC WHICH IS PRIVILEGED OR CONFIDENTIAL AND IS NOT TO BE REPRODUCED, DISCLOSED, USED IN ANY MANNER OR DISTRIBUTED WITHOUT WRITTEN PERMISSION OF SOUTHERN CURRENT LLC" REVISION DESCRIPTIONAPRV'DNODATEBYFLOWERS SOLAR3188 BAILEYS CROSSROADS ROADBENSON, NC 275124.34 MW AC - SOLAR PV SYSTEMTOTAL PV SYSTEM OVERVIEWDUKE ENERGY PROGRESS 3Ø 22.86kV DISTRIBUTION LINE (18,354) 320W SOLAR PANELS MOUNTED ON RACKING SYSTEM IN THIS AREA PERMANENT SITE ACCESS PATH MIN. 20' FENCE SETBACK NEC REQUIRED SECURITY FENCE (EST. 6,000 LINEAR-FT) (2) 630 kW INVERTERS & (1) 1,240 kVA PAD MOUNTED TRANSFORMER (TYP. 3) 15'x30' PARKING AREA INTERCONNECTION POINT DUKE ENERGY PROGRESS TO INSTALL 3Ø OH TAP OFF POLE (2) x CUSTOMER 3Ø DIP ON POLE TO FEED SOLAR FARM PAD MOUNTED TRANSFORMERS CUSTOMER POLE MOUNTED MANUAL GANG OPERATED SWITCH DUKE ENERGY PROGRESS BLADE SWITCH & POLE MOUNTED RECLOSER (REF. FIG 71B) DUKE ENERGY PROGRESS POLE MOUNTED PRIMARY METER CUSTOMER POLE MOUNTED PRIMARY METER PERMANENT GATE ACCESS 15'x30' PARKING AREA CUSTOMER POLE MOUNTED 10kVA TRANSFORMERS 1519 King St. Charleston, S.C. 29405 PERMANENT GATE ACCESS 30' VEGETATED BUFFER OPEN TRENCH (1) x 5" SCHD 40 PVC & (1) x 2" SCHD 40 PVC CONDUIT AT LEAST 48" DEEP (675') OPEN TRENCH (1) x 5" SCHD 40 PVC & (1) x 2" SCHD 40 PVC CONDUIT AT LEAST 48" DEEP (600') OPEN TRENCH (1) x 5" SCHD 40 PVC & (1) x 2" SCHD 40 PVC CONDUIT AT LEAST 48" DEEP (250') OPEN TRENCH (1) x 5" SCHD 40 PVC & (1) x 2" SCHD 40 PVC CONDUIT AT LEAST 48" DEEP (230')T.JONES01/18/20181ISSUED FOR CONSTRUCTIOND.BRUECK BAILEYS CROSSROADS RD CB-30 CB-29 CB-28 CB-27 CB-26 CB-25 CB-24 CB-23 CB-22 CB-21 CB-20 CB-19 CB-42 CB-41 CB-40 CB-39 CB-38 CB-37 CB-35 CB-34 CB-33 CB-32 CB-31 CB-07 CB-08 CB-17 CB-15 CB-12 CB-11 CB-10 CB-09 CB-01 CB-02 CB-03 CB-04 CB-06 CB-05 CB-14 CB-13CB-16 CB-18 TX-2 TX-3 TX-1 TX-4 INV-2 INV-3 INV-1 INV-8 INV-7 INV-5INV-4 CB-36 PM PM RCL S E N W N SCALE T.JONES01/15/20180ISSUED FOR PERMITD.BRUECK"THIS DOCUMENT CONTAINS INTELLECTUAL, DESIGN, OR COPY WRITE PROPERTY OF SOUTHERN CURRENT LLC WHICH IS PRIVILEGED OR CONFIDENTIAL AND IS NOT TO BE REPRODUCED, DISCLOSED, USED IN ANY MANNER OR DISTRIBUTED WITHOUT WRITTEN PERMISSION OF SOUTHERN CURRENT LLC" "THIS DOCUMENT CONTAINS INTELLECTUAL, DESIGN, OR COPY WRITE PROPERTY OF SOUTHERN CURRENT LLC WHICH IS PRIVILEGED OR CONFIDENTIAL AND IS NOT TO BE REPRODUCED, DISCLOSED, USED IN ANY MANNER OR DISTRIBUTED WITHOUT WRITTEN PERMISSION OF SOUTHERN CURRENT LLC" REVISION DESCRIPTIONAPRV'DNODATEBYFLOWERS SOLAR3188 BAILEYS CROSSROADS ROADBENSON, NC 275124.34 MW AC - SOLAR PV SYSTEMTRENCH PLAN4 005 2 005 4 006 KEY CB - ##COMBINER BOX INV - ##INVERTER TX - ##TRANSFORMER COMBINER BOX TO INVERTER TRENCHING MEDIUM VOLTAGE TRENCHING 1519 King St. Charleston, S.C. 29405 3 005 NOTE: 1. CONDUIT INSTALLED UNDER ROAD SHALL BE TO A DEPTH OF 24" FROM FINAL GRADE TO TOP OF ALL CONDUIT EXCEPT MEDIUM VOLTAGE. MEDIUM VOLTAGE CONDUIT SHALL BE INSTALLED TO A MINIMUM DEPTH OF 48" FROM FINAL GRADE TO TOP OF CONDUIT. CONDUIT SHALL EXTEND 5 FEET ON EITHER SIDE OF ROAD. MARK EACH END WITH A SMALL PIECE OF CONDUIT STUBBED UP. 2. MAINTAIN A 2' MINIMUM CLEARANCE BETWEEN TRENCHES AND RACKING POSTS DURING CONSTRUCTION.T.JONES01/18/20181ISSUED FOR CONSTRUCTIOND.BRUECK 24" TO TOP OF CONDUIT 3" MIN. 6" BACKFILL WITH CLEAN FILL AND/OR SOIL ON SITE CONTAINING NO ROCKS LARGER THAN 3/4" AND FREE FROM SHARP ANGULAR SUBSTANCES UNDISTURBED NATIVE SOIL 2-1/2" PVC SCH 40 CONDUIT 6" WIDE ALUMINUM DETECTABLE UNDERGROUND WARNING TAPE, 12" BELOW FINISHED GRADE FINISHED GRADE 33" TO BOTTOM OF TRENCH 48" TO TOP OF CONDUIT 12" 3" MIN. 12" MIN 6" BACKFILL WITH CLEAN FILL AND/OR SOIL ON SITE CONTAINING NO ROCKS LARGER THAN 3/4" AND FREE FROM SHARP ANGULAR SUBSTANCES FINISHED GRADE 6" WIDE ALUMINUM DETECTABLE UNDERGROUND WARNING TAPE, 12" BELOW FINISHED GRADE 5" PVC SCH 40 CONDUIT 59" TO BOTTOM OF TRENCH 2" SCHD 40 PVC CONDUIT FOR FIBER COMMUNICATION WIRE 24" TO TOP OF COMMUNICATION CONDUIT 24" TO TOP OF CONDUIT 12" UNDISTURBED NATIVE SOIL FINISHED GRADE (2) 6" WIDE ALUMINUM DETECTABLE UNDERGROUND WARNING TAPE, 12" BELOW FINISHED GRADE 7.5" 6" (5) 3-1/2" PVC SCH 40 CONDUIT 25" MIN. 3" MIN. BACKFILL WITH CLEAN FILL AND/OR SOIL ON SITE CONTAINING NO ROCKS LARGER THAN 3/4" AND FREE FROM SHARP ANGULAR SUBSTANCES 36" TO BOTTOM OF TRENCH 6" BACKFILL WITH CLEAN FILL AND/OR SOIL ON SITE CONTAINING NO ROCKS LARGER THAN 3/4" AND FREE FROM SHARP ANGULAR SUBSTANCES 8" 24" TO TOP OF CONDUIT 12" (2) 6" WIDE ALUMINUM DETECTABLE UNDERGROUND WARNING TAPE, 12" BELOW FINISHED GRADE 3" MIN. 42" TO BOTTOM OF TRENCH 8" 4" PVC SCH 40 CONDUIT MIN. 25" WIDE T.JONES01/15/20180ISSUED FOR PERMITD.BRUECK"THIS DOCUMENT CONTAINS INTELLECTUAL, DESIGN, OR COPY WRITE PROPERTY OF SOUTHERN CURRENT LLC WHICH IS PRIVILEGED OR CONFIDENTIAL AND IS NOT TO BE REPRODUCED, DISCLOSED, USED IN ANY MANNER OR DISTRIBUTED WITHOUT WRITTEN PERMISSION OF SOUTHERN CURRENT LLC" "THIS DOCUMENT CONTAINS INTELLECTUAL, DESIGN, OR COPY WRITE PROPERTY OF SOUTHERN CURRENT LLC WHICH IS PRIVILEGED OR CONFIDENTIAL AND IS NOT TO BE REPRODUCED, DISCLOSED, USED IN ANY MANNER OR DISTRIBUTED WITHOUT WRITTEN PERMISSION OF SOUTHERN CURRENT LLC" REVISION DESCRIPTIONAPRV'DNODATEBYFLOWERS SOLAR3188 BAILEYS CROSSROADS ROADBENSON, NC 275124.34 MW AC - SOLAR PV SYSTEMTRENCH DETAILSROW-TO-ROW JUMPER DETAIL SCALE: NTS AC CONDUIT TRENCHING DETAIL SCALE: NTS DC CONDUIT TRENCHING DETAIL SCALE: NTS MEDIUM VOLTAGE TRENCHING DETAIL SCALE: NTS UNDISTURBED NATIVE SOIL 1519 King St. Charleston, S.C. 29405 BACKFILL MATERIAL SHOULD BE COMPACTED TO NOT LESS THAT 95% OF THE STANDARD PROCTOR MAXIMUM DRY DENSITY AT MOISTURE CONTENT IN THE RANGE OF +/- 2% OF OPTIMUM. FILL MATERIAL SHOULD BE COMPACTED IN MAXIMUM LIFTS OF 8” LOOSE LIFTS AND THEN BE COMPACTED UNTIL ACHIEVING THE REQUIRED DENSITY.T.JONES01/18/20181ISSUED FOR CONSTRUCTIOND.BRUECK BAILEYS CROSSROADS RD 09/23/4 01/01/1 02/01/1 03/01/1 04/01/1 05/01/1 06/01/1 10/01/109/01/108/01/107/01/1 11/01/1 12/01/1 01/02/1 02/02/1 03/02/1 08/02/107/02/106/02/105/02/104/02/1 09/02/1 10/02/1 11/02/1 12/02/1 01/03/1 02/03/1 05/03/104/03/103/03/110/14/309/14/308/14/307/14/3 03/14/3 04/14/3 05/14/3 06/14/3 06/03/1 07/03/1 08/03/1 09/03/1 01/04/1 02/04/1 01/09/2 02/09/2 03/09/2 04/09/2 05/09/2 10/08/209/08/208/08/207/08/206/08/205/08/2 11/07/2 01/08/2 02/08/2 04/08/2 10/07/209/07/208/07/207/07/2 03/07/2 04/07/2 05/07/2 06/07/2 02/07/201/07/2 11/08/2 06/09/2 07/09/2 08/09/2 09/09/2 10/09/2 11/09/2 06/10/205/10/204/10/203/10/202/10/201/10/2 08/10/2 09/10/2 10/10/2 11/10/2 12/10/2 06/11/205/11/204/11/203/11/2 07/10/2 01/11/2 02/11/2 07/12/206/12/205/12/204/12/201/12/2 02/12/2 03/12/2 11/14/301/15/312/12/211/12/208/12/2 09/12/2 10/12/2 12/11/211/11/210/11/209/11/207/11/2 08/11/2 01/16/309/15/3 10/15/3 11/15/3 06/06/1 03/17/312/16/3 01/17/3 02/17/3 11/17/308/17/3 09/17/3 10/17/3 07/16/305/16/3 06/16/3 04/15/302/15/3 03/15/3 04/18/3 05/18/3 10/13/3 11/13/3 01/14/3 02/14/3 10/03/1 11/03/1 12/03/1 06/13/3 07/13/3 08/13/3 09/13/3 03/04/1 04/04/1 05/04/1 06/04/1 07/04/1 08/04/1 03/05/102/05/101/05/111/04/110/04/109/04/105/13/304/13/303/13/302/13/301/13/3 04/05/1 05/05/1 06/05/1 07/05/1 08/05/1 09/05/1 10/05/1 05/06/104/06/103/06/102/06/101/06/111/05/1 07/06/1 08/06/1 09/06/1 11/06/110/06/1 08/15/307/15/306/15/305/15/3 02/16/3 03/16/3 04/16/3 08/16/3 09/16/3 10/16/3 11/16/3 04/17/3 05/17/3 06/17/3 07/17/3 12/17/3 01/18/3 02/18/3 03/18/3 08/18/3 12/18/3 09/18/3 10/18/3 11/18/307/18/306/18/3 08/19/407/19/4 06/20/405/20/4 03/21/4 04/20/4 02/21/4 06/19/4 03/20/4 01/21/4 10/21/409/21/4 02/20/4 11/20/4 05/19/404/19/403/19/402/19/401/19/4 01/20/411/19/410/19/409/19/4 10/20/409/20/408/20/407/20/4 08/21/407/21/406/21/405/21/4 06/22/405/22/404/22/403/22/4 08/22/407/22/4 11/21/4 01/22/4 02/22/4 04/21/4 11/22/410/22/409/22/4 03/23/402/23/401/23/412/22/4 05/23/404/23/4 07/23/406/23/4 10/23/4 11/23/4 12/23/4 01/24/4 02/24/4 03/24/4 04/24/4 05/24/4 06/24/4 07/24/4 08/24/4 10/24/4 11/24/4 04/25/5 05/25/5 06/25/5 07/25/5 08/25/5 09/25/5 10/25/5 11/25/5 12/25/5 01/26/5 02/26/5 03/26/5 04/26/5 05/26/5 06/26/5 07/26/5 08/26/5 09/26/5 03/27/502/27/501/27/5 12/26/511/26/510/26/5 04/27/5 05/27/5 06/27/5 07/27/5 08/27/5 09/27/5 02/28/501/28/512/27/5 11/27/510/27/5 03/28/5 04/28/5 05/28/5 06/28/5 09/28/5 08/28/507/28/5 08/30/5 09/30/5 10/30/5 10/29/509/29/508/29/5 11/29/5 11/30/5 01/30/5 02/30/5 03/30/5 04/30/5 04/29/503/29/502/29/501/29/511/28/510/28/5 04/31/6 05/31/6 06/31/6 07/31/6 08/31/6 09/31/6 10/31/6 11/31/6 01/32/6 02/32/6 03/31/602/31/601/31/6 02/33/601/33/611/32/6 10/32/609/32/608/32/607/32/606/32/605/32/604/32/603/32/6 03/33/6 04/33/6 05/33/6 06/33/6 07/33/6 08/33/6 09/33/6 10/33/6 11/33/6 01/34/6 02/34/6 01/35/612/34/611/34/6 10/34/609/34/608/34/607/34/606/34/605/34/604/34/603/34/6 04/35/6 05/35/6 06/35/6 02/36/601/36/612/35/6 03/36/6 07/35/6 08/35/6 04/36/6 05/36/6 09/35/6 06/36/6 07/36/610/35/6 02/35/6 12/36/610/36/6 03/35/6 11/35/6 08/36/6 11/36/6 08/37/707/37/706/37/7 05/37/704/37/703/37/702/37/701/37/7 09/37/7 10/37/7 11/37/7 12/37/7 01/38/7 02/38/7 03/38/7 04/38/7 05/38/7 06/38/7 04/39/703/39/702/39/7 01/39/712/38/711/38/710/38/709/38/708/38/707/38/7 05/39/7 06/39/7 07/39/7 08/39/7 09/39/7 10/39/7 11/39/7 12/39/7 01/40/7 09/40/708/40/707/40/7 06/40/705/40/704/40/7 01/41/7 02/41/711/40/7 03/40/7 10/40/7 02/40/7 06/41/7 07/41/7 10/41/7 11/41/7 08/41/7 09/41/7 03/41/7 01/42/7 04/42/703/42/7 04/41/7 05/41/7 02/42/7 05/42/7 08/42/707/42/7 06/42/7 09/42/7 10/42/7 03/08/2 09/36/6 11/42/7 05/30/5 06/30/5 07/30/5 12/24/4 01/25/5 CB-30 02/25/5 03/25/5 CB-29 CB-28 CB-27 CB-26 CB-25 CB-24 CB-23 CB-22 CB-21 CB-20 CB-19 CB-42 CB-41 CB-40 CB-39 CB-38 CB-37 CB-35 CB-34 CB-33 CB-32 CB-31 CB-07 CB-08 CB-17 CB-15 CB-12 CB-11 CB-10 CB-09 CB-01 CB-02 CB-03 CB-04 CB-06 CB-05 CB-14 CB-13CB-16 CB-18 08/23/4 09/24/4 05/29/5 06/29/5 07/29/5 TX-2 TX-3 TX-1 TX-4 INV-2 INV-3 INV-1 INV-8 INV-7 INV-5INV-4 CB-36 SCALE ROW TO ROW JUMPER T.JONES01/15/20180ISSUED FOR PERMITJ.WILSON"THIS DOCUMENT CONTAINS INTELLECTUAL, DESIGN, OR COPY WRITE PROPERTY OF SOUTHERN CURRENT LLC WHICH IS PRIVILEGED OR CONFIDENTIAL AND IS NOT TO BE REPRODUCED, DISCLOSED, USED IN ANY MANNER OR DISTRIBUTED WITHOUT WRITTEN PERMISSION OF SOUTHERN CURRENT LLC" "THIS DOCUMENT CONTAINS INTELLECTUAL, DESIGN, OR COPY WRITE PROPERTY OF SOUTHERN CURRENT LLC WHICH IS PRIVILEGED OR CONFIDENTIAL AND IS NOT TO BE REPRODUCED, DISCLOSED, USED IN ANY MANNER OR DISTRIBUTED WITHOUT WRITTEN PERMISSION OF SOUTHERN CURRENT LLC" REVISION DESCRIPTIONAPRV'DNODATEBYFLOWERS SOLAR3188 BAILEYS CROSSROADS ROADBENSON, NC 275124.34 MW AC - SOLAR PV SYSTEMDC CIRCUIT PLAN1519 King St. Charleston, S.C. 29405 1 005 CIRCUIT # CIRCUITING PATH TWO STRINGS COMBINED WITH Y-HARNESS COMBINER BOX # INVERTER # 06/29/5 (1) x 2" SCHD 40 GRAY PVC CONDUIT INSTALLED UNDER ROAD INSTALLED UNDER ROAD TO A DEPTH OF 24" FROM FINAL GRADE TO TOP OF CONDUIT. CONDUIT SHALL EXTEND 5 FEET ON EITHER SIDE OF ROAD. MARK EACH END WITH A SMALL PIECE OF CONDUIT STUBBED UP. (2) x 2" JUMPERS ARE NEEDED AT THIS LOCATION (2) x 2" JUMPERS ARE NEEDED AT THIS LOCATION (2) x 2" JUMPERS ARE NEEDED AT THIS LOCATION (2) x 2" JUMPERS ARE NEEDED AT THIS LOCATION T.JONES01/15/20180ISSUED FOR CONSTRUCTIOND.BRUECK #8 PV WIRE STAINLESS STEEL ZIP TIE *NOTE: ACTUAL CABLE QUANTITY TO VARY BASED ON LOCATION IN THE ARRAY #6 BARE STRANDED OR EQUIVALENT TIN PLATED BRAID (12" IN LENGTH) GROUND STRAP BONDED WITH COMPRESSION LUG, FLAT WASHER, NUT AND BOLT ON PURLIN HORIZONTAL PURLIN (TYP) PV WIRE IN SPLIT LOOM BETWEEN TABLES. COMBINER BOX HOME RUNS CONDUCTORS FROM OTHER RACKS GROUNDING JUMPER TO NEXT RACK SECTION (IF REQUIRED) PURLIN ZIP TIE (TYP.) SUPPLY CLIPS AS NEEDED TO SUPPORT WIRE BUNDLES NEGATIVE TERMINAL POSITIVE TERMINAL NEGATIVE HOME RUN CONDUCTOR (TYP.) POSITIVE HOME RUN CONDUCTOR (TYP.) WIRE MANAGEMENT DETAIL SCALE: N/A WIRE MANAGEMENT BETWEEN RACKS SCALE: N/A MODULE WIRE MANAGEMENT PLAN (EACH 19 MODULE STRING, TYP) SCALE: N/A LEAPFROG DETAIL FOR STRING OF 19 MODULES SCALE: N/A BEGINNING AND END OF LEAPFROG TECHNIQUE SCALE: N/A T.JONES01/15/20180ISSUED FOR PERMITD.BRUECK"THIS DOCUMENT CONTAINS INTELLECTUAL, DESIGN, OR COPY WRITE PROPERTY OF SOUTHERN CURRENT LLC WHICH IS PRIVILEGED OR CONFIDENTIAL AND IS NOT TO BE REPRODUCED, DISCLOSED, USED IN ANY MANNER OR DISTRIBUTED WITHOUT WRITTEN PERMISSION OF SOUTHERN CURRENT LLC" "THIS DOCUMENT CONTAINS INTELLECTUAL, DESIGN, OR COPY WRITE PROPERTY OF SOUTHERN CURRENT LLC WHICH IS PRIVILEGED OR CONFIDENTIAL AND IS NOT TO BE REPRODUCED, DISCLOSED, USED IN ANY MANNER OR DISTRIBUTED WITHOUT WRITTEN PERMISSION OF SOUTHERN CURRENT LLC" REVISION DESCRIPTIONAPRV'DNODATEBYFLOWERS SOLAR3188 BAILEYS CROSSROADS ROADBENSON, NC 275124.34 MW AC - SOLAR PV SYSTEMWIRING MANAGEMENT DETAILS1519 King St. Charleston, S.C. 29405 T.JONES01/18/20181ISSUED FOR CONSTRUCTIOND.BRUECK TOTAL AUXILIARY POWER: 60 kVA MIN LOAD ON POD CT/PT: 1.52A @ 22.86kV SOLAR PV SYSTEM OVERVIEW Module Name:320W (#) of Modules:18,354 (#) Modules in Series:19 (#) of Strings:966 Inverter Name:Schneider Electric XC630-NA (#) of Inverters:7 System Size (DC):5.87 MW System Size (AC):4.41 MVA AC size limited to:4.34 MW EQUIPMENT SCHEDULE ID ITEM QTY DESCRIPTION A CUSTOMER METER 1 PRIMARY METER, POLE MOUNTED. B GANG SWITCH 2 25KV, 3Ø MANUAL GANG OPERATE POLE MOUNTED SWITCH. C POLE MOUNTED TRANSFORMER 1 10KVA POLE MOUNTED TRANSFORMER W/ 1 LIGHTNING ARRESTOR AND 1 FUSED CUTOUT AT 1.25A D DIP FUSES 3 25kV, 100A CLASS CUTOUTS WITH TYPE K 80A FUSES. E DIP FUSES 3 25kV, 100A CLASS CUTOUTS WITH TYPE K 60A FUSES. F LIGHTENING ARRESTERS 6 18kV LIGHTENING ARRESTORS G PAD MOUNT TRANSFORMER 3 LIQUID-FILLED PAD MOUNT 3-PH (350V : 22.86 KV) RADIAL-FED TRANSFORMER NAMEPLATE RATED FOR 1,240 KVA. NOMINAL IMPEDANCE 5.75%Z. LOAD BREAK SWITCHES ON PRIMARY FEEDS. 40A BAYONET FUSES TO PROTECT TRANSFORMER. MINERAL OIL IMMERSED CURRENT LIMITING FUSES. 2 +/- 2.5% TAPS. H PAD MOUNT TRANSFORMER 1 LIQUID-FILLED PAD MOUNT 3-PH (350V : 22.86 KV) RADIAL-FED TRANSFORMER NAMEPLATE RATED FOR 620 KVA. NOMINAL IMPEDANCE 5.75%Z. LOAD BREAK SWITCHES ON PRIMARY FEEDS. 20A BAYONET FUSES TO PROTECT TRANSFORMER. MINERAL OIL IMMERSED CURRENT LIMITING FUSES. 2 +/- 2.5% TAPS. I INVERTERS 7 SOLAR INVERTER NAMEPLATE RATED FOR 630 KVA. STANDARD w/ INTEGRATED FUSED DC SUBCOMBINER, DC DISCONNECT, AC BREAKER/DISCONNECT, GFDI, ANTI-ISLANDING PROTECTION, AND SURGE PROTECTION. MONITORING AND NETWORKING VIA MODBUS COMMUNICATIONS AND USER-INTERACTIVE LCD. FUSED DC SUBCOMBINER w/ (6) x 350 AMP FUSES. NEMA 3R POLYESTER POWDER COATED STEEL ENCLOSURE. J DISCONNECT ENCLOSURE 7 DISCONNECT SWITCH BOX RATED FOR 1000 VDC. (6) X 350 AMP LOAD BREAK DISCONNECT SWITCHES w/ EXTERNAL HANDLES . NEMA 3R ENCLOSURE. K COMBINER BOX 42 COMBINER BOX - NEMA 3R, 24 INPUTS, 30A FUSES, 350A INTEGRAL DISCONNECT SWITCH, SURGE PROTECTION, 1000V L POSITIVE "Y" HARNESS 483 SUNNECTOR (2) PARALLEL CIRCUIT MALE HARNESS ASSEMBLIES #10 TO #8CU W/ (2) 15A IN-LINE FUSES (#8 - 35A CAPACITY). M NEGATIVE "Y" HARNESS 483 SUNNECTOR (2) PARALLEL CIRCUIT FEMALE HARNESS ASSEMBLIES #10 TO #8CU (#8 - 35A CAPACITY). N MODULES 18354 320W POLY CRYSTALLINE (72) CELL SOLAR MODULE RATED FOR 1500 VDC. TEMPERED GLASS AND CLEAR ANODIZED ALUMINUM FRAME. IP 67 RATED JUNCTION BOX w/ (3) BYPASS DIODES. FACTORY STANDARD 12 AWG 'PV' WIRE LEADS w/ MC4 CONNECTORS. O TRANSFORMER/ PANEL 4 MINI POWER ZONE RATED AT 15 KVA W/ 350V PRIMARY AND 120/240V SECONDARY. SINGLE PHASE 60 AMP/2 POLE MAIN BREAKER RATED FOR 18 KAIR AND (2) X 15A/1P BRANCH CIRCUIT BREAKERS. NEMA 3R ENCLOSURE. BAYONET FUSES 1,240 KVA LOOP FED (350V : 22.86 KV) G UTILITY PRIMARY FEED 22.86kV *INTERCONNECTION* CONNECTION MADE ON EXISTING UTILITY WITH A 3Ø TAP UTILITY's INFRASTRUCTURE OWNER's INFRASTRUCTURE POINT OF DELIVERYTOTAL GENERATION CAPACITY: 4,340 kW 109A @ 22.86kV POINT OF INTERCONNECTIONSEL-651RR E C L O S E R(3)xP.T.'s(3)xP.T.'sGND 1600A/3P SCHNEIDER ELECTRICCONEXT CORE XC 630-NA 6 CIRCUIT350A, 1000VNEMA 3R GND 350A 350A 350A 350A 350A 350A 1000 VDC 350VACA 1 1 A 2 A 2 A A 1 A 2 GND 1600A/3P SCHNEIDER ELECTRICCONEXT CORE XC 630-NA 6 CIRCUIT350A, 1000VNEMA 3R GND 350A 350A 350A 350A 350A 350A 1000VDC 350 VAC BAYONET FUSES BAYONET FUSES GND 1600A/3P SCHNEIDER ELECTRIC CONEXT CORE XC 630-NA 6 CIRCUIT 350A, 1000V NEMA 3R GND 350A 350A 350A 350A 350A 350A 1000 VDC 350VAC BAYONET FUSES 1,240 KVA LOOP FED (22.86 KV : 350V) G GND 1600A/3P SCHNEIDER ELECTRICCONEXT CORE XC 630-NA 6 CIRCUIT350A, 1000VNEMA 3R GND 350A 350A 350A 350A 350A 350A 1000 VDC 350VAC GND 1600A/3P SCHNEIDER ELECTRICCONEXT CORE XC 630-NA 6 CIRCUIT350A, 1000VNEMA 3R GND 350A 350A 350A 350A 350A 350A 1000VDC 350 VAC A 1 1 A 2 A 2 A A 1 A 2 L.A.'s GND I I I I I J J J J J (3) x60A FUSES ON POLE L.A.'s GND C F (3) x80A FUSES ON POLE L.A.'s GND D F 3Ø, 25kV, 1/0 AL URD PRIMARY CABLE WITH1/3 CONCENTRIC NEUTRAL IN 5" SCHD 40PVC CONDUIT AT LEAST 48" DEEP.L.A.'s GND A 1 1 A 2 A 2 A A 1 A 2 A 1 CB-1 (22) STRING DETAIL CB-2 (22) STRING DETAIL 1 A CB-3 (22) STRING DETAIL CB-4 (24) STRING DETAIL 2 A CB-5 (24) STRING DETAIL CB-6 (24) STRING DETAIL 2 A A 1 A 2 A 1 CB-1 (22) STRING DETAIL CB-2 (22) STRING DETAIL 1 A CB-3 (22) STRING DETAIL CB-4 (24) STRING DETAIL 2 A CB-5 (24) STRING DETAIL CB-6 (24) STRING DETAIL 2 A A 1 A 2 INTERCONNECTION TYPE TO MATCH DUKE ENERGY: REQUIREMENTS FOR ELECTRICAL SERVICE AND METER INSTALLATIONS MANUAL, FIGURE 71B. (3) X 1/0 AAC OH PRIMARY WIRES (1) X 1/0 AAC OH NEUTRAL WIRE M B M A 3Ø, 25kV, 1/0 AL URD PRIMARY CABLE WITH 1/3CONCENTRIC NEUTRAL IN 5" SCHD 40 PVCCONDUIT AT LEAST 48" DEEP.3Ø, 25kV, 1/0 AL URD PRIMARY CABLE WITH 1/3CONCENTRIC NEUTRAL IN 5" SCHD 40 PVCCONDUIT AT LEAST 48" DEEP.3Ø, 25kV, 1/0 AL URD PRIMARY CABLE WITH1/3 CONCENTRIC NEUTRAL IN 5" SCHD 40PVC CONDUIT AT LEAST 48" DEEP.GENERATOR DISCONNECT WILL BE RATED FOR LOAD BREAK, VISIBLE OPEN, AND ADJACENT TO THE METER. BLADE SWITCH CB-1 (22) STRING DETAIL CB-2 (22) STRING DETAIL CB-3 (22) STRING DETAIL CB-4 (24) STRING DETAIL CB-5 (24) STRING DETAIL CB-6 (24) STRING DETAIL CB-1 (22) STRING DETAIL CB-2 (22) STRING DETAIL CB-3 (22) STRING DETAIL CB-4 (24) STRING DETAIL CB-5 (24) STRING DETAIL CB-6 (24) STRING DETAIL CB-1 (22) STRING DETAIL CB-2 (22) STRING DETAIL CB-3 (22) STRING DETAIL CB-4 (24) STRING DETAIL CB-5 (24) STRING DETAIL CB-6 (24) STRING DETAIL A 3 ONE PER TRANSFORMERA 3 ONE PER TRANSFORMER TYPICAL AUX POWER SUPPLY SCALE:NTS A 3 15A/1P 15A/1P 15A/1P60A/2P15A/1P 15A/1P 15A/1P GND 50A/2P TO DATA LOGGER A 3 ONE PER TRANSFORMER TYPICAL (22) STRING ONE-LINE DIAGRAM MODULE TO COMBINER BOX SCALE: NTS A 1 22 STRINGS OF 19 MODULES EACH (2 STRINGS COMBINED W/ "Y" CONNECTOR)J TYPICAL (24) STRING ONE-LINE DIAGRAM MODULE TO COMBINER BOX SCALE: NTS A 2 24 STRINGS OF 19 MODULES EACH (2 STRINGS COMBINED W/ "Y" CONNECTOR)K E L M N L M N O GND 1600A/3P SCHNEIDER ELECTRICCONEXT CORE XC 630-NA 6 CIRCUIT350A, 1000VNEMA 3R GND 350A 350A 350A 350A 350A 350A 1000 VDC 350 VAC A 1 1 A 2 A 2 A A 1 A 2 GND 1600A/3P SCHNEIDER ELECTRIC CONEXT CORE XC 630-NA 6 CIRCUIT350A, 1000VNEMA 3R GND 350A 350A 350A 350A 350A 350A 1000VDC 350 VAC I I J J A 1 1 A 2 A 2 A A 1 A 2 CB-1 (22) STRING DETAIL CB-2 (22) STRING DETAIL CB-3 (22) STRING DETAIL CB-4 (24) STRING DETAIL CB-5 (24) STRING DETAIL CB-6 (24) STRING DETAIL CB-1 (22) STRING DETAIL CB-2 (22) STRING DETAIL CB-3 (22) STRING DETAIL CB-4 (24) STRING DETAIL CB-5 (24) STRING DETAIL CB-6 (24) STRING DETAIL ONE PER TRANSFORMER 1,240 KVA LOOP FED (22.86 KV : 350V) G 620 KVA LOOP FED (350V : 22.86 KV) H D.E.B.01/27/20160RELEASE FOR CONSTRUCTIOND.BRUECKJ.WILSON02/14/20171REDUCED FROM 5.0 TO 3.4 MWACD.BRUECKJ.WILSON03/27/20172ADDED CHANGED NOTE PER DEPD.BRUECKGENERAL NOTES: 1.The submission of this drawing acknowledges this is the final design and any change to this diagram could result in a material modification as defined by the state interconnection standards. Any changes to this diagram must be submitted for approval to Duke Energy Progress.M.BATH08/08/20173MODULES CHANGED FROM 340W TO 330WD.BRUECK"THIS DOCUMENT CONTAINS INTELLECTUAL, DESIGN, OR COPY WRITE PROPERTY OF SOUTHERN CURRENT LLC WHICH IS PRIVILEGED OR CONFIDENTIAL AND IS NOT TO BE REPRODUCED, DISCLOSED, USED IN ANY MANNER OR DISTRIBUTED WITHOUT WRITTEN PERMISSION OF SOUTHERN CURRENT LLC" "THIS DOCUMENT CONTAINS INTELLECTUAL, DESIGN, OR COPY WRITE PROPERTY OF SOUTHERN CURRENT LLC WHICH IS PRIVILEGED OR CONFIDENTIAL AND IS NOT TO BE REPRODUCED, DISCLOSED, USED IN ANY MANNER OR DISTRIBUTED WITHOUT WRITTEN PERMISSION OF SOUTHERN CURRENT LLC" REVISION DESCRIPTIONAPRV'DNODATEBYFLOWERS SOLAR3188 BAILEYS CROSSROADS ROADBENSON, NC 275124.34 MW AC - SOLAR PV SYSTEMELECTRICAL ONE LINET.JONES12/06/20174ADDED POLE MOUNTED TRANSFORMERD.BRUECK1519 King St. Charleston, S.C. 29405 T.JONES12/15/20175ADDED FUSES TO POSITIVE "Y"-HARNESSESD.BRUECKT.JONES1/18/20186ISSUED FOR CONSTRUCTIOND.BRUECK 2 1 2 3 4 1 3 T.JONES01/15/20180ISSUED FOR PERMITD.BRUECK"THIS DOCUMENT CONTAINS INTELLECTUAL, DESIGN, OR COPY WRITE PROPERTY OF SOUTHERN CURRENT LLC WHICH IS PRIVILEGED OR CONFIDENTIAL AND IS NOT TO BE REPRODUCED, DISCLOSED, USED IN ANY MANNER OR DISTRIBUTED WITHOUT WRITTEN PERMISSION OF SOUTHERN CURRENT LLC" "THIS DOCUMENT CONTAINS INTELLECTUAL, DESIGN, OR COPY WRITE PROPERTY OF SOUTHERN CURRENT LLC WHICH IS PRIVILEGED OR CONFIDENTIAL AND IS NOT TO BE REPRODUCED, DISCLOSED, USED IN ANY MANNER OR DISTRIBUTED WITHOUT WRITTEN PERMISSION OF SOUTHERN CURRENT LLC" REVISION DESCRIPTIONAPRV'DNODATEBYFLOWERS SOLAR3188 BAILEYS CROSSROADS ROADBENSON, NC 275124.34 MW AC - SOLAR PV SYSTEMELECTRICAL CALCULATIONS1519 King St. Charleston, S.C. 29405 T.JONES01/18/20181ISSUED FOR CONSTRUCTIOND.BRUECK 1519 King Street Charleston, SC 29405 "THIS DOCUMENT CONTAINS INTELLECTUAL, DESIGN, OR COPY WRITE PROPERTY OF SOUTHERN CURRENT LLC WHICH IS PRIVILEGED OR CONFIDENTIAL AND IS NOT TO BE REPRODUCED, DISCLOSED, USED IN ANY MANNER OR DISTRIBUTED WITHOUT WRITTEN PERMISSION OF SOUTHERN CURRENT LLC" "THIS DOCUMENT CONTAINS INTELLECTUAL, DESIGN, OR COPY WRITE PROPERTY OF SOUTHERN CURRENT LLC WHICH IS PRIVILEGED OR CONFIDENTIAL AND IS NOT TO BE REPRODUCED, DISCLOSED, USED IN ANY MANNER OR DISTRIBUTED WITHOUT WRITTEN PERMISSION OF SOUTHERN CURRENT LLC" REVISION DESCRIPTIONAPRV'DNODATEBYFLOWERS SOLAR3188 BAILEYS CROSSROADS ROADBENSON, NC 275124.34 MW AC - SOLAR PV SYSTEMMONITORING ONE LINE DIAGRAMT.JONES01/15/20180ISSUED FOR PERMITD.BRUECKT.JONES01/18/20181ISSUED FOR CONSTRUCTIOND.BRUECK NOTES: 1.INSTALL GROUNDING SYSTEM COMPONENTS PER MANUFACTURERS' INSTURCITONS. 2.ALL WASHERS, NUTS, AND BOLTS SHALL BE STAINLESS STEEL MATERIAL U.N.O. BY THESE DOCUMENTS OR MANUFACTURER'S INSTALLATION INSTRUCTIONS. 3.PROVIDE MIN. OF (1) LAY-IN LUG ATTACHED TO EAST-WEST PURLIN PER EACH CONINUOUS RACKING ROW. HEX-BOLT LOCK WASHER COPPER EGC LAY-IN LUG 13/64" FIELD-DRILLED MOUNTING HOLE FLAT WASHER HEX NUT SERRATED STAR WASHER EAST-WEST PURLIN SET-SCREW INV#X TX#XCB#X 5/8", 8'0" LONG, COPPER-CLAD STEEL DRIVEN GROUND ROD (TYP. 1 PER CONTINUOUS RACKING ROW) GEC BONDING JUMPER EGCEGC GROUNDING ELECTRODE SYSTEM SUPPLY-SIDE BONDING JUMPER LAY-IN GROUNDING LUG ATTACHED TO EAST-WEST PURLIN MODULES ARE BONDED TO RACKing StRUCTURE VIA MECHANICAL ATTACHMENTS LISTED TO UL 2703 NOTES: 1.BOND ALL METALLIC EQUIPMENT ENCLOSURES TO THEIR GROUND BUS. 2.GROUND RODS SHALL BE LOCATED SO AS TO NOT OBSTRUCT MOWING BETWEEN ROWS OF RACKING. EGC 5/8", 8'0" LONG, COPPER-CLAD STEEL DRIVEN GROUND ROD EXOTHERMIC WELD OR IRREVERSIBLE CRIMP TYP.) #3/0 BARE COPPER DIRECT-BURIED GROUND RING AROUND TRANSFORMER AND INVERTER PAD T.JONES01/15/20180ISSUED FOR PERMITD.BRUECKEGC CONNECTION TO PURLIN SCALE: NTS GROUNDING ELECTRODE SYSTEM SCALE: NTS GROUNDING DIAGRAM SCALE: NTS NOTES: 1.ALL STEEL DRIVEN GROUND RODS SHALL BE DRIVEN 1' BELOW GRADE. 2.ALL COMPONENTS SHALL BE LISTED FOR THEIR USE AND INSTALLED IN ACCORDANCE WITH THEIR LISTINGS. ALL GROUND COMPONENTS SHALL BE RATED FOR DIRECT-BURIAL APPLICATION. "THIS DOCUMENT CONTAINS INTELLECTUAL, DESIGN, OR COPY WRITE PROPERTY OF SOUTHERN CURRENT LLC WHICH IS PRIVILEGED OR CONFIDENTIAL AND IS NOT TO BE REPRODUCED, DISCLOSED, USED IN ANY MANNER OR DISTRIBUTED WITHOUT WRITTEN PERMISSION OF SOUTHERN CURRENT LLC" "THIS DOCUMENT CONTAINS INTELLECTUAL, DESIGN, OR COPY WRITE PROPERTY OF SOUTHERN CURRENT LLC WHICH IS PRIVILEGED OR CONFIDENTIAL AND IS NOT TO BE REPRODUCED, DISCLOSED, USED IN ANY MANNER OR DISTRIBUTED WITHOUT WRITTEN PERMISSION OF SOUTHERN CURRENT LLC" REVISION DESCRIPTIONAPRV'DNODATEBYFLOWERS SOLAR3188 BAILEYS CROSSROADS ROADBENSON, NC 275124.34 MW AC - SOLAR PV SYSTEMGROUNDING DETAILS1519 King St. Charleston, S.C. 29405 T.JONES01/18/20181ISSUED FOR CONSTRUCTIONSD.BRUECK TOP VIEW 62" 21" 126" 92"24"10" 8" MAX. 12"18"50"5"18"12"12" 126" 12" 8" 30" 19" 19" 9"10" 10" 16" 53" 16" 123" 41" 53" 16" 49" 19" 19" 9" 10" 10" 16" 324" 1.TRANSFORMER/INVERTER PADS SHALL BE INSTALLED IN A LOCATION TO REMAIN READILY ACCESSIBLE FOR CRANES, LINE TRUCKS OR OTHER NECESSARY LIFTING AND HAULING EQUIPMENT. PADS SHALL HAVE A MINIMUM CLEARANCE FROM OBSTRUCTIONS AND BUILDINGS. 2.SOIL UNDERNEATH PADS SHALL BE FREE OF ROOTS AND OTHER ORGANIC MATERIALS AND BE THOROUGHLY TAMPED TO PREVENT WASHING. EXERCISE CARE IN BACKFILLING AND GRADING AROUND PAD. 3.SERVICE CONDUIT SHALL BE LOCATED IN THE EXTREME RIGHT SIDE OF THE SECONDARY COMPARTMENT AND SHALL NOT EXTEND MORE THAN 30” LEFT OF THIS AS INDICATED IN THE DRAWING. 4.REINFORCE PAD WITH #4 REBARS ON 8" x 8" GRID TIED SECURELY ABOVE BASE ON CLEAN CONCRETE OR BRICK SUPPORTS. ENDS OF BARS TO BE 3" FROM OPENING FOR CABLE ENTRANCE. 5.CONCRETE TO BE 5-1/2% AIR ENTRAINED WITH A MINIMUM 28 DAY STRENGTH OF 3000 PSI MIXTURE TO BE 1:2:4 PROPORTIONS OF CEMENT, SAND AND GRAVEL. USE 6 GALLONS OF WATER PER SACK OF CONCRETE. 6.TOP SURFACE TO BE LEVEL, SMOOTH, AND BEVELED APPROXIMATELY 3/8". 7.OTHER UTILITIES ARE NOT TO BE INSTALLED UNDER TRANSFORMER PAD. 8.USE FIRE ANT CONTROL UNDER ENTIRE PAD INCLUDING PAD OPENINGS. 9.GRADING OF TRANSFORMER PAD SHALL BEGIN WITH REMOVAL OF SURFACE VEGETATION AND TOPSOIL. FOLLOWING TOPSOIL REMOVAL, AREA TO BE GRADED SHOULD BE PROOF-ROLLED TO IDENTIFY ANY AREAS OF SOIL THAT NEED REPAIR. TRANSFORMER PAD SHALL THEN BE GRADED 1' ABOVE ORIGINAL EXISTING SURFACE. MATERIAL USED FOR TRANSFORMER PAD GRADING SHALL BE STRUCTURAL FILL AND ALL FILL MATERIAL SHOULD BE COMPACTED TO NOT LESS THAT 95% OF THE STANDARD PROCTOR MAXIMUM DRY DENSITY AT MOISTURE CONTENT IN THE RANGE OF +/- 2% OF OPTIMUM. FILL MATERIAL SHOULD BE COMPACTED IN MAXIMUM LIFTS OF 8” LOOSE LIFTS AND THEN BE COMPACTED UNTIL ACHIEVING THE REQUIRED DENSITY. ELECTRICAL CONTRACTORS SHALL BE RESPONSIBLE FOR REVIEWING THE SITE SPECIFIC GEOTECHNICAL REPORTS TO ENSURE THE TRANSFORMER PAD GRADING MEETS THESE REQUIREMENTS. CONDUIT CUTOUT INCLUDED ONLY ON PAD #1 SIDE VIEW GRAVEL 6" 126" 6" 21 2"" 31 2"" EXISTING GRADE RAISED MOUND12" 2' FROM EDGE OF SLAB TO EDGE OF MOUND ALL AROUND REFERENCE NOTE #9 5" GALVANIZED BEND 3.5" SCH 40 PVC CONDUIT (#X) FROM AC DISCONNECTS TRANSFORMER PAD DETAIL SCALE: 1" = 2'T.JONES01/15/20180ISSUED FOR PERMITD.BRUECK"THIS DOCUMENT CONTAINS INTELLECTUAL, DESIGN, OR COPY WRITE PROPERTY OF SOUTHERN CURRENT LLC WHICH IS PRIVILEGED OR CONFIDENTIAL AND IS NOT TO BE REPRODUCED, DISCLOSED, USED IN ANY MANNER OR DISTRIBUTED WITHOUT WRITTEN PERMISSION OF SOUTHERN CURRENT LLC" "THIS DOCUMENT CONTAINS INTELLECTUAL, DESIGN, OR COPY WRITE PROPERTY OF SOUTHERN CURRENT LLC WHICH IS PRIVILEGED OR CONFIDENTIAL AND IS NOT TO BE REPRODUCED, DISCLOSED, USED IN ANY MANNER OR DISTRIBUTED WITHOUT WRITTEN PERMISSION OF SOUTHERN CURRENT LLC" REVISION DESCRIPTIONAPRV'DNODATEBYFLOWERS SOLAR3188 BAILEYS CROSSROADS ROADBENSON, NC 275124.34 MW AC - SOLAR PV SYSTEMCONCRETE SLAB DETAILS (PG-1)CONDUIT CUTOUT & TRANSFORMER / INVERTER PLAN VIEW SCALE: 1" = 2' CONDUIT CUTOUT & TRANSFORMER / INVERTER SECTION VIEW SCALE: 1" = 2' 1519 King St. Charleston, S.C. 29405 3 012 T.JONES01/18/20181ISSUED FOR CONSTRUCTIOND.BRUECK TOP VIEW 62" 21" 126" 92"24"10" 8" MAX. 12"18"50"5"18"12"12" 126" 12" 8" 30" 19" 19" 9"10" 10" 16" 53" 16" 123" 221" 8" 12" 324" SIDE VIEW GRAVEL 6" 126" 6" 21 2"" 31 2"" EXISTING GRADE RAISED MOUND12" 2' FROM EDGE OF SLAB TO EDGE OF MOUND ALL AROUND REFERENCE NOTE #9 CONDUIT CUTOUT INCLUDED ONLY ON PAD #1 1.TRANSFORMER/INVERTER PADS SHALL BE INSTALLED IN A LOCATION TO REMAIN READILY ACCESSIBLE FOR CRANES, LINE TRUCKS OR OTHER NECESSARY LIFTING AND HAULING EQUIPMENT. PADS SHALL HAVE A MINIMUM CLEARANCE FROM OBSTRUCTIONS AND BUILDINGS. 2.SOIL UNDERNEATH PADS SHALL BE FREE OF ROOTS AND OTHER ORGANIC MATERIALS AND BE THOROUGHLY TAMPED TO PREVENT WASHING. EXERCISE CARE IN BACKFILLING AND GRADING AROUND PAD. 3.SERVICE CONDUIT SHALL BE LOCATED IN THE EXTREME RIGHT SIDE OF THE SECONDARY COMPARTMENT AND SHALL NOT EXTEND MORE THAN 30” LEFT OF THIS AS INDICATED IN THE DRAWING. 4.REINFORCE PAD WITH #4 REBARS ON 8" x 8" GRID TIED SECURELY ABOVE BASE ON CLEAN CONCRETE OR BRICK SUPPORTS. ENDS OF BARS TO BE 3" FROM OPENING FOR CABLE ENTRANCE. 5.CONCRETE TO BE 5-1/2% AIR ENTRAINED WITH A MINIMUM 28 DAY STRENGTH OF 3000 PSI MIXTURE TO BE 1:2:4 PROPORTIONS OF CEMENT, SAND AND GRAVEL. USE 6 GALLONS OF WATER PER SACK OF CONCRETE. 6.TOP SURFACE TO BE LEVEL, SMOOTH, AND BEVELED APPROXIMATELY 3/8". 7.OTHER UTILITIES ARE NOT TO BE INSTALLED UNDER TRANSFORMER PAD. 8.USE FIRE ANT CONTROL UNDER ENTIRE PAD INCLUDING PAD OPENINGS. 9.GRADING OF TRANSFORMER PAD SHALL BEGIN WITH REMOVAL OF SURFACE VEGETATION AND TOPSOIL. FOLLOWING TOPSOIL REMOVAL, AREA TO BE GRADED SHOULD BE PROOF-ROLLED TO IDENTIFY ANY AREAS OF SOIL THAT NEED REPAIR. TRANSFORMER PAD SHALL THEN BE GRADED 1' ABOVE ORIGINAL EXISTING SURFACE. MATERIAL USED FOR TRANSFORMER PAD GRADING SHALL BE STRUCTURAL FILL AND ALL FILL MATERIAL SHOULD BE COMPACTED TO NOT LESS THAT 95% OF THE STANDARD PROCTOR MAXIMUM DRY DENSITY AT MOISTURE CONTENT IN THE RANGE OF +/- 2% OF OPTIMUM. FILL MATERIAL SHOULD BE COMPACTED IN MAXIMUM LIFTS OF 8” LOOSE LIFTS AND THEN BE COMPACTED UNTIL ACHIEVING THE REQUIRED DENSITY. ELECTRICAL CONTRACTORS SHALL BE RESPONSIBLE FOR REVIEWING THE SITE SPECIFIC GEOTECHNICAL REPORTS TO ENSURE THE TRANSFORMER PAD GRADING MEETS THESE REQUIREMENTS.NETWORK ENCLOSURETOP VIEW5" GALVANIZED BEND 3.5" SCH 40 PVC CONDUIT FROM AC DISCONNECTS 3/4" x10' GROUND ROD TRANSFORMER PAD DETAIL SCALE: 1" = 2'T.JONES01/15/20180ISSUED FOR PERMITD.BRUECK"THIS DOCUMENT CONTAINS INTELLECTUAL, DESIGN, OR COPY WRITE PROPERTY OF SOUTHERN CURRENT LLC WHICH IS PRIVILEGED OR CONFIDENTIAL AND IS NOT TO BE REPRODUCED, DISCLOSED, USED IN ANY MANNER OR DISTRIBUTED WITHOUT WRITTEN PERMISSION OF SOUTHERN CURRENT LLC" "THIS DOCUMENT CONTAINS INTELLECTUAL, DESIGN, OR COPY WRITE PROPERTY OF SOUTHERN CURRENT LLC WHICH IS PRIVILEGED OR CONFIDENTIAL AND IS NOT TO BE REPRODUCED, DISCLOSED, USED IN ANY MANNER OR DISTRIBUTED WITHOUT WRITTEN PERMISSION OF SOUTHERN CURRENT LLC" REVISION DESCRIPTIONAPRV'DNODATEBYFLOWERS SOLAR3188 BAILEYS CROSSROADS ROADBENSON, NC 275124.34 MW AC - SOLAR PV SYSTEMCONCRETE SLAB DETAILS (PG-2)CONDUIT CUTOUT & TRANSFORMER / INVERTER PLAN VIEW SCALE: 1" = 2' 3 013 TRANSFORMER SECTION VIEW SCALE: 1"=2' 1519 King St. Charleston, S.C. 29405 T.JONES01/18/20181ISSUED FOR CONSTRUCTIOND.BRUECK DRIP LOOP #6 AWG BARE GROUND WIRE NYLON EXPANDABLE SLEEVE BUNDLE OF PV WIRE WEEB LUG FOR GROUNDING ATTACHED TO RACKING NYLON EXPANDABLE SLEEVE WIRE LOOM FOR PV WIRE COMBINER BOX #6 AWG BARE GROUND WIRE DRIP LOOP GROUND ROD ATTACH WIRE LOOM WITH STRAPS TO RACKING POST BUNDLE OF PV WIRE #6 AWG BARE GROUND WIRE WEEB LUG FOR GROUNDING ATTACHED TO RACKING DRIP LOOP 2'-6" MIN. 7'-11" VARIES FENCE POSTS 2" SCHD 40 PVC 2" SCHD 80 PVC 2" SCHD 80 PVC WEATHER HEADS FOR DC HOME RUNS UNISTRUT 2" SCHD 80 PVC CONDUIT ABOVE GROUND 2" SCHD 40 PVC CONDUIT BELOW GROUND NYLON EXPANDABLE SLEEVE WIRE LOOM FOR PV WIRE COMBINER BOX DRIP LOOP PV WIRE ENTRY CONNECTOR 4" SCHD 40 PVC THAT SWITCHES TO SCHD 80 PVC ABOVE GROUND CABLE-IN-CONDUIT ATTACH WIRE LOOM WITH STRAPS TO RACKING POST FENCE POST 2 HOLE SPADES ELBOW (3x) PRIMARY COMPARTMENT ONE HOLE LUG SURGE ARRESTER (3x) USE A CONTINUOUS LENGTH OF #2 CU WIRE TO CONNECT THE SECONDARY NEUTRAL TERMINAL TO THE GROUND RING, THE TANK GROUND CONNECTOR IN THE PRIMARY COMPARTMENT, AND THE SYSTEM NEUTRAL. CT'S SECONDARY COMPARTMENT CONTINUOUS LENGTH OF 3/0 CU WIRE CONNECTED TO GROUND RING AND #2 CU WIRE WITH EXOTHERMIC WELDS 3/0 BARE CU GROUND RING ENCLOSURE GASKET LEAD/PLASTIC INSERT CONCRETE PAD "THIS DOCUMENT CONTAINS INTELLECTUAL, DESIGN, OR COPY WRITE PROPERTY OF SOUTHERN CURRENT LLC WHICH IS PRIVILEGED OR CONFIDENTIAL AND IS NOT TO BE REPRODUCED, DISCLOSED, USED IN ANY MANNER OR DISTRIBUTED WITHOUT WRITTEN PERMISSION OF SOUTHERN CURRENT LLC" "THIS DOCUMENT CONTAINS INTELLECTUAL, DESIGN, OR COPY WRITE PROPERTY OF SOUTHERN CURRENT LLC WHICH IS PRIVILEGED OR CONFIDENTIAL AND IS NOT TO BE REPRODUCED, DISCLOSED, USED IN ANY MANNER OR DISTRIBUTED WITHOUT WRITTEN PERMISSION OF SOUTHERN CURRENT LLC" REVISION DESCRIPTIONAPRV'DNODATEBYFLOWERS SOLAR3188 BAILEYS CROSSROADS ROADBENSON, NC 275124.34 MW AC - SOLAR PV SYSTEMTRANSFORMER AND JUMPER DETAILSROW-TO-ROW JUMPER (HARNESS TO COMBINER) SCALE: 1" = 2' ROW-TO-ROW JUMPER (WITHOUT COMBINER BOX) SCALE: 1" = 2' COMBINER MOUNTING BEHIND MODULES (ELEVATION VIEW) SCALE: 1" = 2' ACHOR BOLTTRANSFORMER GROUNDING DETAIL SCALE: NTS SCALE: NTS T.JONES01/15/20180ISSUED FOR PERMITD.BRUECK1519 King St. Charleston, S.C. 29405 T.JONES01/18/20181ISSUED FOR CONSTRUCTIOND.BRUECK PMPMRCL6'6' 6' 6 ' 6' 6'6'GROUND ROD LAYOUT TOP VIEW 8" GROUND ROD LAYOUT FRONT VIEW #2 SD BC (1) DEEP DRIVEN GROUND WHEN SOIL PERMIT (AT ANY ONE OF THE ROD LOCATIONS)T.JONES01/15/20180ISSUED FOR PERMITD.BRUECKGANG SWITCHCUTOUT RECLOSER PRIMARY METER ELECTRIC DISTRIBUTION SYMBOLS INSTALL POLE EXISTING POLE RCL PM 10'-0" 12" 5" 6"6"5"1 6"6" 2 3 12"4 11 5 24" 6 10 8" 7 8 BOND ALL GUYS TO THE NEUTRAL INSULATOR 78" GUY 62" 9 4" FRONT VIEW SIDE VIEW NOTES: 1. TWO DOWN GUYS SHALL BE INSTALLED WHEN 795 CONDUCTOR IS USED. DEADEND CENTERMOUNT BRACKET ON FIBERGLASS CROSSARM HAS PROVISIONS FOR TWO GUYS. 2. NUMBER OF GUYS SHALL BE DETERMINED BY DESIGNER. 3 2 1 0 4/5/17 12/12/16 LOOSIER BURLISON ADCOCK GORLEY BURLISON ADCOCK REVISED BY CK'D 6/30/16 WHITE BURLISON ADCOCK APPR. THREE-PHASE HORIZONTAL CONSTRUCTION - DEADEND CROSSARM GUYED DEC X DEM X DEP X DEF X 03.11-127A BILL OF MATERIALS MACRO UNIT BUBBLE NUMBER 1 2 3 4 5 6 COMPATIBLE UNIT ARMSDE120HFC DECLMP___C IDES35PC ISEYEBOLT5812C K___C EQRISERN2CCUC BKTCOLATRIFGC CU QTY 1 3 3 1 2 2 1 ITEM NUMBER 0010036101 0010540102 0010544104 9220272389 - 9220277353 0010026300 0010540102 - 7 - 7 7 8 9 10 11 11 - ARROH18C ARROH27C GUYING DECLMP___C ISEYEBOLT5812C WGEQBUSHSNAPSC TFUSE15FT100PC - TFUSE25FT100PC - BKTCOSTLXARMC 3 3 - 1 1 3 1 1 1 1 1 ARROH10C 3 0011025301 0010034908 0010543007 0010544005 0012912309 0011061009 0011196508 0011231305 0011061009 0011196508 11231503 0011061009 0011196508 11231701 - - 0010026300 0010540102 9220284709 9220285207 414418 9220284885 414418 9220240204 9220263501 ITEM QTY/ CU 2 2 2 1 1 1 SEE SECTION 04.09 FOR CONNECTOR DETAILS (VARIES) 12 CONDUCTOR, COPPER, 2-SLD, SDW, WP, #2 AWG, SOLID BOLT, MACHINE, 5/8 IN, 11 IN X 12 IN, STEEL, ANSI C135.1 1 1 1 2 2 2 1 4 1 1 4 1 1 4 1 1 1 1 1 1 1 3 3 3 3 2 1 WASHER, SQUARE, SQ, 2-1/4X2-1/4X3/16, GALV WASHER, LOCK, 5/8 IN, STEEL, GALV, COIL, DBL BRACKET, MOUNTING, 48 IN WIDE X 24 IN, FIBERGLASS, 3-PHASE WIRE, TIE, #6, SOLID SOFT DRAWN BARE COPPER CONNECTOR, COMPRESSION, PA, 6SLD-2ACSR DOUBLE TAB ARRESTER, METAL OXIDE, 10KV, METOX DIST CLASS, METAL OXIDE WIRE, TIE, #6, SOLID SOFT DRAWN BARE COPPER CONNECTOR, COMPRESSION, PA, 6SLD-2ACSR DOUBLE TAB ARRESTER, METAL OXIDE, 18KV, METOX DIST CLASS, METAL OXIDE WIRE, TIE, #6, SOLID SOFT DRAWN BARE COPPER CONNECTOR, COMPRESSION, PA, 6SLD-2ACSR DOUBLE TAB ARRESTER, METAL OXIDE, 27KV, METOX DIST CLASS, METAL OXIDE SEE SECTION 02.04 FOR GUYING DETAILS (VARIES) SEE SECTION 03.03 FOR CLAMP DETAILS (VARIES) BOLT, EYE, 5/8 IN, 12 IN, STEEL, ASTM A153, OVAL WASHER, SQUARE, RB, CRV, 3"X3", GALV GUARD, WILDLIFE 5 1/4 DIA X 5 1/2 HT TRANS/CAP FUSE 15KV FAULT TAMER 100A POLYMER TAMER, FAULT FUSE 20A TRANS/CAP FUSE 25KV FAULT TAMER 100A POLYMER TAMER, FAULT FUSE 20A BRACKET, MOUNTING, 8 7/8 IN X 2 1/2 IN IN, GALVANIZED STEEL BOLT, CARRIAGE, 1/2 IN, 6 IN, STEEL, GALV DESCRIPTION BOLT, HEX, 3/4 IN, 10" X 12 IN, STEEL, A307 WASHER, SQUARE, RB, CRV, 3"X3", GALV WASHER, LOCK, 3/4 IN, COIL, DBL, STEEL, GALV, SPRING CROSSARM, DEADEND, FIBERGLASS, 10', ALUM MOUNTING BRACKET SEE SECTION 03.03 FOR CLAMP DETAILS (VARIES) INSULATOR, SUSPENSION, 35KV, GRAY POLYMER, 15000LB TENSION BOLT, EYE, 5/8 IN, 12 IN, STEEL, ASTM A153, OVAL WASHER, SQUARE, RB, CRV, 3"X3", GALV 3 2 1 0 DEC DEM 1/13/17 11/4/16 LOOSIER BURLISON ADCOCK LOOSIER BURLISON ADCOCK REVISED BY CK'D 6/30/16 LOOSIER BURLISON ADCOCK APPR. THREE-PHASE HORIZONTAL CONSTRUCTION - DEADEND CROSSARM GUYED DEP DEF X 03.11-127B PLAN VIEW 5" 5" 3 96" 6" 4 2 1 96" 4"44"44"4" 6 7 8 5 4" #6 SD BC FRONT VIEW MAXIMUM ANGLE BASED ON 280 FOOT RULING SPAN (200-340 FOOT SPANS) CONDUCTOR SIZE #1/0 AAAC AND SMALLER 4/0 AAAC 336.4 AAC 477 AAC 556.5 AAC 795 AAC NOTES: 1. NUMBER OF GUYS SHALL BE DETERMINED BY DESIGNER. 2. A 5/8" MACHINE BOLT SHALL BE INSTALLED AS A SPLIT-OUT BOLT ON MEDIUM ANGLE AND DOUBLE POLE TOP INSULATOR APPLICATIONS. 1 2 3 0 9/30/16 BURLISON WHITE ADCOCK 6/30/16 WHITE BURLISON ADCOCK REVISED BY CK'D APPR. THREE-PHASE HORIZONTAL CONSTRUCTION - MEDIUM ANGLE - DOUBLE CROSSARM DEC DEM DEP DEF X X X X 03.11-112A LIGHT - - - NESC LOADING ZONES MEDIUM - HEAVY - - BILL OF MATERIALS MACRO UNIT BUBBLE NUMBER 1 2 3 ISSTUDBOLT588C STIEF___ALC BKTPTPC COMPATIBLE UNIT IHPTT25C CU QTY 6 4 6 2 ITEM NUMBER 0000080212 0010332104 0010544005 - 0010034908 0010043008 0010332500 0010540102 0010544005 4 - ARMD8LW30WC 1 0010022903 0010210201 0010312007 0010543007 0010544005 9220263501 9220274516 10022903 10034908 4 5 6 8 7 9 ARMD96FC GUYING NSSCC ISPLC NEUSPTIE___ALC - 1 10540102 10544005 - 1 1 1 1 9220284808 - 0010034908 0010510204 0010543007 0010512002 - 10034809 10543007 ITEM QTY/ CU 1 1 1 1 2 1 1 2 2 3 2 2 10 1 4 2 3 2 2 2 2 1 1 1 1 1 1 1 1 DESCRIPTION INSULATOR, POST, TIE, TOP, 25KV, W/O STUD, ANSI 57-1 STUD, LINE POST, 3/4 IN STUD WITH 5/8 X 7.5 IN STEEL PIN WASHER, LOCK, 5/8 IN, STEEL, GLV, LK, 5/8, COIL, DBL SEE SECTION 03.04 FOR INSULATOR TIES (VARIES) BOLT, MACHINE, 5/8 IN, 11 IN X 12 IN, STEEL, ANSI C135.1 BRACKET, MOUNTING, 10 5/8 IN, STEEL, POLE TOP MOUNTING STUD, LINE POST, 5/8X13/4 - 3/4X1 LINE POST INSULATOR STUD WASHER, SQUARE, RB,CRV,3"X3", GLV SQUARE CURVED RIBBED WASHER, LOCK, 5/8 IN, STEEL, GLV, LK, 5/8, COIL, DBL BOLT, DOUBLE ARMING, 5/8 IN, 20 IN, STEEL, PER EEI-NEMA STD CROSSARM, TANGENT, 3-1/2 X 4-1/2 X 8 FT, PENTA 8FT SOUTHERN SCREW, LAG, 1/2 IN X 4 IN, STEEL, HEX, GLV, 1/2 INCH O.D. X WASHER, SQUARE, 2-1/4X2-1/4X3/16, GALV. WASHER, LOCK, 5/8 IN, STEEL, GLV, LK, 5/8, COIL, DBL BOLT, CARRIAGE, 1/2 IN, 6 IN, STEEL, GLV BRACE, POLE, CROSS ARM, 1-3/4" X 1-3/4" X 48" SPAN X 18" BOLT, DOUBLE ARMING, 5/8 IN, 20 IN, STEEL, PER EEI-NEMA STD BOLT, MACHINE, 5/8 IN, 11 IN X 12 IN, STEEL, ANSI C135.1 WASHER, SQUARE, RIBBED, CRV, 3" X 3", GALV. WASHER, LOCK, 5/8 IN, STEEL, GALV, COIL, DOUBLE CROSSARM, TANGENT, 8' LG, FIBERGLASS, BRACELESS CENTERMOUNT SEE SECTION 02.04 FOR GUYING DETAILS (VARIES) BOLT, MACHINE, 5/8 IN, 11 IN X 12 IN, STEEL, ANSI C135.1 CLEVIS, SPOOL, INSL,SPOOL,GLV CLEVIS, SPOOL FOR 3 1/8" SPOOL WASHER, SQUARE, 2-1/4X2-1/4X3/16, GALV. INSULATOR, SPOOL, 3 INCH SECONDARY SPOOL INSULATOR, GRAY SEE SECTION 03.04 FOR INSULATOR TIES (VARIES) BOLT, MACHINE, 5/8 IN, 11 IN X 10 IN, STEEL, ANSI C135.1 WASHER, SQUARE, 2-1/4X2-1/4X3/16, GALV. 1 2 3 0 6/30/16 LOOSIER BURLISON ADCOCK REVISED BY CK'D APPR. THREE-PHASE HORIZONTAL CONSTRUCTION - MEDIUM ANGLE - DOUBLE CROSSARM DEC DEM DEP DEF X 03.11-112B 2'-9"2'-0" 2'-4" 5"5" 2'-8" 14"14" #2 SD BC 72"SW256HRZGOC CN 2930 72" NOTES:BRIDGES SWITCH SHOWN, COMPANY ALSO STOCKS S&C SWITCHES1. THE HOOK STICK SWITCH SHOWN ON DWG. 08.10-36 IS THE PREFERRED INSTALLATION FOR HORIZONTAL GANG SWITCH INSTALLATIONS. THIS SWITCH SHOULD ONLY BE USED ON TALL POLES WHEN A HOOK STICK SWITCH WOULD BE DIFFICULT TO REACH. THIS SWITCH COULD ALSO BE SALVAGED AND RE-USED IF THE POLE IT IS ON MUST BE REPLACED OR REMOVED. 2. CAREFULLY FOLLOW MANUFACTURER'S INSTALLATION INSTRUCTIONS TO ENSURE A PROPERLY ADJUSTED SWITCH. DO NOT DRILL ROD GUIDE HOLES LARGER THAN SPECIFIED. 3. DO NOT INSTALL SWITCH IN ANGLES GREATER THAN 10° 4. GROUND SWITCH FRAME AND HANDLE WITH #2 SD BC. 5. OPERATING ROD GUIDE ASSEMBLIES DO NOT REQUIRE GROUNDING. FOR DEADENDING ON THIS SWITCH. 6. EXTENSION LINKS ARE NOT REQUIRED 7. IT IS EXTREMELY IMPORTANT TO ADJUST THE HANDLE POSITION SO THAT FORCE IS REQUIRED TO SWING THE HANDLE DOWN INTO THE CLOSED POSITION TO ENSURE PROPER "WRAP UP" OF THE OPERATING HANDLE. #2 SD BC 48" 8" (1) DEEP DRIVEN GROUND WHEN SOIL PERMITS (AT ANY ONE OF THE ROD LOCATIONS) SIDE VIEW FRONT VIEW 3 2 1 0 3/22/13 4/20/11 HOFFMAN BURLISON ELKINS ADCOCKGUINNGUINN 7/11/10 HOFFMAN GUINN REVISED BY CK'D ELKINS APPR. 600 AMP HORIZONTAL AIR BREAK SWITCH HANDLE OPERATED 25KV (FMO)DWG. 08.10-37 "THIS DOCUMENT CONTAINS INTELLECTUAL, DESIGN, OR COPY WRITE PROPERTY OF SOUTHERN CURRENT LLC WHICH IS PRIVILEGED OR CONFIDENTIAL AND IS NOT TO BE REPRODUCED, DISCLOSED, USED IN ANY MANNER OR DISTRIBUTED WITHOUT WRITTEN PERMISSION OF SOUTHERN CURRENT LLC" "THIS DOCUMENT CONTAINS INTELLECTUAL, DESIGN, OR COPY WRITE PROPERTY OF SOUTHERN CURRENT LLC WHICH IS PRIVILEGED OR CONFIDENTIAL AND IS NOT TO BE REPRODUCED, DISCLOSED, USED IN ANY MANNER OR DISTRIBUTED WITHOUT WRITTEN PERMISSION OF SOUTHERN CURRENT LLC" REVISION DESCRIPTIONAPRV'DNODATEBYFLOWERS SOLAR3188 BAILEYS CROSSROADS ROADBENSON, NC 275124.34 MW AC - SOLAR PV SYSTEMMEDIUM VOLTAGE DETAILS (PG-1)GOAB GROUND GRID DETAIL SCALE: NTS 10KVA TRANSFORMER 1519 King St. Charleston, S.C. 29405 CUSTOMER-OWNED FACILITIES TO PV SYSTEM POINT OF DELIVERY SWITCH (BYPASS BLADE REMOVED) PRIMARY CT'S AND PT'S BY COMPANY PT CLUSTER RECLOSER NEUTRAL COMPANY METER CONTROL WITH COMMUNICATIONS NOTES: 1. THIS SERVICE ARRANGEMENT IS USED TO CONNECT TO A LARGE IPP STANDALONE SYSTEM WHERE COMPANY PROVIDES A RECLOSER FOR PROTECTION. CUSTOMER RECEIVES PRIMARY VOLTAGE AND PROVIDES THEIR OWN TRANSFORMATION AND OH FACILITIES. 2. WARNING LABEL TO BE PLACED AT METER ON POLE ADVISING OF CUSTOMER GENERATION ON SITE. 3. CUSTOMER PROVIDES ALL WIRING, DISCONNECTS AND TRANSFORMATION BEYOND POINT OF DELIVERY. 4. SINGLE LINE DIAGRAM SHOWN FOR CLARITY. 5. COMPANY PROVIDES ALL FACILITIES TO P.O.D. 3 2 1 0 SELL ALL GENERATION DEC DEM THREE-PHASE PRIMARY METERING 10/28/15 SIMPSON SIMPSON ADCOCK REVISED BY CK'D APPR. IPP RECLOSER INSTALLATION - CUSTOMER OH CONNECTION DEP DEF X FIG 71B 30'30'30'30'30'30'30' 50'T.JONES01/18/20181ISSUED FOR CONSTRUCTIOND.BRUECK T.JONES01/15/20180ISSUED FOR PERMITD.BRUECKSUPPORT DOWN TO THE CUTOUTS ON VERTICAL CONSTRUCTION SEE DWG. 03.22-04 FOR DETAILS ON PROVIDING JUMPER PHASE CLOSEST 36" TO THREE-PHASE BRACKET CN 12912101 BKTCOLATRISTLC MEASURED FROM TOP BRACKET BOLT BOTTOM BRACKET BOLT 4" MIN. ARRESTER ARUGTP10C ARUGTP18C 40" SEE #4 SD BC #6 SD BC (SYSTEM NEUTRAL) MODULAR TERMINAL BRAID GROUND TRM10AL225KITC CN 11171907 NOTE 3 SEE NOTE 4 "A""A" CUTOUT FUSE27CO100C CN 11211802 #6 SD BC U-GUARD OR CONDUIT NOTES: 1. SEE SECTION 26 FOR INSTALLATION OF CABLE TERMINATORS. 2. REMOVE AND DISCARD TEE PIECES FROM ENDS OF BRACKET. 3. ATTACH TAG HOLDER (CN 30837306) TO EACH CABLE INDICATING PHASE AND DESTINATION. ORIENT TAGS TO BE EASILY READ FROM GROUND. INSTALL A SECOND LABEL FOR EACH CABLE ON POLE OR RISER 12" ABOVE LOCID NUMBER UNDER TERMINATOR OR CUTOUT. 4. INSTALL FUSE SIZE AND TYPE USING LOCID LETTERS AND NUMBERS WITH "FUSE SIZE" TAG 6" ABOVE THE LOCID NUMBER LOCATION. SEE DWG. 02.02-20. 5. DO NOT GROUND COLA BRACKET. MAINTAIN 4" MIN. CLEARANCE FROM THE BRACKET TO THE GROUND WIRE. 6. USE 4" #6 SD BC FROM BOTTOM OF ARRESTER TO #4 SD BC NEUTRAL JUMPER. CONNECT GROUND BRAIDS TO #4 SD BC NEUTRAL JUMPER. 7. NEVER LEAVE A CUTOUT BARREL STORED OPEN IN THE CUTOUT BODY. HANG FUSE HOLDERS FROM CUTOUTS ON DRIVE HOOK OR LAG SCREW BY PULL RINGS. 8. FOR POWER FUSE APPLICATIONS, USE CUTOUT SHOWN ON DWG. 08.01-19. SECTION "A-A" 2 3 0 DEC DEM 1/30/15 12/17/14 6/15/10 ROBESON EANES EANES REVISED BY CK'D 1 DANNA GUINN FLETCHER ADCOCK ADCOCK ELKINS APPR. THREE-PHASE RISER 1/0 PRIMARY CABLE DEP DEF X 21.02-01XXXXXX XXXXXXX XX XX X XXX XX X X X X X X X X X X X 3/8" - USE 3/4" BOLT BOLT HEAD 6" 3" CURVE WASHER AND DOUBLE COIL SPRING WASHER SEE NOTE 5 GUY ATTACHMENT 1 4"#6 SD CU GUY MUST BE BONDED TO NEUTRAL "H" (SEE NOTE 1) 2 "X" (SEE NOTE 4) INSTALL GUY MARKERS ON ALL DOWN GUYS SEE NOTE 6 SEE NOTE 2 "L"SEE NOTE 1 NOTES: 1. ENGINEER TO INSTALL STAKE AT POINT WHERE ANCHOR ROD ENTERS THE GROUND "L" TO BE 2/3 OF "H" UNLESS STAKED OTHERWISE AND NOTED ON WORK ORDER. 2. INSTALL GUY MARKERS ON ALL DOWN GUYS REGARDLESS OF LOCATION. 3. IF GUYS ARE INSTALLED DIFFERENTLY THAN ABOVE, MAINTAIN A MINIMUM OF 4" BETWEEN WIRE ATTACHMENT POINT AND GUY ATTACHMENT POINT. 4. IF GUY CROSSES SIDEWALK, MUST BE A MINIMUM OF 9.5 FEET ABOVE ALL PARTS OF THE SIDEWALK. USE SIDEWALK GUY IF NECESSARY. AVOID PLACING DOWN GUYS WHERE VEHICLES ARE LIKELY TO CROSS BETWEEN THE POLE AND THE ANCHOR. USE A STUB POLE AND SPAN GUY IN SUCH CASES. 5. ALL GUYS ABOVE NEUTRAL POSITION MUST HAVE A GUY INSULATOR (LINK) OF SUFFICIENT LENGTH TO EXTEND BEYOND THE LOWEST BARE ENERGIZED COMPONENT BY 24". 6. GUY END (TAIL) MUST BE CUT SO IT DOES NOT STICK OUT OF THE GRIP. THE GUY MARKER SHOULD BE ABLE TO BE PULLED DOWN OVER THE GUY END (TAIL) SO IT IS NOT EXPOSED. 3 0 2 1 6/30/16 BURLISON WHITE REVISED BY CK'D ADCOCK APPR. GUYING - CONSTRUCTION DEC DEM X X DEP DEF X X 02.04-102A MACRO UNIT BUBBLE NUMBER 1 COMPATIBLE UNIT FBGL120C FBGL78C CU QTY 1 1 BILL OF MATERIALS ITEM ITEM NUMBER 76334921 76334922 2 GUYD38C 1 10305415 10047405 10310001 10540102 10036002 10300101 11196508 11061009 11196607 - 2 GUYDD38C 1 10305415 10047405 10310001 10540102 10036002 10300101 11196508 11061009 11196607 QTY/ CU 1 1 45 2 1 1 1 1 1 12 1 90 4 2 2 2 2 24 2 2 -GUYBONDMC - - - GUYBONDSC GUYWIRE38C GUYGUARDC 1 1 1 1 11196508 11061009 11196508 11196508 11061009 10305415 10300101 2 1 1 2 2 2 1 1 DESCRIPTION LINK, FIBERGLASS, CLEVIS, 120", 15M LINK, FIBERGLASS, CLEVIS, 78", 15M WIRE, GUYSTRAND, 3/8", EHS, 7, STR, A855M GRIP, GUY, 3/8", EHS PLATE, GUY, HOOK PLATE UNIV. GUY HOOK FOR ALL STRANDS WASHER, 3", SQUARE, CURVED, 13/16", HOLE BOLT, SQUAREHEAD, 3/4 IN, 12 IN, S, A307, GLV, 10, UNC MARKER, GUY, 8FT, POLY 1.5 INCH, OD, YELLOW CONNECTOR, COMPRESS., COMP,AL,A=2/0STR-2SOL,B=2STR-6SOL WIRE, TIE, #6, SOLID SOFT DRAWN BARE COPPER, TIE CONNECTOR, COMPRESSION, PA,#6SLD-3/0ACSR PARALLEL TYPE AL WIRE, GUYSTRAND, 3/8", EHS, 7, STR, A855M GRIP, GUY, 3/8", EHS PLATE, GUY, HOOK PLATE UNIV. GUY HOOK FOR ALL STRANDS WASHER, 3", SQUARE, CURVED, 13/16", HOLE BOLT, SQUAREHEAD, 3/4 IN, 12 IN, S, A307, GLV, 10, UNC MARKER, GUY, 8FT, POLY 1.5 INCH, OD, YELLOW CONNECTOR, COMPRESS., COMP,AL,A=2/0STR-2SOL,B=2STR-6SOL WIRE, TIE, #6, SOLID SOFT DRAWN BARE COPPER, TIE CONNECTOR, COMPRESSION, PA,#6SLD-3/0ACSR PARALLEL TYPE AL MISCELLANEOUS GUY CUS AND PARTS 11196508 CONNECTOR, COMPRESSION, COMP,AL,A=2STR-6SOL,B=2STR-6SOL CONNECTOR, COMPRESS., COMP,AL,A=2/0STR-2SOL,B=2STR-6SOL WIRE, TIE, #6, SOLID SOFT DRAWN BARE COPPER, TIE CONNECTOR, COMPRESS., COMP,AL,A=2STR-6SOL,B=2STR-6SOL CONNECTOR, COMPRESS., COMP,AL,A=2/0STR-2SOL,B=2STR-6SOL WIRE, TIE, #6, SOLID SOFT DRAWN BARE COPPER, TIE WIRE, GUYSTRAND, 3/8", 7, STR, EX HI, STH, GR, A855M MARKER, GUY, 8FT, POLY 1.5 INCH, OD, YELLOW MACRO UNIT BUBBLE NUMBER 2 1 COMPATIBLE UNIT GUYWIRE516C FBGL24C GUYWIRE716C CU QTY 1 1 1 REMOVE ONLY ITEMS ITEM ITEM NUMBER 10305100 GUYD516C 1 - 4 10305316 11223708 10305100 10048403 10310001 10543007 10034809 10300101 11196508 11196607 11061009 210206 10047504 10310001 GUYD716C 1 10540102 10036002 10300101 11196508 11196607 11061009 QTY/ CU 1 1 1 45 2 1 1 1 1 1 12 1 45 2 1 1 1 1 1 1 12 DESCRIPTION WIRE, GUYSTRAND, 5/16", 7, STR, HI, STH, GR, A855M WIRE, GUYSTRAND, 7/16", UG, 7, STR, UTL, GR, A855M LINK, FBG, CLV, 24", 15M WIRE, GUYSTRAND, 5/16", 7, STR, HI, STH, GR, A855M GRIP, GUY, 5/16", DIA, S, BLK PLATE, GUY, GUY, HOOK PLATE UNIV. GUY HOOK FOR ALL STRANDS WASHER, SQUARE, 2-1/4", SQUARE, FLAT, 13/16", HOLE, GALV. BOLT, MACHINE, 5/8 IN, 10 IN, STEEL, A-ASTM A307, GLV, MACH, MARKER, GUY, 8FT, POLY 1.5 INCH, OD, YELLOW CONNECTOR, COMPRESS., COMP,AL,A=2STR-6SOL,B=2STR-6SOL CONNECTOR, COMPRESS., COMP,AL,A=2/0STR-2SOL,B=2STR-6SOL WIRE, TIE, #6, SOLID SOFT DRAWN BARE COPPER, TIE WIRE, GUYSTRAND, 7/16", UG, 7, STR, UTL, GR, A855M GRIP, GUY, 7/16", S, GRN PLATE, GUY, GUY, HOOK PLATE UNIV. GUY HOOK FOR ALL STRANDS WASHER, SQUARE, RB, CRV, 3"X3", GLV SQUARE CURVED RIBBED BOLT, HEX, 3/4 IN, 10 X 10 IN, STEEL, A307 MARKER, GUY, 8FT, POLY 1.5 INCH, OD, YELLOW CONNECTOR, COMPRESS., COMP,AL,A=2STR-6SOL,B=2STR-6SOL CONNECTOR, COMPRESS., COMP,AL,A=2/0STR-2SOL,B=2STR-6SOL WIRE, TIE, #6, SOLID SOFT DRAWN BARE COPPER, TIE 3 0 2 1 6/30/16 BURLISON WHITE REVISED BY CK'D ADCOCK APPR. GUYING - CONSTRUCTION DEC DEM DEP DEF X 02.04-102B MAKE SURE BUSHING INSERT IS BONDED TO METAL. SEE DETAILS "A" AND "B"X1 LOOP DRAIN WIRE SOLDERED TO GROUND BRAID, OR CONCENTRIC NEUTRAL WIRE IF USING CN CABLE, THROUGH GROUNDING EYE ON ELBOW GROUND BRAIDS #4 BC SD #4 BC SD GROUND LOOP DEP CN 11061108 DEF CN 9220069244 BONDING PAD ACCEPTS 1/2"-13 CONNECTOR (PROVIDED BY OTHER UTILITY) H X00 X2 X3 #4 BC SD GROUND LOOP METAL BUSHING CLAMP BAIL-TAB EYE BOND INSERT TO MOUNTING STUD WHEN BUSHING FLANGE IS PLASTIC INSERT DETAIL "A" METALLIC BUSHING CLAMP NOTES: 1. THE DRAWING ABOVE SHOWS A H0-X0 GROUNDING BUSHING. SOME DESIGNS HAVE SEPARATE H0 AND X0 GROUNDING BUSHINGS. 2. GROUND WIRE IS TO BE BONDED TO TANK GROUND PADS IN BOTH COMPARTMENTS THROUGH THE GROUND STRAP AT THE H0 AND X0 BUSHINGS, AND TO THE PRIMARY CONCENTRIC NEUTRAL WITH A COPPER CONNECTOR. 3. FOR TRANSFORMERS WITH A SEPARATE H0 AND X0 BUSHING USED TO PROVIDE 480Y 3 WIRE SERVICES, THE GROUNDING STRAP SHOULD BE REMOVED FROM THE X0 BUSHING. DO NOT REMOVE THE GROUNDING STRAP ON THE H0 BUSHING. 4. SEE DWG. 20.00-06B FOR ADDITIONAL INFORMATION ON EQUIPMENT GROUNDING AND BONDING. 5. SEE DWGS. 27.06-16 THROUGH 27.06-28 FOR THE GROUNDING REQUIRED ON 3-WIRE SECONDARY SERVICES. 3 2 1 0 DEC DEM 12/17/14 EANES FLETCHER ADCOCK REVISED BY CK'D APPR. GROUND DETAILS FOR THREE-PHASE LOOP FEED TRANSFORMERS DEP X 27.01-04 DEF X GROUNDING PAD DETAIL "B" PLASTIC BUSHING CLAMP MULTI-STACKED RODS SINGLE 8 FT. ROD SQUEEZON CONNECTOR NEUTRAL GRND. WIRE STAPLE 12" STAPLE SPACING FROM 6' ABOVE GRADE TO NEUTRAL#6 SD BC LOCATE ON QUADRANT OF POLE 6" STAPLE SPACING FROM GRADE LEVEL TO 6' ABOVE GRADE #6 SD BC LOCATE ON QUADRANT OF POLE 6" STAPLE SPACING FROM GRADE LEVEL TO 6' ABOVE GRADE GRND. WIRE STAPLE 12" STAPLE SPACING FROM 6' ABOVE GRADE TO NEUTRAL SQUEEZON CONNECTOR NEUTRAL 8"-18"8"-18" SEE SEE DETAIL A DETAIL A 1-8' GROUND RODS 24"24" 4-5' GROUND RODS FRONT VIEW SEE DETAIL B FRONT VIEW GND. WIRE MUST BE INSTALLED ON OPPOSITE SIDE FROM SET SCREW 5/8" COUPLING DETAIL 'A'DETAIL B 3 2 0 1 EQUIPMENT POLE GROUNDING DETAIL 6/30/16 BURLISON WHITE ADCOCK REVISED BY CK'D APPR. DEC DEM DEP XXX DEF X 02.03-102B 4" MAX NOTES:SQUEEZON, THEN COVER WITH BLACK ELECT. TAPE 1. A RISER FOR SECONDARY IS SHOWN. THE CONDUIT RISER CONSTRUCTION IS THE SAME FOR SINGLE OR THREE-PHASE PRIMARY. 2. IF IT IS KNOWN THAT TWO SERVICES WILL BE REQUIRED FROM THE SAME POLE, INSTALL SMALL SECONDARY PEDESTAL AT BASE OF THE POLE INSTEAD OF INSTALLING TWO CONDUIT RISERS. THIS IS MORE ECONOMICAL CONSTRUCTION. SIZE TPX TO SERVE MULTIPLE SERVICES WHEN A PEDESTAL WILL BE USED. USE CU PEDUR8X8PC. 3. SIZE CONDUIT ACCORDING TO SIZE OF TPX, QUAD, SINGLE OR THREE-PHASE #1/0 PRIMARY. ITEM NUMBER COMP. UNIT 21004205 21004502 21004809 DESCRIPTION CRIS440PVC20C CRIS340PVC20C CRIS340PVC30C CRIS440PVC30C CRIS340PVC40C CRIS440PVC40C 2" - 30 FOOT RISER 2" - 40 FOOT RISER 3" - 30 FOOT RISER 3" - 40 FOOT RISER 4" - 30 FOOT RISER 4" - 40 FOOT RISER 4. INSTALL RISER ON SIDE OF POLE AWAY FROM TRAFFIC FLOW. SEE DWG. 10.07-11. JOINT 5. BOTTOM OF TRENCH & FIRST 6" OF BACKFILL SHALL BE FREE OF ALL ROCKS & DEBRIS. BACKFILL TO BE COMPACTED TO PREVENT SETTLING. 6. BOTTOM OF TRENCH MUST BE THOROUGHLY TAMPED. CABLE MUST BE POSITIONED FIRMLY AGAINST TAMPED EARTH DURING BACKFILLING. AFTER BACKFILLING AND BEFORE CABLE IS CUT, PUSH CABLE BACK DOWN INTO DIP TO PROVIDE AS MUCH SLACK AS POSSIBLE. 7. FOR SECONDARY CABLE, CABLE TO BE LOOPED UP AND THE ENDS TAPED TO PREVENT MOISTURE ENTRANCE AT THE TOP OF THE DIP. THIS INCLUDES THE CABLE NEUTRAL. 8. USE 1/4" X 2" WASHER HEAD LAG SCREWS ( ITEM # 10311900) FOR THE INSTALLATION OF CONDUIT STRAPS. 9. PRIMARY AND SECONDARY CONDUCTORS SHALL BE PLACED IN SEPARATE RISERS. 10. SEE DWG. 06.03-05 FOR TRANSFORMER DETAILS. 11. DO NOT INSTALL RISER BENEATH TRANSFORMER. 4'-0" 12" 4'-0" 12" 4'-0" 12" SEE NOTE 2 4'-0" FINAL GRADE 12" MIN. 12" SEE DWG. 22.02-01 3 2 1 0 9/4/15 8/6/14 ROBESON EANES ADCOCK DEC DEM EANES EANES ADCOCK 9/29/11 ROBESON BURLISON ELKINS 5/11/10 DANNA GUINN REVISED BY CK'D ELKINS APPR. #1/0 PRIMARY AND SECONDARY CABLE DIP POLE PVC SCH. 40 CONDUIT POLE RISERS DEP DEF X 21.04-01 "THIS DOCUMENT CONTAINS INTELLECTUAL, DESIGN, OR COPY WRITE PROPERTY OF SOUTHERN CURRENT LLC WHICH IS PRIVILEGED OR CONFIDENTIAL AND IS NOT TO BE REPRODUCED, DISCLOSED, USED IN ANY MANNER OR DISTRIBUTED WITHOUT WRITTEN PERMISSION OF SOUTHERN CURRENT LLC" "THIS DOCUMENT CONTAINS INTELLECTUAL, DESIGN, OR COPY WRITE PROPERTY OF SOUTHERN CURRENT LLC WHICH IS PRIVILEGED OR CONFIDENTIAL AND IS NOT TO BE REPRODUCED, DISCLOSED, USED IN ANY MANNER OR DISTRIBUTED WITHOUT WRITTEN PERMISSION OF SOUTHERN CURRENT LLC" REVISION DESCRIPTIONAPRV'DNODATEBYFLOWERS SOLAR3188 BAILEYS CROSSROADS ROADBENSON, NC 275124.34 MW AC - SOLAR PV SYSTEMMEDIUM VOLTAGE DETAILS (PG-2)D - Engineering Standards 88420DUK Carolinas BILL OF MATERIALS MACRO UNIT BUBBLE # COMPATIBLE UNIT 1 4 6 WILDLIFE GUARD EQUIP BRACKET CU/LA BRACKET CO BACK TO BACK CU QTY 6 3 3 ITEM # 50125214 1412032 938532 81207 50094140 938532 7 25POSTINSJUMPER 1 214569 930031 930913 939033 50125921 931683 931563 930030 50124437 8 PRIMARY METER KIT SE XARM SINGLE 8FT DUK 1 932802 930563 938540 9 10 15 16 17 18 19 20 21 22 2 ARRESTER 10KV ARRESTER 18KV 0740 23 0750 11 0441049 0441067 27 4 3 4 3 4 3 4 3 4 3 4 3 4 3 4 3 0234697 1710 1660 1670 1680 1720 1690 1691 1692 3 or 9 3 3 50 6 6 6 6 6 6 6 6 6 6 3 or 9 BRACKET ARRESTER PM EQPT GROUND 6CU SE 6 1 930031 939033 1461188 50061955 938540 234664 39416 61350 1490676 933366 204211 63253 50119825 1001804 1000577 279453 1000574 71494 441049 441067 1455647 933034 203614 933034 203617 933034 203618 933034 203619 933034 203615 933034 203620 933034 203622 933034 203621 ITEM QTY/ CU DESCRIPTION 1 GUARD, WILDLIFE, 5-1/4" DIA X 5-1/2" HT, ULTRA VIOLET RESISTANT POLYMER, COVERS BUSHING 1 BRACKET, CROSSARM MOUNTING, 3/8" THK, W/ FRONT & BACK PLATES, (2) 3/8" CARRIAGE BOLTS, NUTS & LOCKNUTS, 1/2" C 2 WASHER,LOCK,SPRING,3/8",7/16" ID,1/8" THK,GALV STL,GR B 2 BRACKET, POLE MOUNTING, 9" LG X 6" HT, GALV STL, ANGLE L 3/8" THK X 2" WD 2 BOLT,CARRIAGE,3/8" DIA,16 UNC,8" LG,HOT DIP GALV STL 2 WASHER,LOCK,SPRING,3/8",7/16" ID,1/8" THK,GALV STL,GR B TIE,INSULATOR:F NECK INSULTR,2-7/8" INSULTR DIA,2 AWG TO 2/0 AWG COVERED CU COND,0.412" TO 0.539" DIA RANGE,COMPOSITE,DBL SIDE,ANSI CLASS 57-1,CONDUCTOR COLOR CODE WHITE 1 WASHER,LOCK:DOUBLE COIL SPRING,3/4",DYKO PLTD GALV STL 1 1 BOLT,DOUBLE ARMING, 3/4" DIA, 14" LG, GALV STL, THD UNC ROLLED CONE PT, FULL THD, W/ (4) SQ NUTS 2 WASHER:SQUARE,3/4",2-1/4" ID,2-1/4" OD,3/16" THK,GALV 1 INSULATOR:LINE POST,25KV,6" DIA X 8.5" LG,LIGHT GRAY PORCELAIN,MUNSELL ANSI 57.1 1 BOLT,MACHINE, 3/4" DIA, 10 UNC, 16" LG, SQ HEAD, HOT DIP GALV CS, ASTM A307, W/ NUT, 6" MIN THD LG 1 BOLT,MACHINE, 5/8" DIA, 11 UNC, 12" LG, SQ HEAD, HOT DIP GALV STL, CONE PT, 6" THD LG, W/ SQ NUT 1 WASHER,LOCK, DBL COIL SPRING, 5/8", GALV STL, 750 PER PACKAGE 1 1 2 1 CROSSARM,POLE, 3-1/2" X 4-1/2", 8' LG, PENTACHLOROPHENOL TREATED, SOL FIR/PINE, (6) PIN, 11/16" HOLES, W/ (2) BRACE,POLE, CROSSARM, WOOD, PURCHASED & STOCKED IN PAIRS; W/ METAL END FITTINGS, 9/16" HOLE @ CROSSARM, 11/16" BOLT,CARRIAGE, 1/2" DIA, 13 UNC, 7" LG, HOT DIP GALV STL, ASTM A153, GR 2, CGE DRG. 819A, CGE SIN - 050061923 2 WASHER,LOCK, SPRING, 1/2", 0.512" ID, 0.869" OD, 0.125" THK, GALV STL, ASTM A153, GR B WASHER,LOCK, DBL COIL SPRING, 3/4", DYKO PLTD GALV STL, ELECTRIC MATERIALS ORDER BY PRESCRIPTION EMERGENCY ALT 3 WASHER, SQ, 3/4", 2-1/4" ID, 2-1/4" OD, 3/16" THK, GALV STL, ASTM A153, GR AISI-1018 1 BRACKET, METER, 1.25" WD X 7" LG X .375" THK, ALUM, F/ ARRESTOR MOUNTING 1 BOLT,MACHINE:1/2" DIA,2" LG,HEX HD,GALV STL,GR 2,W/ HEX NUTS 1 WASHER,LOCK, SPRING, 1/2", 0.512" ID, 0.869" OD, 0.125" THK, GALV STL, ASTM A153, GR B 20 WIRE/CABLE,ELECTRICAL,BARE:SOL SD,6 AWG,CU 1 BRACKET, TRANSFORMER CLUSTER MOUNTING, GALV STL, F/ INSTRUMENT TRANSFORMER USED IN PRIMARY METERING F/ SYSTEM 30 CONDUIT:RIGID,HEAVY WALL,1",8' LG,SCH 40,GRAY PVC,COUPLED OR BELLED ONE END,90 DEG C WIRING 0.1 STAPLE, 1-1/2" LG, STL, 8 GA - .162" DIA, BEZINAL COATED, 8 LB PLASTIC PAILS 1 12 CONNECTOR,ELECTRICAL:H-TYPE,1/0 AWG 6 X 1 STR ACSR,2 AWG 7 STR AA COND,0.398"-0.268",0.332"-0.169" WIRE SIZE 8 STRAP,CONDUIT:2 HOLE,1" CONDUIT,GALV STL,5/16" HOLES CONNECTOR,ELECTRICAL,TERMINAL:LUG,8 AWG SOL-2/0 AWG STR COND,CU CONNECTOR,W/ BRZ FLAT WASHER 1 END,CONDUIT:THINWALL,RIGID,1",ALUM,COMPRESSION CLAMP,WEATHERHEAD,5 KNOCKOUTS 1 TAPE,ELECTRICAL,HIGH VOLTAGE,2" WD X 30' LG X 30 MIL THK,LINELESS,THERMAL ARRESTERS 1 1 1 1 1 1 1 ARRESTER,ELECTRICAL, METAL OXIDE, DISTRIBUTION, 8.4KV, HEAVY DUTY, LIGHTNING, 10KV, POLYMER HOUSING, SURGE, STD LINE ARRESTER,ELECTRICAL, METAL OXIDE, DISTRIBUTION, 15.3KV, 18KV, POLYMER HOUSING, HD, LIGHTNING, PER DUKE SPEC PA CUTOUTS CUTOUT,FUSE, NON-LOADBREAK, 100A, 10KAIC, 14.4KV, 110KV BIL, W/ NON-EXPENDABLE CAP UNIT, PARALLEL GROOVE CUTOUT,FUSE, LOADBREAK, 100A, 8KAIC, 25KV, 125KV BIL, W/ NON-EXPENDABLE CAP UNIT, PARALLEL GROOVE CONNECTOR, PT'S TRANSFORMER,INSTRUMENT, VOLTAGE, 60:1 RATIO, 7200/120V, OUTDOOR, DBL LOOP CORE, 110KV BIL, ACCURACY 0.3 W, X, TRANSFORMER,INSTRUMENT, VOLTAGE, 120:1 RATIO, 14400V, OUTDOOR, POLYURETHANE CORE, 125KV BIL, 0.3 W, X, M, Y AC JUMPERS WIRE/CABLE,ELECTRICAL, 2/0 AWG, SOFT DRAWN CU, POLY COVER, BLACK, DESIGNED, MFR, TESTED & PACKAGED PER DUKE SP CONNECTORS 1 CLAMP,HOT LINE, 8 AWG SOL-2/0 AWG STR LINE, 8 AWG SOL-2/0 AWG STR TAP, BRZ/CU 1 STIRRUP,4 AWG SOL-2/0 AWG STR COND,CU 1 CLAMP,HOT LINE, 8 AWG SOL-2/0 AWG STR LINE, 8 AWG SOL-2/0 AWG STR TAP, BRZ/CU 1 STIRRUP,COMPRESSION,4 AWG ACSR COND,ALUM,PREFILLED W/ INHIBITOR 1 CLAMP,HOT LINE, 8 AWG SOL-2/0 AWG STR LINE, 8 AWG SOL-2/0 AWG STR TAP, BRZ/CU 1 STIRRUP,COMPRESSION,2 AWG ACSR COND,ALUM,PREFILLED W/ INHIBITOR 1 CLAMP,HOT LINE, 8 AWG SOL-2/0 AWG STR LINE, 8 AWG SOL-2/0 AWG STR TAP, BRZ/CU 1 STIRRUP,COMPRESSION,1/0 AWG ACSR COND,ALUM,PREFILLED W/ INHIBITOR 1 CLAMP,HOT LINE, 8 AWG SOL-2/0 AWG STR LINE, 8 AWG SOL-2/0 AWG STR TAP, BRZ/CU 1 STIRRUP,1 AWG SOL-250 MCM STR COND,CU 1 CLAMP,HOT LINE, 8 AWG SOL-2/0 AWG STR LINE, 8 AWG SOL-2/0 AWG STR TAP, BRZ/CU 1 STIRRUP,COMPRESSION,4/0 AWG ACSR COND,ALUM,W/ INHIBITOR 1 CLAMP,HOT LINE, 8 AWG SOL-2/0 AWG STR LINE, 8 AWG SOL-2/0 AWG STR TAP, BRZ/CU 1 1 STIRRUP, COMPRESSION, 0.666" DIA, 336.4 MCM COND, ALUM, DUKE MARKED #WITH, HIGH CONDUCTIVE, W/ FACTORY INSTALL 1 CLAMP,HOT LINE, 8 AWG SOL-2/0 AWG STR LINE, 8 AWG SOL-2/0 AWG STR TAP, BRZ/CU STIRRUP, COMPRESSION, 0.856" DIA, 556 MCM COND, ALUM, DUKE MARKED #WITH, HIGH CONDUCTIVE, W/ FACTORY INSTALLED 4kV - 25kV Primary Metering Overhead To Overhead Wye Construction 1519 King St. Charleston, S.C. 29405 T.JONES01/18/20181ISSUED FOR CONSTRUCTIOND.BRUECK M POINT OF DELIVERY TO PV SYSTEM CUSTOMER-OWNED FACILITIES PRIMARY CT'S AND PT'S BY CONTRACTOR 100A, 120/240V NEMA 3R BREAK PANEL W/ 60A/2P MAIN BREAKER (4) x 20A/2P BREAKERS UPS ENCLOSURE MAIN MAIN COMMUNICATION ENCLOSURE WITH AUX SUPPLY LIGHTNING ARRESTOR/ CUT OUT FUSED AT 1.25A #6 WP CU NEUTRAL CUSTOMER METER 1" PVC CONDUIT #6AWG WIRE 10KVA SINGLE PHASE TRANSFORMER 1/2" PVC CONDUIT FOR DATA WIRE CUSTOMER POLE MOUNTED METER CUSTOMER POLE MOUNTED TRANSFORMER 1/2" PVC DONDUIT FOR DATA WIRE NOTE: CONDUIT TO BE SCHD 40 PVC BELOW GROUND AND SCHD 80 PVC ABOVE GROUND FIBER IN 2" PVC CONDUIT 1/2" PVC CONDUIT FOR #14AWG WIRE TO TRANSFORMER PAD #1 T.JONES01/15/20180ISSUED FOR PERMITD.BRUECK"THIS DOCUMENT CONTAINS INTELLECTUAL, DESIGN, OR COPY WRITE PROPERTY OF SOUTHERN CURRENT LLC WHICH IS PRIVILEGED OR CONFIDENTIAL AND IS NOT TO BE REPRODUCED, DISCLOSED, USED IN ANY MANNER OR DISTRIBUTED WITHOUT WRITTEN PERMISSION OF SOUTHERN CURRENT LLC" "THIS DOCUMENT CONTAINS INTELLECTUAL, DESIGN, OR COPY WRITE PROPERTY OF SOUTHERN CURRENT LLC WHICH IS PRIVILEGED OR CONFIDENTIAL AND IS NOT TO BE REPRODUCED, DISCLOSED, USED IN ANY MANNER OR DISTRIBUTED WITHOUT WRITTEN PERMISSION OF SOUTHERN CURRENT LLC" REVISION DESCRIPTIONAPRV'DNODATEBYFLOWERS SOLAR3188 BAILEYS CROSSROADS ROADBENSON, NC 275124.34 MW AC - SOLAR PV SYSTEMMEDIUM VOLTAGE DETAILS (PG-3)GROUNDING DETAILS 120/240 GROUNDING STRAP #6 WP CU SEE NOTE 2 5-1/2" 12" MIN. #6 WP CU ANY TYPE SINGLE-PHASE TRANSFORMER 12" FOR 50 KVA & BELOW (24" FOR 75 KVA & ABOVE) NEUTRAL 4" MIN. 30" MIN. CONDUIT/U-GUARD MUST BE 40" MIN. ABOVE JOINT USE 40" MIN. CLEARANCE FROM NEUTRAL/ SECONDARY TO JOINT USE JOINT USE FRONT VIEW NOTES: 1. MINIMUM BOLT HOLE SPACING IS 4"; NO HOLES SHOULD BE DRILLED CLOSER THAN 4". 2. THE CUTOUT CAN BE MOUNTED AT VARIOUS HEIGHTS AND/OR POSITIONS ON THE POLE FOR EASE OF INSTALLATION AND OPERATION. 3. THE BOTTOM OF THE TRANSFORMER TANK MUST MAINTAIN 30 INCHES OF CLEARANCE ABOVE JOINT USE CABLES. 3 2 1 0 5/23/12 ROBESON REVISED BY CK'D GUINN ELKINS7/9/10 SIMMONS APPR. BURLISON ELKINS SINGLE-PHASE TRANSFORMER MOUNTING DIMENSIONS DWG. 06.06-04 1519 King St. Charleston, S.C. 29405 T.JONES01/18/20181ISSUED FOR CONSTRUCTIOND.BRUECK INVERTER #XX 1,040A 350V 1,242A 703V 957V 1,665A N/A BentekSolar COMBINER BOX #XX 207A 703V 957V 277A N/A CAUTION SOUTHERN CURRENT LLC. MAIN PV DISCONNECT LOCATED AT MANUAL GANG SWITCH LOCATIONS OF SERVICE AND PV SYSTEM DISCONNECTS S E N W N NOTES: 1. TO BE PLASTIC PLACARD WITH ENGRAVED LETTERS. 2. TO BE PLACED ON FENCE GATE AT ENTRANCE TO SITE SOLAR PV ARRAYS LOCATED WITHIN SECURITY FENCE. INVERTERS WITH AC AND DC DISCONNECTS FOR PHOTOVOLTAIC SYSTEM LOCATED ON CONCRETE PADS. 085/08/2 091/08/2 PM PM RCLBAILEYS CROSSROADS ROAD PV LABEL SCHEDULE (NEC 2014) MANUFACTURER PART #QTY DESCRIPTION N/A N/A 1 Placard, Additional power source label, 8" x 8", Polyester, Red. Hellermann Tyton 596-00588 49 Pre-Printed Solar Label, "WARNING - DC CONDUCTORS OF THIS PHOTOVOLTAIC...", 4.125" X 2.0", Vinyl, Orange/White. Hellermann Tyton 596-00497 7 Pre-Printed Solar Label, "WARNING - ELECTRICAL SHOCK HAZARD", 3.75" X 2.0", Vinyl, Orange/White. Hellermann Tyton 596-00499 7 Pre-Printed Solar Label, "WARNING - TURN OFF PV BEFORE WORKING..", 4.125" X 2", Vinyl, Orange/White. Hellermann Tyton 596-00239 7 Solar Label, Printable, PHOTOVOLTAIC AC DISCONNECT, 3.75" x 1.0", Polyester, Red. Hellermann Tyton 596-00613 1 Pre-Printed Solar Label, Reflective, "SOLAR ELECTRIC SYSTEM CONNECTED", 6.5" X 1.0", Yellow. Hellermann Tyton 596-00238 7 Solar Label, Printable, 2017 Code, PHOTOVOLTAIC DC DISCONNECT, 3.75" x 1.0", PET, Red. Hellermann Tyton 558-00381 42 Printable Solar Label, ARC FLASH & SHOCK HAZARD, 3.75" X 2.0", Polyester, Orange/White. Hellermann Tyton 596-00496 42 Solar Label, WARNING ELECTRICAL SHOCK HAZARD…DC VOLTAGE, 3.75" x 2.5", Vinyl, Orange/White, Hellermann Tyton 596-00253 7 Solar Label, Printable, DC Module, 4.0" x 2.0", Polyester, Red. Hellermann Tyton 596-00244 7 Solar Label, Reflective, 2017 Code, DO NOT DISCONNECT UNDER LOAD, 6.5" x 1.0", Vinyl, Red. Hellermann Tyton 558-00309 7 Adhesive Labels, Solid Color Continuous Roll, 1.0" x 250', Vinyl, White. Hellermann Tyton 558-00313 7 Adhesive Labels, Solid Color Continuous Roll, 2.0" x 250', Vinyl, White. Hellermann Tyton 558-00309 42 Adhesive Labels, Solid Color Continuous Roll, 1.0" x 250', Vinyl, White. N/A N/A 60 Placard, "DANGER: HIGH VOLTAGE...", 7" x 10", 0.55" Polythylene Plastic, Red/White/Black. ELECTRIC POWER SOURCE DIRECTORY (SEE DETAIL) THIS PANEL FED FROM COMBINER BOX X-XX INVERTER #XX COMBINER BOX #XX M ELECTRIC POWER SOURCE DIRECTORY (SEE DETAIL) MOUNTED EVERY 100' "THIS DOCUMENT CONTAINS INTELLECTUAL, DESIGN, OR COPY WRITE PROPERTY OF SOUTHERN CURRENT LLC WHICH IS PRIVILEGED OR CONFIDENTIAL AND IS NOT TO BE REPRODUCED, DISCLOSED, USED IN ANY MANNER OR DISTRIBUTED WITHOUT WRITTEN PERMISSION OF SOUTHERN CURRENT LLC" "THIS DOCUMENT CONTAINS INTELLECTUAL, DESIGN, OR COPY WRITE PROPERTY OF SOUTHERN CURRENT LLC WHICH IS PRIVILEGED OR CONFIDENTIAL AND IS NOT TO BE REPRODUCED, DISCLOSED, USED IN ANY MANNER OR DISTRIBUTED WITHOUT WRITTEN PERMISSION OF SOUTHERN CURRENT LLC" REVISION DESCRIPTIONAPRV'DNODATEBYFLOWERS SOLAR3188 BAILEYS CROSSROADS ROADBENSON, NC 275124.34 MW AC - SOLAR PV SYSTEMLABEL PLAN'PV' LABELS - INVERTER SCALE: NTS NOTES: ALL SIGNAGE SHALL MEET THE REQUIREMENTS BELOW: 1.BE LABEL TYPE (LAMINATED STICKER WITH POLYESTER FILM) OR PLACARD TYPE (MIN. 1/16” PLASTIC PLACARD WITH ENGRAVED LETTERS). 2.APPLICATION BY ADHESIVE BACK, WITH ADHESIVE SUITABLE FOR LIFE OF PV SYSTEM. 3.LISTED TO UL 969 4.REFLECTIVE AND SUITABLE FOR THEIR ENVIRONMENT. SIGNAGE LOCATED OUTSIDE SHALL BE SUITABLE FOR DIRECT SUNLIGHT, RAIN, SNOW, ICE, FOG, AND SALT AIR WITH A MINIMUM TEMPERATURE RATING OF -40 TO 176 DEG F 5.RED BACKGROUND, WHITE LETTERING 6.LETTERING SHALL BE ALL CAPITAL LETTERS WITH ARIAL OR SIMILAR FONT, NON-BOLD 'PV' LABELS - DC COMBINER BOX SCALE: NTS 'PV' LABELS - ELECTRIC POWER SOURCE DIRECTORY SCALE: NTS 'PV' LABELS - COMPANY METER SCALE: NTS SEE FIG. 71B ON PG. 020 'PV' LABELS - SECURITY FENCE SCALE: NTS 1519 King St. Charleston, S.C. 29405 T.JONES01/15/20180ISSUED FOR PERMITD.BRUECKT.JONES01/18/20181ISSUED FOR CONSTRUCTIOND.BRUECK CONCRETE PAD CONDUIT CUTOUT (TYP.) #3/0 BARE CU GROUND CONDUCTOR (TYP.) CONNECT EQUIPMENT PAD REBAR TO GROUND RING WITH #3/0 BARE CU GROUND CONDUCTOR (TYP.) 3/4" x 10' LONG GROUND ROD (TYP.)NETWORK ENCLOSURETOP VIEWUPS ENCLOSURETOP VIEW MAIN COMM ENCLOSURETOP VIEW IRREVERSIBLE CONNECTION (TYP.) MAIN COMMUNICATION ENCLOSURE AND UPS ENCLOSURE INCLUDED ONLY ON PAD #1 #3/0 BARE CU (TYP.) TO TX TO UPS ENCLOSURE TO NETWORK ENCLOSURE FENCE POST WITH POST CAPS 4'-31 8" 2'-33 8" UNISTRUT ADEQUATE TO SUPPORT EQUIPMENT MOUNTED TO FENCE POST WITH U-BOLT. UNISTRUT SHALL HAVE END CAPS.EQUIPMENT SHALL BE SECURED TO UNISTRUT USING 3/8" DIA HARDWARE HORIZONTAL UNISTRUT CHANNEL AND CONDUIT STRAPS AS REQUIRED FOR SECURING CONDUIT TO TX TO INV TO INV TO MAIN COMM. ENCLOSURE TO NEXT TX PAD 1'-33 4" 1'-33 4" HORIZONTAL UNISTRUT CHANNEL AND CONDUIT STRAPS AS REQUIRED FOR SECURING CONDUIT FENCE POST WITH POST CAPS UNISTRUT ADEQUATE TO SUPPORT EQUIPMENT MOUNTED TO FENCE POST WITH U-BOLT. UNISTRUT TO HAVE END CAPS. EQUIPMENT SHALL BE SECURED TO UNISTRUT USING 3/8" DIA HARDWARE TO MINI POWER ZONE TO MAIN COMM. ENCLOSURE 1'-115 8" 1'-33 4" HORIZONTAL UNISTRUT CHANNEL AND CONDUIT STRAPS AS REQUIRED FOR SECURING CONDUIT FENCE POST WITH POST CAPS UNISTRUT ADEQUATE TO SUPPORT EQUIPMENT MOUNTED TO FENCE POST WITH U-BOLT. UNISTRUT TO HAVE END CAPS. EQUIPMENT SHALL BE SECURED TO UNISTRUT USING 3/8" DIA HARDWARE TO UPS ENCLOSURE TO PYRANOMETER TO ANEMOMETER TO MODULE TEMPERATURE SENSORS 1'-33 4" 1'-33 4" HORIZONTAL UNISTRUT CHANNEL AND CONDUIT STRAPS AS REQUIRED FOR SECURING CONDUIT FENCE POST WITH POST CAPS UNISTRUT ADEQUATE TO SUPPORT EQUIPMENT MOUNTED TO FENCE POST WITH U-BOLT. UNISTRUT TO HAVE END CAPS. EQUIPMENT SHALL BE SECURED TO UNISTRUT USING 3/8" DIA HARDWARE 0ISSUED FOR PERMITJ.WILSON1519 King Street Charleston, SC 29405 "THIS DOCUMENT CONTAINS INTELLECTUAL, DESIGN, OR COPY WRITE PROPERTY OF SOUTHERN CURRENT LLC WHICH IS PRIVILEGED OR CONFIDENTIAL AND IS NOT TO BE REPRODUCED, DISCLOSED, USED IN ANY MANNER OR DISTRIBUTED WITHOUT WRITTEN PERMISSION OF SOUTHERN CURRENT LLC" "THIS DOCUMENT CONTAINS INTELLECTUAL, DESIGN, OR COPY WRITE PROPERTY OF SOUTHERN CURRENT LLC WHICH IS PRIVILEGED OR CONFIDENTIAL AND IS NOT TO BE REPRODUCED, DISCLOSED, USED IN ANY MANNER OR DISTRIBUTED WITHOUT WRITTEN PERMISSION OF SOUTHERN CURRENT LLC" REVISION DESCRIPTIONAPRV'DNODATEBYFLOWERS SOLAR3188 BAILEYS CROSSROADS ROADBENSON, NC 275124.34 MW AC - SOLAR PV SYSTEMGROUND RING AND MONITORING DETAILCONCRETE PAD EQUIPMENT GROUNDING AND GROUND RING SCALE: 1" = 2'T.JONES01/15/20182 021 MINI POWER ZONE SCALE: 1"=1' NETWORK ENCLOSURE UPS ENCLOSURE MAIN COMMUNICATION ENCLOSURE 3 021 5 021 4 021 SCALE: 1"=1'SCALE: 1"=1'SCALE: 1"=1' NOTE: ·MOUNT WEATHER STATION EQUIPMENT PER MANUFACTURER'S SPECIFICATIONS. ·SEE MONITORING DIAGRAM FOR CONDUIT SIZES.0ISSUED FOR CONSTRUCTIONJ.WILSONT.JONES01/18/2018