STRUCTURAL PLANSw w w . l i t t l e o n l i n e . c o m
This drawing and the design shown are the property
of Little Diversified Architectural Consulting. The
reproduction, copying or other use of this drawing
without their written consent is prohibited and any
infringement will be subject to legal action.
Little 2016c
PROJECT MANAGER
DESIGN TEAM
PRINCIPAL IN CHARGE
PROJECT TEAM
REVISIONS
PROJECT NAME
SHEET TITLE
PROJECT NO.
SHEET NUMBER
ISSUE FOR
ISSUE DATE
410 Blackwell St. Suite 10
Durham, NC 27701
T: 919-474-2500
10/06/17
10/9/2017 3:30:53 PM C:\Users\katie.buckman\Documents\513.7505.00_CU_WrestlingExpansion_A-16_katie.buckman.rvt513.7505.00
CS
COVER SHEET
Campbell Convocation
Center Wrestling
Department Renovation
and Expansion
BID/PERMIT SET
Rob Klinedinst
Katie Buckman
Anne Lebo
Campbell Convocation Center Wrestling Department
Renovation and Expansion
56 Main Street, Buies Creek, NC 27506
BID/PERMIT SET - 10/06/17
OWNER
Campbell University
143 Main Street
Buies Creek, NC 27506
919-893-1200
Jim Roberts
ARCHITECT
Little
410 Blackwell St. Suite 10
Durham, NC 27701
919-474-2500
Katie Buckman, AIA
FIRE PROTECTION
Little
410 Blackwell St. Suite 10
Durham, NC 27701
919-474-2500
Miles Grubbs, PE
MECHANICAL
Little
410 Blackwell St. Suite 10
Durham, NC 27701
919-474-2500
Miles Grubbs, PE
ELECTRICAL/ FA
Little
410 Blackwell St. Suite 10
Durham, NC 27701
919-474-2500
Melissa Taylor, PE
07 - PLUMBING
P0.0.1 PLUMBING GENERAL NOTES, SCHEDULES, AND
DETAILS
PD101 PLUMBING DEMOLITION FLOOR PLAN
P1.1.1 PLUMBING DRAINAGE PLAN - LEVEL 1
P1.2.1 PLUMBING PIPING PLAN - LEVEL 1
P1.3.1 PLUMBING ROOF PLAN
P7.1.1 PLUMBING RISER
08 - FIRE SUPPRESSION
FS1.0.1 FIRE PROTECTION PLAN - LEVEL 1
09 - MECHANICAL
M0.0.1 MECHANICAL GENERAL NOTES & LEGEND
M1.1.1 MECHANICAL DUCTWORK PLAN - LEVEL 1
M1.1.2 MECHANICAL PLAN - ROOF
M5.0.1 MECHANICAL DETAILS
M6.0.1 MECHANICAL SCHEDULES AND CONTROL DIAGRAM
10 - ELECTRICAL
E0.0.0 ELECTRICAL COVERSHEET
ED1.1.1 DEMOLITION POWER PLAN - CONVOCATION AREA C
ED1.2.1 DEMOLITION LIGHTING PLAN - CONVOCATION AREA C
E1.1.1 POWER PLAN - CONVOCATION AREA C
E1.2.1 LIGHTING PLAN - CONVOCATION AREA C
E1.3.1 MECHANICAL POWER PLAN - CONVOCATION AREA C
E5.1.1 ELECTRICAL DETAILS
E5.1.2 ELECTRICAL DETAILS
E6.0.0 LIGHTING FIXTURE SCHEDULE
E7.0.0 SINGLE LINE DIAGRAM
E7.0.1 PANEL SCHEDULES
11 - FIRE ALARM
FA0.0.0 FIRE ALARM COVERSHEET
FAD1.1.1 FIRE ALARM DEMOLITION PLAN - CONVOCATION AREA C
FA1.1.1 FIRE ALARM PLAN - CONVOCATION AREA C
01-GENERAL / LIFE SAFETY
CS COVER SHEET
G0.0.1 BUILDING CODE SUMMARY
G0.1.1 FIRE RESISTANCE DESIGNS
G1.1.1 LIFE SAFETY PLAN - LEVEL 01
04 - ARCHITECTURE
AD1.1.1 DEMOLITION FLOOR PLAN
AD1.1.2 DEMOLITION ROOF PLAN
AD1.2.1 DEMOLITION REFLECTED CEILING PLAN
A0.1.0 WALL TYPES
A1.1.1 FLOOR PLAN AREA C
A1.1.2 FLOOR PLAN AREA D
A1.1.3 ROOF PLAN
A1.2.1 REFLECTED CEILING PLAN
A2.1.0 EXTERIOR ELEVATIONS
A2.1.1 EXTERIOR ELEVATIONS
A2.2.0 FRAMING SYSTEM ELEVATIONS
A3.1.0 BUILDING SECTIONS
A3.2.0 WALL SECTIONS
A3.2.1 WALL SECTIONS
A4.0.0 ENLARGED PLANS AND INTERIOR ELEVATIONS
A8.1.1 FINISH SCHEDULE
A9.0.0 DOOR SCHEDULE AND DETAILS
06 - STRUCTURAL
S0.0.1 GENERAL NOTES
S0.0.2 STATEMENT OF SPECIAL INSPECTIONS
S1.0.1 CONVOCATION AREA C FOUNDATION PLAN
S1.0.2 CONVOCATION AREA C ROOF FRAMING PLAN
S2.0.1 MASONRY DETAILS
S3.0.1 FOUNDATION DETAILS
S3.1.1 FRAMING DETAILS
S3.1.2 FRAMING DETAILS
SUSP CLG SUSPENDED CEILING
SV SHEET VINYL
SYS SYSTEM
TEMP TEMPERED, TEMPORARY
TME TO MATCH EXISTING
TYP TYPICAL
UNO UNLESS NOTED OTHERWISE
VB VINYL BASE
VCT VINYL COMPOSITE TILE
VERT VERTICAL(LY)
VIF VERIFY IN FIELD
VIN VINYL
VT VINYL TILE
W WIDTH
W/ WITH
W/O WITHOUT
WB WOOD BASE
WC WATER CLOSET
WD WOOD
WGT WEIGHT
WIN WINDOW
WTW WALL TO WALL
PFN PREFINISH(ED)
PL, PLAM PLASTIC LAMINATE
PLAS PLASTER, PLASTIC
PLWD PLYWOOD
PNL PANEL
PNT PAINT(ED)
PR PAIR
PT PRESSURE TREAT(ED)
PTN PARTITION
RB RUBBER BASE
RBT RUBBER TILE
REC RECEPTACLE
REF REFERENCE, REFER
REFR REFRIGERATOR
REM REMOVE
REQ'D REQUIRED
RM ROOM
RS RESILIENT
SCW SOLID CORE WOOD
SECT SECTION
SF SQUARE FEET
SFRM SPRAYED FIRE RESISTIVE MATERIAL
SHR SHOWER
SIM SIMILAR
SPEC SPECIFICATION(S)
SS STAINLESS STEEL
SSM SOLID SURFACE MATERIAL
ST STONE
STD STANDARD
STOR STORAGE
SUSP SUSPENDED
LBL LABEL
LCKR LOCKER
LIN LINOLEUM
LT LIGHT
LVL LAMINATED VENEER LUMBER
LVT LUXURY VINYL TILE
MATL MATERIAL(S)
MAX MAXIMUM
MB MARKER BOARD
MECH MECHANICAL
MFR MANUFACTURE(R)
MIN MINIMUM
MISC MISCELLANEOUS
MP METAL PANEL
MTD MOUNTED
MTL METAL
MULL MULLION
MWK MILLWORK
N NORTH
NIC NOT IN CONTRACT
NO, # NUMBER
NR NOISE REDUCTION
NRC NOISE REDUCTION COEFFICIENT
NTS NOT TO SCALE
OC ON CENTER
OFF OFFICE
OH OPPOSITE HAND
OPNG OPENING
PED PEDESTAL, PEDESTRIAN, PEDIATRIC
PERF PERFORATE(D)
PFB PREFABRICATE(D)
FUT FUTURE
FWC FABRIC WALL COVERING
FWP FABRIC WRAPPED PANEL
GA GAUGE
GALV GALVANIZED
GB GLASS BOARD
GC GENERAL CONTRACTOR
GL GLASS, GLAZING
GR GROUT
GRAN GRANITE
GWB GYPSUM WALL BOARD
GYP GYPSUM
HC HOLLOW CORE
HDR HEADER
HDW HARDWARE
HGT HEIGHT
HORIZ HORIZONTAL(LY)
HR HOUR
HVAC HEATING, VENTILATION, AND AIR
CONDITIONING
HWD HARDWOOD
IBC INTERNATIONAL BUILDING CODE
ID INSIDE DIAMETER
INCL INCLUDE(D), (ING)
INSUL INSULATE(D), (ING)
INT INTERIOR
JAN JANITOR'S CLOSET
JT JOINT
KPL KICK PLATE
L LENGTH
LAM LAMINATE(D)
DIM DIMENSION
DR DOOR
DS DOWNSPOUT
DWG DRAWING(S)
DWN DOWN
EA EACH
EL ELEVATION
ELEC ELECTRICAL
EOS EDGE OF SLAB
EP EPOXY FLOORING
EQ EQUAL(LY)
EQPT EQUIPMENT
EW EACH WAY
EWC ELECTRIC WATER COOLER
EXIST EXISTING
EXP EXPANSION
EXT EXTERIOR
FAAP FIRE ALARM ANNUNCIATOR PANEL
FBO FURNISHED BY OTHERS
FE FIRE EXTINGUISHER
FEC FIRE EXTINGUISHER CABINET
FF FINISH FLOOR
FIN FINISH(ED)
FLR FLOOR(ING)
FO FACE OF
FOB FACE OF BRICK
FOG FACE OF GLASS
FOS FACE OF SHEATHING
FR FIRE RETARDANT TREATED
FT FOOT, FEET
FURR FURR(ED), (ING)
ACT ACOUSTIC CEILING TILE
ADA AMERICANS WITH DISABILITIES ACT
ADJ ADJUSTABLE
AFF ABOVE FINISH FLOOR
AL ALUMINUM
ALT ALTERNATE
APPROX APPROXIMATE
ARCH ARCHITECT(URAL)
BD BOARD
BO BOTTOM OF
C/L, CL CENTERLINE
CAB CABINET
CLG CEILING
CLOS CLOSET
CLR CLEAR(ANCE)
COL COLUMN
CON,
CONC
CONCRETE
CONST CONSTRUCTION
CONT CONTINUOUS / CONTINUE
CONTR CONTRACTOR
COORD COORDINATE
CPT CARPET
CRB COVED RUBBER BASE
CT CERAMIC OR PORCELAIN TILE
CTR CENTER
DBL DOUBLE
DEG DEGREE
DEMO DEMOLISH / DEMOLITION
DET, DTL DETAIL
DIA DIAMETER
STRUCTURAL
Little
410 Blackwell St. Suite 10
Durham, NC 27701
919-474-2500
David Blankfard, PE
PLUMBING
Little
410 Blackwell St. Suite 10
Durham, NC 27701
919-474-2500
Miles Grubbs, PE
NO. REASON DATE
PROJECT LOCATION:
JOHN W. POPE JR. CONVOCATION CENTER
56 MAIN ST., BUIES CREEK, NC 27506
Lighting schedule (each fixture type)
Method of Compliance:
ELECTRICAL SYSTEM AND EQUIPMENT
MECHANICAL SYSTEMS, SERVICE SYSTEMS AND EQUIPMENT
Thermal Zone
Interior design conditions
Building heating load
Building cooling load
Mechanical Spacing Conditioning System
List equipment efficiencies
ENERGY REQUIREMENTS:
ENERGY SUMMARY
THERMAL ENVELOPE
Method of Compliance:
Roof/ceiling Assembly (each assembly)
Exterior Walls (BRICK VENEER)
Climate Zone:
SPECIAL APPROVALS
ACCESSIBLE PARKING
PLUMBING FIXTURE REQUIREMENTS
STRUCTURAL DESIGN
SOIL BEARING CAPACITIES:
LATERAL DESIGN CONTROL:
SEISMIC DESIGN CATEGORY:
Wind Load:
Ground Snow Load:
DESIGN LOADS:
Live Load:
LIFE SAFETY SYSTEM REQUIREMENTS
FIRE PROTECTION REQUIREMENTS
ALLOWABLE HEIGHT
Mixed Occupancy:
Special Provisions:
Special Uses:
Primary Occupancy:
ALLOWABLE AREA
Gross Building Area (sq. ft.): 113,790 sf
Building Height:
Fire District:
Standpipes:
Sprinklers:
Construction Type:
BASIC BUILDING DATA
2012 EDITION OF NC CODE FOR:
LEAD DESIGN PROFESSIONAL:
2012 APPENDIX B
FOR ALL COMMERCIAL PROJECTS
total interior wattage specified vs. allowed (whole building or space by space) - SEE FIXTURE SCHEDULE
total exterior wattage specified vs. allowed - SEE FIXTURE SCHEDULE
total wattage per fixture - SEE FIXTURE SCHEDULE
number of ballasts in fixture - SEE FIXTURE SCHEDULE
ballast type used in the fixture - SEE FIXTURE SCHEDULE
number of lamps in fixture - SEE FIXTURE SCHEDULE
Lamp type required in fixture - SEE FIXTURE SCHEDULE
PerformancePrescriptive
winter dry bulb
summer dry bulb
winter dry bulb
summer dry bulb
relative humidity
Unitary
description of unit
heating efficiency
cooling efficiency
size category of unit
No Change to Building System
Prescriptive (Energy Code)
Description of assembly
U-Value of total assembly
R-Value of insulation
Skylights in each assembly
U-Value of skylight
Description of assembly
U-Value of total assembly
R-Value of insulation
U-Value of assembly
solar heat gain coefficient
projection factor
Door R-Value
total square footage of skylights in each assembly
Openings (windows or doors with glazing)
low e required, if applicable
Prescriptive (ASHRAE 90.1)Performance (Energy Code)
No Change to Building Envelope
Special Approval: (Local Jurisdiction, Department of Insurance, ICC, etc., describe below)
8' ACCESS
AISLE
LOT OR PARKING
AREA
TOTAL
VAN SPACES WITHREGULAR
WITH 5'
ACCESS AISLE
PROVIDEDREQUIRED
TOTAL # OF PARKING SPACES TOTAL #
ACCESSIBLE
PROVIDED
# OF ACCESSIBLE SPACES PROVIDED
SHOWERS/
TUBS
DRINKING FOUNTAINSLAVATORIESURINALSWATER CLOSETS
MALE FEMALE MALE FEMALE REGULAR ACCESSIBLE
USE
Pile size, type, and capacity
Presumptive Bearing Capacity
Field Test (provide copy of test report)
WindEarthquake
DynamicEquivalent Lateral ForceSimplified
Yes NoArchitectural, Mechanical, Components anchored ?
Analysis Procedure
Seismic Base Shear: V =
Moment Frame Inverted Pendulum
Dual w/ Intermediate R/C or Special SteelBuilding Frame
Bearing Wall Dual w/ Special Moment Frame
S1 %gSs %g
Basic Structural System (check one)
Site Classification (Table 1613.5.2)
Spectral Response Acceleration
Occupancy Category (Table 1604.5)
Provide the following Seismic Design Parameters:
BA
Vx =Vy =Wind Base Shears (for MWFRS)
Basic Speed
Exposure Category:
Mezzanine
Floor
Roof
Panic Hardware:No Yes
Smoke Detection Systems:No Yes
Fire Alarm:No Yes
Emergency Lighting:No Yes
YesNoExit Signs:
* Indicate section number permitting reduction
Tenant Separation
Smoke Barrier Separation
Party/Fire Wall Separation
Occupancy Separation
Corridor Separation
Shafts - Other
Shafts - Exit
beams and joists
including supporting
Roof Construction
beams and joists **
including supporting
Floor Construction
Interior Walls and Partitions
South
West
East
North
Exterior
and Partitions
Nonbearing walls
Interior
South
West
East
North
Exterior
Bearing Walls
girders, trusses
including columns,
Structural Frame,
JOINTS
RATED
FOR
DESIGN #DESIGN #
FOR
RATED
ASSEMBLY
PENETRATED
RATED
DESIGN # FORDETAIL #
AND
SHEET #
REQ'D
REDUCTION)
(W/ TBL. 601a
PROVIDED
RATINGBUILDING ELEMENT
(FEET)
DISTANCE
SEPARATION
FIRE
Life Safety Plan Sheet #, if provided
Type
Feet=H+20'=
Type
StoriesStories+1=
Feet
StoriesBuilding Hgt. in Stories
Building Hgt. in Feet
SPRINKLERS
Type of Construction
SHOWN ON PLANS
REFERENCE
CODE
(TABLE 503)
ALLOWABLE INCREASE FOR
S
S
5
4
3
2
1
b.
a.
e.
d.
c.
b.
a.
control towers must comply with 412.1.2.
The maximum area of parking garages must comply with 406.3.5. The maximum area of air traffic
Maximum Building Area = total number of stories in the building x E (506.4).
Unlimited area applicable under conditions of Section 507
Single story building I = 300 percent
Multi-story building I = 200 percent
The sprinkler increase per Section 506.3 is as follows:
Percent of frontage increase I = 100 [F/P - 0.25] x W/30 = (%)
W = Minimum width of public way = (W)
Ratio (F/P) = (F/P)
Total Building Perimeter = (P)
Perimeter which fronts a public way or open space having 20 feet minimum with = (F)
Frontage area increases from Section 506.2 are computed thus:
4321
5
STORY NO.
AND USE
DESCRIPTION
(ACTUAL)
PER STORY
BLDG. AREA
(A)
AREA
TABLE 503
(B)
INCREASE
OPEN SPACE
AREA FOR
(C)
AREA
BUILDING
MAXIMUM
(F)
UNLIMITED
AREA OR
ALLOWABLE
(E)
INCREASE
SPRINKLER
AREA FOR
(D)
=+< 1.00_
_< 1+Actual Area of Occupancy B
Allowable Area of Occupancy BAllowable Area of Occupancy A
Actual Area of Occupancy A
Separated Mixed Occupancy (508.4) - See below for area calculations
For each story, the area of the occupancy shall be such that the sum of the ratios of the actual floor area of each use divided
by the allowable floor area for each use shall not exceed 1.
Non-Separated Mixed Occupancy (508.3)
The required type of construction for the building shall be determined by applying the height and area limitations for each of the
applicable occupancies to the entire building. The most restrictive type of construction, so determined, shall apply to the entire
building.
Exception:Separation: Hr.YesNo
5
RepairUtility and Miscellaneous OpenParking Garage Enclosed
S-2 Low High-piledStorageS-1 Moderate
R-4R-1 R-2 R-3MercantileResidential
4123I-3 Use Condition
I-1Institutional I-4I-3I-2
F-2 Low
H-5 HPMH-2 Deflagrate H-3 Combust H-4 HealthHazardous
Business
A-5
H-1 Detonate
F-1 ModerateFactoryEducational
A-4A-3A-2A-1Assembly
TOTAL
Basement
1st Floor
2nd Floor
3rd Floor
4th Floor
5th Floor
6th Floor
UPFITNEWEXISTINGFLOOR
Feet
No Yes (Primary)
DryWetIIIIIClass:IYesNo
NFPA 13DNFPA 13RNFPA 13YesNo
(check all that apply)I-B II-B III-B
V-AIVIII-AII-AI-A
AlterationUpfitRenovation (Existing Bldg.)New Construction
E-MAILPHONE #LICENSE #NAMEFIRM
Retaining walls > 5' high
Structural
Sprinkler-Standpipe
Mechanical
Plumbing
Fire Alarm
Electrical
Civil
Architectural
DESIGNER
Phone #
CountyCity
StatePrivateCity/County
Code Enforcement Jurisdiction:
Owned By:
Owner or Authorized Agent:
Proposed Use:
Address:
Name of Project:
Feet
FLOOR EXISTING NEW
14th Floor
13th Floor
12th Floor
11th Floor
10th Floor
9th Floor
8th Floor
7th Floor
REN0/RENO/
UPFIT
=
** Ceiling panels are not a part of floor assembly.
No Change to Building Structural Design
x yV =
Reconstruction The following data shall be considered minimum and any special attribute required to meet the energy
code shall also be provided. Each Designer shall furnish the required portions of the project information
for the plan data sheet. If performance method, state the annual energy cost for the standard reference
design vs. annual energy cost for the proposed design.
56 Main Street, Buies Creek, NC 27546
4A
18 DEGREES F
94 DEGREES F
68 DEGREES F
76 DEGREES F
45-60 PERCENT
SEE MECHANICAL SHEETS
SEE MECHANICAL SHEETS
SEE MECHANICAL SHEETS
60 MIL. THERMOPLASTIC PVC ROOF SYSTEM ON 5" RIGID INSULATION
.033
R-30 MIN.
N/A
N/A
N/A
12" CMU, 2" SPRAY FOAM INS., 2" AIRSPACE, 4" BRICK VENEER
R-13 SPRAY FOAM INSULATION
5" STOREFRONT, 1" INSULATED GLAZING
.24
N/A
YES
3.5
1 HR
N/A
N/A
N/A
N/A
2 HR2 HR
0/N.C.0/N.C.
1 HR2 HR
212
180
11
160
1B1B .
.
.
.
.
.
ExistingExistingExisting
EAST LOT
.
Existing ExistingExisting
2612
70K
19.3K 39.4K
NOT USEDN/AUL81,090 SFA-3,4 & BLEVEL1
...
...
...
...
...
..4,770 SF
..N/A
.
62'-4"
..
..
..
..
..
..
..
..
.
1,230 SF
.
.
.
.
.
70K
.
(Table 2902.1)
f
Other
Addition Repair
CONSTRUCTED: (date)
RENOVATED: (date)
ORIGINAL USE(S): (ch.3):
CURRENT USE(S) (ch.3):
PROPOSED USE(S): (ch.3)
V-B
Flood Hazard Area:No Yes
State
Convocation Center - Wrestling Expansion and Renovation
Arena and Services (Whole Building) Wrestling Practice Area and Support (Work Area)
CAMPBELL UNIVERSITY - JIM ROBERTS 910-893-1240
Little Diversified Architectural Consulting
ASSEMBLY
ASSEMBLY
ASSEMBLY
62'-4"
Accessory Occupancy:
Incidental Uses:
Furnace room where any piece of equipment is over 400,000 Btu per hour input
Rooms with boilers where the largest piece of equipment is over 15 psi and 10 horsepower
Refrigerant machine room
Hydrogen cutoff rooms, not classified as Group H
Incinerator rooms
Paint shops not classified as Group H , located in occupancies other than Group F
Laboratories and vocational shops, not classified as Group H, located in a Group E or I-2 occupancy
Laundry rooms over 100 square feet
Group I-3 cells equipped with padded surfaces
Group I-2 waste and linen collection rooms over 100 sqaure feet
Stationary storage battery systems having a liquid electrolyte capacity of more than 50 gallons, or a
lithium-ion capacity of 1,000 pounds used for facility standby power or uninterrupted power Supplies.
Rooms containing fire pumps
Group I-2 storage rooms over 100 square feet
Group I-2 Commercial kitchens
Group I-2 laundries equal to or less than 100 square feet
Group I-2 rooms or spaces that contain fuel-fired heating equipment
Waste and linen collection rooms over 100 sqaure feet
402
0
LEVEL 2
LEVEL 3
A-3,4 & B 32,700 SF
-
UL
-
N/A
N/A
NOT USED
NOT USED
LIFE SAFETY PLAN REQUIREMENTS
Life Safety Plan Sheet #
Fire and/or smoke rated wall locations (chapter 7)
2 HR2 HR
0 HR
__________
EXISTING
NEW
REQUIRED
-1
2311
-
0/N.C.0/N.C.
2 HR2 HR
1 HR
113,790 SF
-
32,700 SF
75,090 SF
0 HR
Walls below grade (each assembly)
.
Partial
5
RepairUtility and Miscellaneous OpenParking Garage Enclosed
S-2 Low High-piledStorageS-1 Moderate
R-4R-1 R-2 R-3MercantileResidential
4123I-3 Use Condition
I-1Institutional I-4I-3I-2
F-2 Low
H-5 HPMH-2 Deflagrate H-3 Combust H-4 HealthHazardous
Business
A-5
H-1 Detonate
F-1 ModerateFactoryEducational
A-4A-3A-2A-1Assembly
(Table 508.2.5)
403 404 405 406 407 408 409 410
411 412 413 414 415 416 417 418 419
420 421 422 423 424 425 426 427
509.2 509.3 509.4 509.5 509.6 509.7 509.8 509.9
Incidental Use Separation (508.2.5)
This separation is not exempt as a Non-Separated Use (see exceptions)
Incidental Use Separation)N/A
Partial
Assumed and real property line locations
Exterior wall opening area with repect to distance to assumed property lines (706.8)
Existing Structures within 30' of the proposed building
Occupancy types for each area as it related to occupant load calculation (Table 1004.1.1)
Occupant loads for each area
Exit access travel distances (1014.3 & 1028.8)
Dead end lengths (1018.4)
Clear exit widths for each exit door
Maximum calculated occupant load capacity each exit door can accomodate based on egress width (1005.1)
Actual occupant load for each exit door
A separate schematic plan indicating where fire rated floor/ceiling and/or roof structure is provided for purposes of occupancy separation
Location of doors with panic hardware (1008.1.10)
Location of doors with delayed egress locks and the amount of delay (1008.1.9.7)
Location of doors with electronmagnetic egress locks (1008.1.9.8)
Location of doors with hold-open devices
Location of emergency escape windows (1029)
The square footage of each smoke compartment (407.4)
Note any code exceptions or table notes that may have been utilized regarding the items above
ACCESSIBLE DWELLING UNITS (SECTION 1107)
TOTAL
UNITS
ACCESSIBLE
UNITS
REQUIRED
ACCESSIBLE
UNITS
PROVIDED
TYPE A
UNITS
REQUIRED
TYPE A
UNITS
PROVIDED
TYPE B
UNITS
REQUIRED
TYPE B
UNITS
PROVIDED
TOTAL
ACCESSIBLE
UNITS PROVIDED
N/A -------
132" ACCESS
AISLE
Existing
Existing
Existing
Existing
Existing
Existing
Importance
Factors:Snow (I )
Seismic (I )
Wind (I )W
S
E
1.15
1.1
1.25
20
N/A
100/125
psf
psf
psf
psf
15
mph (ASCE-7)95
C
C D
III III IV
19 10
BA C D E F
Data Source:Field Test Presumptive Historical Data
psf5500
psf-
-
SPECIAL INSPECTIONS REQUIRED:Yes No
15
--
N/A
-
6
-
5
6
-
5
SPACE
3 4 5
Performance (ASHRAE 90.1)
.27
Description of assembly
U-Value of total assembly
R-Value of insulation
N/A
-
-
Floors over unconditioned space (each assembly)
Description of assembly
U-Value of total assembly
R-Value of insulation
N/A
-
-
.
Floorsslab on grade
Description of assembly
U-Value of total assembly
R-Value of insulation
4" CONCRETE SLAB W/ 2" RIGID (HOR. & VERT.) AT PERIM. FTG.
.1
R-10
Horizontal/vertical requirement PROVIDED
Slab heated N/A
MECHANICAL SUMMARY
Boiler
size category. If oversized, state reason EXISTING
.Chiller
size category. If oversized, state reason EXISTING
ELECTRICAL SUMMARY
Energy Code:
PerformancePrescriptiveASHRAE 90.1:
Additional Prescriptive Compliance
506.2.6 Automatic daylighting control systems
506.2.5 On-site supply of renewable energy
506.2.4 Higher Efficiency service water heating
506.2.3 Energy Recovery Ventilation Systems
506.2.2 Reduced lighting power density
506.2.1 More efficient mechanical equipment
N.C.= Non Combustible
N.R.= Not Required
N/A = Not Applicable
S = Section
T = Table
LITTLE
LITTLE
LITTLE
LITTLE
LITTLE David Blankfard
Katie Buckman
Melissa Taylor
Miles Grubbs
Miles Grubbs
LITTLE Melissa Taylor
LITTLE Miles Grubbs
027108
12045
041114
039783
039783
041114
039783
919-474-2549
919-474-2561
919-474-2525
919-474-2558
david.blankfard@littleonline.com
katie.buckman@littleonline.com
melissa.taylor@littleonline.com
miles.grubbs@littleonline.com
919-474-2558 miles.grubbs@littleonline.com
919-474-2558 miles.grubbs@littleonline.com
919-474-2525 melissa.taylor@littleonline.com
2008
-
EXST. BLDG.
ADDITION
ADDITION
UL
UL
UL
UL
2 HR2 HR
2 HR2 HR
2 HR2 HR
2 HR2 HR
1 HR2 HR
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
0/N.C.0/N.C.
0/N.C.0/N.C.
0/N.C.0/N.C.
N/A
N/A
N/A
N/A
N/A
G1.1.1
-Table includes public access facilities and new facilities added as part of this project. Locker fixtures not added as part of this
project are not included in table.
15
15
14
12
11
1 1
N/A
SEE MECHANICAL SHEETS
SEE MECHANICAL SHEETS
SEE MECHANICAL SHEETS
SEE MECHANICAL SHEETS
.061 (R-13 INSULATION, R-3.33 CMU)
G0.1.1 X732
Y622
G0.1.1 U905
G0.1.1 U905
G0.1.1 U905
G0.1.1 U905
G0.1.1 U905
G0.1.1 U905
G0.1.0 P732
N/A
N/A
A.WHERE NEW PARTITION ALIGNS WITH THE FACE OF AN EXISTING
FURRED COLUMN OR PARTITION, REMOVE CORNER BEAD, TAPE AND
SPACKLE NEW PARTITION TO EXISTING GYPSUM BOARD.
B.ALL EXISTING WALL SURFACES AND PARTITIONS TO REMAIN SHALL BE
PATCHED, SPACKLED AND SANDED SMOOTH SO AS NOT TO LEAVE ANY
EVIDENCE OF DEMOLITION OR REPAIR WORK. PREPARE SURFACES
FOR NEW FINISHES AS REQUIRED.
C.PROVIDE RECESSED FIRE EXTINGUISHER CABINETS, SMOKE
DETECTORS, AND ALL OTHER LIFE SAFETY DEVICES AS REQUIRED BY
CODE. PROVIDE DRAWING SHOWING NUMBER, LOCATION, AND
SPECIFICATION OF SUCH DEVICES FOR L&AA REVIEW PRIOR TO
FRAMING OF WALLS. DO NOT PLACE IN FIRE RATED PARTITIONS.
D.ALL WORK SHALL CONFORM TO THE CONTRACT DOCUMENTS WHICH
INCLUDE THE OWNER/CONTRACTOR AGREEMENT, THE PROJECT
MANUAL (WHICH CONTAINS THE GENERAL CONDITIONS, AND THE
SPECIFICATIONS), THE DRAWINGS AND ALL ADDENDA AND
MODIFICATIONS ISSUED BY THE ARCHITECT.
E.THE CONTRACTOR SHALL REVIEW ALL DOCUMENTS AND VERIFY ALL
DIMENSIONS AND FIELD CONDITIONS AND SHALL CONFIRM THAT WORK
IS BUILDABLE AS SHOWN. ANY CONFLICTS OR OMISSIONS SHALL BE
IMMEDIATELY REPORTED TO THE ARCHITECT FOR CLARIFICATION
PRIOR TO THE PERFORMANCE OF ANY WORK IN QUESTION.
F.CONTRACTOR SHALL COORDINATE WITH TENANT THE SCHEDULE FOR
ALL TELEPHONE COMPANY AND DATA INSTALLATIONS.
G."ALIGN" SHALL MEAN TO ACCURATELY LOCATE FINISH FACES IN THE
SAME PLANE.
H.CONTRACTOR SHALL COORDINATE AND PROVIDE METAL BACKING
PLATES OR SOLID WOOD BLOCKING (FIRE TREATED) IN PARTITIONS
AND CEILING FOR ALL MILLWORK, WALL AND CEILING ATTACHED ITEMS
AS REQUIRED BY EACH SPECIFIC ITEM.
I.ALL WORK NOTED "BY OTHERS" OR "NIC" SHALL BE PROVIDED BY
OWNER OR UNDER SEPARATE CONTRACT.
J.DO NOT SCALE DRAWINGS. WRITTEN DIMENSIONS GOVERN. ALL
PARTITION LOCATIONS, DIMENSIONS AND TYPES, ALL DOOR AND
WINDOW LOCATIONS SHALL BE AS SHOWN ON PARTITION PLAN. IN
CASE OF CONFLICT, NOTIFY ARCHITECT; PARTITION PLAN BY DESIGN
INTENT ARCHITECT SUPERSEDES OTHER PLANS.
K.ALL PARTITIONS ARE DIMENSIONED FROM FINISH FACE TO FINISH FACE,
UNLESS OTHERWISE NOTED. ALL DIMENSIONS MARKED "CLEAR" SHALL
BE MAINTAINED AND SHALL ALLOW FOR THICKNESS OF ALL FINISHES
INCLUDING CARPET, CERAMIC TILE, VCT, ETC.
L.PARTITIONS AT BUILDING PERIMETER SHALL BE CENTERED ON
CENTER LINE OF COLUMN OR WINDOW MULLION, UNLESS OTHERWISE
NOTED.
M.COLUMN CENTER LINES (OR GRID LINES) ARE SHOWN FOR
DIMENSIONING, VERIFY EXACT LOCATIONS IN FIELD.
N.PARTITION TYPES ENCLOSING ROOMS AND SPACES SHALL BE
CONTINUOUS THROUGHOUT ENTIRE ROOM OR SPACE.
O.PROVIDE ACOUSTICAL CAULKING AROUND ALL PERIMETER EDGES
AND/OR PENETRATIONS AT SOUND INSULATED WALLS. OFFSET
ELECTRICAL AND TELEPHONE OUTLETS 16" MINIMUM IN SEPARATE
STUD CAVITIES.
w w w . l i t t l e o n l i n e . c o m
This drawing and the design shown are the property
of Little Diversified Architectural Consulting. The
reproduction, copying or other use of this drawing
without their written consent is prohibited and any
infringement will be subject to legal action.
Little 2017c
PROJECT MANAGER
DESIGN TEAM
PRINCIPAL IN CHARGE
PROJECT TEAM
REVISIONS
PROJECT NAME
SHEET TITLE
PROJECT NO.
SHEET NUMBER
ISSUE FOR
ISSUE DATE
B
1 2 3 4 5 6 7
A
C
D
E
F
410 Blackwell Street, Suite 10
Durham, NC 27701
T: 919.474.2500
Rob Klinedinst
Katie Buckman
Anne Lebo
10/06/17
10/9/2017 3:30:57 PM C:\Users\katie.buckman\Documents\513.7505.00_CU_WrestlingExpansion_A-16_katie.buckman.rvt513.7505.00
G0.0.1
BUILDING CODE
SUMMARY
Campbell Convocation
Center Wrestling
Department Renovation
and Expansion
BID/PERMIT SET
BUILDING CODE SUMMARY
NO. REASON DATE
GENERAL NOTES - CONSTRUCTION
w w w . l i t t l e o n l i n e . c o m
This drawing and the design shown are the property
of Little Diversified Architectural Consulting. The
reproduction, copying or other use of this drawing
without their written consent is prohibited and any
infringement will be subject to legal action.
Little 2017c
PROJECT MANAGER
DESIGN TEAM
PRINCIPAL IN CHARGE
PROJECT TEAM
REVISIONS
PROJECT NAME
SHEET TITLE
PROJECT NO.
SHEET NUMBER
ISSUE FOR
ISSUE DATE
B
1 2 3 4 5 6 7
A
C
D
E
F
410 Blackwell Street, Suite 10
Durham, NC 27701
T: 919.474.2500
Rob Klinedinst
Katie Buckman
Anne Lebo
10/06/17
10/9/2017 3:30:58 PM C:\Users\katie.buckman\Documents\513.7505.00_CU_WrestlingExpansion_A-16_katie.buckman.rvt513.7505.00
G0.1.0
FIRE RESISTANCE
DESIGNS
Campbell Convocation
Center Wrestling
Department Renovation
and Expansion
BID/PERMIT SET
NO. REASON DATE
UL P732 Continued UL P732 ContinuedUL P732 ContinuedUL P732
UL P732 - APPLIES TO ALL ROOF SUPPORT (JOISTS, GIRDERS, OR BEAMS).
UL X732 - APPLIES TO ALL STEEL COLUMNS (W SHAPE) WITHOUT FULL CMU WRAP FROM SLAB TO FLOOR DECK OR
ROOF DECK. PROTECTION MUST RUN TO TOP OF ALL COLUMNS.
UL Y622 - APPLIES TO STEEL TUBES WITHOUT FULL CMU WRAP FROM SLAB TO ROOF DECK. RPTECTION MUST RUN TO
TOP OF ALL COLUMNS.
UL U905 - APPLIES TO CMU WALLS, LOAD BEARING SHALL BE 2 HOUR EXTERIOR AND 1 HOUR INTERIOR.
w w w . l i t t l e o n l i n e . c o m
This drawing and the design shown are the property
of Little Diversified Architectural Consulting. The
reproduction, copying or other use of this drawing
without their written consent is prohibited and any
infringement will be subject to legal action.
Little 2017c
PROJECT MANAGER
DESIGN TEAM
PRINCIPAL IN CHARGE
PROJECT TEAM
REVISIONS
PROJECT NAME
SHEET TITLE
PROJECT NO.
SHEET NUMBER
ISSUE FOR
ISSUE DATE
B
1 2 3 4 5 6 7
A
C
D
E
F
410 Blackwell Street, Suite 10
Durham, NC 27701
T: 919.474.2500
Rob Klinedinst
Katie Buckman
Anne Lebo
10/06/17
10/9/2017 3:30:58 PM C:\Users\katie.buckman\Documents\513.7505.00_CU_WrestlingExpansion_A-16_katie.buckman.rvt513.7505.00
G0.1.1
FIRE RESISTANCE
DESIGNS
Campbell Convocation
Center Wrestling
Department Renovation
and Expansion
BID/PERMIT SET
NO. REASON DATE
UL Y622UL U905
UL X732
UL P732 - APPLIES TO ALL ROOF SUPPORT (JOISTS, GIRDERS, OR BEAMS).
UL X732 - APPLIES TO ALL STEEL COLUMNS (W SHAPE) WITHOUT FULL CMU WRAP FROM SLAB TO FLOOR DECK OR
ROOF DECK. PROTECTION MUST RUN TO TOP OF ALL COLUMNS.
UL Y622 - APPLIES TO STEEL TUBES WITHOUT FULL CMU WRAP FROM SLAB TO ROOF DECK. RPTECTION MUST RUN TO
TOP OF ALL COLUMNS.
UL U905 - APPLIES TO CMU WALLS, LOAD BEARING SHALL BE 2 HOUR EXTERIOR AND 1 HOUR INTERIOR.
VBALLREFSTAND
PORTABLE WRESTLING MAT CART
PORTABLE BASKETBALLGOAL - MAIN COURT UNIT
VBALLEQUIPCART
BASKETBALL
BALL CART
VBALLBALL
CART
PORTABLE BASKETBALL GOALS- PRACTICE COURT UNIT PORTABLE BASKETBALL GOALS- PRACTICE COURT UNIT
PORTABLE BASKETBALL GOALS- PRACTICE COURT UNIT PORTABLE BASKETBALL GOALS- PRACTICE COURT UNIT
PORTABLEFLOORCOVERINGSTACK
PORTABLEFLOORCOVERINGSTACK
PORTABLEFLOORCOVERINGSTACK
PORTABLEFLOORCOVERINGSTACK
PORTABLEFLOORCOVERINGSTACK
PORTABLEFLOORCOVERINGSTACK
PORTABLEFLOORCOVERINGSTACK
PORTABLE BASKETBALLGOAL - MAIN COURT UNIT
UP
UP UP UP
UP UP UP
DN
197.20'
193.70'
197.20'
FECFEC FEC
CR
CR
OVERALL DIAGONAL DISTANCE - 153'
DISTANCE BETWEEN EXITS - 150'
TRAVEL PATH: 166'COMMON PATH: 33'TRAVEL PATH: 241'TRAVEL PATH: 97'
TRAVEL PATH: 111'TRAVEL PATH: 77'
4983 SF
A-3 WRESTLING
PRACTICE
7 SF EA
4760 SF
A-3 PRACTICE GYM
7 SF EA
PANIC
ACCESS
REQUEST
Yes
No
No
72
.2
370
272
PANIC
ACCESS
REQUEST
Yes
Yes
No
34
.2
170
136
EXISTING
EXISTING -
FLIP DOOR
SWING
1911 SF
BUSINESS
100 SF EA
579 SF
A-3 EXERCISE
50 SF EA
7 SF
15 SF
50 SF
100 SF
300 SF
Calculating...
1240 SF
A-3 LOCKERS
50 SF EA
319 SF
A-3 LOCKERS
50 SF EA
PANIC
ACCESS
REQUEST
Yes
No
No
72
370
326
PANIC
ACCESS
REQUEST
Yes
No
No
34
170
147
TRAVEL PATH: 114'
PANIC
ACCESS
REQUEST
Yes
Yes
No
68
.2
340
294
120
90
LOUNGE
1149
COACH
1146 ASST.
COACH
OFFICES
1144
144 SF
ASSEMBLY
15 SF EA
120 SF
STORAGE
300 SF EA
12 1
STORAGE
1147FITNESS
1148 CONFERENCE
1145
10
20 OCC.
712 OCC.
25 OCC.
7
LIMIT OF WORK - AREA C
LIMIT OF WORK -
AREA D
01
01
CR
CLEAR OPENING WIDTH
EXIT EGRESS DEAD END DISTANCE
OVERALL DIAGONAL DISTANCE
CARD READERCR
PANIC
ACCESS
REQUEST
34"
Yes
No
0.2"
170
75
No
34"
0.2"
170
75
CLEAR WIDTH PER OCCUPANT
OCCUPANT CAPACITY
ACTUAL OCCUPANT LOAD
PANIC HARDWARE
ACCESS CONTROL DEVICE
(E.G. CARD READER)
CLEAR STAIR WIDTH
CLEAR WIDTH PER OCCUPANT
OCCUPANT CAPACITY
ACTUAL OCCUPANT LOAD
EXIT REMOTENESS DISTANCE
OVERALL DIAGONAL DIMENSION - 14'
DISTANCE BETWEEN EXITS - 14'
EXIT EGRESS COMMON PATH
EXIT EGRESS DISTANCE
TRAVEL DISTANCE SHOWN: 000'
TRAVEL DISTANCE SHOWN: 000'
Area Name
150 SF
100 SF EA
AREA
LOAD FACTOR
ILLUMINATED EXIT SIGN
REQUEST TO EXIT
FIRE EXTINGUISHER CABINET - RECESSED
120 DOOR FIRE RATING IN MINUTES
FIRE BARRIER FIRE & SMOKE BARRIER
1-HOUR
2-HOUR
3-HOUR
0.5-HOUR
1-HOUR
FIRE PARTITIONFIRE WALL
2-HOUR
3-HOUR
4-HOUR
1-HOUR
2-HOUR
3-HOUR
0-HOUR 1-HOUR
SMOKE BARRIERSMOKE PARTITION
RATED WALLS & PARTITIONS
w w w . l i t t l e o n l i n e . c o m
This drawing and the design shown are the property
of Little Diversified Architectural Consulting. The
reproduction, copying or other use of this drawing
without their written consent is prohibited and any
infringement will be subject to legal action.
Little 2017c
PROJECT MANAGER
DESIGN TEAM
PRINCIPAL IN CHARGE
PROJECT TEAM
REVISIONS
PROJECT NAME
SHEET TITLE
PROJECT NO.
SHEET NUMBER
ISSUE FOR
ISSUE DATE
B
1 2 3 4 5 6 7
A
C
D
E
F
410 Blackwell Street, Suite 10
Durham, NC 27701
T: 919.474.2500
Rob Klinedinst
Katie Buckman
Anne Lebo
10/06/17
10/9/2017 3:31:10 PM C:\Users\katie.buckman\Documents\513.7505.00_CU_WrestlingExpansion_A-16_katie.buckman.rvt513.7505.00
G1.1.1
LIFE SAFETY PLAN -
LEVEL 01
Campbell Convocation
Center Wrestling
Department Renovation
and Expansion
BID/PERMIT SET
3/32" = 1'-0"G1.1.1
1 CONVOCATION AREA C AND D - LIFE SAFETY PLAN
AREA C
NOT TO SCALE
EXISTING BUILDING AREA D
KEY PLAN
LIFE SAFETY LEGEND
GENERAL NOTES - FLOOR PLAN
X SHEET KEYNOTES
1.ROOF OF EXISTING AND NEW WRESTLING GYM AND SUPPORT SPACES REQUIRES 1 HOUR
FIRE RATING. SPRAY FIRE PROOFING TO BE PROVIDED/MAINTAINED AT JOISTS, DECKING,
BRIDGING, AND ALL RELATED STRUCTURAL WORK. MATCH EXISTING. SEE G1.1.1 FIRE
RATED DESIGNS.
2.ALL INTERIOR LOAD BEARING MASONRY WALLS SUPPORTING ROOF ONLY SHALL MAINTAIN
A 1 HOUR FIRE RATING FOLLOWING UL U905.
3.ALL EXTERIOR LOAD BEARING WALLS SHALL MAINTAIN A 2 HOUR FIRE RATING FOLLOWING
UL U905.
4.ROOF STRUCTURE/DECKING TO MAINTAIN A 1 HOUR FIRE RATING FOLLOWING UL P732
5.UNWRAPPED STRUCTURAL TUBE COLUMNS IN EXTERIOR LOAD BEARING WALLS TO
MAINTAIN A 2 HOUR FIRE RATING FOLLOWING UL U622.
NO. REASON DATE
01 SEMI-RECESSED FIRE EXTINGUISHER CABINET
A.THE CONTRACTOR SHALL REMOVE SUCH EXISTING WORK AS
CALLED FOR IN CONTRACT OR AS REQUIRED TO CLEAR THE
AREAS FOR NEW CONSTRUCTION.
B.THE CONTRACTOR SHALL REMOVE ALL EXISTING WIRE NOT
BEING USED ABOVE LAY-IN CEILINGS; CONDUIT BEING
ABANDONED SHALL BE REMOVED COMPLETELY BACK TO THE
SOURCE. ALL EXISTING CIRCUITS NOT BEING USED SHALL BE
MARKED AS SPARE CIRCUITS IN THE DESIGNATED PANEL.
C.ALL DEMOLITION WORK SHALL BE PREFORMED WITH "DUE CARE
AND DILIGENCE" AS TO PREVENT THE ARBITRARY DESTRUCTION
OR INTERRUPTION OF CONCEALED UTILITIES WHICH ARE
INTENDED TO REMAIN IN USE AND THE ROUTING OF WHICH
COULD NOT BE PREDETERMINED UNTIL DEMOLITION WAS
STARTED. ALL SUCH DISCOVERIES OF UTILITIES DURING THE
DEMOLITION PROCESS WHICH ARE IN A LOCATION DIFFERENT
FROM THAT INDICATED, OR ARE UNIDENTIFIED, SHALL BE
REPORTED TO THE ARCHITECT PRIOR TO REMOVAL FOR FINAL
DISPOSITION.
D.WORK DESIGNATED TO REMAIN SHALL BE PROTECTED FROM
DAMAGE AND PATCHED OR REPAIRED SHOULD DAMAGE OCCUR.
E.WHERE EXISTING EQUIPMENT IS TO BE RELOCATED, EXTREME
CARE SHALL BE TAKEN TO PREVENT DAMAGE DURING THE
REMOVAL. WHERE DAMAGE OCCURS, THE EQUIPMENT SHALL BE
REPLACED OR REPAIRED TO THE SATISFACTION OF THE OWNER
AT NO ADDITIONAL COST.
F.EXCEPT AS OTHERWISE NOTED, ALL EXISTING ELECTRICAL
WORK WHICH WILL NOT BE RENDERED OBSOLETE AND WHICH
MAY BE DISTURBED DUE TO ANY CHANGES REQUIRED UNDER
THIS CONTRACT, SHALL BE RESTORED TO ITS ORIGINAL
OPERATING CONDITION. OTHER ELECTRICAL WORK OR
MATERIAL RENDERED OBSOLETE SHALL BE REMOVED OR
ABANDONED WHERE CONCEALED AND REMOVED WHERE
EXPOSED. OLD, UNUSED WIRING AND DEVICES SHALL BE
REMOVED FROM THE ABANDONED (CONCEALED) CONDUITS.
OUTLETS SHALL BE PROVIDED WITH BLANK COVERS.
G.ALL DEBRIS BECOMES THE PROPERTY OF THE CONTRACTOR
AND SHALL BE REMOVED DAILY FROM THE PREMISES AT THE
CONTRACTOR'S EXPENSE AND BE DISPOSED OF ACCORDING TO
LOCAL CODES AND GOVERNING AUTHORITIES. VERIFY SALVAGE
MATERIALS WITH THE OWNER'S REPRESENTATIVE.
H.WHERE EXISTING FIXTURES, WIRING DEVICES, AND ELECTRICAL
EQUIPMENT ARE REMOVED, RECONNECT CIRCUITING AS
REQUIRED TO MAINTAIN CONTINUITY TO OUTLETS REMAINING
ON THE CIRCUIT WITHIN OCCUPIED SPACES.
I.WHERE REQUIRED BY NEW CONSTRUCTION, PROVIDE
EXTENSION RINGS, COVERPLATES, OR ACCESS PLATES AS
REQUIRED TO MAINTAIN ACCESS TO EXISTING WIRING.
J.FIELD VERIFY LOCATIONS OF EXISTING OUTLETS. WHERE NEW
CONSTRUCTION CONFLICTS WITH EXISTING OUTLETS, REMOVE
WIRING DEVICES OR RELOCATE FIXTURES AS REQUIRED,
WHETHER OR NOT SPECIFICALLY INDICATED.
K.WHERE EXISTING WIRING DEVICES ARE REMOVED AND
JUNCTION BOXES ARE NOT REUSED, PROVIDE BLANK
COVERPLATES.
L.WHERE EXISTING CIRCUITS ARE EXTENDED TO SERVE NEW OR
RELOCATED DEVICES OR FIXTURES, PROVIDE TYPE AND SIZE
OF CONDUCTORS TO MATCH EXISTING.
M.EXISTING CIRCUITING SHALL BE FIELD VERIFIED AND
ADJUSTMENTS SHALL BE MADE, AS REQUIRED BY FIELD
CONDITIONS.
N.WHERE EXISTING ELECTRICAL WORK INTERFERES WITH NEW
WORK AND WHERE SUCH INSTALLATIONS ARE TO REMAIN IN
USE, THE INSTALLATIONS SHALL BE DISCONTINUED AND
RELOCATED AND/OR RECONNECTED TO COORDINATE WITH NEW
ELECTRICAL WORK.
O.FEEDERS AND BRANCH CONDUIT SYSTEMS ENTERING AND
LEAVING AREAS TO BE REMODELED WHICH SERVICE OTHER
ACTIVE AREAS SHALL BE THE RESPONSIBILITY OF THIS
CONTRACTOR TO MAINTAIN CONTINUITY OF THESE SYSTEMS.
P.CONTRACTOR SHALL CONSULT OTHER TRADES PRIOR TO
COMMENCING THIS WORK, TO AVOID CONFLICT.
Q.DEMOLITION DRAWINGS ARE DIAGRAMMATIC AND SHOW INTENT
OF WORK TO BE DONE. CONTRACTOR SHALL PROVIDE ALL
MATERIALS, EQUIPMENT, LABOR REQUIRED AND COST FOR
REMOVAL OF ALL SYSTEMS CALLED FOR IN CONTRACT.
R.ALL EXISTING CONSTRUCTION SHALL REMAIN UNLESS NOTED
OTHERWISE.
S.CONTRACTOR SHALL SUBMIT A TYPE WRITTEN INVENTORY OF
MAJOR ELECTRICAL EQUIPMENT TO BE REMOVED IN
DEMOLITION PHASE. INVENTORY SHALL DESCRIBE ITEM AND
QUANTITY. AFTER OWNER HAS DECIDED WHICH EQUIPMENT TO
RETAIN, CONTRACTOR SHALL REMOVE, COMPLETE FROM THE
PROJECT SITE, ALL OTHER REMAINING ELECTRICAL EQUIPMENT
INCLUDING ALL ITEMS NOT LISTED IN INVENTORY THAT ARE TO
BE REMOVED IN DEMOLITION PHASE.
T.REMOVE ALL EXISTING FIXTURES, WIRING DEVICES, ELECTRICAL
EQUIPMENT AND CIRCUITING WHETHER SPECIFICALLY
INDICATED OR NOT, AS REQUIRED BY THE ARCHITECTURAL
DEMOLITION WORK IN THE AREA TO BE RENOVATED.
U.CONTRACTOR TO PATCH AND REPAIR ALL AREAS AFFECTED BY
THE DEMOLITION.
V.FOR MECHANICAL DEMOLITION NOTES, REFER TO MECHANICAL
PLANS.
W.FIXTURES SHALL BE CLEANED THOROUGHLY AND RELAMPED
BEFORE TURNING THEM OVER TO OWNER.
X.IT IS THE INTENT OF THIS DOCUMENT TO UTILIZE THE REUSE
OF BUILDING STANDARDS, SUCH AS, BUT NOT LIMITED TO,
DOORS AND FRAMES, HARDWARE, ELECTRICAL AND TELEPHONE
RECEPTACLES, DIFFUSERS, SPEAKERS, EXIT SIGNS AND
PLUMBING FIXTURES WHERE POSSIBLE. ALL SUCH BUILDING
MATERIALS REMOVED DURING DEMOLITION SHALL BE
INVENTORIED AND NEATLY STORED ON SITE FOR REUSE. ALL
SURPLUS FIXTURES AND MATERIAL ITEMS REMOVED DURING
DEMOLITION BUT NOT REUSED DURING THIS PROJECT SHALL BE
STORED FOR LATER USE. CONTRACTORS SHALL COORDINATE
THE SEQUENCE FOR DEMOLITION AND THE LOCATION OF ON
SITE STORAGE AREAS FOR EXISTING ITEMS TO BE REUSED,
AND PROVIDE THE BUILDING WITH COPIES OF DEMOLITION
INVENTORY.
Y.THE GENERAL CONTRACTOR SHALL COORDINATE WITH THE
MECHANICAL AND ELECTRICAL ENGINEERING DRAWINGS FOR
ADDITIONAL HVAC OR ELECTRICAL DEMOLITION REQUIRED.
Z.REMOVE ALL CONSTRUCTION SHOWN ON THE DRAWINGS AS
EXISTING TO BE REMOVED, INCLUDING, BUT NOT LIMITED TO:
FLOORING, PARTITIONS, (INCLUDING ELEMENTS OCCURRING
ABOVE THE FINISHED CEILINGS), HANGERS, STRAPS AND OTHER
ACCESSORY OBJECTS CONNECTED WITH THE ITEMS BEING
REMOVED.
AA.ON REMAINING WALLS ADJACENT TO THOSE BEING
DEMOLISHED, EXISTING BASE SHALL BE REMOVED BACK TO
NEAREST INSIDE CORNER AND WALLS SHALL BE REPAIRED SO AS
TO CREATE A SMOOTH SURFACE READY TO RECEIVE NEW
BASE.
EXISTING WALL TO REMAIN
EXISTING CONSTRUCTION TO BE DEMOLISHED
EXISTING DOOR TO REMAIN
EXISTING DOOR TO BE DEMOLISHED
EXISTING CASEWORK OR OTHER ITEM TO BE DEMOLISHED
EXISTING CEILING GRID TO REMAIN
EXISTING CEILING GRID TO BE DEMOLISHED
01
3'-2"23'-2 1/4"5' - 3 5/8"4' - 8"8' - 0"7' - 4"8' - 0"7' - 4"8' - 0"7' - 4"8' - 0"7' - 4"8' - 0"6' - 8"43' - 0 1/2"8' - 7 5/8"17' - 7 3/4"10 1/4"13'-10 3/4"2'-7 3/4"eG
e10
eE.6
eE
eF
02
03
0404 04 04 04 04 05
2'-8"
0632 3/8"6' - 2"
07
08
09
09
09
0909 09
35' - 4 3/8"
w w w . l i t t l e o n l i n e . c o m
This drawing and the design shown are the property
of Little Diversified Architectural Consulting. The
reproduction, copying or other use of this drawing
without their written consent is prohibited and any
infringement will be subject to legal action.
Little 2017c
PROJECT MANAGER
DESIGN TEAM
PRINCIPAL IN CHARGE
PROJECT TEAM
REVISIONS
PROJECT NAME
SHEET TITLE
PROJECT NO.
SHEET NUMBER
ISSUE FOR
ISSUE DATE
B
1 2 3 4 5 6 7
A
C
D
E
F
410 Blackwell Street, Suite 10
Durham, NC 27701
T: 919.474.2500
Rob Klinedinst
Katie Buckman
Anne Lebo
10/06/17
10/9/2017 3:30:50 PM C:\Users\katie.buckman\Documents\513.7505.00_CU_WrestlingExpansion_A-16_katie.buckman.rvt513.7505.00
AD1.1.1
DEMOLITION FLOOR
PLAN
Campbell Convocation
Center Wrestling
Department Renovation
and Expansion
BID/PERMIT SET
X SHEET KEYNOTESGENERAL NOTES - DEMOLITION
DEMOLITION LEGEND
3/16" = 1'-0"AD1.1.1
1 CONVOCATION AREA C FLOOR PLAN - DEMOLITION
01 DEMOLISH EAST WALL. SHORE ROOF AS REQUIRED. PROTECT
ABUTTING WALL TO NORTH THAT REMAINS. CUT FOUNDATION TO
ALLOW FOR NEW SLAB POUR.
02 NEW OPENING IN RATED STAIR WALL FOR DOOR 1047C. PROVIDE
LINTEL. STAIR EXIT ACCESS MUST BE MAINTAINED DURING ALL
OCCUPIED HOURS DURING DEMO. AND CONSTRUCTION.
03 DEMO. WATER TABLE AND BRICK VENEER FROM NEW INTERIOR
PORTION OF WALL UP TO NEW BRICK LINTEL ABOVE NEW ROOF.
MAINTAIN BRICK AND 4" BLOCK BELOW NEW FLOOR SLAB. REMOVE
RIGID INSULATION AND CUT BACK BRICK TIES FLUSH WITH BLOCK.
WALL WILL BE FURRED OUT.
04 REMOVE EXTERIOR WINDOW. MAINTAIN BOND BEAM ABOVE
WINDOW. SAWCUT NEW OPENING FROM WINDOW JAMBS TO
BELOW NEW SLAB LEVEL. FACE OF BRICK AT AREA BEING
DEMOLISHED IS INSET 4". (EXISTING EXTERIOR WALL, INCLUDING
BRICK AND WATERTABLE, WILL BE MAINTAINED AS AN EXPOSED
FINISH IN THE NEW ADDITION. PROTECT VENEER FROM DAMAGE
DURING DEMO AND NEW CONSTRUCTION. TOOTH IN BRICK AND
BLOCK TO CREATE CLEAN CORNER CONDITIONS AT BOTH SIDES
OF THE WALL ON BOTH SIDES OF NEW OPENING.) UTILIZE BRICK
AND PRECAST PIECES FROM DEMOLISHED PORTION OF WALL TO
TOOTH IN. OPENING WILL RECEIVE PAINTED PLYWOOD TRIM
PIECE ON SHIMS THAT SITS SHY OF FACE OF CMU AND FACE OF
WALL BRICK. GRIND SAWCUT SURFACE TO CREATE EVEN/FLUSH
CONDITION TO RECEIVE PLYWOOD TRIM.
05 REMOVE CORNER OF WALL AS INDICATED. PROVIDE SHORING AS
REQUIRED. SAWCUT OPENING TO HEAD HEIGHT OF EXISTING
WINDOWS TO BELOW NEW SLAB LEVEL. EXISTING EXTERIOR
WALL, INCLUDING BRICK AND WATERTABLE, WILL BE MAINTAINED
AS AN EXPOSED FINISH IN THE NEW ADDITION. PROTECT VENEER
FROM DAMAGE DURING DEMO AND NEW CONSTRUCTION. TOOTH
IN BRICK AND BLOCK TO CREATE CLEAN CORNER CONDITIONS AT
BOTH SIDES OF THE WALL ON BOTH SIDES OF NEW OPENING.
UTILIZE BRICK AND PRECAST PIECES FROM DEMOLISHED
PORTION OF WALL TO TOOTH IN. OPENING WILL RECEIVE
PLYWOOD TRIM PIECE ON SHIMS THAT SITS SHY OF FACE OF CMU
AND FACE OF WALL BRICK.
06 DEMO. WATER TABLE AND BRICK VENEER TO WALL CORNER UP
TO NEW BRICK LINTEL ABOVE NEW ROOF. MAINTAIN BRICK AND 4"
BLOCK BELOW NEW FLOOR SLAB. REMOVE RIGID INSULATION AND
CUT BACK BRICK TIES FLUSH WITH BLOCK. WALL WILL BE
PAINTED, BUT LEFT EXPOSED. SAWCUT WATERTABLE PRECAST
AND BRICK TO ACCOMMODATE NEW EXTEIOR WALL FINISH.
07 NEW OPENING IN WALL FOR DOOR 1040B. PROVIDE LINTEL PER
STRUCTURAL DRAWINGS. PROVIDE SHORING AS REQUIRED.
08 DEMO WALL AND DOOR. MAINTAIN 4" BEARING WIDTH AND BEAM
POCKET FOR BEAM ABOVE. SEE STRUCTURAL DRAWINGS.
PROVIDE SHORING AS REQUIRED.
09 DEMO WALL AND DOOR AS INDICATED.
AREA C
NOT TO SCALE
EXISTING BUILDING
KEY PLAN
NO. REASON DATE
01
eG
e10
eE.6
eE
eF
02
03
A.THE CONTRACTOR SHALL REMOVE SUCH EXISTING WORK AS
CALLED FOR IN CONTRACT OR AS REQUIRED TO CLEAR THE
AREAS FOR NEW CONSTRUCTION.
B.THE CONTRACTOR SHALL REMOVE ALL EXISTING WIRE NOT
BEING USED ABOVE LAY-IN CEILINGS; CONDUIT BEING
ABANDONED SHALL BE REMOVED COMPLETELY BACK TO THE
SOURCE. ALL EXISTING CIRCUITS NOT BEING USED SHALL BE
MARKED AS SPARE CIRCUITS IN THE DESIGNATED PANEL.
C.ALL DEMOLITION WORK SHALL BE PREFORMED WITH "DUE CARE
AND DILIGENCE" AS TO PREVENT THE ARBITRARY DESTRUCTION
OR INTERRUPTION OF CONCEALED UTILITIES WHICH ARE
INTENDED TO REMAIN IN USE AND THE ROUTING OF WHICH
COULD NOT BE PREDETERMINED UNTIL DEMOLITION WAS
STARTED. ALL SUCH DISCOVERIES OF UTILITIES DURING THE
DEMOLITION PROCESS WHICH ARE IN A LOCATION DIFFERENT
FROM THAT INDICATED, OR ARE UNIDENTIFIED, SHALL BE
REPORTED TO THE ARCHITECT PRIOR TO REMOVAL FOR FINAL
DISPOSITION.
D.WORK DESIGNATED TO REMAIN SHALL BE PROTECTED FROM
DAMAGE AND PATCHED OR REPAIRED SHOULD DAMAGE OCCUR.
E.WHERE EXISTING EQUIPMENT IS TO BE RELOCATED, EXTREME
CARE SHALL BE TAKEN TO PREVENT DAMAGE DURING THE
REMOVAL. WHERE DAMAGE OCCURS, THE EQUIPMENT SHALL BE
REPLACED OR REPAIRED TO THE SATISFACTION OF THE OWNER
AT NO ADDITIONAL COST.
F.EXCEPT AS OTHERWISE NOTED, ALL EXISTING ELECTRICAL
WORK WHICH WILL NOT BE RENDERED OBSOLETE AND WHICH
MAY BE DISTURBED DUE TO ANY CHANGES REQUIRED UNDER
THIS CONTRACT, SHALL BE RESTORED TO ITS ORIGINAL
OPERATING CONDITION. OTHER ELECTRICAL WORK OR
MATERIAL RENDERED OBSOLETE SHALL BE REMOVED OR
ABANDONED WHERE CONCEALED AND REMOVED WHERE
EXPOSED. OLD, UNUSED WIRING AND DEVICES SHALL BE
REMOVED FROM THE ABANDONED (CONCEALED) CONDUITS.
OUTLETS SHALL BE PROVIDED WITH BLANK COVERS.
G.ALL DEBRIS BECOMES THE PROPERTY OF THE CONTRACTOR
AND SHALL BE REMOVED DAILY FROM THE PREMISES AT THE
CONTRACTOR'S EXPENSE AND BE DISPOSED OF ACCORDING TO
LOCAL CODES AND GOVERNING AUTHORITIES. VERIFY SALVAGE
MATERIALS WITH THE OWNER'S REPRESENTATIVE.
H.WHERE EXISTING FIXTURES, WIRING DEVICES, AND ELECTRICAL
EQUIPMENT ARE REMOVED, RECONNECT CIRCUITING AS
REQUIRED TO MAINTAIN CONTINUITY TO OUTLETS REMAINING
ON THE CIRCUIT WITHIN OCCUPIED SPACES.
I.WHERE REQUIRED BY NEW CONSTRUCTION, PROVIDE
EXTENSION RINGS, COVERPLATES, OR ACCESS PLATES AS
REQUIRED TO MAINTAIN ACCESS TO EXISTING WIRING.
J.FIELD VERIFY LOCATIONS OF EXISTING OUTLETS. WHERE NEW
CONSTRUCTION CONFLICTS WITH EXISTING OUTLETS, REMOVE
WIRING DEVICES OR RELOCATE FIXTURES AS REQUIRED,
WHETHER OR NOT SPECIFICALLY INDICATED.
K.WHERE EXISTING WIRING DEVICES ARE REMOVED AND
JUNCTION BOXES ARE NOT REUSED, PROVIDE BLANK
COVERPLATES.
L.WHERE EXISTING CIRCUITS ARE EXTENDED TO SERVE NEW OR
RELOCATED DEVICES OR FIXTURES, PROVIDE TYPE AND SIZE
OF CONDUCTORS TO MATCH EXISTING.
M.EXISTING CIRCUITING SHALL BE FIELD VERIFIED AND
ADJUSTMENTS SHALL BE MADE, AS REQUIRED BY FIELD
CONDITIONS.
N.WHERE EXISTING ELECTRICAL WORK INTERFERES WITH NEW
WORK AND WHERE SUCH INSTALLATIONS ARE TO REMAIN IN
USE, THE INSTALLATIONS SHALL BE DISCONTINUED AND
RELOCATED AND/OR RECONNECTED TO COORDINATE WITH NEW
ELECTRICAL WORK.
O.FEEDERS AND BRANCH CONDUIT SYSTEMS ENTERING AND
LEAVING AREAS TO BE REMODELED WHICH SERVICE OTHER
ACTIVE AREAS SHALL BE THE RESPONSIBILITY OF THIS
CONTRACTOR TO MAINTAIN CONTINUITY OF THESE SYSTEMS.
P.CONTRACTOR SHALL CONSULT OTHER TRADES PRIOR TO
COMMENCING THIS WORK, TO AVOID CONFLICT.
Q.DEMOLITION DRAWINGS ARE DIAGRAMMATIC AND SHOW INTENT
OF WORK TO BE DONE. CONTRACTOR SHALL PROVIDE ALL
MATERIALS, EQUIPMENT, LABOR REQUIRED AND COST FOR
REMOVAL OF ALL SYSTEMS CALLED FOR IN CONTRACT.
R.ALL EXISTING CONSTRUCTION SHALL REMAIN UNLESS NOTED
OTHERWISE.
S.CONTRACTOR SHALL SUBMIT A TYPE WRITTEN INVENTORY OF
MAJOR ELECTRICAL EQUIPMENT TO BE REMOVED IN
DEMOLITION PHASE. INVENTORY SHALL DESCRIBE ITEM AND
QUANTITY. AFTER OWNER HAS DECIDED WHICH EQUIPMENT TO
RETAIN, CONTRACTOR SHALL REMOVE, COMPLETE FROM THE
PROJECT SITE, ALL OTHER REMAINING ELECTRICAL EQUIPMENT
INCLUDING ALL ITEMS NOT LISTED IN INVENTORY THAT ARE TO
BE REMOVED IN DEMOLITION PHASE.
T.REMOVE ALL EXISTING FIXTURES, WIRING DEVICES, ELECTRICAL
EQUIPMENT AND CIRCUITING WHETHER SPECIFICALLY
INDICATED OR NOT, AS REQUIRED BY THE ARCHITECTURAL
DEMOLITION WORK IN THE AREA TO BE RENOVATED.
U.CONTRACTOR TO PATCH AND REPAIR ALL AREAS AFFECTED BY
THE DEMOLITION.
V.FOR MECHANICAL DEMOLITION NOTES, REFER TO MECHANICAL
PLANS.
W.FIXTURES SHALL BE CLEANED THOROUGHLY AND RELAMPED
BEFORE TURNING THEM OVER TO OWNER.
X.IT IS THE INTENT OF THIS DOCUMENT TO UTILIZE THE REUSE
OF BUILDING STANDARDS, SUCH AS, BUT NOT LIMITED TO,
DOORS AND FRAMES, HARDWARE, ELECTRICAL AND TELEPHONE
RECEPTACLES, DIFFUSERS, SPEAKERS, EXIT SIGNS AND
PLUMBING FIXTURES WHERE POSSIBLE. ALL SUCH BUILDING
MATERIALS REMOVED DURING DEMOLITION SHALL BE
INVENTORIED AND NEATLY STORED ON SITE FOR REUSE. ALL
SURPLUS FIXTURES AND MATERIAL ITEMS REMOVED DURING
DEMOLITION BUT NOT REUSED DURING THIS PROJECT SHALL BE
STORED FOR LATER USE. CONTRACTORS SHALL COORDINATE
THE SEQUENCE FOR DEMOLITION AND THE LOCATION OF ON
SITE STORAGE AREAS FOR EXISTING ITEMS TO BE REUSED,
AND PROVIDE THE BUILDING WITH COPIES OF DEMOLITION
INVENTORY.
Y.THE GENERAL CONTRACTOR SHALL COORDINATE WITH THE
MECHANICAL AND ELECTRICAL ENGINEERING DRAWINGS FOR
ADDITIONAL HVAC OR ELECTRICAL DEMOLITION REQUIRED.
Z.REMOVE ALL CONSTRUCTION SHOWN ON THE DRAWINGS AS
EXISTING TO BE REMOVED, INCLUDING, BUT NOT LIMITED TO:
FLOORING, PARTITIONS, (INCLUDING ELEMENTS OCCURRING
ABOVE THE FINISHED CEILINGS), HANGERS, STRAPS AND OTHER
ACCESSORY OBJECTS CONNECTED WITH THE ITEMS BEING
REMOVED.
AA.ON REMAINING WALLS ADJACENT TO THOSE BEING
DEMOLISHED, EXISTING BASE SHALL BE REMOVED BACK TO
NEAREST INSIDE CORNER AND WALLS SHALL BE REPAIRED SO AS
TO CREATE A SMOOTH SURFACE READY TO RECEIVE NEW
BASE.
EXISTING WALL TO REMAIN
EXISTING CONSTRUCTION TO BE DEMOLISHED
EXISTING DOOR TO REMAIN
EXISTING DOOR TO BE DEMOLISHED
EXISTING CASEWORK OR OTHER ITEM TO BE DEMOLISHED
EXISTING CEILING GRID TO REMAIN
EXISTING CEILING GRID TO BE DEMOLISHED
w w w . l i t t l e o n l i n e . c o m
This drawing and the design shown are the property
of Little Diversified Architectural Consulting. The
reproduction, copying or other use of this drawing
without their written consent is prohibited and any
infringement will be subject to legal action.
Little 2017c
PROJECT MANAGER
DESIGN TEAM
PRINCIPAL IN CHARGE
PROJECT TEAM
REVISIONS
PROJECT NAME
SHEET TITLE
PROJECT NO.
SHEET NUMBER
ISSUE FOR
ISSUE DATE
B
1 2 3 4 5 6 7
A
C
D
E
F
410 Blackwell Street, Suite 10
Durham, NC 27701
T: 919.474.2500
Rob Klinedinst
Katie Buckman
Anne Lebo
10/06/17
10/9/2017 3:30:51 PM C:\Users\katie.buckman\Documents\513.7505.00_CU_WrestlingExpansion_A-16_katie.buckman.rvt513.7505.00
AD1.1.2
DEMOLITION ROOF
PLAN
Campbell Convocation
Center Wrestling
Department Renovation
and Expansion
BID/PERMIT SET
3/16" = 1'-0"AD1.1.2
1 CONVOCATION AREA C ROOF PLAN - DEMOLITION
X SHEET KEYNOTES
01 REMOVE EXISTING ROOF DRAINS (3). MINIMIZE DAMAGE TO EXISTING
MEMBRANE TO REMAIN.
02 EXISTING PVC ROOF MEMBRANE, OVERLAY BOARD, AND
INSULATION. INSPECT ROOF FOR DAMAGE AND WEAR. DOCUMENT
CONDITION WITH PHOTOS FOR OWNER AND REVIEW ANY
CONCERNS WITH OWNER. NEW ROOF WILL BE SEAMED TO
EXISTING. MAINTAIN ROOF ACCESS THROUGH EAST WALL OF STAIR
TOWER. DEMOLISH WALLS AS INDICATED AND DESCRIBED ON
DEMOLITION FLOOR PLAN. PRIOR TO DEMO OF EXTERIOR WALL,
SEPARATE PVC MEMBRANE FROM WALL AND PROTECT IN PLACE.
03 CUT DOWN WALL AND PARAPET TO BEAM BEARING LEVEL.
MAINTAIN WATER TIGHT CONDITION AT EAST WALL OF STAIR
TOWER. CUT BRICKS AND BLOCK AT JOINT TO WALL RATHER THAN
REMOVING. NEW ROOF WILL BE SEAMED TO EXISTING. PRIOR TO
DEMO OF WALL PARAPET, SEPARATE PVC MEMBRANE FROM WALL
AND PROTECT IN PLACE.
AREA C
NOT TO SCALE
EXISTING BUILDING
KEY PLAN
NO. REASON DATE
GENERAL NOTES - DEMOLITION
DEMOLITION LEGEND
SD
01
eG
e10
eE.6
eE
eF
01
01
01
WRESTLING
GYM
1142
WRESTLING
LOCKERS
1140
WRESTLING
LOCKERS
1140
VESTIBULE
1139
STAIR
1047
A.THE CONTRACTOR SHALL REMOVE SUCH EXISTING WORK AS CALLED
FOR IN CONTRACT OR AS REQUIRED TO CLEAR THE AREAS FOR NEW
CONSTRUCTION.
B.THE CONTRACTOR SHALL REMOVE ALL EXISTING WIRE NOT BEING USED
ABOVE LAY-IN CEILINGS; CONDUIT BEING ABANDONED SHALL BE
REMOVED COMPLETELY BACK TO THE SOURCE. ALL EXISTING CIRCUITS
NOT BEING USED SHALL BE MARKED AS SPARE CIRCUITS IN THE
DESIGNATED PANEL.
C.ALL DEMOLITION WORK SHALL BE PREFORMED WITH "DUE CARE AND
DILIGENCE" AS TO PREVENT THE ARBITRARY DESTRUCTION OR
INTERRUPTION OF CONCEALED UTILITIES WHICH ARE INTENDED TO
REMAIN IN USE AND THE ROUTING OF WHICH COULD NOT BE
PREDETERMINED UNTIL DEMOLITION WAS STARTED. ALL SUCH
DISCOVERIES OF UTILITIES DURING THE DEMOLITION PROCESS WHICH
ARE IN A LOCATION DIFFERENT FROM THAT INDICATED, OR ARE
UNIDENTIFIED, SHALL BE REPORTED TO THE ARCHITECT PRIOR TO
REMOVAL FOR FINAL DISPOSITION.
D.WORK DESIGNATED TO REMAIN SHALL BE PROTECTED FROM DAMAGE
AND PATCHED OR REPAIRED SHOULD DAMAGE OCCUR.
E.WHERE EXISTING EQUIPMENT IS TO BE RELOCATED, EXTREME CARE
SHALL BE TAKEN TO PREVENT DAMAGE DURING THE REMOVAL. WHERE
DAMAGE OCCURS, THE EQUIPMENT SHALL BE REPLACED OR REPAIRED
TO THE SATISFACTION OF THE OWNER AT NO ADDITIONAL COST.
F.EXCEPT AS OTHERWISE NOTED, ALL EXISTING ELECTRICAL WORK WHICH
WILL NOT BE RENDERED OBSOLETE AND WHICH MAY BE DISTURBED DUE
TO ANY CHANGES REQUIRED UNDER THIS CONTRACT, SHALL BE
RESTORED TO ITS ORIGINAL OPERATING CONDITION. OTHER
ELECTRICAL WORK OR MATERIAL RENDERED OBSOLETE SHALL BE
REMOVED OR ABANDONED WHERE CONCEALED AND REMOVED WHERE
EXPOSED. OLD, UNUSED WIRING AND DEVICES SHALL BE REMOVED
FROM THE ABANDONED (CONCEALED) CONDUITS. OUTLETS SHALL BE
PROVIDED WITH BLANK COVERS.
G.WHERE REQUIRED BY NEW CONSTRUCTION, PROVIDE EXTENSION
RINGS, COVERPLATES, OR ACCESS PLATES AS REQUIRED TO MAINTAIN
ACCESS TO EXISTING WIRING. FIELD VERIFY LOCATIONS OF EXISTING
OUTLETS. WHERE NEW CONSTRUCTION CONFLICTS WITH EXISTING
OUTLETS, REMOVE WIRING DEVICES OR RELOCATE FIXTURES AS
REQUIRED, WHETHER OR NOT SPECIFICALLY INDICATED.
H.WHERE EXISTING WIRING DEVICES ARE REMOVED AND JUNCTION BOXES
ARE NOT REUSED, PROVIDE BLANK COVERPLATES.
I.WHERE EXISTING CIRCUITS ARE EXTENDED TO SERVE NEW OR
RELOCATED DEVICES OR FIXTURES, PROVIDE TYPE AND SIZE OF
CONDUCTORS TO MATCH EXISTING.
J.EXISTING WORK TO BE REMOVED IS SHOWN DASHED, EXISTING WORK TO
REMAIN IS SHOWN WITH A SOLID LINE, AND NEW WORK IS SHOWN WITH A
HEAVY, SOLID LINE.
K.EXISTING CIRCUITING SHALL BE FIELD VERIFIED AND ADJUSTMENTS
SHALL BE MADE, AS REQUIRED BY FIELD CONDITIONS.
L.WHERE EXISTING ELECTRICAL WORK INTERFERES WITH NEW WORK AND
WHERE SUCH INSTALLATIONS ARE TO REMAIN IN USE, THE
INSTALLATIONS SHALL BE DISCONTINUED AND RELOCATED AND/OR
RECONNECTED TO COORDINATE WITH NEW ELECTRICAL WORK.
M.FEEDERS AND BRANCH CONDUIT SYSTEMS ENETERING AND LEAVING
AREAS TO BE REMODELED WHICH SERVICE OTHER ACTIVE AREAS SHALL
BE THE RESPONSIBILITY OF THIS CONTRACTOR TO MAINTAIN
CONTINUITY OF THESE SYSTEMS.
N.CONTRACTOR SHALL CONSULT OTHER TRADES PRIOR TO THE
COMMENCING THIS WORK, TO AVOID CONFLICT.
O.DEMOLITION DRAWINGS ARE DIAGRAMMATIC AND SHOW INTENT OF
WORK TO BE DONE. CONTRACTOR SHALL PROVIDE ALL MATERIALS,
EQUIPMENT, LABOR REQUIRED AND COST FOR REMOVAL OF ALL
SYSTEMS CALLED FOR IN CONTRACT.
P.CONTRACTOR SHALL SUBMIT A TYPE WRITTEN INVENTORY OF MAJOR
ELECTRICAL EQUIPMENT TO BE REMOVED IN DEMOLITION PHASE.
INVENTORY SHALL DESCRIBE ITEM AND QUANTITY. AFTER OWNER HAS
DECIDED WHICH EQUIPMENT TO RETAIN, CONTRACTOR SHALL REMOVE,
COMPLETE FROM THE PROJECT SITE, ALL OTHER REMAINING
ELECTRICAL EQUIPMENT INCLUDING ALL ITEMS NOT LISTED IN
INVENTORY THAT ARE TO BE REMOVED IN DEMOLITION PHASE.
Q.REMOVE ALL EXISTING FIXTURES, WIRING DEVICES, ELECTRICAL
EQUIPMENT AND CIRCUITING WHETHER SPECIFICALLY INDICATED OR
NOT, AS REQUIRED BY THE ARCHITECTURAL DEMOLITION WORK IN THE
AREA TO BE RENOVATED.
R.FIXTURES SHALL BE CLEANED THOROUGHLY AND RELAMPED BEFORE
TURNING THEM OVER TO OWNER.
S.IT IS THE INTENT OF THIS DOCUMENT TO UTILIZE THE REUSE OF
BUILDING STANDARDS, SUCH AS, BUT NOT LIMITED TO, DOORS AND
FRAMES, HARDWARE, ELECTRICAL AND TELEPHONE RECEPTACLES,
DIFFUSERS, SPEAKERS, EXIT SIGNS AND PLUMBING FIXTURES WHERE
POSSIBLE. ALL SUCH BUILDING MATERIALS REMOVED DURING
DEMOLITION SHALL BE INVENTORIED AND NEATLY STORED ON SITE FOR
REUSE. ALL SURPLUS FIXTURES AND MATERIAL ITEMS REMOVED
DURING DEMOLITION BUT NOT REUSED DURING THIS PROJECT SHALL
BE STORED FOR LATER USE. CONTRACTORS SHALL COORDINATE THE
SEQUENCE FOR DEMOLITION AND THE LOCATION OF ON SITE STORAGE
AREAS FOR EXISTING ITEMS TO BE REUSED, AND PROVIDE THE BUILDING
WITH COPIES OF DEMOLITION INVENTORY.
T.THE GENERAL CONTRACTOR SHALL COORDINATE WITH THE
MECHANICAL AND ELECTRICAL ENGINEERING DRAWINGS FOR
ADDITIONAL HVAC OR ELECTRICAL DEMOLITION REQUIRED.
U.REMOVE ALL CONSTRUCTION SHOWN ON THE DRAWINGS AS EXISTING
TO BE REMOVED, INCLUDING, BUT NOT LIMITED TO: FLOORING,
PARTITIONS, (INCLUDING ELEMENTS OCCURRING ABOVE THE FINISHED
CEILINGS), HANGERS, STRAPS AND OTHER ACCESSORY OBJECTS
CONNECTED WITH THE ITEMS BEING REMOVED.
EXISTING WALL TO REMAIN
EXISTING CONSTRUCTION TO BE DEMOLISHED
EXISTING DOOR TO REMAIN
EXISTING DOOR TO BE DEMOLISHED
EXISTING CASEWORK OR OTHER ITEM TO BE DEMOLISHED
EXISTING CEILING GRID TO REMAIN
EXISTING CEILING GRID TO BE DEMOLISHED
w w w . l i t t l e o n l i n e . c o m
This drawing and the design shown are the property
of Little Diversified Architectural Consulting. The
reproduction, copying or other use of this drawing
without their written consent is prohibited and any
infringement will be subject to legal action.
Little 2017c
PROJECT MANAGER
DESIGN TEAM
PRINCIPAL IN CHARGE
PROJECT TEAM
REVISIONS
PROJECT NAME
SHEET TITLE
PROJECT NO.
SHEET NUMBER
ISSUE FOR
ISSUE DATE
B
1 2 3 4 5 6 7
A
C
D
E
F
410 Blackwell Street, Suite 10
Durham, NC 27701
T: 919.474.2500
Rob Klinedinst
Katie Buckman
Anne Lebo
10/06/17
10/9/2017 3:30:53 PM C:\Users\katie.buckman\Documents\513.7505.00_CU_WrestlingExpansion_A-16_katie.buckman.rvt513.7505.00
AD1.2.1
DEMOLITION
REFLECTED CEILING
PLAN
Campbell Convocation
Center Wrestling
Department Renovation
and Expansion
BID/PERMIT SET
X SHEET KEYNOTES
3/16" = 1'-0"AD1.2.1
1 CONVOCATION AREA C REFLECTED CEILING PLAN - DEMOLITION
01 REMOVE EXISTING CEILING AND FIXTURES IN AREA INDICATED.
AREA C
NOT TO SCALE
EXISTING BUILDING
KEY PLAN
NO. REASON DATE
GENERAL NOTES - DEMOLITION
DEMOLITION LEGEND
1/2" CONTINUOUS CLOSED CELL
NEOPRENE COMPRESSED FILLER
INTERIOR PARTITION
AS SCHEDULED
CONTOUR GWB TO SILL
BELOW AS REQUIRED
PROVIDE BREAK METAL
(COLOR TO MATCH WALLS)
GLASS
WINDOW WALL
MULLION
NOTE: NO PHYSICAL OR MECHANICAL
ATTACHMENT TO MULLION SHALL BE ALLOWED.
2 HOUR RATED
PARTITION
1 HOUR RATED
PARTITION
LOWER RATED OR
NON RATED
PARTITION AS
NOTED ON PLANS
PARTITION TO MULLION
RATING HIERARCHY
DESIGN LATERAL LOAD OF 5 PSF, AND NO VERTICAL LOAD (NON-LOAD-
BEARING).
DEFLECTION LIMIT OF L/360 SHALL BE USED FOR BRITTLE WALL FINISHES,
SUCH AS TILE, TERRAZO, AND PLASTER. DEFLECTION LIMIT OF L/240 MAY
BE USED FOR ALL OTHER CONDITIONS.
"WITH SHELVING" DESIGN FOR 16" SHELVING UNIT, LOAD OF 73 POUNDS
PER LINEAR FOOT INCLUDING CONTENTS, CENTERED 8" FROM FACE OF
WALL, FOR ONE ROW OF SHELVING ROUGHLY 4' A.F.F.
DEFLECTION LIMIT OF L/240 DEFLECTION LIMIT OF L/360
WALL
HEIGHT
WITH
SHELVING
<10'362S125-18
16" O.C
362S125-18
16" O.C
362S125-18
16" O.C
362S125-18
16" O.C
<12'362S125-18
16" O.C
362S125-33
16" O.C
362S125-18
16" O.C
362S125-33
16" O.C
<14'362S125-18
16" O.C
362S125-33
16" O.C
362S125-33
16" O.C
362S125-33
16" O.C
<16'362S125-33
16" O.C
362S125-33
16" O.C
362S125-54
16" O.C
362S125-54
16" O.C
<18'362S125-43
16" O.C
362S125-43
16" O.C
600S125-33
16" O.C
600S125-33
16" O.C
<20'362S125-68
16" O.C
362S125-68
16" O.C
600S125-33
16" O.C
600S125-33
16" O.C
NOTES:
1.
2.
3.
600 S 162 - 54
MEMBER WEB DEPTH
(6" = 600 x 1/100")
STYLE
S = STUD OR JOIST SECTION
T = TRACK SECTIONS
U = CHANNEL SECTIONS
F = FURRING CHANNEL SECTIONS
FLANGE WIDTH
(1-5/8" = 1.625" = 162 x 1/100")
MIL THICKNESS
(.054" = 54 MILS;
1 MIL = 1/1000")
18 MIL = 25 GA
27 MIL = 22 GA
30 MIL = 20 GA (DRYWALL)
33 MIL = 20 GA (STRUCTURAL)
43 MIL = 18 GA
54 MIL = 16 GA
68 MIL = 14 GA
WITH
SHELVING
WITHOUT
SHELVING
WITHOUT
SHELVING
CONCRETE / CMU WALL
3/4" MAX ACOUSTICAL SEALANT OR ACRYLIC
FIRESTOP SEALANT. BACKER ROD AS NEEDED
(1) OR (2) LAYERS OF GYPSUM WALLBOARD PER
PARTITION TAG
METAL STUD PER PARTITION TAG
ONE SIDE OF DOOR OPENINGS
AT RECESSES
AT LOCATION STRUCUTRE
INTERRUPTS THE WALL THICKNESS
AT CHANGE OF WALL THICKNESS
CHANGE IN HEIGHT OF WALL
MORE THAN 16"
BUILDING EXPANSION JOINT
ALIGNED WITH BUILDING JOINTSUNBOUNDED INTERSECTION
BOUNDED INTERSECTION
L / 2LPROVIDE CONTROL JOINTS IN CMU PARTITION AS NOTED ABOVE AND AT MAXIMUM SPACING OF L.
L = 24' MAX OR 3 TIMES THE HEIGHT OF THE PARTITION
15' MAX30' MAX30' MAX
FLOORLATCH SIDE OF
DOOR
STRUCTURE
CEILING
CONTROL
JOINT
INTERSECTING
PARTITION
OPENING
GENERAL NOTE: FOLLOW
GUIDELINES FOR CONTROL JOINTS
PER ASTM C-840 STANDARD
SPECIFICATION FOR APPLICATION
AND FINISHING OF GYPSUM BOARD
PLAN OVER DRYWALL
6" METAL STUD WALL
w/ 5/8" GYP. BD. EACH SIDE
FULLY-RECESSED FIRE
EXTINGUISHER CABINET.
FINISH SHALL BE BRUSHED S.S.
ELEVATION
DOUBLE, 22 GA. 6" STUDS
ON EA. SIDE
VERIFY W/ MANUF.
10 1/2"
PLAN OVER CMU
1 1/2" MTL. STUD FURROUT
W/ 5/8" GYP. BD. EACH SIDE
RATED CMU WALL
w/ FILLED CELLS
FE
VERIFY W/ MANUF.
11 1/2"
F.E.C.
FIRE-RATED F.E.C.
FE
FE
TOP OF EXTINGUISHER AT
48" AFF
PLAN
BASE
CEILING
TOP
BASE & FLOOR FINISH AS
SCHEDULED
1" GYPSUM LINER PANEL
TYPE X GYPSUM PANELS,
FACE LAYER JOINT FINISHED.
1 HR - (1) 5/8"
2 HR - (2) 5/8"
C-H Studs @ 24" O.C.
CONTINUOUS METAL
J-RUNNER
TYPE X GYPSUM PANELS,
FACE LAYER JOINT FINISHED.
1 HR - (1) 5/8"
2 HR - (2) 5/8"
C-H Studs @ 24" O.C.CONTINUOUS METAL
J-RUNNER
PROVIDE 1/2" SPACE FROM
RUNNER TO TOP OF STUD TO
ALLOW FOR FLOOR SLAB
DEFLECTION
SEE RCP & FINISH
SCHEDULE FOR CEILING
MATERIAL & FINISH
SHAFT SIDE
SHAFT SIDE
FLOOR CONSTRUCTION
NOTE:
1 HR = UL U469
2 HR = UL U438
2-1/2" = 12'-3" MAX.
4" = 17'-6" MAX.
2-1/2" = 12'-3" MAX.
4" = 17'-6" MAX.
BASE AS SCHEDULED
(SOUND ATTENUATION - SAND
FILLED) >S
8" x 8" x 16" NOMINAL CMU
PLAN
BASE
CEILING
TOP
REINFORCING AS REQ'D,
SEE STRUCTURAL
SET BOTTOM COURSE IN
FULL MORTAR BED
(SOUND ATTENUATION - SAND
FILLED) >S
SEE HEAD OF WALL DETAILS
FOR APPLICABLE PARTITION
HEIGHT CATEGORY & RATING
SEE RCP & FINISH
SCHEDULE FOR CEILING
MATERIAL & FINISH
SEALANT BOTH SIDES AS
REQUIRED
NOTE:
1.
2.
( ) = MODIFIER
2 HR = UL U906
3 HR = UL U914
4 HR = UL U901
8" x 8" x 16" NOMINAL CMU
FLOOR FINISH AS SCHEDULED
BASE & FLOOR
FINISH AS
SCHEDULED
(SOUND ATTENUATION
BLANKETS) >S
(1) LAYER 5/8" GYPSUM
BOARD BOTH SIDES
PLAN
BASE
CEILING
TOP
METAL STUDS @ 16" O.C.
CONTINUOUS METAL
RUNNER
(SOUND ATTENUATION
BLANKETS) >S
(1) LAYER 5/8" GYPSUM
BOARD BOTH SIDES
METAL STUDS @ 16" O.C.
SEE HEAD OF WALL
DETAILS FOR APPLICABLE
PARTITION HEIGHT
CATEGORY & RATING
SEE RCP & FINISH
SCHEDULE FOR CEILING
MATERIAL & FINISH
HOLD GWB 1/2" ABOVE SLAB
NOTE:
1.
2.
( ) = MODIFIER
TYPE X FIRE RATED
CORE FOR RATED
CONDITION
1 HR = UL U419
2 HR = UL U411
HEAD DETAIL - UL HW-D-1011
FIRE TRAK DEFLECTION SYSTEM 1HR. & 2HR. SHADOWLINE
3" DEFLECTION
4" DEFLECTION AT EAST & WEST DATA HALL WALLS
FIRE RATED GYPSUM
COMPOUND OR FIRE
CAULK
ROOF SLAB
FIRE TRAK SHADOWLINE
POSI CLIPS2"4" @ E&W3"2"8"METAL STUD
5/8" TYPE 'X' GYP.
2 HR. RATING REQUIRES
ADDITIONAL LAYER OF TYPE
'X' GYP.
CORNER BEAD
5/8" TYPE 'X' GYP.
2 HR. RATING REQUIRES
ADDITIONAL LAYER OF
TYPE 'X' GYP.
FIRE TRAK DEFLECTION SYSTEM 1HR. & 2HR. SHADOWLINE
3" DEFLECTION
METAL STUD
FIRE TRAK SHADOWLINE
POSI CLIPS6"3"4"5/8" TYPE 'X' GYP.
2 HR. RATING REQUIRES
ADDITIONAL LAYER OF TYPE 'X' GYP.1' - 1"CORNER BEAD
CORNER BEAD
METAL STUD
5/8" TYPE 'X' GYP.
2 HR. RATING REQUIRES
ADDITIONAL LAYER OF TYPE 'X' GYP.
5/8" TYPE 'X' GYP.
2 HR. RATING REQUIRES
ADDITIONAL LAYER OF TYPE 'X' GYP.
SEALANT AND BACKER ROD
SEALANT AND BACKER ROD
VERTICAL REINFORCEMENT PER
STRUCTURAL DRAWINGS
VERTICAL REINFORCEMENT PER
STRUCTURAL DRAWINGS
REFER TO STRUCTURAL DRAWINGS FOR HORIZONTAL
REINFORCEMENT AT CONTROL JOINTS
PREFORMED CONTROL JOINT GASKET
CONTROL JOINT - BOTH SIDES
ACOUSTICAL SEALANT -
BOTH SIDES
METAL STUD PER
PARTITION TYPE
GWB PER PARTITION TYPE
1/2" MAX 1/2" MAX
1/2" MIN
TWO LAYER OF GWB
NON-RATED
JOINT
RATED JOINT
WHI -647-3024
WH1-651-0318.1
METAL RUNNER TRACK- SEE HEAD
DETAILS THIS SHEET
PARTITION AS SCHEDULED ON PLANS
CEILING - SEE REFLECTED CEILING PLANS
SOUND ATTENUATION BLANKETS PER
PARTITION TAG
METAL STUD TO STRUCTURE
8"STRUCTURE
8"METAL STUD BRACING TO STRUCTURE
METAL RUNNER TRACK
PARTITION AS SCHEDULED ON PLANS
CEILING - SEE REFLECTED CEILING PLANS
SOUND ATTENUATION BLANKETS PER
PARTITION TAG
CONTRACTOR OPTION - METAL
STUD TO STRUCTURE ILO BRACING
TAPE AND JOINT COMPOUND
GYPSUM SUSPENDED CEILING
RUNNER CHANNEL
FURRING CHANNEL AND CLIP
TOGGLE BOLT
GYPSUM WALL BOARD PER TAG
STEEL STUD PER TAG
STEEL STUD TRACK
ACOUSTICAL TILE PER FINISH SCHEDULE
PARTITION CEILING TRACK
PARTITION CLIP COORDINATE
TYPE WITH TILE
VERTICAL STRUCT OR STABILIZER BAR
SPLAY WIRES PERPENDICULAR
TO PARTITION4
5.00°"T" SECTION
STEEL STUD PER PARTITION TAG
MINERAL WOOL BATT
INSULATION
ROOF / FLOOR DECK
FIRESTOP JOINT SPRAY
METAL CEILING
TRACK RUNNER
PARTITION PER PLAN
SOUND ATTENUATION
BLANKETS
LAYER OF GWB COPED
INTO METAL DECK
PARTITION PER PLAN
CONTINUOUS
ACOUSTICAL
SEALANT BETWEEN
GWB AND DECK
METAL CEILING RUNNER
SCREWED TO DECK
RATED CONDITION NON - RATED CONDITION
ROOF / FLOOR DECK
1"1"FORMING MATERIAL -
MINERAL WOOL
ROOF / FLOOR DECK
FIRESTOP JOINT SPRAY
METAL CEILING
TRACK RUNNER
PARTITION PER PLAN 1"ACOUSTICAL SEALANT1"FASTEN METAL
CEILING TRACK
RUNNER TO CLIPS
BEAM PER STRUCTURAL
Z-CLIP @ 2'-0" O.C. FASTEN
BEFORE SFRM APPLICATION
SFRM PER UL RATING
6"NO GWB SCREWS ABOVE
THIS POINT. NO SCREWS
INTO RUNNER
2" WIDE STEEL STRAPS -
24" O.C.
FORMING MATERIAL -
MINERIAL WOOL PLUGS
SOUND ATTENUATION
BLANKETS
RATED HEAD CONDITION NON RATED HEAD CONDITION NON RATED HEAD CONDITION
AT BEAM
ROOF / FLOOR DECK
NO GWB SCREWS ABOVE
THIS POINT. NO SCREWS
INTO RUNNER
METAL CEILING
TRACK RUNNER
PARTITION PER PLAN
2" WIDE STEEL
STRAPS - 24" O.C.
PARTITION PER PLAN
NO GWB SCREWS ABOVE
THIS POINT. NO SCREWS
INTO RUNNER6"6"1"CONTROL JOINT
ACOUSTICAL SEALANT - BOTH
SIDES
METAL STUD PER PARTITION
TYPE
GWB PER PARTITION TYPE
7/8" HAT CHANNEL
CMU PARTITION
CMU PARTITION PER PLAN
ROOF/ FLOOR JOIST PER STRUCUTURAL1"SFRM PER FLOOR ASSEMBLY
CUT BLOCK AS NEED TO PROVIDE 1" GAP BETWEEN
STRUCUTRAL AND PARTITION
ROOF/FLOOR DECKING PER ASSEMBLY
CONT. ANGLE PER STRUCTRAL FOR
PARTITION LATERAL BRACING
CUT BLOCK AS NEED TO PROVIDE
1" GAP BETWEEN STRUCUTRAL
AND PARTITION
MINERAL WOOL BATT INSULATION
SPRAY OR TROWELED FIRESTOP
CMU PARTITION RATED HEAD DETAIL
AT JOIST / BEAM
CMU PARTITION RATED HEAD DETAIL
BETWEEN JOIST / BEAM 1"CMU PARTITION PER PLAN
ANGLE PER STRUCTURAL
ANCHORED TO BEAM / JOIST
CUT BLOCK AS NEED TO PROVIDE
1" GAP BETWEEN STRUCUTRAL
AND PARTITION
ROOF/FLOOR DECKING PER
ASSEMBLY
CONT. ANGLE PER STRUCTRAL
FOR PARTITION LATERAL
BRACING
MINERAL WOOL BATT
INSULATION
SPRAY OR TROWELED
FIRESTOP
CMU PARTITION RATED HEAD DETAIL
AT JOIST / BEAM
CMU PARTITION HEAD DETAIL
AT BEAM1"SFRM
BEAM, SEE STRUCTURAL
ROOF/FLOOR DECKING
PER ASSEMBLY
CONT. ANGLE WELDED
TO BEAM1"FIRE STOPPING AT RATED
CONDITIONS,
COMPRESSIBLE FILLER W/
ACOUSTICAL SEALANT AT
NON RATED CONDITIONS
1.FIRE- AND SMOKE-RATED PARTITION ASSEMBLIES CONTINUE TO
STRUCTURE ABOVE (HEAD CONDITION "A") UNLESS NOTED OTHERWISE,
OR UNLESS OTHERWISE INDICATED BY THE CORRESPONDING FIRE
RATED ASSEMBLY DIAGRAM.
2.PROVIDE ACOUSTICAL CAULKING AROUND ALL PERIMETERS EDGES AND
PENETRATIONS AT SOUND-INSULATED WALLS. OFFSET ELECT. AND
TELEPHONE OUTLETS 16" MIN (SEPARATE STUD CAVITIES). AT SOUND
INSULATED WALLS PROVIDE ACOUSTICAL CAULKING AROUND ALL
PERIMETERS EDGES AND PENETRATIONS. OFFSET ELECT. AND
TELEPHONE OUTLETS 16” MIN (SEPARATE STUD CAVITIES)
3.WALLS ARE DIMENSIONED TO FINISH FACE OF WALL, UNLESS INDICATED
OTHERWISE.
4.WHERE ADJACENT PARTITION TYPES ARE OF DIFFERENT OVERALL
THICKNESS, ALIGN FINISHES ON VISIBLE SIDE, AND FURR OPPOSITE SIDE
AS REQUIRED FOR A FLUSH INSTALLATION.
5.PARTITION TYPES AROUND ROOMS AND SPACES SHALL BE CONTINUOUS
AROUND THE ENTIRE SPACE. WHERE MORE THAN ONE PARTITION TYPE
IS INDICATED, THE WALL TYPE WITH THE HIGHEST FIRE AND/OR
ACOUSTICAL PERFORMANCE SHALL BE USED.
6.FIRE SAFE ALL PENETRATIONS THROUGH FIRE RATED WALLS TO THE
LEVEL OF PROTECTION REQUIRED BY THE WALL. FIRE SAFE AT
PERIMETERS OF RATED WALLS WHERE VOIDS OCCUR, SUCH AS DECK
FLUTES.
7.REFER TO THE FINISH SCHEDULE AND/OR FLOOR PLANS FOR LOCATION
OF FINISH MATERIALS FOR WALL TYPES INDICATING DIFFERENT FINISHES
ON EACH SIDE OF WALL.
8.WET WALLS IN TOILET ROOMS TO RECEIVE CERAMIC TILE SHALL USE
MOISTURE-RESISTANT FIBERGLASS-MAT GYPSUM BOARD IN PLACE OF
GWB.
9.BRACE ALL CHASE WALLS FROM STUD TO STUD AT 4” OC MIN. VERTICAL
AND PER MANUFACTURER'S RECOMMENDATION UNLESS NOTED
OTHERWISE.
10.PROVIDE STEEL STUD GAUGES AND/OR DIAGONAL BRACING AT TOPS OF
WALLS PER MANUFACTURER'S RECOMMENDATIONS FOR WALL TYPE,
HEIGHT, AND USE BASED ON L/240 LIMITING HEIGHTS."
11.ALL CORNERS AND EDGES EXPOSED TO VIEW SHALL RECEIVE METAL
EDGE BEADS TREATED WITH DRYWALL COMPOUND TO A HEIGHT OF 6”
ABOVE FINISHED CEILINGS MIN."
12.ALL UL-RATED WALL ASSEMBLIES SHALL BE IDENTIFIED W/ STENCILING
ABOVE THE FINISHED CEILING ON BOTH FACES, ON ALL WALLS AS "FIRE
AND SMOKE BARRIER - PROTECT ALL OPENINGS" WITH HOUR RATING
INCLUDED.
13.ALL MATERIALS USED IN RATED ASSEMBLIES SHALL CONFORM TO
REFERENCED STANDARDS."
14.USE MOISTURE- AND MOLD-RESISTANT GWB ON INTERIOR SIDE OF
MECHANICAL ROOM WALLS."
15.PROVIDE CONTINUOUS HORIZONTAL BRIDGING FOR WALLS EXTENDING
10'-0" OR GREATER IN HEIGHT FROM FINISH FLOOR.
PARTITION RATING:
0xxx NON-RATED
1xxx 1-HOUR RATED
2xxx 2-HOUR RATED
3xxx 3-HOUR RATED
4xxx 4-HOUR RATED
PARTITION RATING
PARTITION MATERIAL
NOMINAL WIDTH OF STRUCTURE
NXNX X
PARTITION HEIGHT CATEGORY
(EXTEND TO STRUCTURE IF NOT INDICATED)
PARTITION MODIFIER
PARTITION CONSTRUCTION:
xFxx FURRING
xGxx GYP / METAL STUD
xSxx SHAFT
xMxx MASONRY
xWxx GYP / WOOD STUD
xExx EXISTING
NOMINAL WIDTH OF STRUCTURE:
(SEE PARTITION STRUCTURE KEY AT LEFT)
PARTITION HEIGHT CATEGORY:
xxxA EXTEND TO STRUCTURE ABOVE
xxxB TERMINATE ABOVE CEILING
xxxC TERMINATE AT CEILING
xxxP PARTIAL HEIGHT PARTITIONS
PARTITION MODIFIER:
A ABOVE ACCESS FLOOR
B BALLISTIC LEVEL RATED
E EXTRA LAYER OF GYPSUM
G GROUT MASONRY SOLID
I IMPACT RESISTANT
K SMOKE RATED
M METAL PANEL
O MOVABLE PARTITION
(OPERABLE)
R MOISTURE RESISTANT
S SOUND ATTENUATION BATTS
V VAPOR BARRIER
Z ACCENT WALL
(SEE INTERIOR DETAILS)
NON STRUCTURAL METAL FRAMING CONCRETE MASONRY UNIT (CMU)
METAL FURRING CHANNELS
NON STRUCTURAL SHAFT FRAMING
WOOD FRAMING
xG1x 1-5/8" METAL STUD
xG2x 2-1/2" METAL STUD
xG3x 3-5/8" METAL STUD
xG4x 4" METAL STUD
xG6x 6" METAL STUD
xG8x 8" METAL STUD
xM4x 4" CMU
xM6x 6" CMU
xM8x 8" CMU
xM12x 12" CMU
xF0x 1/2" FURRING CHANNEL
xF1x 7/8" FURRING CHANNEL
xF2x 1-1/2" FURRING CHANNEL
NOTE: FOR SIZES ABOVE xF2x USE NON-
STRUCTURAL METAL FRAMING ATTACHED
TO SUBSTRATE
xS2x 2-1/2" C-H STUD W/ 1" GYP SHAFT LINER
xS4x 4" C-H STUD W/ 1" GYP SHAFT LINER
xS6x 6" C-H STUD W/ 1" GYP SHAFT LINER
xW4x 2X4 WOOD FRAMING
xW6x 2X6 WOOD FRAMING
xW8x 2X8 WOOD FRAMING
w w w . l i t t l e o n l i n e . c o m
This drawing and the design shown are the property
of Little Diversified Architectural Consulting. The
reproduction, copying or other use of this drawing
without their written consent is prohibited and any
infringement will be subject to legal action.
Little 2017c
PROJECT MANAGER
DESIGN TEAM
PRINCIPAL IN CHARGE
PROJECT TEAM
REVISIONS
PROJECT NAME
SHEET TITLE
PROJECT NO.
SHEET NUMBER
ISSUE FOR
ISSUE DATE
B
1 2 3 4 5 6 7
A
C
D
E
F
410 Blackwell Street, Suite 10
Durham, NC 27701
T: 919.474.2500
Rob Klinedinst
Katie Buckman
Anne Lebo
10/06/17
10/9/2017 3:30:20 PM C:\Users\katie.buckman\Documents\513.7505.00_CU_WrestlingExpansion_A-16_katie.buckman.rvt513.7505.00
A0.1.0
WALL TYPES
Campbell Convocation
Center Wrestling
Department Renovation
and Expansion
BID/PERMIT SET
GENERAL NOTES - PARTITIONS
PARTITION HEIRARCHY
LIMITING HEIGHTS - STEEL STUD
PARTITION TAG KEY
NOT TO SCALE
<xS3A> SHAFT - SLAB TO DECK
NOT TO SCALE
<xMxA> MASONRY - SLAB TO DECK
NOT TO SCALE
<xGxA> GWB - SLAB TO DECK
NOT TO SCALE
HEAD OF WALL DETAIL - DEFLECTION TRACK NOT TO SCALE
HEAD DETAIL - DEFLECTION TRACK
PARTITION STRUCTURE KEY
PARTITION TYPES
FIRE EXTINGUISHER CABINETGWB PARTITION, DEFLECTION TRACK
CMU CONTROL JOINTSGWB CONTROL JOINTS
NOT TO SCALE
CONTROL JOINT - CMU
NOT TO SCALE
HEAD - GWB - COND. B(2)
NOT TO SCALE
HEAD - GWB - COND. B(1)
NOT TO SCALE
HEAD - GWB - COND. C
NOT TO SCALE
HEAD - GWB - COND. C (ACT)
NOT TO SCALE
HEAD - GWB - PERPENDICULAR TO DECK - COND. A
NOT TO SCALE
HEAD - GWB - PARALLEL TO DECKING
NOT TO SCALE
GWB CONTROL JOINT AT FRAMING CHANGE
GWB HEAD CONDITIONS
CMU HEAD CONDITIONS
NOT TO SCALE
HEAD - CMU - PARALLEL TO DECKING
NOT TO SCALE
HEAD - CMU RATED - PERPENDICULAR TO DECKING
NO. REASON DATE
FECFEC 1.ALL INTERIOR LOAD BEARING MASONRY WALLS SUPPORTING ROOF ONLY
SHALL MAINTAIN A 1 HOUR FIRE RATING FOLLOWING UL U905.
2.ALL EXTERIOR LOAD BEARING WALLS SHALL MAINTAIN A 2 HOUR FIRE
RATING FOLLOWING UL U905.
3.ROOF STRUCTURE/DECKING TO MAINTAIN A 1 HOUR FIRE RATING
FOLLOWING UL P732
4.UNWRAPPED STRUCTURAL TUBE COLUMNS IN EXTERIOR LOAD BEARING
WALLS TO MAINTAIN A 2 HOUR FIRE RATING FOLLOWING UL U622.
5.WORK NOTED "BY OTHERS" OR "NIC" SHALL BE PROVIDED BY OWNER OR
UNDER SEPARATE CONTRACT.
6.SEE SHEET PARTITION TAG KEY AND A0.1.0 FOR PARTITION TYPES.
7.SEE SHEET A9.0.0 FOR DOOR TYPES AND DETAILS
8.PROVIDE CONTROL JOINTS ON GYP. BD. ASSEMBLIES PER SPECIFICATIONS
AND WHERE SHOWN.
9.EXTEND WALLS TO DECK ABOVE STOREFRONT SYSTEMS AND GLASS WALL
PARTITIONS.
10.REVIEW DOCUMENTS AND VERIFY DIMENSIONS AND FIELD CONDITIONS WHEN
APPLICABLE. CONFIRM THAT WORK IS BUILDABLE AS SHOWN. ANY
CONFLICTS OR OMISSIONS SHALL BE IMMEDIATELY REPORTED TO THE
ARCHITECT FOR CLARIFICATION PRIOR TO THE PERFORMANCE OF WORK IN
QUESTIONS.
11.COORDINATE AND PROVIDE METAL OR RATED SOLID WOOD BLOCKING (FIRE
TREATED) IN PARTITIONS AND CEILING FOR MILLWORK, WALL AND CEILING
ATTACHED ITEMS AS SPECIFIED.
12.DO NOT SCALE DRAWINGS. WRITTEN DIMENSIONS GOVERN. ALL PARTITION
LOCATIONS, DIMENSIONS AND TYPES, DOOR AND WINDOW LOCATIONS
SHALL BE AS SHOWN ON PARTITION PLAN. INCASE OF CONFLICT, NOTIFY
ARCHITECT.
13.COORDINATE WITH TENANT AND OWNER, THE SCHEDULE FOR TELEPHONE,
DATA, SECURITY AND AUDIO VISUAL INSTALLATIONS.
14.PARTITIONS AT BUILDING PERIMETER SHALL BE CENTERED ON CENTER LINE
OF COLUMN OR WINDOW MULLION, UNLESS OTHERWISE NOTED.
15.PROVIDE PARTITION TYPE WITH THE HIGHEST UL AND/OR ACOUSTICAL
PERFORMANCE RATING WHERE MORE THAN ONE PARTITION TYPE IS
INDICATED. PARTITIONS SHALL BE HEAD CONDITION 'A' UNLESS OTHERWISE
NOTED.
16.OFFSET ELECTRICAL AND TELEPHONE OUTLETS 16" MINIMUM IN SEPARATE
STUD WALL CAVITIES.
1.AT SOUND INSULATED WALLS PROVIDE ACOUSTICAL CAULKING
AROUND ALL PERIMETERS EDGES AND PENETRATIONS. OFFSET ELECT.
AND TELEPHONE OUTLETS 16" MIN (SEPARATE STUD CAVITIES)
2.WALLS ARE DIMENSIONED TO FINISH FACE OF WALL, UNLESS
INDICATED OTHERWISE
3.WHERE ADJACENT PARTITION TYPES ARE OF DIFFERENT OVER ALL
THICKNESS, ALIGN FINISHES ON VISIBLE SIDE, AND FURR OPPOSITE
SIDE AS REQUIRED FOR A FLUSH INSTALLATION
4.PARTITION TYPES AROUND ROOMS AND SPACES SHALL BE
CONTINUOUS AROUND THE ENTIRE SPACE. WHERE MORE THAN ONE
PARTITION TYPE IS INDICATED, THE WALL TYPE WITH THE HIGHEST FIRE
AND OR ACOUSTICAL PERFORMANCE SHALL BE USED.
5.FIRE SAFE ALL PENETRATIONS THROUGH FIRE RATED WALLS TO THE
LEVEL OF PROTECTION REQUIRED BY THE WALL. FIRE SAFE AT
PERIMETERS OF RATED WALLS WHERE VOIDS OCCUR, SUCH AS FLOOR
DECK FLUTES.
6.REFER TO THE FINISH SCHEDULE AND / OR FLOOR PLANS FOR
LOCATION OF FINISH MATERIALS FOR WALL TYPES INDICATING
DIFFERENT FINISHES ON EACH SIDE OF THE WALL.
7.WET WALLS IN TOILET ROOMS TO RECEIVE CERAMIC TILE SHALL USE
MOISTURE RESISTANT FIBERGLASS-MAT GYP. BOARD IN PLACE OF GYP.
BOARD.
8.CROSS BRACE ALL CHASE WALLS FROM STUD TO STUD AT 4" O.C. MIN.,
VERTICAL AND PER MANUFACTURES RECOMMENDATION UNLESS
NOTED OTHERWISE.
9.PROVIDE STEEL STUD GAUGES AND OR DIA. BRACING AT TOPS OF
WALLS PER MANUFACTURES RECOMMENDATIONS FOR WALL TYPE,
HEIGHT & USE - BASED ON L/240 LIMITING HEIGHTS.
10.ALL EXPOSED TO VIEW, CORNERS & ENDS SHALL RECEIVE MTL. EDGE
BEADS TREATED WITH DRYWALL COMPOUND TO A HEIGHT OF 6" ABOVE
FINISHED CEILINGS.
11.ALL UL RATED WALL ASSEMBLIES SHALL BE IDENTIFIED w/ STENCILING
ABOVE THE FINISHED CEILING ON BOTH FACES, ON ALL WALLS AS "FIRE
& SMOKE BARRIER-PROTECT ALL OPENINGS" WITH HOUR RATING
INCLUDED.
12.ALL MATERIALS USED IN RATED ASSEMBLIES SHALL CONFORM TO
REFERENCED STANDARDS.
13.USE MOISTURE AND MOLD-RESISTANT GWB ON INTERIOR SIDE OF
MECHANICAL ROOM WALLS
PARTITION RATING:
0xxx NON-RATED
1xxx 1-HOUR RATED
2xxx 2-HOUR RATED
3xxx 3-HOUR RATED
4xxx 4-HOUR RATED
PARTITION RATING
PARTITION MATERIAL
NOMINAL WIDTH OF STRUCTURE
NXNX X
PARTITION HEIGHT CATEGORY
(EXTEND TO STRUCTURE IF NOT INDICATED)
PARTITION MODIFIER
PARTITION CONSTRUCTION:
xFxx FURRING
xGxx GYP / METAL STUD
xSxx SHAFT
xMxx MASONRY
xWxx GYP / WOOD STUD
xExx EXISTING
NOMINAL WIDTH OF STRUCTURE:
(SEE PARTITION STRUCTURE KEY AT LEFT)
PARTITION HEIGHT CATEGORY:
xxxA EXTEND TO STRUCTURE ABOVE
xxxB TERMINATE ABOVE CEILING
xxxC TERMINATE AT CEILING
xxxP PARTIAL HEIGHT PARTITIONS
PARTITION MODIFIER:
A ABOVE ACCESS FLOOR
B BALLISTIC LEVEL RATED
E EXTRA LAYER OF GYPSUM
G GROUT MASONRY SOLID
I IMPACT RESISTANT
K SMOKE RATED
M METAL PANEL
O MOVABLE PARTITION
(OPERABLE)
R MOISTURE RESISTANT
S SOUND ATTENUATION BATTS
V VAPOR BARRIER
Z ACCENT WALL
(SEE INTERIOR DETAILS)
INTERIOR
ELEVATION
MARKER
ELEVATION DATUM
POINT
EXTERIOR
ELEVATION
MARKER NORTH ARROW
DOOR NUMBER
ALUMINUM FRAMING
SYSTEM TAG
DETAIL MARKER
SECTION MARKER
COLUMN GRID
AND GRID BUBBLES
ROOM NAME
ROOM NUMBER
A301
2
CARD READER
AFS-20
CR
WALL TAG
WINDOW TAG
TOILET
ACCESSORIES TAG
SHEET KEYNOTE
MATERIALS TAG
EQUIPMENT TAG
0A00A KX
00
?
A
EQ-1
PTD
2222
VIEW ELEMENTS SITE & LOCATION ELEMENTSARCHITECTURAL ELEMENTS
ANNOTATIONS
00
00AA
ROOM
NAME
101
1
A101
SIM
A5.0.2B
1
A5.0.2B
1
1
1
1
Level Name
0'-0"
CEILING TYPE
FINISH ELEVATIONACT-1
+1' - 0"
A2.1.1
3
RECEPTION
1143
ASST.
COACH
OFFICES
1144
COACH
1146
STORAGE
1147
FITNESS
1148LOUNGE
1149
WRESTLING
GYM
1142
COACH
LOCKERS
1137
1D
A3.1.0
1C
A3.1.0
1A
A3.1.0
2M8A
2M8A
COACH
RESTROOM
1138
CONFERENCE
1145
92' - 7 3/8"11' - 4"2' - 8"40' - 0" MAT, TYP.6 3/16"8"2' - 0"2' - 0"2' - 0"16' - 0"2' - 4"16' - 0"9' - 0"6' - 8"6' - 2"2' - 10"7' - 5"5' - 11"8"5' - 11"3' - 5"16' - 0"11' - 0"8' - 0"A2.1.1
2
2A
A3.2.0
4A
A3.2.0
1A
A3.2.1
WRESTLING
LOCKERS
1140
VESTIBULE
1139
STAIR
1047
WRESTLING
GYM
ADDITION
CORRIDOR
1150
A2.1.1
1
A4.0.0
5A
A4.0.0
5D
A4.0.01A1137A1138A1139A1140A
1047C
1149A1148A1147A1146A1144B
1143A
1136A
0G6A S
0G6A S
0G3A S
0G6A S
0G6A S
0G6B0G6B0G6B8'-6"8'-3"3'-4"N-35' - 11 3/16"
8' - 0"
8 3/8"
2A
A3.2.0
Sim
eG
e10
eE.6
eE
eF
01
0202
MAINTAIN 10'-0" X 7'-0"
CLR. PER OWNER
REQUEST
0303 03 03 03 03 03 03 03
2' - 9"4' - 1"4' - 1"4' - 1"4' - 8"4' - 4 5/8"4' - 8 1/8"4' - 8 1/8"4' - 8 1/8"2' - 0 1/2"
04
04
A3.2.1
5A
N-2 N-2
N-3N-1N-1N-1
05
05
05 05
05
06
03
07
2' - 0"2' - 0"1' - 0"1' - 5"8"EQ
E Q 6' - 4"1' - 1"A2.2.0
2D
6A
A3.2.0
40' - 0" MAT, TYP.
38' - 0"6' - 6 3/8"29' - 10 7/8"6' - 6 3/8"ALIGN WITH EXISTING CMU FACE AT INTERIOR OF SPACE42' - 11 5/8"24' - 0"ALIGN
ALIGN
7' - 4"16' - 8"4'-0"8'-0"7'-4"8'-0"7'-4"8'-0"7'-4"8'-0"7'-4"12'-0"3'-4"8'-0"7'-4"8'-0"7'-4"8'-0"2'-8"1' - 7"6' - 0"9' - 4"5' - 8 1/4"5' - 3 5/8"4' - 8"8' - 0"7' - 4"8' - 0"7' - 4"8' - 0"7' - 4"8' - 0"7' - 4"8' - 0"7' - 4"8' - 0"7' - 4"8' - 0"7' - 4"8' - 0"
ALIGN ALIGN
10' - 8 3/4"
122' - 0"16' - 4 3/4"08
08
08
08
080808080808
08080808080808080808
08
08
09
2' - 6"4' - 10"4' - 10"
09
2' - 6"4' - 10"4' - 10"
09
2' - 6"4' - 10"4' - 10"
09
2' - 5"
09
2' - 5"2' - 5"093' - 9"4' - 9"3' - 9"4' - 9"10
10
11
11
12
12
1145A1144A1140BWRESTLING
ENTRY
1136
0G6A
6A
A3.2.0
Sim
w w w . l i t t l e o n l i n e . c o m
This drawing and the design shown are the property
of Little Diversified Architectural Consulting. The
reproduction, copying or other use of this drawing
without their written consent is prohibited and any
infringement will be subject to legal action.
Little 2017c
PROJECT MANAGER
DESIGN TEAM
PRINCIPAL IN CHARGE
PROJECT TEAM
REVISIONS
PROJECT NAME
SHEET TITLE
PROJECT NO.
SHEET NUMBER
ISSUE FOR
ISSUE DATE
B
1 2 3 4 5 6 7
A
C
D
E
F
410 Blackwell Street, Suite 10
Durham, NC 27701
T: 919.474.2500
Rob Klinedinst
Katie Buckman
Anne Lebo
10/06/17
10/9/2017 3:30:24 PM C:\Users\katie.buckman\Documents\513.7505.00_CU_WrestlingExpansion_A-16_katie.buckman.rvt513.7505.00
A1.1.1
FLOOR PLAN AREA C
Campbell Convocation
Center Wrestling
Department Renovation
and Expansion
BID/PERMIT SET
X SHEET KEYNOTES
GENERAL NOTES - FLOOR PLAN
GENERAL NOTES - PARTITION TYPES
PARTITION TAG LEGEND
FLOOR PLAN LEGEND X SHEET KEYNOTES
3/16" = 1'-0"A1.1.1
1 CONVOCATION AREA C FLOOR PLAN
AREA C
NOT TO SCALE
EXISTING BUILDING
KEY PLAN
NO. REASON DATE
01 NEW WRESTLING MAT BY OWNER - PROMATS RESILIT MODEL
RSP-625 OR EQUAL, 1 1/4" THICK, 40' X 40', ONE TONE, STANDARD
DESIGN - BURNT ORANGE WITH BLACK LINES. BY OWNER
02 EXISTING WRESTING MATS
03 RUBBER TRANSITION STRIP - EXISTING MONDO FLOORING IN
PRACTICE GYM. VCT IN CORRIDOR. TRANSITION STRIP TO MATCH
VCT. SEE FINISH SCHEDULE
04 FITNESS EQUIPMENT IN THIS AREA BY OWNER. SHOWN FOR SPACE
PLANNING PURPOSES AND POWER/DATA LOCATIONS ONLY
05 FURNITURE IN THIS AREA BY OWNER. SHOWN FOR SPACE
PLANNING PURPOSES AND POWER/DATA LOCATIONS ONLY
06 REFRIGERATOR BY OWNER. SHOWN FOR SPACE PLANNING
PURPOSES AND POWER LOCATION ONLY. NO WATER.
07 RUBBER TRANSITION STRIP - VCT IN CORRIDOR TO CARPET TILE IN
VESTIBULE. SEE FINISH SCHEDULE.
08 PROVIDE ROLLER SHADES - MANUALLY OPERATED WITH CORD AT
ALL NEW EXTERIOR WINDOW LOCATIONS
09 PROVIDE MINI BLINDS AT ALL INTERIOR WINDOWS IN
CONFIGURATIONS SHOWN
10 NEW WALL MATS BY OWNER, TYP. PRESERVE EXISTING MATS IN
PLACE WHERE POSSIBLE. RELOCATE AS NECESSARY DURING
CONSTRUCTION.
11 2 HOUR FIRE RATED COLUMN WRAP - UL SYSTEM Y622. PROVIDE
1.25" RIGID INSULATION AT INTERIOR FACE AND 2.75" RIGID
INSULATION AT EXTERIOR FACE AND ALUMINUM WRAP AROUND
ENTIRE SYSTEM. DETAIL VAIRIES FROM "POST" IN SOUTH WALL. NO
CMU HERE.
12 2 HOUR FIRE RATED COLUMN
UP
DN
193.70'
197.20'
197.20'
INTERIOR
ELEVATION
MARKER
ELEVATION DATUM
POINT
EXTERIOR
ELEVATION
MARKER NORTH ARROW
DOOR NUMBER
ALUMINUM FRAMING
SYSTEM TAG
DETAIL MARKER
SECTION MARKER
COLUMN GRID
AND GRID BUBBLES
ROOM NAME
ROOM NUMBER
A301
2
CARD READER
AFS-20
CR
WALL TAG
WINDOW TAG
TOILET
ACCESSORIES TAG
SHEET KEYNOTE
MATERIALS TAG
EQUIPMENT TAG
0A00A KX
00
?
A
EQ-1
PTD
2222
VIEW ELEMENTS SITE & LOCATION ELEMENTSARCHITECTURAL ELEMENTS
ANNOTATIONS
00
00AA
ROOM
NAME
101
1
A101
SIM
A5.0.2B
1
A5.0.2B
1
1
1
1
Level Name
0'-0"
CEILING TYPE
FINISH ELEVATIONACT-1
+1' - 0"
011036A 1.ALL INTERIOR LOAD BEARING MASONRY WALLS SUPPORTING ROOF ONLY
SHALL MAINTAIN A 1 HOUR FIRE RATING FOLLOWING UL U905.
2.ALL EXTERIOR LOAD BEARING WALLS SHALL MAINTAIN A 2 HOUR FIRE
RATING FOLLOWING UL U905.
3.ROOF STRUCTURE/DECKING TO MAINTAIN A 1 HOUR FIRE RATING
FOLLOWING UL P732
4.UNWRAPPED STRUCTURAL TUBE COLUMNS IN EXTERIOR LOAD BEARING
WALLS TO MAINTAIN A 2 HOUR FIRE RATING FOLLOWING UL U622.
5.WORK NOTED "BY OTHERS" OR "NIC" SHALL BE PROVIDED BY OWNER OR
UNDER SEPARATE CONTRACT.
6.SEE SHEET PARTITION TAG KEY AND A0.1.0 FOR PARTITION TYPES.
7.SEE SHEET A9.0.0 FOR DOOR TYPES AND DETAILS
8.PROVIDE CONTROL JOINTS ON GYP. BD. ASSEMBLIES PER SPECIFICATIONS
AND WHERE SHOWN.
9.EXTEND WALLS TO DECK ABOVE STOREFRONT SYSTEMS AND GLASS WALL
PARTITIONS.
10.REVIEW DOCUMENTS AND VERIFY DIMENSIONS AND FIELD CONDITIONS WHEN
APPLICABLE. CONFIRM THAT WORK IS BUILDABLE AS SHOWN. ANY
CONFLICTS OR OMISSIONS SHALL BE IMMEDIATELY REPORTED TO THE
ARCHITECT FOR CLARIFICATION PRIOR TO THE PERFORMANCE OF WORK IN
QUESTIONS.
11.COORDINATE AND PROVIDE METAL OR RATED SOLID WOOD BLOCKING (FIRE
TREATED) IN PARTITIONS AND CEILING FOR MILLWORK, WALL AND CEILING
ATTACHED ITEMS AS SPECIFIED.
12.DO NOT SCALE DRAWINGS. WRITTEN DIMENSIONS GOVERN. ALL PARTITION
LOCATIONS, DIMENSIONS AND TYPES, DOOR AND WINDOW LOCATIONS
SHALL BE AS SHOWN ON PARTITION PLAN. INCASE OF CONFLICT, NOTIFY
ARCHITECT.
13.COORDINATE WITH TENANT AND OWNER, THE SCHEDULE FOR TELEPHONE,
DATA, SECURITY AND AUDIO VISUAL INSTALLATIONS.
14.PARTITIONS AT BUILDING PERIMETER SHALL BE CENTERED ON CENTER LINE
OF COLUMN OR WINDOW MULLION, UNLESS OTHERWISE NOTED.
15.PROVIDE PARTITION TYPE WITH THE HIGHEST UL AND/OR ACOUSTICAL
PERFORMANCE RATING WHERE MORE THAN ONE PARTITION TYPE IS
INDICATED. PARTITIONS SHALL BE HEAD CONDITION 'A' UNLESS OTHERWISE
NOTED.
16.OFFSET ELECTRICAL AND TELEPHONE OUTLETS 16" MINIMUM IN SEPARATE
STUD WALL CAVITIES.
1.FIRE- AND SMOKE-RATED PARTITION ASSEMBLIES CONTINUE TO
STRUCTURE ABOVE (HEAD CONDITION "A") UNLESS NOTED OTHERWISE,
OR UNLESS OTHERWISE INDICATED BY THE CORRESPONDING FIRE
RATED ASSEMBLY DIAGRAM.
2.PROVIDE ACOUSTICAL CAULKING AROUND ALL PERIMETERS EDGES AND
PENETRATIONS AT SOUND-INSULATED WALLS. OFFSET ELECT. AND
TELEPHONE OUTLETS 16" MIN (SEPARATE STUD CAVITIES). AT SOUND
INSULATED WALLS PROVIDE ACOUSTICAL CAULKING AROUND ALL
PERIMETERS EDGES AND PENETRATIONS. OFFSET ELECT. AND
TELEPHONE OUTLETS 16” MIN (SEPARATE STUD CAVITIES)
3.WALLS ARE DIMENSIONED TO FINISH FACE OF WALL, UNLESS INDICATED
OTHERWISE.
4.WHERE ADJACENT PARTITION TYPES ARE OF DIFFERENT OVERALL
THICKNESS, ALIGN FINISHES ON VISIBLE SIDE, AND FURR OPPOSITE SIDE
AS REQUIRED FOR A FLUSH INSTALLATION.
5.PARTITION TYPES AROUND ROOMS AND SPACES SHALL BE CONTINUOUS
AROUND THE ENTIRE SPACE. WHERE MORE THAN ONE PARTITION TYPE
IS INDICATED, THE WALL TYPE WITH THE HIGHEST FIRE AND/OR
ACOUSTICAL PERFORMANCE SHALL BE USED.
6.FIRE SAFE ALL PENETRATIONS THROUGH FIRE RATED WALLS TO THE
LEVEL OF PROTECTION REQUIRED BY THE WALL. FIRE SAFE AT
PERIMETERS OF RATED WALLS WHERE VOIDS OCCUR, SUCH AS DECK
FLUTES.
7.REFER TO THE FINISH SCHEDULE AND/OR FLOOR PLANS FOR LOCATION
OF FINISH MATERIALS FOR WALL TYPES INDICATING DIFFERENT FINISHES
ON EACH SIDE OF WALL.
8.WET WALLS IN TOILET ROOMS TO RECEIVE CERAMIC TILE SHALL USE
MOISTURE-RESISTANT FIBERGLASS-MAT GYPSUM BOARD IN PLACE OF
GWB.
9.BRACE ALL CHASE WALLS FROM STUD TO STUD AT 4” OC MIN. VERTICAL
AND PER MANUFACTURER'S RECOMMENDATION UNLESS NOTED
OTHERWISE.
10.PROVIDE STEEL STUD GAUGES AND/OR DIAGONAL BRACING AT TOPS OF
WALLS PER MANUFACTURER'S RECOMMENDATIONS FOR WALL TYPE,
HEIGHT, AND USE BASED ON L/240 LIMITING HEIGHTS."
11.ALL CORNERS AND EDGES EXPOSED TO VIEW SHALL RECEIVE METAL
EDGE BEADS TREATED WITH DRYWALL COMPOUND TO A HEIGHT OF 6”
ABOVE FINISHED CEILINGS MIN."
12.ALL UL-RATED WALL ASSEMBLIES SHALL BE IDENTIFIED W/ STENCILING
ABOVE THE FINISHED CEILING ON BOTH FACES, ON ALL WALLS AS "FIRE
AND SMOKE BARRIER - PROTECT ALL OPENINGS" WITH HOUR RATING
INCLUDED.
13.ALL MATERIALS USED IN RATED ASSEMBLIES SHALL CONFORM TO
REFERENCED STANDARDS."
14.USE MOISTURE- AND MOLD-RESISTANT GWB ON INTERIOR SIDE OF
MECHANICAL ROOM WALLS."
15.PROVIDE CONTINUOUS HORIZONTAL BRIDGING FOR WALLS EXTENDING
10'-0" OR GREATER IN HEIGHT FROM FINISH FLOOR.
PARTITION RATING:
0xxx NON-RATED
1xxx 1-HOUR RATED
2xxx 2-HOUR RATED
3xxx 3-HOUR RATED
4xxx 4-HOUR RATED
PARTITION RATING
PARTITION MATERIAL
NOMINAL WIDTH OF STRUCTURE
NXNX X
PARTITION HEIGHT CATEGORY
(EXTEND TO STRUCTURE IF NOT INDICATED)
PARTITION MODIFIER
PARTITION CONSTRUCTION:
xFxx FURRING
xGxx GYP / METAL STUD
xSxx SHAFT
xMxx MASONRY
xWxx GYP / WOOD STUD
xExx EXISTING
NOMINAL WIDTH OF STRUCTURE:
(SEE PARTITION STRUCTURE KEY AT LEFT)
PARTITION HEIGHT CATEGORY:
xxxA EXTEND TO STRUCTURE ABOVE
xxxB TERMINATE ABOVE CEILING
xxxC TERMINATE AT CEILING
xxxP PARTIAL HEIGHT PARTITIONS
PARTITION MODIFIER:
A ABOVE ACCESS FLOOR
B BALLISTIC LEVEL RATED
E EXTRA LAYER OF GYPSUM
G GROUT MASONRY SOLID
I IMPACT RESISTANT
K SMOKE RATED
M METAL PANEL
O MOVABLE PARTITION
(OPERABLE)
R MOISTURE RESISTANT
S SOUND ATTENUATION BATTS
V VAPOR BARRIER
Z ACCENT WALL
(SEE INTERIOR DETAILS)
w w w . l i t t l e o n l i n e . c o m
This drawing and the design shown are the property
of Little Diversified Architectural Consulting. The
reproduction, copying or other use of this drawing
without their written consent is prohibited and any
infringement will be subject to legal action.
Little 2017c
PROJECT MANAGER
DESIGN TEAM
PRINCIPAL IN CHARGE
PROJECT TEAM
REVISIONS
PROJECT NAME
SHEET TITLE
PROJECT NO.
SHEET NUMBER
ISSUE FOR
ISSUE DATE
B
1 2 3 4 5 6 7
A
C
D
E
F
410 Blackwell Street, Suite 10
Durham, NC 27701
T: 919.474.2500
Rob Klinedinst
Katie Buckman
Anne Lebo
10/06/17
10/9/2017 3:30:25 PM C:\Users\katie.buckman\Documents\513.7505.00_CU_WrestlingExpansion_A-16_katie.buckman.rvt513.7505.00
A1.1.2
FLOOR PLAN AREA D
Campbell Convocation
Center Wrestling
Department Renovation
and Expansion
BID/PERMIT SET
X SHEET KEYNOTES
GENERAL NOTES - FLOOR PLAN
GENERAL NOTES - PARTITION TYPES
PARTITION TAG LEGEND
FLOOR PLAN LEGEND X SHEET KEYNOTES
3/16" = 1'-0"A1.1.2
1 CONVOCATION AREA D FLOOR PLAN
NOT TO SCALE
EXISTING BUILDING AREA D
KEY PLAN
NO. REASON DATE
01 FLIP EXISTING DOOR SWING OR REPLACE WITH NEW RATED DOOR
IN CONFIGURATION SHOWN. PANIC HARDWARE REQUIRED. THIS
DOOR IS NOW CONSIDERED THIRD EXIT FROM BASKETBALL
PRACTICE GYM. SOUTHEAST EXIT THROUGH CORRIDOR TO MAIN
HALL WAS DEMOLISHED TO ACCOMMODATE EXTENDED WRESTLING
LOCKER ROOM.
A2.1.1
3
1D
A3.1.0
1C
A3.1.0
1A
A3.1.0
A2.1.1
2
2A
A3.2.0
4A
A3.2.0
1A
A3.2.13/16" / 12"3/16" / 12"5/16" / 12"5/16" / 12"eG
e10
eE.6
eE
eF
01
6A
A3.2.0
01
....
02
03
..
.....
.
.5/16" / 12"3/16" / 12".
...04
05 05
05 05
06 0741' - 0 3/8"9' - 4"86' - 11 5/8"42' - 0 3/4"
17' - 6"
17' - 4 1/4"17' - 6 1/4"
.
09
1.SEE WALL SECTIONS FOR EXTERIOR WALL CONSTRUCTION.
2.PROVIDE STRUCTURAL CALCULATIONS PRIOR TO INSTALLATION OF
WINDOW WALL - SIGNED AND SEALED.
3.WINDOW WALL SYSTEM PERIMETER SEALANT TO ADJACENT MATERIALS
MUST BE INSTALLED BEFORE MULLION CAPS ARE SNAPPED INTO PLACE
- NO EXCEPTIONS.
4.PRECAST RETURN JOINTS AND VERTICAL & HORIZONTAL JOINTS
ADJACENT TO WINDOW WALL SYSTEM MUST BE CAULKED/SEALED
PRIOR TO WINDOW WALL INSTALLATION.
5.PROVIDE BOND BREAKER TAPE AT ALL T & F CLIPS, TYPICAL.
6.CLOSURE PLATES SHALL BE INSTALLED AT TOP & BOTTOM OF ALL
VERTICAL MULLIONS PRIOR TO INSTALLATION OF GLAZING UNITS.
7.HORIZONTAL TO VERTICAL MULLION BUTT JOINTS SHALL NOT EXCEED
1/32" IN WIDTH.
8.MULLION FACE CAP TO BE 1" FROM FACE OF CAP TO FACE OF GLASS.
9.DO NOT INSTALL GLAZING UNITS IF PERIMETER JOINTS TO ADJACENT
MATERIAL IS LESS THAN 1/2" OR MORE THAN 1", TYPICAL.
10.GC TO VERIFY PRECAST FINISH IS SMOOTH AT ALL LOCATIONS WHERE
PERIMETER CURTAINWALL SEALANT IS TO BE INSTALLED.
11.SEE A2.2.0 FOR JAMB DETAILS AT DOUBLE STACK BOND AND ROWLOCK
COMBINATION AND SINGLE ROWLOCK JAMB.
w w w . l i t t l e o n l i n e . c o m
This drawing and the design shown are the property
of Little Diversified Architectural Consulting. The
reproduction, copying or other use of this drawing
without their written consent is prohibited and any
infringement will be subject to legal action.
Little 2017c
PROJECT MANAGER
DESIGN TEAM
PRINCIPAL IN CHARGE
PROJECT TEAM
REVISIONS
PROJECT NAME
SHEET TITLE
PROJECT NO.
SHEET NUMBER
ISSUE FOR
ISSUE DATE
B
1 2 3 4 5 6 7
A
C
D
E
F
410 Blackwell Street, Suite 10
Durham, NC 27701
T: 919.474.2500
Rob Klinedinst
Katie Buckman
Anne Lebo
10/06/17
10/9/2017 3:30:25 PM C:\Users\katie.buckman\Documents\513.7505.00_CU_WrestlingExpansion_A-16_katie.buckman.rvt513.7505.00
A1.1.3
ROOF PLAN
Campbell Convocation
Center Wrestling
Department Renovation
and Expansion
BID/PERMIT SET
3/16" = 1'-0"A1.1.3
1 CONVOCATION AREA C ROOF PLAN
AREA C
NOT TO SCALE
EXISTING BUILDING
KEY PLAN
NO. REASON DATE
01 AIR HANDLING UNIT
02 LINE OF EXISTING 60 MIL PVC ROOF TO REMAIN - LTTR R20. SYSTEM
CONSISTS OF EXISTING PVC ROOF MEMBRANE, 1/2" OVERLAY
BOARD, AND 4" INSULATION. INSPECT ROOF FOR DAMAGE AND
WEAR. DOCUMENT CONDITION WITH PHOTOS FOR OWNER AND
REVIEW ANY CONCERNS WITH OWNER. NEW ROOF WILL BE SEAMED
TO EXISTING. THIS IS LOW POINT OF STRUCTURE. LOW POINT OF
ROOFING TO OCCUR IN LINE WITH ROOF DRAINS. NEW SYSTEM IS
THICKER THAN EXISTING SYSTEM DUE TO ENERGY CODE
REQUIREMENT OF R30 LTTR AT NEW PORTION OF ROOF
03 LINE OF EXISTING 60 MIL PVC ROOF TO REMAIN - LTTR R20. SYSTEM
CONSISTS OF EXISTING PVC ROOF MEMBRANE, 1/2" OVERLAY
BOARD, AND 4" INSULATION. INSPECT ROOF FOR DAMAGE AND
WEAR. DOCUMENT CONDITION WITH PHOTOS FOR OWNER AND
REVIEW ANY CONCERNS WITH OWNER. NEW ROOF WILL BE SEAMED
TO EXISTING. SEE A3.2.1 FOR DETAIL AT OLD ROOF TO NEW.
04 EXISTING EXHAUST FAN
05 CONCENTRIC ROOF DRAIN - TAPER INSULATION CREATE LOW POINT
AT DRAIN. MAINTAIN LTTR R30 AT NEW ROOF. EXISTING ROOF IS R20
AND UP TO 2" THINNER.
06 PROVIDE WALK PADS FROM EXISTING ROOF ACCESS AT EAST STAIR
DOOR TO (2) NEW AIR HANDLING UNITS.
07 HATCH INDICATES EXISTING ROOF TO REMAIN. DIMENSIONS ARE
APPROXIMATE.
09 ARROWS INDICATE DIRECTION OF SLOPE OF TAPERED INSULATION
SLOPE, TYP.
X SHEET KEYNOTES
GENERAL NOTES - EXTERIOR
SLOPED W/STRUCTURESLOPED W/STRUCTURESLOPED W/STRUCTURESLOPED W/STRUCTURESLOPED W/STRUCTURESLOPED W/STRUCTURE
CCTV
CCTV
WS
WS
A2.1.1
3
A2.1.1
2
ACT-1
+12' - 10"ACT-1
+12' - 10"
ACT-1
+12' - 10"
ACT-1
+12' - 10"
ACT-1
+12' - 10"
ACT-1
+12' - 10"
ACT-1
+9' - 0"
ACT-1
+12' - 10"
eG eG
e10
eE.6 eE.6
eE eE
eF eF
ACT-1
+9' - 0"
ACT-1
+9' - 0"
ACT-1
+9' - 0"
ACT-1
+9' - 0"
GWB
+8' - 10"
GWB
+8' - 10"2"8' - 10"
12' - 8"
0G3
0G3B
0G3B
01
0G6A
B
6A
A3.2.0
02
02
03
04
04
04
1.CEILING HEIGHTS ARE GIVEN FROM FINISHED FLOOR ELEV. ANY
CONFLICT / DISCREPANCY SHALL BE REPORTED TO ARCHITECT.
2.REFER TO ELECTRICAL DRAWINGS FOR LIGHTING SPECIFICATIONS.
3.ALL LIGHTING FIXTURES ON THIS PLAN ARE SHOWN FOR LOCATION
REFERENCE ONLY. COORDINATE WITH ELECTRICAL DWGS FOR FIXTURE
TYPE AND WIRING DIAGRAMS.
4.ARCHITECTURAL CEILING PLANS SHALL GOVERN FOR LOCATIONS OF ALL
CEILING DEVICES AS SHOWN. ENGINEERING DOCUMENTS SHALL
PREVAIL ONLY IN CASE OF SCOPE OF WORK AND ELEMENTS OCCURING
ABOVE CEILING. DISCREPANCIES MUST BE BROUGH UP TO THE
ARCHITECT'S ATTENTION. AT TIME OF BID, ANY DISCREPANCIES NOT
BROUGHT UP TO THE ARCHITECT'S ATTENTION SHALL BE THE
RESPONSIBILITY OF THE GC.
5.REFER TO MECHANICAL, ELECTRICAL, AND SPRINKLER DRAWINGS FOR
DEVICES.
6.CENTER SUSPENDED CEILING GRIDS IN ROOMS.
7.TILES SHALL BE INSTALLED SO GRAIN LINES OF TILE ARE RUNNING IN
SAME DIRECTION FOR EACH CEILING TYPE.
8.ACOUSTICAL CONTRACTOR SHALL MIX TILE IN A UNIFORM MANNER TO
ELIMINATE BANDING OR BATCHING.
9.FOLLOWING COMPLETION OF ACOUSTICAL CEILING INSTALLATION, ALL
JOINTS SHALL BE STRAIGHT AND TRUE TO LINE, WITH EXPOSED
SURFACES FLUSH AND LEVEL.
10.SPRINKLER HEADS SHALL BE CENTERED IN MODULE OF THE TILE
INDICATED. SPRINKLER HEAD ESCHUTIONS IN COLOR GYP. BOARD
PLANES SHALL BE CUSTOM FINISHED BY MANUFACTURER TO MATCH
CEILING COLOR AS SCHEDULED.
11.IF CEILING DIFFUSER, LIGHT FIXTURES OR OTHER ELEMENTS ON OR
ABOVE THE CEILING CAN NOT BE LOCATED AS SHOWN ON THE
DRAWINGS, SUCH INTERFERENCE SHALL BE REPORTED IMMEDIATELY TO
ARCHITECT FOR RELOCATION.
12.PROVIDE EMERGENCY BATTERY PACKS OR EMERGENCY CIRCUITS AS
REQUIRED BY CODE. SEE ELECTRICAL DRAWINGS FOR CIRCUITRY OF
EMERGENCY LIGHT FIXTURES.
13.PROVIDE FINAL QUANTITY AND LOCATION OF EMERGENCY DEVICES,
(INCLUDING BUT NOT LIMITED TO: BATTERY PACKS, EXIT SIGNS, FIRE
ALARMS, ETC.) IN COMPLIANCE WITH MUNICIPAL AGENCY HAVING
JURISDICTION.
14.DIMMERS AND SWITCHES SHALL BE GANGED TOGETHER IN LARGEST
MULTI-GANG BOXES WITH COMMON FACE PLATES POSSIBLE. STACKING
OF LARGE BOXES (5 SWITCHES ABOVE 5 SWITCHES) IS ACCEPTABLE.
15.MATERIALS PLACED IN CEILING SHALL BE REQUIRED TO HAVE A PLENUM
RATING.
16.STENCIL RATED WALLS ABOVE CEILING.
17.18" CLEARANCE MUST BE MAINTAINED BETWEEN THE UNDERSIDE OF ANY
SPRINKLER HEADS AND THE TOP OF ANY OBSTRUCTION BELOW EXCEPT
FOR THOSE SPRINKLER HEADS INSTALLED ABOVE SUSPENDED CEILING
CLOUDS.
18.ALL EXPOSED CONDUIT, PIPING, DUCT WORK, AND STRUCTURE IN AREA A
WHERE SPACE IS OPEN TO DECK ABOVE SHALL BE PAINTED OUT; REFER
TO FINISH SCHEDULE FOR PAINT SPECIFICATION.
19.PROVIDE CONTROL JOINTS ON GYP.BD. ASSEMBLIES PER
SPECIFICATIONSC CONSTRAINTS. LOCATE AS SHOWN ON RCP (AS
APPLICABLE).
2 X 2 DIRECT/INDIRECT
FLUORESCENT LIGHT
FIXTURE
4' LINEAR PENDANT DIRECT/
INDIRECT FLUORESCENT
LIGHT FIXTURE
RECESSED LIGHT FIXTURE
ACT CEILING SYSTEM
GWB CEILING
MECHANICAL RETURN
DIFFUSER
MECHANICAL SUPPLY
DIFFUSER
8' LINEAR LIGHT FIXTURE
WALL SCONCE (INTERIOR)
SPRINKLER HEAD
EXIT SIGN
SINGLE SECURITY CAMERA
PTZ = PAN, TILT, ZOOM
DOUBLE SECURITY CAMERA
PTZ = PAN, TILT, ZOOM
RECESSED PROJECTION
SCREEN
PROJECTOR
WALL SCONCE (EXTERIOR)
MECHANICAL SUPPLY
DIFFUSER
MECHANICAL RETURN
DIFFUSER
PENDANT LIGHT FIXTURE
2 X 4 DIRECT/INDIRECT
FLUORESCENT LIGHT
FIXTURE
w w w . l i t t l e o n l i n e . c o m
This drawing and the design shown are the property
of Little Diversified Architectural Consulting. The
reproduction, copying or other use of this drawing
without their written consent is prohibited and any
infringement will be subject to legal action.
Little 2017c
PROJECT MANAGER
DESIGN TEAM
PRINCIPAL IN CHARGE
PROJECT TEAM
REVISIONS
PROJECT NAME
SHEET TITLE
PROJECT NO.
SHEET NUMBER
ISSUE FOR
ISSUE DATE
B
1 2 3 4 5 6 7
A
C
D
E
F
410 Blackwell Street, Suite 10
Durham, NC 27701
T: 919.474.2500
Rob Klinedinst
Katie Buckman
Anne Lebo
10/06/17
10/9/2017 3:30:28 PM C:\Users\katie.buckman\Documents\513.7505.00_CU_WrestlingExpansion_A-16_katie.buckman.rvt513.7505.00
A1.2.1
REFLECTED CEILING
PLAN
Campbell Convocation
Center Wrestling
Department Renovation
and Expansion
BID/PERMIT SET
3/16" = 1'-0"A1.2.1
1 CONVOCATION AREA C REFLECTED CEILING PLAN
GENERAL NOTES - RCP
RCP LEGEND
X SHEET KEYNOTES
AREA C
NOT TO SCALE
EXISTING BUILDING
KEY PLAN
NO. REASON DATE
01 INSET NEW BULKHEAD MIN. 2" FROM FINISH FACE OF WRESTLING
ROOM WALL. BUILD UP TO BOND BEAM ABOVE. PAINT P-1 ON FACE
AND UNDERSIDE. FUTURE BRANDING OPPORTUNITY FOR OWNER.
02 EXPOSED STEEL JOIST, TYPICAL - SPRAY WITH FIREPROOFING.
PATCH AND REPAIR MISSING/DAMAGED FIREPROOFING ON EXISTING
STEEL JOISTS. UL 1 HOUR RATED ROOF SYSTEM - P732
03 SPRAY JOISTS IN AREAS WITH CEILING AS WELL - UL SYSTEM
NUMBER P732 - 1 HOUR FIRE RATING
04 SEE FLOOR PLAN FOR LOCATIONS OF ROLLER SHADES AND MINI
BLINDS, TYP.
1.SEE WALL SECTIONS FOR EXTERIOR WALL CONSTRUCTION.
2.PROVIDE STRUCTURAL CALCULATIONS PRIOR TO INSTALLATION OF
WINDOW WALL - SIGNED AND SEALED.
3.WINDOW WALL SYSTEM PERIMETER SEALANT TO ADJACENT MATERIALS
MUST BE INSTALLED BEFORE MULLION CAPS ARE SNAPPED INTO PLACE
- NO EXCEPTIONS.
4.PRECAST RETURN JOINTS AND VERTICAL & HORIZONTAL JOINTS
ADJACENT TO WINDOW WALL SYSTEM MUST BE CAULKED/SEALED
PRIOR TO WINDOW WALL INSTALLATION.
5.PROVIDE BOND BREAKER TAPE AT ALL T & F CLIPS, TYPICAL.
6.CLOSURE PLATES SHALL BE INSTALLED AT TOP & BOTTOM OF ALL
VERTICAL MULLIONS PRIOR TO INSTALLATION OF GLAZING UNITS.
7.HORIZONTAL TO VERTICAL MULLION BUTT JOINTS SHALL NOT EXCEED
1/32" IN WIDTH.
8.MULLION FACE CAP TO BE 1" FROM FACE OF CAP TO FACE OF GLASS.
9.DO NOT INSTALL GLAZING UNITS IF PERIMETER JOINTS TO ADJACENT
MATERIAL IS LESS THAN 1/2" OR MORE THAN 1", TYPICAL.
10.GC TO VERIFY PRECAST FINISH IS SMOOTH AT ALL LOCATIONS WHERE
PERIMETER CURTAINWALL SEALANT IS TO BE INSTALLED.
11.SEE A2.2.0 FOR JAMB DETAILS AT DOUBLE STACK BOND AND ROWLOCK
COMBINATION AND SINGLE ROWLOCK JAMB.
1C
A3.1.0
1A
A3.1.0
LEVEL 1
0"
WATERTABLE
4' - 0"
ROOF BEARING
16' - 0"
T/ PARAPET
20' - 8"
4A
A3.2.0
E-4 E-3 E-5
eG eE.6 eEeF
CJ CJ CJ
w w w . l i t t l e o n l i n e . c o m
This drawing and the design shown are the property
of Little Diversified Architectural Consulting. The
reproduction, copying or other use of this drawing
without their written consent is prohibited and any
infringement will be subject to legal action.
Little 2017c
PROJECT MANAGER
DESIGN TEAM
PRINCIPAL IN CHARGE
PROJECT TEAM
REVISIONS
PROJECT NAME
SHEET TITLE
PROJECT NO.
SHEET NUMBER
ISSUE FOR
ISSUE DATE
B
1 2 3 4 5 6 7
A
C
D
E
F
410 Blackwell Street, Suite 10
Durham, NC 27701
T: 919.474.2500
Rob Klinedinst
Katie Buckman
Anne Lebo
10/06/17
10/9/2017 3:30:30 PM C:\Users\katie.buckman\Documents\513.7505.00_CU_WrestlingExpansion_A-16_katie.buckman.rvt513.7505.00
A2.1.0
EXTERIOR ELEVATIONS
Campbell Convocation
Center Wrestling
Department Renovation
and Expansion
BID/PERMIT SET
GENERAL NOTES - ELEVATIONS
X SHEET KEYNOTES
1/4" = 1'-0"A2.1.0
2 EAST ELEVATION
NO. REASON DATE
01 MODULAR FACE BRICK - RUNNING BOND PATTERN
2 AHU
03 BRICK HEADER COURSE
04 BRICK ROWLOCK COURSE
06 BRICK DOUBLE SOLDIER COURSE
07 BRICK STACK BOND COURSE
09 ALUMINUM STOREFRONT SYSTEM
10 CAST STONE WATER TABLE
11 CAST STONE CORNICE
06
09
10
01 01
01 01
07 07 07 07
11
03
04
03
04 04 04
03
04 04
06 06
09 09
03
10
2
1D
A3.1.0
LEVEL 1
0"
WATERTABLE
4' - 0"
ROOF BEARING
16' - 0"
T/ PARAPET
20' - 8"
2A
A3.2.0
CJ
10' - 0"28' - 0"10' - 0"4' - 8"1A
A3.1.0
LEVEL 1
0"
WATERTABLE
4' - 0"
ROOF BEARING
16' - 0"
T/ PARAPET
20' - 8"14' - 8"1D
A3.1.0
LEVEL 1
0"
WATERTABLE
4' - 0"
ROOF BEARING
16' - 0"
T/ PARAPET
20' - 8"
2A
A3.2.0
20' - 8"E-1
E-2 E-2 E-2
E-1E-1E-1E-1
E-3
e10
CJ CJ CJ CJ
EQ EQ
1' - 1 3/8"2' - 0"1' - 1 3/8"1' - 1 3/8"2' - 0"1' - 1 3/8"1' - 1 3/8"2' - 0"1' - 1 3/8"2' - 5 3/4"2' - 0"1' - 1 3/8"4' - 8"10' - 0"6A
A3.2.0
1' - 1 3/8"2' - 0"1' - 1 3/8"1' - 1 3/8"2' - 0"1' - 1 3/8"
1.SEE WALL SECTIONS FOR EXTERIOR WALL CONSTRUCTION.
2.PROVIDE STRUCTURAL CALCULATIONS PRIOR TO INSTALLATION OF
WINDOW WALL - SIGNED AND SEALED.
3.WINDOW WALL SYSTEM PERIMETER SEALANT TO ADJACENT MATERIALS
MUST BE INSTALLED BEFORE MULLION CAPS ARE SNAPPED INTO PLACE
- NO EXCEPTIONS.
4.PRECAST RETURN JOINTS AND VERTICAL & HORIZONTAL JOINTS
ADJACENT TO WINDOW WALL SYSTEM MUST BE CAULKED/SEALED
PRIOR TO WINDOW WALL INSTALLATION.
5.PROVIDE BOND BREAKER TAPE AT ALL T & F CLIPS, TYPICAL.
6.CLOSURE PLATES SHALL BE INSTALLED AT TOP & BOTTOM OF ALL
VERTICAL MULLIONS PRIOR TO INSTALLATION OF GLAZING UNITS.
7.HORIZONTAL TO VERTICAL MULLION BUTT JOINTS SHALL NOT EXCEED
1/32" IN WIDTH.
8.MULLION FACE CAP TO BE 1" FROM FACE OF CAP TO FACE OF GLASS.
9.DO NOT INSTALL GLAZING UNITS IF PERIMETER JOINTS TO ADJACENT
MATERIAL IS LESS THAN 1/2" OR MORE THAN 1", TYPICAL.
10.GC TO VERIFY PRECAST FINISH IS SMOOTH AT ALL LOCATIONS WHERE
PERIMETER CURTAINWALL SEALANT IS TO BE INSTALLED.
11.SEE A2.2.0 FOR JAMB DETAILS AT DOUBLE STACK BOND AND ROWLOCK
COMBINATION AND SINGLE ROWLOCK JAMB.
w w w . l i t t l e o n l i n e . c o m
This drawing and the design shown are the property
of Little Diversified Architectural Consulting. The
reproduction, copying or other use of this drawing
without their written consent is prohibited and any
infringement will be subject to legal action.
Little 2017c
PROJECT MANAGER
DESIGN TEAM
PRINCIPAL IN CHARGE
PROJECT TEAM
REVISIONS
PROJECT NAME
SHEET TITLE
PROJECT NO.
SHEET NUMBER
ISSUE FOR
ISSUE DATE
B
1 2 3 4 5 6 7
A
C
D
E
F
410 Blackwell Street, Suite 10
Durham, NC 27701
T: 919.474.2500
Rob Klinedinst
Katie Buckman
Anne Lebo
10/06/17
10/9/2017 3:30:31 PM C:\Users\katie.buckman\Documents\513.7505.00_CU_WrestlingExpansion_A-16_katie.buckman.rvt513.7505.00
A2.1.1
EXTERIOR ELEVATIONS
Campbell Convocation
Center Wrestling
Department Renovation
and Expansion
BID/PERMIT SET
1/4" = 1'-0"A2.1.1
2 NORTH ELEVATION
1/4" = 1'-0"A2.1.1
3 WEST ELEVATION
1/4" = 1'-0"A2.1.1
1 SOUTH ELEVATION
NO. REASON DATE
GENERAL NOTES - ELEVATIONS
X SHEET KEYNOTES
01 MODULAR FACE BRICK - RUNNING BOND PATTERN
2 AHU
03 BRICK HEADER COURSE
04 BRICK ROWLOCK COURSE
06 BRICK DOUBLE SOLDIER COURSE
07 BRICK STACK BOND COURSE
09 ALUMINUM STOREFRONT SYSTEM
10 CAST STONE WATER TABLE
11 CAST STONE CORNICE
01
03
04
06
07
09
10
11
09 09 09 09
09 09 09
11
11
10
10
10
070707070707070707
06 06 06 06 06 06 06 06
03
03
0404 04 04 04 04 04 04 04 04 04 04 04 04 04
03 03 03 03 03 03 03 03 03 03
03
0303 03
01
01
01
01
01
0101
01
22
03
1 5/8"2' - 5"2"2' - 5"2"8"2"1' - 8"2 3/8"2"4' - 0"2"4"2"4' - 2"2"3' - 4"2"8' - 0"
ALUMINUM WRAP
MATCH STOREFRONT
EG.1,
TYP.
EG.1,
TYP.
2"2' - 5"2"2' - 5"2"8"2"1' - 8"2"8' - 0"2"4' - 0"2"4"2"3' - 0"2"6A
A3.2.0
8' - 0"
EG.1,
TYP.
EG.1,
TYP.
ALUMINUM WRAP.
MATCH STOREFRONT 8' - 0"2"4' - 0"2"6"2"2' - 10"2"2"1'-8"2"
EG.1,
TYP.
2' - 0"12' - 8"7' - 10"7"4' - 3"8' - 8"
3' - 1 1/2"3' - 1 1/2"2' - 5"3' - 7"EG.1,
TYPICAL
FOR ALL
STOREFRONT
DOOR
OPENING
6' - 0"8' - 0"3' - 3"6"4' - 3"2"8"2' - 8"2' - 8"
5'-4"16'-3"
8"2'-0"2'-8"2'-0"2'-11"2'-0"2'-8"2'-0"8"2'-8"2'-8"8"2"
5'-4"
29'-11"
ALUM. WRAP.
MATCH STOREFRONT
DOOR
OPENING
IG.1 IG.1 IG.1 IG.1 IG.1 IG.1 IG.1
8' - 0"2"7' - 8"2"16' - 0"
2"10"2"3' - 0"2"8"2"1' - 8"2"3' - 0"2"6"1' - 2"2"8"2"3' - 0"2"
1G.1 1G.1
DOOR
OPENING
DOOR
OPENING
1G.1 1G.1
5' - 11"
2"1' - 7"2"8"2"3' - 0"2"8' - 0"2"7' - 8"2"3' - 0"9' - 0"
3' - 2"10"1' - 10"5' - 0"IG.1 IG.1 IG.1 IG.1
SILL BELOW
12" CMU
BRICK STACK BOND
BRICK ROWLOCK
COURSE - RECESS 1_
2"
FACE BRICK CAST STONE
BELOW
HORIZONTAL JOINT
REINFORCING
SEALANT BOTH SIDES
PREFINISHED
ALUMINUM
STOREFRONT UNIT
SILL BELOW
SEALANT BOTH SIDES
PREFINISHED
ALUMINUM
STOREFRONT UNIT
2" FOAM
INSULATION
12" CMU
FACE BRICK CAST STONE
BELOWHORIZONTAL JOINT
REINFORCING BRICK ROWLOCK
COURSE - RECESS 1/2"
METAL STUD AND DESIGN BY
SUPPLIER.
PREFINISHED ALUMINUM WRAP
MATCH STOREFRONT
CONTRACTOR TO PROVIDE
MEMBRANE WRAP TO
SEPARATE METAL STUDS
FROM ALUMINUM SYSTEM AND
BLOCK TO PREVENT GALVANIC
REACTION
8"1/4"8" .3/8"STACK BOND 4X8X8" SOLID CMU
FLUSH WITH FACE OF INTERIOR
WALL
2" RIGID INSULATION
SEALANT, BOTH
SIDES
IG.1 1/4" TEMPERED GLASS
IG.2 1/4" TEMPERED GLASS (BACKPAINTED)
IG.3 1/4" TEMPERED GLASS (FROSTED)
IG.4 NOT USED
EG.1 1" TEMPERED INSULATED GLASS
EG.2 NOT USED
EG.3 1" TEMPERED SPANDREL GLASS
w w w . l i t t l e o n l i n e . c o m
This drawing and the design shown are the property
of Little Diversified Architectural Consulting. The
reproduction, copying or other use of this drawing
without their written consent is prohibited and any
infringement will be subject to legal action.
Little 2017c
PROJECT MANAGER
DESIGN TEAM
PRINCIPAL IN CHARGE
PROJECT TEAM
REVISIONS
PROJECT NAME
SHEET TITLE
PROJECT NO.
SHEET NUMBER
ISSUE FOR
ISSUE DATE
B
1 2 3 4 5 6 7
A
C
D
E
F
410 Blackwell Street, Suite 10
Durham, NC 27701
T: 919.474.2500
Rob Klinedinst
Katie Buckman
Anne Lebo
10/06/17
10/9/2017 3:30:36 PM C:\Users\katie.buckman\Documents\513.7505.00_CU_WrestlingExpansion_A-16_katie.buckman.rvt513.7505.00
A2.2.0
FRAMING SYSTEM
ELEVATIONS
Campbell Convocation
Center Wrestling
Department Renovation
and Expansion
BID/PERMIT SET
NOT TO SCALE
STOREFRONT E-1
NOT TO SCALE
STOREFRONT E-2
NOT TO SCALE
STOREFRONT E-3
NOT TO SCALE
STOREFRONT E-4
NOT TO SCALE
STOREFRONT E-5
NOT TO SCALE
HOLLOW METAL SYSTEM - N-1
NOT TO SCALE
HOLLOW METAL FRAM - N-2 (AND N-2 REVERSED)
NOT TO SCALE
STOREFRONT N-3
1 1/2" = 1'-0"A2.2.0
5D TYP. JAMB DETAIL WITH DOUBLE STACK BOND AND ROWLOCK
1 1/2" = 1'-0"A2.2.0
3D TYP. JAMB DETAIL WITH ROWLOCK
3" = 1'-0"A2.2.0
2D INTERIOR MULLION DETAIL
NO. REASON DATE
GENERAL NOTES - RCP
EG.1,
TYPICAL
FOR ALL
EG.1,
TYPICAL
FOR ALL
EG.1,
TYPICAL
FOR ALL
1C
A3.1.0
1A
A3.1.0
LEVEL 1
0"
ROOF BEARING
16' - 0"
T/ PARAPET
20' - 8"
4A
A3.2.0
WRESTLING
GYM
ADDITION
1142.1
eGeE.6 eF
1 HOUR RATED ASSEMBLY
SINGLE PLY MEMBRANE ROOF CONCENTRIC ROOF DRAIN
SEE PLUMBING DRAWINGS
A3.2.0
2A
Sim
A3.2.1
1A
Sim
A3.2.0
6A
Sim
1D
A3.1.0
LEVEL 1
0"
WATERTABLE
4' - 0"
ROOF BEARING
16' - 0"
T/ PARAPET
20' - 8"
e10
1 HOUR RATED ASSEMBLY
SINGLE PLY MEMBRANE ROOF
WRESTLING
GYM
1142
A3.2.1
5D
EXST.NEW A3.2.0
6A Sim
1D
A3.1.0
LEVEL 1
0"
ROOF BEARING
16' - 0"
T/ PARAPET
20' - 8"
1A
A3.2.1
e10
1 HOUR RATED ASSEMBLY
SINGLE PLY MEMBRANE ROOF
AHU AHU
N-1 N-1 N-2 N-2 N-1
LOUNGE
1149
FITNESS
1148
COACH
1146
CONFERENCE
1145
ASST.
COACH
OFFICES
1144
RECEPTION
1143
PARAPET BEYOND A3.2.0
4A
Sim
A3.2.0
2A
Sim
w w w . l i t t l e o n l i n e . c o m
This drawing and the design shown are the property
of Little Diversified Architectural Consulting. The
reproduction, copying or other use of this drawing
without their written consent is prohibited and any
infringement will be subject to legal action.
Little 2017c
PROJECT MANAGER
DESIGN TEAM
PRINCIPAL IN CHARGE
PROJECT TEAM
REVISIONS
PROJECT NAME
SHEET TITLE
PROJECT NO.
SHEET NUMBER
ISSUE FOR
ISSUE DATE
B
1 2 3 4 5 6 7
A
C
D
E
F
410 Blackwell Street, Suite 10
Durham, NC 27701
T: 919.474.2500
Rob Klinedinst
Katie Buckman
Anne Lebo
10/06/17
10/9/2017 3:30:42 PM C:\Users\katie.buckman\Documents\513.7505.00_CU_WrestlingExpansion_A-16_katie.buckman.rvt513.7505.00
A3.1.0
BUILDING SECTIONS
Campbell Convocation
Center Wrestling
Department Renovation
and Expansion
BID/PERMIT SET
3/16" = 1'-0"A3.1.0
1D NORTH SOUTH SECTION 1
3/16" = 1'-0"A3.1.0
1C EAST WEST SECTION 1
3/16" = 1'-0"A3.1.0
1A EAST WEST SECTION 2
NO. REASON DATE
LEVEL 1
0"
WATERTABLE
4' - 0"
ROOF BEARING
16' - 0"
T/ PARAPET
20' - 8"
A3.2.0
1D
CAST STONE COPING
CAST STONE CORNICE
BRICK HEADER COURSE -
RECESS 1/2"
BRICK HEADER COURSE -
RECESS 1/2"
SINGLE-PLY MEMBRANE,
1/2" OVERLAY BOARD,
MIN. R30 RIGID
INSULATION
ON METAL ROOF DECK.
DOUBLE SOLDIER COURSE
THROUGH WALL FLASHING
SHELF ANGLE. SEE
STRUCTURAL
6 3/4"6"6 1/2"1 3/4"4"7' - 8 1/8"12' - 8"COMPACTED AGGREGATE
PIERS
REINFORCED CONCRETE
FOOTING
GRAVEL DRYBED
6" DIA. FOUNDATION
DRAIN
FIELD BRICK - COMMON BOND
PATTERN WITH FLEMISH
HEADERS EVERY 6TH COURSE.
LEVEL 1
0"
WATERTABLE
4' - 0"
ROOF BEARING
16' - 0"
T/ PARAPET
20' - 8"
eE.6
CAST STONE WATERTABLE
BRICK HEADER COURSE -
RECESS 1/2"
CAST STONE COPING
CAST STONE CORNICE
BRICK HEADER COURSE -
RECESS 1/2"
(THIS COURSE ON NORTH WALL
AND WRAPPING WRESTLING PRACTICE
GYM ROOM. - SEE ELEVATIONS)
BRICK HEADER COURSE -
RECESS 1/2"
SINGLE-PLY MEMBRANE
ON MIN. R30 RIGID INSULATION
ON METAL ROOF DECK.
THRU-WALL FLASHING
COMPACTED AGGREGATE
PIERS
REINFORCED CONCRETE
FOOTING
GRAVEL DRYBED
6" DIA. FOUNDATION
DRAIN
FIELD BRICK - COMMON BOND
PATTERN WITH FLEMISH
HEADERS EVERY 6TH COURSE.
VARIESeE.6
A3.2.0
1B
A3.2.0
1D
4' - 4"2' - 0"9' - 4"4' - 8"4 7/8"3 5/8"2"2"11 5/8"
SLOPE
4"FACE BRICK
BRICK HEADER
COURSE - RECESSED
W/ WEEP/CAVITY VENT @ 16" O.C.
MAINTAIN 1" AIR SPACE
HORIZONTAL JOINT
REINFORCING AT 16"
O.C. VERTICALLY
12" CMU
CAST STONE
CORNICE SEE DETAIL
2/A423
12" CMU BOND BEAM
FULLY ADHERED
ROOFING MEMBRANE
FLASHING
P.T. WOOD NAILER
SEALANT &
BACKER ROD
CAST STONE COPING
SEE DETAIL 7/A423
2" FOAM INSULATION
(R-13 MINIMUM)
FILL BLOCK CORES AT
STONE ANCHOR
LOCATIONS
PREFINISHED METAL
COUNTER FLASHING
PREFINISHED METAL
RECEIVER FLASHING
PROVIDE SEALANT AT COPING
ANCHOR PENETRATIONS THRU
MEMBRANE & FLASHING
CAST STONE
ANCHORS AS
REQUIRED
RIGID METAL FLASHING
UNDER COPING CAP
TYP.
FLEXIBLE MEMBRANE
FLASHING
1/2"3 5/8"3/8"1' - 1"3/8"3 5/8"4 3/4"1/2"ACCENT BRICK
HEADER COURSE - RECESS
1/2"
CAST STONE WATER
TABLE SEE DETAIL 5/A423
FILL BLOCK CORES
AT STONE ANCHOR
LOCATIONS
4" CMU
FACE BRICK
CAST STONE
ANCHORS AS
REQUIRED
FACE BRICK THRU-WALL
FLASHING
LEVEL 1
0"
WATERTABLE
4' - 0"
ROOF BEARING
16' - 0"
T/ PARAPET
20' - 8"
CAST STONE WATERTABLE
BRICK HEADER COURSE -
RECESS 1/2"
CAST STONE COPING
CAST STONE CORNICE
BRICK HEADER COURSE -
RECESS 1/2"
BRICK HEADER COURSE -
RECESS 1/2"
SINGLE-PLY MEMBRANE
ON MIN. R30 RIGID INSULATION
ON METAL ROOF DECK.
THRU-WALL FLASHING
COMPACTED AGGREGATE
PIERS
REINFORCED CONCRETE
FOOTING
GRAVEL DRYBED
6" DIA. FOUNDATION
DRAIN
FIELD BRICK - COMMON BOND
PATTERN WITH FLEMISH
HEADERS EVERY 6TH COURSE.
DOUBLE SOLDIER COURSE
6 3/4"
PREFINISHED ALUMINUM
STOREFRONT
ROLLER SHADES AT ALL
EXTERIOR WINDOWS
THROUGH WALL FLASHING
SHELF ANGLE. SEE
STRUCTURAL
A3.2.0
1A
A3.2.0
1D
1' - 8"4' - 8"1' - 4"8' - 0"4' - 8"3_
4"
FACE BRICK
OPEN HEAD JOINT
WEEPS @ 24" O.C.
HORIZONTAL JOINT
REINFORCING
CAST STONE SILL
ANCHOR AS REQUIRED.
SEALANT & BACKER
ROD
PREFINISHED
ALUMINUM
STOREFRONT UNIT
SILL STARTER
SOLID SURFACE
STOOL AS
SCHEDULED
P.T. WOOD
BLOCKING
2" FOAM
INSULATION
12" CMU
BRICK HEADER COURSE -
RECESS 1/2"
THRU-WALL FLASHING
w w w . l i t t l e o n l i n e . c o m
This drawing and the design shown are the property
of Little Diversified Architectural Consulting. The
reproduction, copying or other use of this drawing
without their written consent is prohibited and any
infringement will be subject to legal action.
Little 2017c
PROJECT MANAGER
DESIGN TEAM
PRINCIPAL IN CHARGE
PROJECT TEAM
REVISIONS
PROJECT NAME
SHEET TITLE
PROJECT NO.
SHEET NUMBER
ISSUE FOR
ISSUE DATE
B
1 2 3 4 5 6 7
A
C
D
E
F
410 Blackwell Street, Suite 10
Durham, NC 27701
T: 919.474.2500
Rob Klinedinst
Katie Buckman
Anne Lebo
10/06/17
10/9/2017 4:29:54 PM C:\Users\katie.buckman\Documents\513.7505.00_CU_WrestlingExpansion_A-16_katie.buckman.rvt513.7505.00
A3.2.0
WALL SECTIONS
Campbell Convocation
Center Wrestling
Department Renovation
and Expansion
BID/PERMIT SET
3/4" = 1'-0"A3.2.0
4A WALL SECTION - ENTRANCE
3/4" = 1'-0"A3.2.0
2A WALL SECTION - NORTH/SOUTH WALL
1 1/2" = 1'-0"A3.2.0
1D PARAPET DETAIL
1 1/2" = 1'-0"A3.2.0
1B TYP. WATERTABLE DETAIL
NO. REASON DATE
3/4" = 1'-0"A3.2.0
6A WALL SECTION AT WINDOW
1 1/2" = 1'-0"A3.2.0
1A TYP. SILL DETAIL
FEC4'-0"19" MAX
9" MIN29" MIN34" MAX40" MAX6'-0"9"2'-0"
42"
36" MAX
36" MAX19"MIN17"-19"1'-9"
WALL MIRROR
TOILET TISSUE DISPENSER
GRAB BAR
EDGE OF PAPER
MAX BOWL DEPTH 6"
RECESSED OR
COUNTER MOUNTED
SOAP DISPENSER
TOILET SEAT COVER
ACCESSIBLE TOILET
(1'-3" @ OTHERS)
MIRRORALL EXPOSED HOT AND COLD WATER
PIPES SHALL BE INSULATED WITH
PRODUCT SPECIFICALLY MANUFACTURED
FOR THIS PURPOSE UNLESS COVERED
WITH ADA APRON.
SOAP
DISPENSER
3'-4"3'-4"1'-6" MIN.e10
eE.6
eF
0M6B
0M6B
0G3B
0G3B
4' - 5 1/4"7' - 6 1/4"3' - 5 7/8"3' - 2"11 5/8"MAINTAIN
7' X 10' CLEAR
PER OWNER
REQUEST
2' - 0"2' - 0"2' - 0"2' - 0"2' - 0"1137A
1136A
COACH
RESTROOM
1138
COACH
LOCKERS
1137
?
?
1138A
01
02
1' - 0"3' - 6"3' - 0"6"
1' - 6"
0304
05
06
07
08
09
10
0G3B
e10
eE.6
eE
1' - 4"1' - 6"2' - 0"2' - 0"2' - 0"2' - 0"2' - 4 1/2"2' - 0 1/2"2' - 0"2' - 0"1' - 8"
1140B
1140A
1139A
2M8A 3' - 2"1' - 0"8' - 1"
0G3B 0G3B
2M12A
2M12A
1' - 8"2' - 0"2' - 0"2' - 0"2' - 0"2' - 0"2' - 0"2' - 0"2' - 0"2' - 0"2' - 0"2' - 0"2' - 0"2' - 0"2' - 0"2' - 0"2' - 0"2' - 0"2' - 0"10 7/8"2' - 0"2' - 0"2' - 0"2' - 0"2' - 0"2' - 0"2' - 0"2' - 0"2' - 0"2' - 0"2' - 0"2' - 0"2' - 0"
0G3B
0G3B
REUSE 30 EXISTING WOOD
LOCKERS IN PLACE. REMAINING
WOOD LOCKERS BY OWNER -
MATCHING CONSTRUCTION,
FINISH, AND MATERIALS
2M8A
2M8A
2M8A0G3B0G3B
5' - 11 1/4"
2' - 0"2' - 0"2' - 0"2' - 0"2' - 6"1' - 4"4"2' - 10"RESIDENTIAL
APPLIANCE BY
OWNER. POWER
PROVIDED.
NO WATER TO THIS
ROOM
SEE FINISH SCHEDULE
FOR CASEWORK AND
COUNTERTOP LAMINATE
COLORS.
w w w . l i t t l e o n l i n e . c o m
This drawing and the design shown are the property
of Little Diversified Architectural Consulting. The
reproduction, copying or other use of this drawing
without their written consent is prohibited and any
infringement will be subject to legal action.
Little 2017c
PROJECT MANAGER
DESIGN TEAM
PRINCIPAL IN CHARGE
PROJECT TEAM
REVISIONS
PROJECT NAME
SHEET TITLE
PROJECT NO.
SHEET NUMBER
ISSUE FOR
ISSUE DATE
B
1 2 3 4 5 6 7
A
C
D
E
F
410 Blackwell Street, Suite 10
Durham, NC 27701
T: 919.474.2500
Rob Klinedinst
Katie Buckman
Anne Lebo
10/06/17
10/9/2017 3:30:47 PM C:\Users\katie.buckman\Documents\513.7505.00_CU_WrestlingExpansion_A-16_katie.buckman.rvt513.7505.00
A4.0.0
ENLARGED PLANS AND
INTERIOR ELEVATIONS
Campbell Convocation
Center Wrestling
Department Renovation
and Expansion
BID/PERMIT SET
1/2" = 1'-0"A4.0.0
1D TYPICAL BATHROOM MOUNTING HEIGHTS
X SHEET KEYNOTES
X TOILET ACCESSORIES LEGEND
E GRAB BAR 18" VERTICAL
R 18" X 34" SHOWER GRAB BAR
S ADA 'L' SHOWER SEAT (TRANSFER SHOWER)
SEE FINISH MATERIAL SCHEDULE ON SHEET A811 FOR FINISH
INFORMATION
GENERAL FINISH NOTES
1/4" = 1'-0"A4.0.0
5D ENLARGED PLAN - COACH LOCKERS
NO. REASON DATE
1/4" = 1'-0"A4.0.0
5A ENLARGED PLAN - TEAM LOCKERS
1/4" = 1'-0"A4.0.0
1A LOUNGE WEST
01 TOILET PAPER DISPENSER
02 GRAB BAR 42" LONG
03 GRAB BAR 36" LONG
04 MIRROR GLASS - 3'-0" HIGH X 2'-0" WIDE
05 SHOWER CURTAIN AND ROD
06 ROBE HOOK
07 SOAP DISPENSER
08 PAPER TOWEL DISPENSER
09 BUILT IN WOOD SHELVES BY OWNER. MATCH LOCKER MATERIOR
10 CUSTOM WOOD LOCKERS BY OWNER. MATCH CONSTRUCTION IN
EXISTING WRESTLING LOCKER ROOM. PROVIDE
OPENING FOR RECEPTACLE. SEE ELECTRICAL FOR LOCATION.
A.SEE SHEET A811 FOR FINISH MATERIAL SCHEDULE.
B.CONTRACTOR SHALL PROVIDE ALL INTERIOR FINISHES AS
SPECIFIED HEREIN. LITTLE DIVERSIFIED ARCHITECTURAL
CONSULTING SHALL BE NOTIFIED OF ANY DISCREPANCIES OR
OMISSIONS PRIOR TO PROCEEDING WITH WORK.
C.ALL INTERIOR FINISHES SHALL HAVE A CLASS A FLAME SPREAD
RATING.
D.CONTRACTOR SHALL BE SOLELY RESPONSIBLE FOR THE
ACCURACY OF HIS MEASUREMENTS AND TOTAL YARDAGE
REQUIREMENTS TO BE FURNISHED. NO REQUESTS FOR MATERIALS
OR INSTALLATION EXTRAS WILL BE CONSIDERED DUE TO
MEASUREMENT OR TAKEOFF ERRORS BY CONTRACTOR. REFER TO
ARCH. PLAN A101 FOR ALL DIMENSIONS.
E.VARIATIONS IN FLOOR LEVEL IN EXCESS OF 1" FOR EVERY 10'-0"
SHALL BE LEVELED BY CONTRACTOR. LEVELING SHALL BE
COMPLETED WITH FLOOR READY TO RECEIVE NEW FINISHES AS
SPECIFIED. CONTRACTOR SHALL VERIFY SLAB CONDITION PRIOR
TO BID SUBMISSION.
F.ALL MISCELLANEOUS GRILLES, PLATES, OR OTHER DEVICES SHALL
BE PAINTED TO MATCH THE WALL OR CEILING IN WHICH THEY ARE
INSTALLED.
G.UNLESS OTHERWISE NOTED PROVIDE MINIMUM 3-COAT PAINT
SYSTEMS AS SPECIFIED FOR EACH SUBSTRATE; REFER TO FINISH
PLAN FOR COLORS AND SHEENS.
H.ALL NEW AND EXISTING FINISHES SCHEDULED TO REMAIN SHALL BE
PROTECTED DURING CONSTRUCTION. ANY DAMAGE SHALL BE
REPAIRED BY CONTRACTOR INVOLVED AT HIS COST WITH NO COST
TO OWNER.
I.CLEAN HVAC DIFFUSERS, DRAPERY POCKETS, FIRE EXTINGUISHER
CABINET, AND SPEAKER GRILLS. DO NOT PAINT EQUIPMENT,
UNLESS OTHERWISE NOTED.
J.PAINT FOR WALLS AND SOFFITS SHALL BE TWO COATS OF
EGGSHELL/SATIN OVER ONE COAT OF PRIMER IN THE INDICATED
COLOR UNLESS OTHERWISE NOTED.
K.PATCH & SAND ALL EXISTING WALLS, COLUMNS SOFFITS, ETC. TO
BE READY FOR PAINT.
w w w . l i t t l e o n l i n e . c o m
This drawing and the design shown are the property
of Little Diversified Architectural Consulting. The
reproduction, copying or other use of this drawing
without their written consent is prohibited and any
infringement will be subject to legal action.
Little 2017c
PROJECT MANAGER
DESIGN TEAM
PRINCIPAL IN CHARGE
PROJECT TEAM
REVISIONS
PROJECT NAME
SHEET TITLE
PROJECT NO.
SHEET NUMBER
ISSUE FOR
ISSUE DATE
B
1 2 3 4 5 6 7
A
C
D
E
F
410 Blackwell Street, Suite 10
Durham, NC 27701
T: 919.474.2500
Rob Klinedinst
Katie Buckman
Anne Lebo
10/06/17
10/9/2017 3:30:48 PM C:\Users\katie.buckman\Documents\513.7505.00_CU_WrestlingExpansion_A-16_katie.buckman.rvt513.7505.00
A8.1.1
FINISH SCHEDULE
Campbell Convocation
Center Wrestling
Department Renovation
and Expansion
BID/PERMIT SET
FINISH MATERIAL SCHEDULE
Location Tag Description Manufacturer
Finish Description
CommentsStyle Size Product Number Color Install Notes
CEILING ACT-1 ACOUSTICAL CEILING TILES ARMSTRONG FINE FISSURED
TEGULAR
2' X 2' #1732
HM
DOORS/HM
FRAMES
P-1 PAINT SHERWIN
WILLIAMS
SEMI GLOSS 1674 DEEP ONYX
WALL P-2 PAINT SHERWIN
WILLIAMS
EGGSHELL 653 EUROPEAN WHITE
WALL P-3 PAINT SHERWIN
WILLIAMS
EGGSHELL-
EPOXY
653 EUROPEAN WHITE USE IN ALL WET
LOCATIONS
BASE MCT-1 BUILT UP MOSAIC TILE BASE DALTILE KEYSTONES 6" X 8" MB-5A BUFFSTONE RANGE D147
BASE RB-1 RUBBER BASE- COVE ROPPE COVE 4"H ROLL P193 BLACK BROWN
FLOOR CON-1 SEALED CONCRETE
FLOOR CPT-1 CARPET TILE LEES FACULTY REMIX 24"x24" DK163 RENEWED BLUE 575
FLOOR MCT -1 MOSAIC CERAMIC TILE DALTILE KEYSTONES 2" X 2" MOSAIC TILE PATTERN 3027 76% BUFFSTONE RANGE D147, 12% EBONY D311, 12% PUMPKIN SPICE D090 GROUT 903 BIRCH
FLOOR RS-1 SPORTS FLOORING MONDO ADVANCE 6 MM 018 DARK GREY SEAM IN IN OLD VEST.
LOCATION ONLY.
FLOOR VCT-1 VINYL COMPOSITION TILE ARMSTRONG STANDARD
EXELON IMPERIAL
TEXTURE
12"x12"51915 CHARCOAL
CASEWORK PL-1 PLASTIC LAMINATE FORMICA 515-58 GRAPHITE GRAFIX; MATTE FINISH COUNTERTOPS CABINETS
CASEWORK PL-2 PLASTIC LAMINATE FORMICA 7697-58 BISQUE CERAMIC; MATTE FINISH CABINET BODY
TYPICAL
COUNTERTOPS-
MISC. SSM-1 SOLID SURFACE MATERIAL CORIAN NOCTURNE WINDOW STOOLS/
RESTROOMS
COUNTERTOPS-
MISC. WT-1 WINDOW TREATMENT- BLINDS SPRING WINDOW
FASHIONS
WHIT SATIN 205 ALL LOCATIONS BY
OWNER
BY OWNER.
WD. DOORS WD-1 LAMPTON DOORS CUSTOM COLOR #1 MATCH EXISTING
ROOM FINISH SCHEDULE
Room # Room Name Floor Finish Base Finish Wall Finish Ceiling Finish Comments
1136 WRESTLING ENTRY VCT RB-1 P-2 ACT-1
1137 COACH LOCKERS MCT-1 MCTB-1 P-2 ACT-1/GYP. SEALED CONCRETE FLOOR IN BACK AREA FOR
FUTURE EQUIPMENT. GYP CEILING OVER
SHOWER (P-3)
1138 COACH RESTROOM MCT-1 MCTB-1 P-3 ACT-1
1139 VESTIBULE CPT-1 RB-1 P-3 ACT-1
1140 WRESTLING
LOCKERS
CPT-1 RB-1 P-3 ACT-1
1142 WRESTLING GYM RS-1 RB-1 P-2 EXPOSED - REPAIR FIRE
SPRAY WHERE NEEDED.
PAINT TO MATCH
EXISTING
MONDO AT FLOOR PATCH NEAR ENTRANCE FROM
MAIN CORRIDOR. SEAM TO EXISTING.
1142.1 WRESTLING GYM
ADDITION
RS-1 RB-1 P-2 EXPOSED - FIRE SPRAY
STRUCTURE TO MATCH
EXISTING. PAINT TO
MATCH EXISTING
MONDO TO MATCH EXISTING UNDER NEW MAT.
SEAM TO EXISTING.
1143 RECEPTION VCT-1 RB-1 P-2 ACT-1
1144 ASST. COACH
OFFICES
CPT-1 RB-1 P-2 ACT-1
1145 CONFERENCE CPT-1 RB-1 P-2 ACT-1
1146 COACH CPT-1 RB-1 P-2 ACT-1
1147 STORAGE VCT-1 RB-1 P-2 ACT-1
1148 FITNESS CPT-1 RB-1 P-2 ACT-1
1149 LOUNGE CPT-1 RB-1 P-2 ACT-1
1150 CORRIDOR VCT-1 RB-1 P-2 EXPOSED - FIRE SPRAY
STRUCTURE TO MATCH
EXISTING. PAINT TO
MATCH EXISTING
DO NOT PAINT EXPOSED BRICK. CLEAN ONLY.
AREA C
NOT TO SCALE
EXISTING BUILDING
KEY PLAN
NO. REASON DATE
GENERAL NOTES - FINISH
X = 54" MIN.
Y = 52" MIN.
Y = 48" MIN. (IF BOTH
CLOSER & LATCH ON DR)
NOTE: ERECT ALL DOOR FRAMES AND ADJACENT WALLS PER
APPLICABLE PLAN CONFIGURATION. NOTIFY ARCHITECT OF
CONFLICTS PRIOR TO INSTALLATION OF DOOR FRAMES AND/OR
ADJACENT WALLS.
X = 12" MIN. (IF BOTH
CLOSER & LATCH ON DR)
Y = 48" MIN.FRONT APPROACHPUSH SIDE
X = 18" MIN.
(24" MIN. PREFERRED)
Y = 60" MIN.
Y = 42" MIN.LATCH SIDE APPROACHX = 24" MIN.X = 24" MIN.
Y = 54" MIN. (IF
CLOSER ON DR)
Y = 48" MIN.
X = 42" MIN., IF Y = 54"HINGE SIDE APPROACHX = 36" MIN., IF Y = 60"
PULL SIDE
YX XYXYYX
XY YX
DOOR AS SCHEDULED
PARTITION AS SCHEDULED
HOLLOW METAL FRAME,
SEE FRAME TYPE SCHEDULE
ANCHOR TO STUDS
CONTINUOUS SEALANT
BOTH SIDES, TYP.
METAL STUD HEAD FRAMING
2"HOLLOW METAL FRAME,
SEE FRAME TYPE SCHEDULE
DOOR AS SCHEDULE
ANCHOR TO STUDS
DOUBLE STUD FRAMING
AT DOOR JAMB
PARTITION AS SCHEDULED
STEEL REINFORCING
S/A DOOR JAMBS/A HEADERSHEAR BLOCK PKG.D.L.O.5"7"D.L.O.DETAIL D
JAMB
DETAIL B
SINGLE ACTING HEADER
FOR SURFACE CLOSER
DETAIL A
MEETING STILE
5"
1/8"
5"
DETAIL C
BOTTOM RAIL10"REQUEST TO EXIT
BUTTON ON EGRESS
SIDE. CARD READER ON
EXTERIOR WITHIN 5' OF
EGRESS
DOOR CLOSER AS
SCHEDULED
NOTE:
ALL ELECTRONIC LOCKS ON EGRESS DOORS
SHALL UNLOCK UPON ACTIVATION OF THE FIRE
ALARM AND SPRINKLER SYSTEM.
MOTION DETECTOR ON
EGRESS SIDE AS
SCHEDULED
NOTE:
COORDINATE WITH SECURITY SYSTEM AND
SECURITY RISER DIAGRAM.
PROVIDE POWER
THROUGH REQUIRED
CONDUIT TO ELECTRIC
HINGES,
ELECTROMECHANICAL
LOCKS, CARD READERS,
DOOR OPERATORS AND
ANY OTHER HARDWARE.
STUB UP 12"
ABOVE CEILING AT JAMB
AND HINGE.40" MIN.48" MAX.8"
NOTE:
TYPICAL LOCATION FOR SPECIALTY DEVICES NEAR A DOOR
* VERIFY THAT ALL MOUNTING
HEIGHTS ARE IN ACCORDANCE
WITH LOCAL JURISDICTIONAL
CODES
48" AFFS T
E V
18" AFFF
AFF8"S LIGHT SWITCH
T THERMOSTAT
V VOICE/DATA
E RECEPTACLE
F WALL MOUNTED
FURNITURE INFEED
10"6"
SIGN
BRAILE
SIGN
9"48" MIN.60" MAX.NOTE:
TYPICAL LOCATION FOR SPECIALTY DEVICES NEAR A GLASS
OFFICE FRONT AND DOOR
* VERIFY THAT ALL MOUNTING
HEIGHTS ARE IN ACCORDANCE
WITH LOCAL JURISDICTIONAL
CODES
48" AFFS T
E V
18" AFFF
AFF8"S LIGHT SWITCH
T THERMOSTAT
V VOICE/DATA
E RECEPTACLE
F WALL MOUNTED
FURNITURE INFEED
6"6"
F
FLUSH
FG
FULL GLAZE 1' - 1"5' - 2"HG
HALF GLASS 3' - 6"2' - 9"N 2' - 9"3"
NARROW LITE
SF2
ALUMINUM STOREFRONT
ENTRANCE DOOR PAIR
F1 F2
HOLLOW METAL
PAINTED P-1;
SEMI GLOSS FINISH
2"
SCHEDULE
SEE 2"2"SCHEDULESEE2"
SCHEDULE
SEE 2"2"SCHEDULESEEHOLLOW METAL
PAINTED P-1;
SEMI GLOSS FINISH
CEILING CEILING
AT DOORS w/ CRs PROVIDE 1/2" CONDUIT AT BOTH JAMBS TO
12" ABOVE CEILING, FROM STRIKE JAMB AND BUTT JAMB FOR
ELECTRIC HINGE
F3 F4
HOLLOW METAL
PAINTED P-1;
SEMI GLOSS FINISH
2"
SCHEDULE
SEE 2"4"SCHEDULESEE2"
SCHEDULE
SEE 2"4"SCHEDULESEEHOLLOW METAL
PAINTED P-1;
SEMI GLOSS FINISH
CEILING CEILING
AT DOORS w/ CRs PROVIDE 1/2" CONDUIT AT BOTH JAMBS TO
12" ABOVE CEILING, FROM STRIKE JAMB AND BUTT JAMB FOR
ELECTRIC HINGE
SF2
ALUMINUM STOREFRONT
ENTRANCE DOOR PAIR
DETAIL A
DETAIL CDETAIL DDETAIL BEXIT DEVICE, SEE
HDWR. SCHEDULE
1.CAULK DOOR JAMBS AND HEADS AT DOORS LOCATED IN WALLS TO
BE SOUND INSULATED.
2.HOLLOW METAL DOOR FRAMES TO BE FULLY WELDED FRAMES.
3.CAULK DOOR JAMBS AND HEADS WHERE GAPS, BETWEEN WALL AND
FRAME EXCEEDS 1/16".
4.PROVIDE (3) JAMB AND (1) BASE ANCHOR PER JAMB AT GYP. BOARD
PARTITIONS.
5.DOORS SHALL OPERATE FREELY WITHOUT BINDING.
6.FRAME ROUGH OPENINGS AS RECOMMENDED BY METAL STUD MFR.
AND DOOR FRAME MFR.
7.PROVIDE ANCHORS AND ACCESSORIES AS REQ'D. FOR CONDITIONS
& PER MFR. RECOMMENDATIONS.
8.DOOR FRAMES SHALL BE SECURED RIGIDLY IN PLACE AND BRACED
TO FLOOR AND STRUCTURE ABOVE TO PREVENT BREAK OUT TO
PARTITIONS.
9.DOORS TO BE LOCATED 6" FROM FACE OF WALL INCLUDING DOOR
FRAME, U.O.N.
10.ERECT ALL DOOR FRAMES AND ADJACENT WALLS TO CONFORM TO
THE APPLICABLE PLAN CONFIGURATION. NOTIFY LITTLE OF ANY
CONFLICTS PRIOR TO INSTALLATION OF DOOR FRAMES AND
ADJACENT WALLS DURING TRACK LAYOUT.
11.COORDINATE WITH SECURITY SYSTEM, SECURITY RISER DIAGRAM
AND FIRE ALARM SYSTEM.
12.CONFIGURE CURTAIN WALL/STOREFRONT SYSTEM TO
ACCOMMODATE CONDUIT FOR SECURITY DEVICES.
13.DOOR UNDERCUTS SHALL BE KEPT TO A MINIMAL DIMENSION AND
SHALL BE UNIFORM THROUGHOUT PROJECT, U.O.N.
14.FOR 1-HOUR DOORS USED IN STAIRWAY ENCLOSURES THE AVERAGE
TEMPERATURE RISE DEVELOPED ON THE UNEXPOSED SIDE SHALL
NOT EXCEED 450 DEGREES F AT THE END OF 30 MINUTES OF
STANDARD FIRE TEST EXPOSURE.
15.BOTH SIDES OF ALL EXTERIOR DOORS SHALL HAVE THE SAME
ELEVATION WITH NO MORE THAN 1/2" DIFFERENCE ON EITHER SIDE.
16.INSTALLATION OF ALL DOORS AND HARDWARE SHALL MEET MINIMUM
ADA REQUIREMENTS.
SIGN:LOCATION: TYPE:
WRESTLING LOCKERS ROOM 1140 2
RESTROOM ROOM 1138 1
EXIT ROOM 1143, 1136 2
EXIT NORTH BASKETBALL GYM DOOR 1
COACH LOCKERS ROOM 1137 1
JANITOR JAN. CLOSET IN WRESTLING GYM 1
LOUNGE ROOM 1149 1
FITNESS ROOM 1148 1
STORAGE ROOM 1147 1
HEAD COACH ROOM 1146 1
CONFERENCE ROOM 1145 1
ASST. COACH ROOM 1144 2
WHERE SIGN WILL BE MOUNTED ON GLASS, PROVIDE BLANK BACKER
PLATE TO MOUNTH ON OPPOSITE SIDE OF GLASS. COORDINATE FINAL
LOCATIONS/NUMBERS/MESSAGES WITH OWNER AND ARCHITECT.
SIGN TYPE 1: 8-1/4" x 7" PAINTED ACRYLIC SIGN
SIGN TYPE 2: 6" x 8" PAINTED ACRYLIC SIGN
EXIT
RESTROOMWOMENMEN
SIGN TYPE 1:
SIGN TYPE 2:
JANITOR
NOTES:
1. CHARACTERS AND TACTILE CHARACTERS OF SIGNS SHALL MEET THE
REQUIREMENTS OF APPLICABLE ACCESSIBILITY CODES. INCLUDE BRAIL
LETTERING UNDER SIGNAGE MESSAGE.
2. SIGNAGE AND ROOM NUMBERS TO BE APPROVED BY OWNER.
SIGN TYPES
w w w . l i t t l e o n l i n e . c o m
This drawing and the design shown are the property
of Little Diversified Architectural Consulting. The
reproduction, copying or other use of this drawing
without their written consent is prohibited and any
infringement will be subject to legal action.
Little 2017c
PROJECT MANAGER
DESIGN TEAM
PRINCIPAL IN CHARGE
PROJECT TEAM
REVISIONS
PROJECT NAME
SHEET TITLE
PROJECT NO.
SHEET NUMBER
ISSUE FOR
ISSUE DATE
B
1 2 3 4 5 6 7
A
C
D
E
F
410 Blackwell Street, Suite 10
Durham, NC 27701
T: 919.474.2500
Rob Klinedinst
Katie Buckman
Anne Lebo
10/06/17
10/9/2017 3:30:49 PM C:\Users\katie.buckman\Documents\513.7505.00_CU_WrestlingExpansion_A-16_katie.buckman.rvt513.7505.00
A9.0.0
DOOR SCHEDULE AND
DETAILS
Campbell Convocation
Center Wrestling
Department Renovation
and Expansion
BID/PERMIT SET
DOOR SCHEDULE
Door Number
Door
Panel Type
Door Frame
CommentsWidth Height Thickness # Leafs Material Finish Rating Hardware Type Material Finish
1036A 3' - 0" 7' - 8" 1 3/4" 1 N HM P-1 90 MIN. 9 F3 HM P-1
1047C 3' - 0" 7' - 8" 1 3/4" 1 N HM P-1 120 MIN. 4 F3 HM P-1
1136A 6' - 0" 7' - 8" 1 3/4" 2 N HM P-1 0 MIN. 7 F4 HM P-1
1137A 3' - 0" 7' - 8" 1 3/4" 1 F WD STAIN - MATCH EXIST. 0 MIN. 1 F3 HM P-1
1138A 3' - 0" 7' - 8" 1 3/4" 1 F WD STAIN - MATCH EXIST. 0 MIN. 5 F3 HM P-1
1139A 3' - 0" 7' - 8" 1 3/4" 1 F WD. STAIN - MATCH EXIST. 0 MIN. 2 F3 HM P-1
1140A 3' - 0" 7' - 8" 1 3/4" 1 F WD. STAIN - MATCH EXIST. 0 MIN. 3 F3 HM P-1
1140B 6' - 0" 7' - 8" 1 3/4" 2 F HM P-1 90 MIN. 8 F4 HM P-1
1143A 6' - 0" 7' - 10" 1 3/4" 2 ALUM. BONE WHITE 0 MIN. 7 F2 ALUM. BONE WHITE
1144A 3' - 0" 7' - 10" 1 3/4" 1 WD. STAIN - MATCH EXIST. 0 MIN. 1 F1 HM P-1
1144B 3' - 0" 7' - 10" 1 3/4" 1 WD. STAIN - MATCH EXIST. 0 MIN. 1 F1 HM P-1
1145A 3' - 0" 7' - 10" 1 3/4" 1 WD. STAIN - MATCH EXIST. 0 MIN. 1 F1 HM P-1
1146A 3' - 0" 7' - 10" 1 3/4" 1 WD. STAIN - MATCH EXIST. 0 MIN. 1 F1 HM P-1
1147A 6' - 0" 7' - 10" 1 3/4" 2 F WD. STAIN - MATCH EXIST.0 MIN. 6 F2 HM P-1
1148A 3' - 0" 7' - 10" 1 3/4" 1 WD. STAIN - MATCH EXIST. 0 MIN. 2 F1 HM P-1
1149A 3' - 0" 7' - 10" 1 3/4" 1 WD. STAIN - MATCH EXIST. 0 MIN. 2 F1 HM P-1
DOOR SCHEDULE NOTES
NOTES:
1) SEE SPECIFICATIONS FOR DOOR HARDWARE SCHEDULE -
INCLUDING DESCRIPTION OF
DOOR OPERATION (LOCK OPERATION, COORDINATION WITH
ACCESS CONTROL SYSTEM ETC.)
2) ALL DOOR HARDWARE UTILIZED IS MECHANICAL OR
ELECTROMECHANICAL AND PROVIDES
FREE EGRESS FROM SPACES SERVED - NO MAGNETIC LOCKS ARE
UTILIZED.
12" = 1'-0"A9.0.0
2C ADA DOOR CONFIGURATIONS
3" = 1'-0"A9.0.0
5A DETAIL - INTERIOR HM DOOR HEAD
3" = 1'-0"A9.0.0
4A DETAIL - INTERIOR HM DOOR JAMB
1/2" = 1'-0"A9.0.0
1E DIAGRAM - ACCESS CONTROL
1/2" = 1'-0"A9.0.0
1C DIAGRAM - DEVICE LOCATION
1/2" = 1'-0"A9.0.0
1A DIAGRAM - DEVICE LOCATION_PERP.
1/4" = 1'-0"A9.0.0
4C ELEVATION - DOOR TYPES
1/4" = 1'-0"A9.0.0
11 ELEVATION - FRAME TYPES
3/8" = 1'-0"A9.0.0
3A ELEVATION - STOREFRONT ENTRANCES
12" = 1'-0"A9.0.0
2A INTERIOR SIGN SCHEDULE
NO. REASON DATE
SF-2
F
F
F
F
F
F
1.THESE NOTES SHALL APPLY UNLESS INDICATED OTHERWISE BY DRAWINGS OR SPECIFICATIONS. IN THE EVENT THAT CONFLICTS
OCCUR BETWEEN THESE NOTES, DRAWINGS OR SPECIFICATIONS NOTIFY THE STRUCTURAL ENGINEER FOR RESOLUTION PRIOR TO
PROCEEDING WITH THE WORK.
2.STRUCTURAL DRAWINGS INDICATE TYPICAL AND CERTAIN SPECIFIC CONDITIONS ONLY. SHOP DRAWINGS SHALL DETAIL ALL
CONDITIONS IN ACCORDANCE WITH THE SPECIFIED STANDARDS AND THE SPECIFIC REQUIREMENTS OF THIS PROJECT.
3.SUBMIT SHOP DRAWINGS ON ALL STRUCTURAL MATERIALS FOR APPROVAL BEFORE FABRICATION. CONTRACTOR SHALL REVIEW AND
APPROVE SHOP DRAWINGS PRIOR TO SUBMISSION.
4.THE STRUCTURE INDICATED BY THE DRAWINGS AND SPECIFICATIONS IS STRUCTURALLY STABLE ONLY IN ITS COMPLETED FORM. THE
CONTRACTOR IS SOLELY RESPONSIBLE FOR THE MEANS, METHODS, SEQUENCES AND OPERATIONS OF CONSTRUCTION AND SHALL
PROVIDE TEMPORARY BRACING AS REQUIRED TO MAINTAIN THE STABILITY OF THE STRUCTURE DURING CONSTRUCTION.
5.ALL DETAILS, SECTIONS, AND NOTES INDICATED ON THE DRAWINGS SHALL APPLY AT ALL LOCATIONS WHERE CONDITIONS ARE SIMILAR
TO THOSE INDICATED BY THE DETAIL, SECTION, OR NOTE.
6.CENTERLINES OF COLUMNS AND FOUNDATIONS SHALL COINCIDE WITH GRID LINE INTERSECTIONS UNLESS NOTED OTHERWISE.
7.CENTERLINES OF FLOOR AND ROOF FRAMING MEMBERS SHALL COINCIDE WITH GRID LINES UNLESS NOTED OTHERWISE.
8.EQUALLY SPACE FLOOR AND ROOF FRAMING MEMBERS BETWEEN GRID LINES UNLESS NOTED OTHERWISE.
9.USE ONLY DIMENSIONS INDICATED ON THE DRAWINGS. DO NOT SCALE THE DRAWINGS OR USE ANY DIMENSIONS TAKEN FROM
ELECTRONIC DATA FILES.
10.IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO COORDINATE THE STRUCTURAL WORK WITH CIVIL, ARCHITECTURAL,
MECHANICAL, ELECTRICAL, AND PLUMBING DRAWINGS AND ALL OTHER RELEVANT TRADES. IN CASE OF CONFLICT BETWEEN
STRUCTURAL WORK AND DRAWINGS RELATED TO OTHER TRADES THE CONTRACTOR SHALL MAKE IN THEIR BID ALLOWANCE FOR THE
MORE SEVERE REQUIREMENTS. CONFLICTS BETWEEN THE STRUCTURAL WORK AND THE DRAWINGS OF OTHER TRADES SHALL NOT
BE A REASON FOR ANY ADDITIONAL COST OR DELAY IN EXECUTION OF THE WORK.
11.THE CONTRACTOR SHALL NOTIFY THE ARCHITECT AND STRUCTURAL ENGINEER OF ANY DISCREPANCIES BETWEEN THE STRUCTURAL
DOCUMENTS AND ANY OTHER DOCUMENTS OR EXISTING CONDITIONS FOR RESOLUTION PRIOR TO PROCEEDING WITH THE WORK.
GENERAL CONDITIONS AND STATEMENTS
DESIGN CRITERIA
DESIGN CODES
1.BUILDING CODE 2012 NORTH CAROLINA BUILDING CODE BASED ON 2009 INTERNATIONAL BUILDING CODE
2.STEEL AISC 360-10 SPECIFICATIONS FOR STRUCTURAL STEEL BUILDINGS
3.CONCRETE ACI 318-08 BUILDING CODE REQUIREMENTS FOR STRUCTURAL CONCRETE
4.CONCRETE MASONRY ACI 530-08 BUILDING CODE REQUIREMENTS FOR MASONRY STRUCTURES
5.DESIGN LOADS ASCE7-05
DESIGN LOADS
1.BUILDING OCCUPANCY GROUP III
2.ROOF LIVE LOAD 20 PSF
3.SNOW LOAD GROUND SNOW LOAD 15 PSF
Is 1.1
Ct 1.0
Ce 1.0
Pf 16.5 PSF
20 PSF
4.FLOOR LIVE LOAD LIGHT STORAGE 125 PSF
OFFICE/FITNESS 100 PSF
CORRIDORS 100 PSF
5.WIND LOAD WIND SPEED 95 MPH
EXPOSURE B
Iw 1.15
Kd 0.85
Kz 0.85
kzt 1.0
GCpi +/- 0.18
COMPONENTS AND CLADDING PRESSURES IN ACCORDANCE WITH ASCE7-05
WIND BASE SHEAR NS 39.4 KIPS
WIND BASE SHEAR EW 19.3 KIPS
6.SEISMIC LOAD Ie 1.25
SITE CLASSIFICATION C
Sds 0.190
Sd1 0.100
SEISMIC DESIGN CATEGORY C
SEISMIC FORCE RESISTING SYSTEM ORDINARY REINFORCED MASONRY SHEAR
WALLS; R=2
ANALYSIS PROCEDURE EQUIVALENT LATERAL FORCE
SEISMIC BASE SHEAR 70 KIPS
SELECTIVE DEMOLITION
1.THE CONTRACTOR IS FULLY RESPONSIBLE FOR THE MEANS OF DEMOLITION AND THE INTEGRITY AND STABILITY OF THE EXISTING
STRUCTURE DURING DEMOLITION AND THROUGHOUT CONSTRUCTION UNTIL THE WORK IS COMPLETED.
2.EXISTING CONDITIONS AND STRUCTURAL MEMBERS INDICATED ARE FOR REFERENCE ONLY AND SHALL BE VERIFIED AT THE SITE BY
THE CONTRACTOR. NOTIFY THE STRUCTURAL ENGINEER OF ANY DISCREPANCIES BETWEEN CONDITIONS INDICATED AND THOSE
FOUND AT THE SITE PRIOR TO THE START OF DEMOLITION OF EXISTING STRUCTURAL MEMBERS.
3.PRIOR TO THE START OF DEMOLITION WORK VERIFY THAT ANY ELECTRICAL SYSTEM, MECHANICAL SYSTEM, PLUMBING SYSTEM, OR
UTILITY EMBEDDED IN THE EXISTING STRUCTURE IS NOT DAMAGED OR DISRUPTED BY THE DEMOLITION WORK UNLESS IT IS REQUIRED
BY THE WORK AND ADEQUATE MEASURES ARE TAKEN TO PRESERVE THE SYSTEM OR UTILITY BEYOND THE AREA OF DEMOLITION.
4.WHERE NEW OPENINGS ARE INDICATED TO BE CUT THROUGH EXISTING CONCRETE MEMBERS, THE CONTRACTOR SHALL CORE DRILL
ALL CORNERS OF THE OPENING AND SAW CUT OPENING EDGES BETWEEN CORE DRILLED HOLES. DO NOT CUT BEYOND HOLES. CUT
AND CHIP CORNER HOLES TO PRODUCE SQUARE OPENING CORNERS AS REQUIRED.
DEFERRED SUBMITTALS
1.LIGHT GAGE METAL FRAMING
2.CEILING SEISMIC BRACING
3.MECHANICAL, PLUMBING, ELECTRICAL, DUCTWORK, AND SPRINKLER SEISMIC BRACING
4.EQUIPMENT ANCHORAGE AND CALCULATIONS
THE FOLLOWING ITEMS SHALL BE DESIGNED BY A SPECIALTY ENGINEER FOR THE CONTRACTOR. DRAWINGS AND CALCULATIONS SHALL
BE SUBMITTED TO THE ARCHITECT FOR REVIEW, SEALED AND SIGNED BY A STRUCTURAL ENGINEER LICENSED IN THE PROJECT STATE.
1.SOIL BEARING CAPACITY SHALL BE VERIFIED BY A NORTH CAROLINA GEOTECHNICAL ENGINEER.
2.FOUNDATIONS ARE DESIGNED FOR AN ALLOWABLE UNIFORM BEARING PRESSURE OF 5500 PSF ON SHORT
AGGREGATE PIERS.
3.SHORT AGGREGATE PIERS SHALL BE ENGINEERED BY THE FOUNDATION SUBCONTRACTOR IN ACCORDANCE WITH
"CONTROL OF SETTLEMENT AND UPLIFT OF STRUCTURES USING SHORT AGGREGATE PIERS" AND "SETTLEMENT OF
STRUCTURES SUPPORTED ON MARGINAL OR INADEQUATE SOILS STIFFENED WITH SHORT AGGREGATE PIERS" BY
EVERT C. LAWTON AND NATHANIEL S. FOX TO PROVIDE AN ALLOWABLE UNIFORM BEARING PRESSURE AT THE
BOTTOM OF FOOTINGS OF 5500 PSF WITH A MAXIMUM SETTLEMENT OF 1 INCH AND A MAXIMUM DIFFERENTIAL
SETTLEMENT OF 1/2 INCH BETWEEN ADJACENT COLUMNS AND BETWEEN WALLS AND ADJACENT COLUMNS.
4.FOUNDATION SUBCONTRACTOR SHALL SUBMIT DESIGN CALCULATIONS, PLANS, AND DETAILS FOR PIER
INSTALLATION SEALED BY A PROFESSIONAL ENGINEER IN THE STATE OF NORTH CAROLINA.
5.ALL FILL MATERIALS SHALL BE APPROVED BY THE GEOTECHNICAL ENGINEER. ALL FILL WITHIN 10'-0" OF THE
BUILDING FOUNDATION PERIMETER SHALL BE COMPACTED TO 95% OF STANDARD PROCTOR. THE TOP 12" BELOW
FLOOR SLABS AND FOOTINGS SHALL BE COMPACTED TO 98% OF STANDARD PROCTOR.
6.FOOTING BEARING ELEVATIONS SHALL BE ADJUSTED AT TIME OF EXCAVATION TO ACHIEVE THE REQUIRED BEARING
CAPACITY IF SO REQUIRED.
7.PROVIDE POSITIVE DRAINAGE AWAY FROM BUILDING FOUNDATIONS BOTH DURING CONSTRUCTION AND
PERMANENTLY.
8.MAINTAIN STABILITY OF EXCAVATIONS UNTIL PROPERLY BACKFILLED. KEEP EXCAVATIONS FREE OF LOOSE
MATERIAL. DEWATER EXCAVATIONS AND REMOVE ANY WET MATERIAL PRIOR TO PLACING CONCRETE.
9.PLACE A 3" THICKNESS "MUDMAT" OF CONCRETE IN THE BOTTOM OF FOOTINGS THAT WILL BE EXPOSED TO RAIN.
10.HEAVY EQUIPMENT USED FOR PLACING OR COMPACTING BACKFILL SHALL NOT BE OPERATED WITHIN A DISTANCE
EQUAL TO THE HEIGHT OF THE BACKFILL ABOVE THE TOP OF FOOTING, (1 HORIZONTAL TO 1 VERTICAL). HAND
OPERATED COMPACTION EQUIPMENT SHALL BE USED FOR COMPACTION OPERATIONS IN THIS AREA.
11.GRADE SHALL BE SUCH THAT THE THICKNESS OF ANY FOUNDATION OR SLAB ON GRADE IS NOT REDUCED BY MORE
THAN 5% OF THAT INDICATED.
12.EXCAVATION BRACING SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR. EXCAVATION BRACING SHALL BE
DESIGNED FOR LATERAL LOADING RESULTING FROM AN EQUIVALENT FLUID PRESSURE OF 60 PCF AND A SURFACE
SURCHARGE OF 250 PSF.
SOIL AND SUBSURFACE CONDITIONS
1.SUBMIT MIX DESIGNS FOR EACH TYPE OF CONCRETE SPECIFIED.
2.SUBMIT DATA FOR ALL ADMIXTURES, CURING COMPOUNDS AND HARDENERS THAT ARE INTENDED FOR USE.
3.CONCRETE SHALL HAVE THE MINIMUM 28 DAY COMPRESSIVE STRENGTH AND WEIGHTS:
LOCATION 28 DAY STRENGTH UNIT WEIGHT
FOUNDATIONS AND SLAB ON GRADE 4,000 PSI 145 PCF
4.CONCRETE WORK SHALL CONFORM TO ACI 318.
5.REINFORCING BARS SHALL CONFORM TO ASTM A615 GRADE 60.
6.WELDED WIRE FABRIC SHALL CONFORM TO ASTM A82 AND A185. PROVIDE MATERIAL IN SHEETS. LAP ALL WELDED WIRE FABRIC ONE
FULL SQUARE PLUS 2" AT ALL SHEET EDGES.
7.SLAB ON GRADE DOWELS SHALL BE SMOOTH RODS CONFORMING TO ASTM A36 WITH ENDS SMOOTH CUT.
8.REINFORCING BAR SUPPORT DEVICES SHALL CONFORM TO CRSI MANUAL OF STANDARD PRACTICE.
9.CONCRETE CLEAR COVER ON EMBEDDED REINFORCING SHALL BE AS FOLLOWS:
LOCATION BAR SIZE MINIMUM CLEAR COVER
FOOTINGS ALL 3" BOTTOM AND SIDES, 2" TOP
CONCRETE EXPOSED TO EARTH OR WEATHER #5 AND SMALLER 1 1/2"
CONCRETE NOT EXPOSED TO EARTH OR WEATHER
SLABS, WALLS AND JOISTS #11 AND SMALLER 3/4"
10.ALL CONTINUOUS BARS SHALL HAVE A CLASS B TENSION LAP SPLICE AT ALL SPLICES UNO. PROVIDE CORNER BARS FOR ALL
CONTINUOUS BARS AT ALL FOUNDATION AND WALL CORNERS AND INTERSECTIONS. LAP CORNER BARS 48 BAR DIAMETERS EACH
END.
11.PROVIDE (2) #5 x 4'-0" LONG TOP DIAGONAL BARS AT ALL REENTRANT CORNERS IN ALL SLABS ON GRADE AND ELEVATED SLABS.
12.PROVIDE DOWELS TO FOOTINGS TO MATCH ALL WALL, PIER AND COLUMN VERTICAL REINFORCING UNO. EMBED DOWELS IN FOOTING
WITH HOOK TO WITHIN 3" OF BOTTOM OF FOOTING. EXTEND DOWELS ABOVE FOOTING FOR 48 BAR DIAMETER LAP SPLICE WITH
VERTICAL REINFORCING UNO.
13.CONSTRUCTION OR CONTRACTION JOINTS SHALL BE INSTALLED IN SLABS ON GRADE AT A SPACING NOT TO EXCEED 15-0" OC EACH
DIRECTION UNO ON FOUNDATION PLAN. ASPECT RATIO OF SLAB AREAS BETWEEN JOINTS (RATIO OF LONG SIDE TO SHORT SIDE)
SHALL NOT EXCEED 1.5. SAW CUT JOINTS SHALL BE MADE AS SOON AS SLABS WILL SUPPORT MEN AND EQUIPMENT. EMBEDDED EDGE
ANGLES SHALL BE DISCONTINUOUS AT SLAB JOINT LOCATIONS.
14.CONSTRUCTION AND CONTRACTION JOINTS IN WALLS SHALL BE LOCATED AT 100'-0" OC MAXIMUM AND 25'-0" MAXIMUM FROM WALL
CORNERS. ALIGN JOINTS IN WALLS WITH JOINTS IN SLABS AT LOCATIONS WHERE SLABS ARE CONNECTED TO WALLS.
15.CONFORM TO ACI 306 FOR COLD WEATHER CONCRETE AND ACI 305 FOR HOT WEATHER CONCRETE WORK WHEN ANY COMBINATION
OF TEMPERATURE, HUMIDITY OR WIND SPEED RESULTS IN CONDITIONS THAT WOULD IMPAIR THE QUALITY OF CONCRETE.
CONCRETE IS TO BE REJECTED IF ITS TEMPERATURE AT TIME OF PLACEMENT IS 90 DEGREES F OR ABOVE.
16.CHAMFER ALL EXPOSED CONCRETE EDGES 3/4" UNO. SEE ARCHITECTURAL DRAWINGS FOR DETAILS.
17.THE CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATING ALL EMBEDDED ITEMS IN CONCRETE WORK. COORDINATE WITH THE
FOLLOWING: CIVIL, ARCHITECTURAL, MECHANICAL, ELECTRICAL AND PLUMBING DRAWINGS, PRECAST SHOP DRAWINGS,
MECHANICAL, ELECTRICAL AND PLUMBING EQUIPMENT AND FIXTURE REQUIREMENTS.
CAST IN PLACE STRUCTURAL CONCRETE
CEILING DESIGN NOTE
1.ALL SUSPENDED CEILING FRAMING SYSTEMS SHALL BE DESIGNED BY THE SUPPLIER TO CONFORM WITH LOCAL SEISMIC
REQUIREMENTS. CEILING WEIGHT SHALL INCLUDE ALL LIGHT FIXTURES AND OTHER EQUIPMENT THAT IS LATERALLY SUPPORTED
BY THE CEILING. FOR PURPOSES OF DETERMINING THE LATERAL FORCE, A CEILING WEIGHT OF NOT LESS THAN 4 PSF SHALL BE
USED. SUPPLIER SHALL SUBMIT A LETTER OF CERTIFICATION SIGNED BY A NORTH CAROLINA PROFESSIONAL ENGINEER.
1.UNO HOLLOW MASONRY UNITS SHALL CONFORM TO ASTM C90, LIGHTWEIGHT, WITH A MINIMUM COMPRESSIVE STRENGTH F'm = 1,500
PSI ON THE NET BLOCK AREA.
2.MORTAR SHALL CONFORM TO ASTM C270 CEMENT-LIME TYPE M OR S. MINIMUM COMPRESSIVE STRENGTH TO BE 1,800 PSI.
3.COURSE MASONRY GROUT SHALL CONFORM TO ASTM C476 WITH MAXIMUM AGGREGATE SIZE OF 3/8". MINIMUM COMPRESSIVE
STRENGTH SHALL BE 2,000 PSI AT 28 DAYS. PROVIDE CLEAN OUT OPENINGS WHERE GROUT POUR EXCEEDS 5'-0".
4.PROVIDE MINIMUM REINFORCING FOR ALL CONCRETE MASONRY WALLS UNO ON PLANS:
PROVIDE W1.7 HORIZONTAL JOINT REINFORCING AT 16" OC WITH FORMED "L" AND "T" SECTIONS AT WALL CORNERS AND
INTERSECTIONS. REINFORCE VERTICALLY WITH 1 #5 CENTERED IN GROUT FILLED CELL FULL HEIGHT OF WALL WITH DOWEL TO
FOUNDATION AT WALL CORNERS, ENDS, INTERSECTIONS, OPENING JAMBS, EACH SIDE OF CONTROL JOINTS AND SPACED AT 32" OC
MAXIMUM. LAP VERTICAL REINFORCING 72 BAR DIAMETER AT ALL SPLICES UNO.
5.MINIMUM MASONRY WALL FOOTINGS SHALL PROJECT 4" MINIMUM ON EACH SIDE OF WALL AND BE 12" DEEP WITH (2) #5 CONTINUOUS.
6.BOND BEAMS SHALL BE REINFORCED WITH (2) #5 CONTINUOUS. LAP 32" AT ALL SPLICES. PROVIDE CORNER BARS AT ALL WALL
CORNERS AND INTERSECTIONS.
7.PROVIDE DOWELS TO MATCH VERTICAL BARS AT THE BASE OF ALL WALLS. LAP 48 BAR DIAMETERS MINIMUM WITH VERTICAL BARS
UNO.
CONCRETE MASONRY
1.STRUCTURAL STEEL JOIST AND JOIST GIRDER DESIGN, FABRICATION AND ERECTION SHALL CONFORM TO THE STEEL JOIST
INSTITUTE "STANDARD SPECIFICATION AND LOAD TABLES". JOISTS AND JOIST GIRDERS SHALL BE DESIGNED TO SUPPORT
ADDITIONAL CONCENTRATED LOADS, END MOMENTS AND REACTIONS RESULTING FROM THE SPECIFIED END MOMENTS
WHERE INDICATED ON THE DRAWINGS.
2.JOIST BRIDGING SHALL BE PROVIDED AND INSTALLED IN ACCORDANCE WITH SJI SPECIFICATIONS. BRIDGING SHALL BE
INSTALLED AND ANCHORED AT ENDS OF ALL BRIDGING RUNS TO WALLS OR STEEL FRAMES PRIOR TO PLACEMENT OF ROOF
DECK. PROVIDE BOLTED "X" BRIDGING IN ACCORDANCE WITH OSHA STANDARDS.
3.JOIST MANUFACTURER SHALL DESIGN JOISTS FOR THE NET UPLIFT PRESSURE INDICATED. WHERE NO NET UPLIFT PRESSURE
IS INDICATED DESIGN JOISTS FOR A MINIMUM NET UPLIFT OF 15 PSF (ASD). PROVIDE ADDITIONAL UPLIFT BRIDGING AS
REQUIRED.
4.CAMBER JOISTS IN ACCORDANCE WITH SJI SPECIFICATIONS.
5.JOISTS SHALL BE FASTENED TO SUPPORTING STEEL WITH A MINIMUM OF 1/8" FILLET WELD x 2" LONG EACH SIDE.
6.PROVIDE BOLTED CONNECTIONS AT SUPPORTS AND BOTTOM CHORD STABILIZER PLATES AT COLUMNS IN ACCORDANCE WITH
OSHA STANDARDS.
7.CONCENTRATED LOADS SHALL BE PERMITTED TO BE ATTACHED TO JOISTS AT JOIST PANEL POINTS ONLY. WHERE IT IS
NECESSARY TO ATTACH A CONCENTRATED LOAD TO THE JOIST BETWEEN PANEL POINTS THE JOIST SHALL BE REINFORCED
TO SUPPORT THE CONCENTRATED LOAD.
8.JOIST AND JOIST GIRDER BOTTOM CHORD EXTENSIONS SHALL NOT BE WELDED TO STABILIZER PLATES UNLESS
SPECIFICALLY NOTED OTHERWISE.
STEEL JOISTS
1.STRUCTURAL STEEL CONSTRUCTION DETAILING, FABRICATION AND ERECTION SHALL CONFORM TO THE AISC "SPECIFICATION FOR
STRUCTURAL STEEL BUILDINGS"
2.STRUCTURAL STEEL MEMBERS SHALL CONFORM TO THE FOLLOWING STANDARDS:
WIDE FLANGE SHAPES ASTM A992
ANGLE, CHANNELS AND PLATES ASTM A36
ANCHOR RODS <= 3/4"Ø ASTM F1554 GRADE 36
RECTANGULAR HSS ASTM A500 GRADE C, 50 ksi
HEADED STUDS ASTM A108, GRADE 1015-1020
3.ALL STEEL EXPOSED TO WEATHER SHALL BE HOT DIPPED GALVANIZED.
4.SPLICING OF STRUCTURAL STEEL MEMBERS IS PROHIBITED WITHOUT PRIOR WRITTEN APPROVAL OF THE ENGINEER FOR THE
LOCATION AND TYPE OF SPLICE.
5.CAMBER BEAMS WHERE INDICATED. WHERE NO CAMBER IS INDICATED, BEAMS SHALL BE FABRICATED SO THAT AFTER ERECTION,
ANY NATURAL CAMBER IS UPWARD.
6.ALL COPES, HOLES, OPENINGS AND MODIFICATIONS REQUIRED IN STRUCTURAL STEEL MEMBERS FOR ERECTION OR THE WORK
OF OTHER TRADES SHALL BE INDICATED ON THE SHOP DRAWINGS AT TIME OF SUBMITTAL FOR REVIEW.
7.FIELD MODIFICATION OF STRUCTURAL STEEL IS PROHIBITED WITHOUT PRIOR WRITTEN APPROVAL OF THE STRUCTURAL ENGINEER
OF RECORD.
8.SHOP DRAWINGS SHALL BE SUBMITTED FOR ALL STRUCTURAL STEEL AND SHALL INDICATE COMPLETE CONNECTION INFORMATION,
BOTH SHOP AND FIELD.
9.PROVIDE A SHOP COAT OF FABRICATOR'S STANDARD RUST INHIBITIVE PRIMER TO ALL STEEL UNO.
10.SEE ARCHITECTURAL DRAWINGS FOR FIRE PROTECTIVE MATERIAL APPLIED TO STRUCTURAL STEEL. DO NOT PRIME STEEL WHICH IS
TO RECEIVE SPRAY APPLIED FIRE PROTECTIVE MATERIAL. DO PRIME STEEL WHICH IS TO RECEIVE INTUMESCENT FIRE PROTECTIVE
COATING.
11.FILL SOLID WITH NON-SHRINK GROUT UNDER ALL BASE AND BEARING PLATES.
12.CONNECTION NOTES:
A.STRUCTURAL STEEL CONNECTIONS NOT SPECIFICALLY DETAILED ON THE STRUCTURAL DRAWINGS SHALL BE DESIGNED
BY THE CONTRACTOR TO SUPPORT MEMBER REACTION INDICATED. REACTIONS INDICATED ARE SERVICE LOAD FORCES
(ASD) FOR APPLICABLE LOAD COMBINATIONS. WHERE NO REACTION IS INDICATED PROVIDE A CONNECTION DESIGNED TO
SUPPORT A VERTICAL SHEAR REACTION OF 80% OF THE MAXIMUM TOTAL UNIFORM LOAD FOR THE APPROPRIATE BEAM
SECTION AND SPAN AS DETERMINED PER THE MAXIMUM TOTAL UNIFORM LOAD TABLES IN THE AISC MANUAL.
B.CONNECTION MATERIALS SHALL CONFORM TO THE FOLLOWING STANDARDS AND MATERIAL PROPERTIES:
ANGLES ASTM A36
WT ASTM A992
PLATES ASTM A36
BOLTS ASTM A325 OR ASTM A490
NUTS ASTM A563
WASHERS ASTM F436
WELDING ELECTRODES E70XX
C.STANDARD SHEAR CONNECTIONS SHALL BE DETAILED AS DOUBLE ANGLE OR SINGLE PLATE CONNECTIONS IN
ACCORDANCE WITH THE CONNECTION TABLES IN THE AISC "MANUAL OF STEEL CONSTRUCTION ALLOWABLE STRESS
DESIGN". BOLTED CONNECTIONS SHALL BE DETAILED USING TYPE N BOLTS INSTALLED IN SNUG TIGHTENED JOINTS UNO.
D.BRACED FRAME CONNECTIONS, MOMENT CONNECTIONS AND COLLECTOR ELEMENT CONNECTIONS SHALL BE DESIGNED
BY A NORTH CAROLINA PROFESSIONAL ENGINEER. STRUCTURAL CALCULATIONS FOR THESE CONNECTIONS SHALL BE
SUBMITTED AND SHALL BE SEALED BY THE ENGINEER RESPONSIBLE FOR THE DESIGN.
E.PROVIDE STIFFENERS, CONTINUITY PLATES, DOUBLER PLATES OR OTHER ADDITIONAL MEMBER LOCAL STRENGTHENING
MEASURES AS REQUIRED FOR THE CONNECTION DESIGN.
F.BOLTED CONNECTIONS SHALL BE MADE WITH A MINIMUM OF (2) 3/4"Ø BOLTS AND HAVE A MINIMUM SHEAR CAPACITY
OF 10 KIPS.
G. BOLTED CONNECTIONS SHALL CONFORM TO THE PROVISIONS OF THE RESEARCH COUNCIL ON STRUCTURAL
CONNECTIONS "SPECIFICATION FOR STRUCTURAL JOINTS USING ASTM A325 OR A490 BOLTS."
H.WELDED CONNECTIONS SHALL BE MADE WITH CONTINUOUS FILLET WELDS UNO. MINIMUM WELD SIZE SHALL BE 1/4" OR AS
REQUIRED BY AISC SPECIFICATION, WHICHEVER IS LARGER. MINIMUM WELD LENGTH SHALL BE 2".
I.ALL WELDS SHALL BE MADE BY CERTIFIED WELDERS.
J.BOLTED CONNECTIONS APART OF MOMENT CONNECTIONS, TENSION CONNECTIONS, BRACED FRAME CONNECTIONS,
MOMENT FRAME CONNECTIONS, COLLECTOR ELEMENT CONNECTIONS AND AS INDICATED SHALL BE SLIP-CRITICAL.
STRUCTURAL STEEL
1.EXISTING DRAWINGS WERE AVAILABLE FOR THIS PROJECT. ALL EXISTING DIMENSIONS, CONNECTION DETAILS, MEMBER SIZES,
FRAMING CONFIGURATION, ETC. HAVE BEEN ASSUMED CORRECT FROM THE EXISTING DRAWINGS. THE GENERAL CONTRACTOR
IS TO FIELD VERIFY ALL EXISTING CONDITIONS PRIOR TO STARTING CONSTRUCTION OR PREPARING SHOP DRAWINGS. NOTIFY
THE ARCHITECT AND ENGINEER OF ANY AREA WHERE THE EXISTING CONDITIONS DO NOT MATCH THE CONDITIONS ASSUMED ON
THESE DRAWINGS.
EXISTING CONDITIONS
1.EXCEPT WHERE INDICATED ON THE DRAWINGS, POST-INSTALLED ANCHORS SHALL CONSIST OF THE FOLLOWING ANCHOR TYPES
AS PROVIDED BY HILTI, INC. CONTACT HILTI AT (800) 879-8000 FOR PRODUCT RELATED QUESTIONS.
A.ANCHORAGE TO CONCRETE
1)ADHESIVE ANCHORS FOR CRACKED AND UNCRACKED CONCRETE USE:
a)HILTI HIT-HY 200 SAFE SET SYSTEM WITH HILTI HIT-Z ROD PER ICC ESR-3187.
b)HILTI HIT-HY 200 SAFE SET SYSTEM WITH HILTI HOLLOW DRILL BIT SYSTEM WITH HAS-E THREADED
ROD PER ICC ESR-3187
c)HILTI HIT-RE 500-v3 EPOXY ADHESIVE ANCHORING SYSTEM WITH HAS-E THREADED ROD PER ICC
ESR-3814 FOR SLOW CURE APPLICATIONS.
2)MEDIUM DUTY MECHANICAL ANCHORS FOR CRACKED AND UNCRACKED CONCRETE USE:
a)HILTI KWIK HUS-EZ AND KWIK HUS EZ-1 SCREW ANCHORS PER ICC ESR-3027
b)HILTI KWIK BOLT-TZ EXPANSION ANCHORS PER ICC ESR-1917
c)HILTI KWIK-BOLT 3 EXPANSION ANCHORS (UNCRACKED CONCRETE ONLY) PER ICC ESR-2302
3)HEAVY DUTY MECHANICAL ANCHORS FOR CRACKED AND UNCRACKED CONCRETE USE:
a)HILTI HDA UNDERCUT ANCHORS PER ICC ESR 1546
b)HILTI HSL-3 EXPANSION ANCHORS PER ICC ESR 1545
B.REBAR DOWELING INTO CONCRETE
1)ADHESIVE ANCHORS FOR CRACKED AND UNCRACKED CONCRETE USE:
a)HILTI HY-200 SAFE SET SYSTEM WITH HILTI HOLLOW BIT DRILL SYSTEM WITH CONTINUOUSLY
DEFORMED REBAR PER ICC ESR-3187
b)HILTI HIT-RE 500-v3 EPOXY ANCHORING SYSTEM WITH CONTINUOUSLY DEFORMED REBAR PER
ICC ESR-3814
C.ANCHORAGE TO SOLID GROUTED MASONRY
1)ADHESIVE ANCHORS USE:
a)HILTI HIT-HY 70 MASONRY ADHESIVE ANCHORING SYSTEM (ICC PENDING)
b)STEEL ANCHOR ELEMENT SHALL BE HILTI HAS-E CONTINUOUSLY THREADED ROD OR
CONTINUOUSLY DEFORMED STEEL REBAR
2)MECHANICAL ANCHORS USE:
a)HILTI KWIK HUS-EZ SCREW ANCHOR PER ICC ESR-3056
b)HILTI KWIK BOLT-3 EXPANSION ANCHORS PER ICC ESR-1385
D.ANCHORAGE TO HOLLOW / MULTI-WYTHE MASONRY
1)ADHESIVE ANCHORS USE:
a)HILTI HIT-HY 70 MASONRY ADHESIVE ANCHORING SYSTEM PER ICC ESR-3342
b)STEEL ANCHOR ELEMENT SHALL BE HILTI HAS-E CONTINUOUSLY THREADED ROD OR
CONTINUOUSLY DEFORMED STEEL REBAR
c)THE APPROPRIATE SIZE SCREEN TUBE SHALL BE USED PER ADHESIVE MANUFACTURER'S
RECOMMENDATION
2.ANCHOR CAPACITY USED IN DESIGN SHALL BE BASED ON THE TECHNICAL DATA PUBLISHED BY HILTI OR SUCH OTHER METHOD
AS APPROVED BY THE STRUCTURAL ENGINEER OF RECORD. SUBSTITUTION REQUESTS FOR ALTERNATE PRODUCTS MUST BE
APPROVED IN WRITING BY THE STRUCTURAL ENGINEER OF RECORD PRIOR TO USE. CONTRACTOR SHALL PROVIDE
CALCULATIONS DEMONSTRATING THAT THE SUBSTITUTED PRODUCT IS CAPABLE OF ACHIEVING THE PERFORMANCE VALUES OF
THE SPECIFIED PRODUCT. SUBSTITUTIONS WILL BE EVALUATED BY THEIR HAVING AN ICC ESR SHOWING COMPLIANCE WITH THE
RELEVANT BUILDING CODE FOR SEISMIC USES, LOAD RESISTANCE, INSTALLATION CATEGORY, AND AVAILABILITY OF
COMPREHENSIVE INSTALLATION INSTRUCTIONS. ADHESIVE ANCHOR EVALUATION WILL ALSO CONSIDER CREEP, IN-SERVICE
TEMPERATURE AND INSTALLATION TEMPERATURE.
3.INSTALL ANCHORS PER THE MANUFACTURER INSTRUCTIONS, AS INCLUDED IN THE ANCHOR PACKAGING.
4.OVERHEAD ADHESIVE ANCHORS MUST BE INSTALLED USING THE HILTI PROFI SYSTEM.
5.THE CONTRACTOR SHALL ARRANGE AN ANCHOR MANUFACTURER'S REPRESENTATIVE TO PROVIDE ONSITE INSTALLATION
TRAINING FOR ALL OF THEIR ANCHORING PRODUCTS SPECIFIED. THE STRUCTURAL ENGINEER OF RECORD MUST RECEIVE
DOCUMENTED CONFIRMATION THAT ALL OF THE CONTRACTOR'S PERSONNEL WHO INSTALL ANCHORS ARE TRAINED PRIOR TO
THE COMMENCEMENT OF INSTALLING ANCHORS.
6.ANCHOR CAPACITY IS DEPENDANT UPON SPACING BETWEEN ADJACENT ANCHORS AND PROXIMITY OF ANCHORS TO EDGE OF
CONCRETE. INSTALL ANCHORS IN ACCORDANCE WITH SPACING AND EDGE CLEARANCES INDICATED ON DRAWINGS.
7.EXISTING REINFORCING BARS IN THE CONCRETE STRUCTURE MAY CONFLICT WITH SPECIFIC ANCHOR LOCATIONS.EXISTING
REBAR AND STANDS MUST NOT BE CUT OR DAMAGED. UNLESS NOTED ON THE DRAWINGS THAT THE BARS CAN BE CUT. THE
CONTRACTOR SHALL REVIEW THE EXISTING STRUCTURAL DRAWINGS AND SHALL UNDERTAKE TO LOCATE THE POSITION OF
THE REINFORCING BARS AT THE CONCRETE ANCHORS, BY HILTI FERROSCAN, GPR, X-RAY, CHIPPING OR OTHER MEANS.
POST-INSTALLED ANCHORS
ADDL ADDITIONAL
ADH ADHESIVE
AESS ARCHITECTURALLY EXPOSED
STRUCTURAL STEEL
AFF ABOVE FINISHED FLOOR
ALT ALTERNATE
ARCH ARCHITECT
B/ BOTTOM OF
BCB BOTTOM CHORD BRACING
BCX BOTTOM CHORD EXTENSION
BFF BELOW FINISHED FLOOR
BLDG BUILDING
BOTT BOTTOM
BP BASE PL
BRG BEARING
BTWN BETWEEN
CIP CAST IN PLACE
CJ CONTRACTION OR
CONSTRUCTION JOINT
CL CENTERLINE
CLR CLEAR
CMU CONCRETE MASONRY UNIT
COL COLUMN
CONC CONCRETE
CONN CONNECTION
CONT CONTINUOUS
CTR CENTER
DBA DEFORMED BAR ANCHOR
DCJ DOWELED CONSTRUCTION
JOINT
DEFL DEFLECTION
DIA,Ø DIAMETER
DWG DRAWING
DWL DOWEL
EA EACH
EF EACH FACE
EJ EXPANSION JOINT
EL ELEVATION
ELEC ELECTRICAL
EOD EDGE OF DECK
EOS EDGE OF SLAB
EQ EQUAL
EW EACH WAY
EXP EXPANSION
EXT EXTERIOR
FFE FINISHED FLOOR ELEVATION
FIN FINISHED
FLR FLOOR
FOB FACE OF BRICK
FOM FACE OF MASONRY
FOS FACE OF STUD
FTG FOOTING
GA GAGE
GALV GALVANIZED
GC GENERAL CONTRACTOR
GLB GLULAM BEAM
HD HEADED
HORIZ HORIZONTAL
INT INTERIOR
JBE JOIST BEARNING ELEVATION
LLH LONG LEG HORIZONTAL
LLV LONG LEG VERTICAL
LSH LONG SIDE HORIZONTAL
LSV LONG SIDE VERTICAL
LW LIGHT WEIGHT
MECH MECHANICAL
MFR MANUFACTURER
MIN MINIMUM
MOW MIDDLE OF WALL
NTS NOT TO SCALE
NW NORMAL WEIGHT
OC ON CENTER
PAF POWER ACTUATED FASTENER
PJF PRE-MOLDED JOINT FILLER
PL PLATE
PT PRESSURE TREATED or POST
TENSIONED
QTY QUANTITY
REINF REINFORCEMENT
REF REFERENCE
REQD REQUIRED
SCHD SCHEDULE
SIM SIMILAR
SOG SLAB ON GRADE
SPEC SPECIFICATIONS
STD STANDARD
T/TOP OF
TCX TOP CHORD EXTENSION
TYP TYPICAL
UNO UNLESS NOTED OTHERWISE
VERT VERTICAL
VIF VERFIY IN FIELD
WP WORK POINT
WWF WELDED WIRE FABRIC
ABBREVIATIONS
1.ROOF DECK SHALL BE FORMED FROM STEEL CONFORMING TO THE FOLLOWING:
A.GALVANIZED DECK ASTM A653 WITH A MINIMUM YIELD STRENGTH OF 33 KSI.
2.THE DESIGN, MANUFACTURE AND ERECTION OF STEEL ROOF DECK AND ITS ANCHORAGE SHALL BE IN ACCORDANCE WITH THE
ANSI/SDI "STANDARD FOR STEEL ROOF DECK".
3.PROVIDE ROOF DECK OF TYPE, DEPTH AND MINIMUM THICKNESS INDICATED.
4.ROOF DECK SHALL BE INSTALLED IN LENGTHS TO PROVIDE 3 CONTINUOUS SPANS MINIMUM.
5.INSTALL ROOF DECK WITH A MINIMUM END BEARING LENGTH OF 1 1/2".
6.ROOF DECK SHALL BE FASTENED TO SUPPORTS AS INDICATED ON THE DRAWINGS.
METAL ROOF DECK
w w w . l i t t l e o n l i n e . c o m
This drawing and the design shown are the property
of Little Diversified Architectural Consulting. The
reproduction, copying or other use of this drawing
without their written consent is prohibited and any
infringement will be subject to legal action.
Little 2017c
PROJECT MANAGER
DESIGN TEAM
PRINCIPAL IN CHARGE
PROJECT TEAM
REVISIONS
PROJECT NAME
SHEET TITLE
PROJECT NO.
SHEET NUMBER
ISSUE FOR
ISSUE DATE
B
1 2 3 4 5 6 7
A
C
D
E
F
410 Blackwell Street, Suite 410
Durham, NC 27701
T: 919.474.2500
10/6/2017 3:53:03 PM C:\Users\carl.schuett\Documents\513.7505.00_CU_WrestlingExpansion_S-16_carl.schuett.rvt513.7505.00
10/06/2017
S0.0.1
GENERAL NOTES
Campbell Convocation
Center Wrestling
Department Renovation
and Expansion
BID/PERMIT SET
Rob Klinedinst
Katie Buckman
David Blankfard, PE, SE
w w w . l i t t l e o n l i n e . c o m
This drawing and the design shown are the property
of Little Diversified Architectural Consulting. The
reproduction, copying or other use of this drawing
without their written consent is prohibited and any
infringement will be subject to legal action.
Little 2017c
PROJECT MANAGER
DESIGN TEAM
PRINCIPAL IN CHARGE
PROJECT TEAM
REVISIONS
PROJECT NAME
SHEET TITLE
PROJECT NO.
SHEET NUMBER
ISSUE FOR
ISSUE DATE
B
1 2 3 4 5 6 7
A
C
D
E
F
410 Blackwell Street, Suite 10
Durham, NC 27701
T: 919.474.2500
10/06/2017
10/6/2017 3:53:03 PM C:\Users\carl.schuett\Documents\513.7505.00_CU_WrestlingExpansion_S-16_carl.schuett.rvt513.7505.00
10/06/2017
S0.0.1
GENERAL NOTES
Campbell Convocation
Center Wrestling
Department Renovation
and Expansion
BID/PERMIT SET
Rob Klinedinst
Katie Buckman
David Blankfard, PE, SE
NO. REASON DATENO. REASON DATE
w w w . l i t t l e o n l i n e . c o m
This drawing and the design shown are the property
of Little Diversified Architectural Consulting. The
reproduction, copying or other use of this drawing
without their written consent is prohibited and any
infringement will be subject to legal action.
Little 2017c
PROJECT MANAGER
DESIGN TEAM
PRINCIPAL IN CHARGE
PROJECT TEAM
REVISIONS
PROJECT NAME
SHEET TITLE
PROJECT NO.
SHEET NUMBER
ISSUE FOR
ISSUE DATE
B
1 2 3 4 5 6 7
A
C
D
E
F
410 Blackwell Street, Suite 10
Durham, NC 27701
T: 919.474.2500
10/06/2017
10/6/2017 3:53:03 PM C:\Users\carl.schuett\Documents\513.7505.00_CU_WrestlingExpansion_S-16_carl.schuett.rvt513.7505.00
10/06/2017
S0.0.2
STATEMENT OF
SPECIAL INSPECTIONS
Campbell Convocation
Center Wrestling
Department Renovation
and Expansion
BID/PERMIT SET
Rob Klinedinst
Katie Buckman
David Blankfard, PE, SE
NO. REASON DATE
eG
eF
eE.6
eE
e10
VIF
1' - 7"
FOM
5' - 11 1/4"77' - 4 3/4" FOM 44' - 8" FOM
1E
S3.0.1
6C
S3.0.1
5C
S3.0.1
1C
S3.0.1
1A
S3.0.1
FOM2' - 0"38' - 0 1/8" FOM
HSS8x6x3/8
HSS8x6x3/8
HSS8x6x3/8
HSS8x6x3/8
FOM
3' - 8 3/4"
FOM
1' - 8 3/4"
1E
S3.0.1
SW
SWSWSWSWSW
SWSWSWSW VIF17' - 8"1 1/2" VIF42' - 11 5/8" FOM7' - 3 1/4" FOM16' - 8 3/4" FOM5' - 11 3/8"7' - 1"16' - 10 7/8"7' - 1"5' - 11 3/8"1E
S3.0.1 16' - 8" FOMSWCJ, TYP
CJ, TYPCJ, TYPCJ, TYPCJ, TYP
EXIST FDN, TYP EXIST CMU WALL
1E
S3.0.1
6C
S3.0.1
1E
S3.0.1
SIM
SW
SW SW
5C
S3.0.1
5 7/8"
EXIST SOG
6A
S3.0.1
1C
S3.0.1
TYP
S
MATCH EXIST<-2' - 0">SMATCH EXIST<-2' - 0">RE-ENTRANT CORNER,
SEE TYP/3C S3.0.1
SMATCH EXIST<-2' - 0">AT EA EXIST/NEW FTG INTERFACE PROVIDE
(3) 5/8"Ø SMOOTH DWL x1'-6" LG TO EXIST
FTG w/ HILTI HIT-HY 200, EMBED 6", COAT
END IN NEW FTG w/ GREASE
INDICATES MP1 UNO,
SEE
EXIST COL, TYP
/2B S2.0.1
ALIGN
SSEXIST STORM LINE, VIF
NOTES:
1. SEE S0.0.1 FOR GENERAL NOTES AND ABBREVIATIONS.
2. FINISHED FLOOR ELEVATION TO MATCH EXISTING. REFERENCE ELEVATION 0'-0", DATUM.
3. TOP OF FOOTING 2'-0" BELOW FINISHED FLOOR ELEVATION, UNO. <No> INDICATES TOP OF FOOTING ELEVATION, SEE PLAN.
4. INDICATES STEP IN WALL FOOTING, SEE .
5. "MP#" INDICATES MASONRY PILASTER TYPE, SEE . INDICATES LOCATION OF MP.
6. SEE S3.01 FOR TYPICAL SLAB CONSTRUCTION DETAILS.
7. "SW#" INDICATES MASONRY SHEAR WALL TYPE. SEE S201 FOR MINIMUM SHEAR WALL REINFORCING AND SCHEDULE.
8. SEE FOR SLAB REPAIR DETAILS.S/5E S3.0.1
/4A S3.0.1
/2B S2.0.1
5" CONCRETE SLAB ON
GRADE w/ 6x6 W2.9xW2.9
WWF ON 15 MIL POLY VAPOR
BARRIER OVER 4" OF
COMPACTED WASHED STONE
w w w . l i t t l e o n l i n e . c o m
This drawing and the design shown are the property
of Little Diversified Architectural Consulting. The
reproduction, copying or other use of this drawing
without their written consent is prohibited and any
infringement will be subject to legal action.
Little 2017c
PROJECT MANAGER
DESIGN TEAM
PRINCIPAL IN CHARGE
PROJECT TEAM
REVISIONS
PROJECT NAME
SHEET TITLE
PROJECT NO.
SHEET NUMBER
ISSUE FOR
ISSUE DATE
B
1 2 3 4 5 6 7
A
C
D
E
F
410 Blackwell Street, Suite 10
Durham, NC 27701
T: 919.474.2500
10/06/2017
10/6/2017 3:53:06 PM C:\Users\carl.schuett\Documents\513.7505.00_CU_WrestlingExpansion_S-16_carl.schuett.rvt513.7505.00
10/06/2017
S1.0.1
CONVOCATION AREA C
FOUNDATION PLAN
Campbell Convocation
Center Wrestling
Department Renovation
and Expansion
BID/PERMIT SET
Rob Klinedinst
Katie Buckman
David Blankfard, PE, SE
3/16" = 1'-0"S1.0.1
1A CONVOCATION AREA C FOUNDATION PLAN
ADDITION
NOT TO SCALE
EXISTING BUILDING
KEY PLAN
NO. REASON DATE
eG
eF
eE.6
eE
e10
17' - 8"7' - 4"15' - 8"1E
S3.1.1
3E
S3.1.1W16x67 GALV2.5K2C8x11.5
C8x11.5
6C
S3.1.1
5' - 4"
VERIFY SPACING IN FIELD
(E) 30K7 30K7 AT 4'-10" OC
ALIGN CL OF JOIST
w/ EDGE OF EXIST
ROOF DECK, LAP
NEW ROOF DECK
3" AND FASTEN
PER .
5' - 4"W16x67 GALVW16x67 GALVC8x11.5
C8x11.5 1A
S3.1.1
4A
S3.1.1
3E
S3.1.2
4C
S3.1.1
1E
S3.1.2
3' - 4 3/4"
EXIST JOIST, TYP
1' - 0" OFFSET FROM
JBE=(16' - 7 1/2")
JBE=(16' - 8")
JBE=(16' - 0")
JBE=(16' - 8")
L2 L2 L2 L2 L2
L2 L2 L2
L3L3L3L4
L1
L2D1
D1 L11E
S3.1.1
RTU-1
(MAX WT + CURB = 1,200#)
L5x3x1/4 UNDER ROOF CURB AND AROUND
OPNGS, SEE AND TYP/4E S3.1.1 /6E S3.1.1
4A
S3.1.1
5' - 2 3/8"
3' - 7 1/2"
4E
S3.1.2
SW
SWSWSWSWSWSWSWSW SW
SW SW 5' - 11 3/8"7' - 1"16' - 10 7/8"7' - 1"5' - 11 3/8"(14' - 0 1/2")(14' - 0 1/2")(14' - 0 1/2")RTU-2
(MAX WT + CURB = 1,200#)
18K3 w/ 2 1/2" SEATS AT 4'-10" OC
1B
S3.1.2
TYP
INDICATES MP1 UNO,
SEE /2B S2.0.1
LO
HI
SIM
/3C S3.1.1
L5L5
SEE FOR
ADD'L DETAILS AT
NEW OPNG IN CMU
WALL, TYP
/1E S3.1.2
SHORE EXIST DECK
UNTIL NEW JOIST IS
INSTALLED
NOTES:
1.SEE S0.0.1 FOR GENERAL NOTES AND ABBREVIATIONS.
2. (No) INDICATES TOP OF STEEL OR JOIST BEARING ELEVATION ABOVE REFERENCE
DATUM. [+No] INDICATES DECK BEARING ELEVATION FROM TOP OF STEEL.
3."MP#" INDICATES MASONRY PILASTER TYPE, SEE .INDICATES
LOCATION OF MP#.
4."L#" INDICATES BOND BEAM LINTEL, SEE FOR SCHEDULE.
5."SW#" INDICATES MASONRY SHEAR WALL TYPE. SEE S2.0.1 FOR MINIMUM SHEAR WALL
REINFORCING AND SCHEDULE.
6.SEE S2.0.1 FOR MINIMUM SEISMIC REINFORCING REQUIRED AT ALL WALLS.
7.SEE S3.1.1 FOR TYPICAL ROOF FRAMING DETAILS.
8.HOT DIP GALVANIZE ALL EXTERIOR LINTELS.
9.SEE ARCHITECTURAL DRAWINGS FOR DIMENSIONS NOT SHOWN.
10.SEE ARCHITECTURAL DRAWINGS FOR FIREPROOFING REQUIREMENTS.
11.SEE S2.0.1 FOR LOOSE LINTEL SHCEDULE.
/1A S2.0.1
/2B S2.0.1
D1 :METAL ROOF DECK, 1 1/2" TYPE "B", 20 GA,
GALV G60 FINISH, SEE S3.1.1 FOR ATTACHMENT
w w w . l i t t l e o n l i n e . c o m
This drawing and the design shown are the property
of Little Diversified Architectural Consulting. The
reproduction, copying or other use of this drawing
without their written consent is prohibited and any
infringement will be subject to legal action.
Little 2017c
PROJECT MANAGER
DESIGN TEAM
PRINCIPAL IN CHARGE
PROJECT TEAM
REVISIONS
PROJECT NAME
SHEET TITLE
PROJECT NO.
SHEET NUMBER
ISSUE FOR
ISSUE DATE
B
1 2 3 4 5 6 7
A
C
D
E
F
410 Blackwell Street, Suite 10
Durham, NC 27701
T: 919.474.2500
10/06/2017
10/6/2017 3:53:10 PM C:\Users\carl.schuett\Documents\513.7505.00_CU_WrestlingExpansion_S-16_carl.schuett.rvt513.7505.00
10/06/2017
S1.0.2
CONVOCATION AREA C
ROOF FRAMING PLAN
Campbell Convocation
Center Wrestling
Department Renovation
and Expansion
BID/PERMIT SET
Rob Klinedinst
Katie Buckman
David Blankfard, PE, SE
3/16" = 1'-0"S1.0.2
1A CONVOCATION AREA C ROOF FRAMING PLAN
ADDITION
NOT TO SCALE
EXISTING BUILDING
KEY PLAN
NO. REASON DATE
SEE ARCHOPNGMASONRY LINTEL, SEE
PLAN AND SCHD FOR
LOCATIONS, SIZE AND
REINF
U-BLOCK BOND BEAM w/ (2)
#5 UNDER OPNG, FILL w/
GROUT, SEE NOTE 2-A
VERT REINF BEYOND
NOTES:
1.BRICK VENEER NOT SHOWN FOR CLARITY.
2.SEE */S*** FOR LOOSE LINTEL WHERE REQUIRED AT
OPENINGS IN BRICK VENEER.
REINF, SEE OTHER
DETAILS (FILL BLOCK
CELLS w/ GROUT AT REINF)
CONT KNOCK-OUT
BLOCK BOND BEAM w/ (2)
#5 CONT FILLED w/ CONC,
CONT ABOVE STEEL
LINTEL, SEE NOTE 2-A
STEEL LINTEL, SEE
PLAN AND SCHD
CMU SOAPS, EA SIDE
5/8"Ø x 6" HD STUD
AT 24" OC (2 MIN),
SHOP WELDED
SEE ARCHOPNGU-BLOCK BOND BEAM w/ (2)
#5 UNDER OPNG, FILL w/
GROUT, SEE NOTE 2-A
VERT REINF BEYOND
2'-0" MIN, TYP
U-BLOCK BOND BEAM;
SEE LINTEL SCHD FOR
REINF FILL w/ GROUT
VERT REINF IN WALL AT
OPNG, SEE NOTE 1-B;
FILL BLOCK CELLS w/
GROUT FULL HEIGHT
AT REBAR
OPNG
2'-0" MIN, TYP
STEEL LINTEL AND PL,
SEE PLAN AND SCHD
FILL BLOCK CELLS
FULL HEIGHT UNDER
BRG, UNO
OPNG
8" MIN
(1) #5 CTRD IN WALL AT
OPNG, FILL BLOCK CELLS w/
GROUT FULL HEIGHT AT
REBAR; SEE NOTE 1-B
CONT 'KNOCK-OUT' BLOCK
BOND BEAM w/ (2) #5 CONT
FILLED w/ CONC; CONT
ABOVE STEEL LINTEL, SEE
NOTE 2-A
NOT AT CONTROL JOINT
SEE LINTEL SCHD
FOR SIZE AND
REINF
AT CONTROL JOINT
GROUT SOLID
24" DEEP x16" WIDE
ADDL VERT WALL
REINF
BRG
8"48 BAR ØJAMB VERT REINFOFFSET & LAPBRG
8"
NOTE:
FOR ADDL INFORMATION
SEE "NOT AT CONTROL
JOINT"
NOTE:
VENEER MASONRY AND SHELF
ANGLES NOT SHOWN FOR CLARITY
SECTION AT MASONRY LINTEL
TOP REINF, SEE
LINTEL SCHD
TYP VERT REINF MOW
(IF SPACING IS LESS
THAN CLEAR SPAN)
BOTT REINF, SEE
LINTEL SCHD
SEE ARCH
B/LINTEL SEE SCHDDW
MASONRY CJ
5/8"Ø x6" TALL HD
STUDS AT 24" OC
BEAM, SEE SCHD
3/8" PLATE
SECTION AT STEEL LINTEL
CMU SOAP ES
ARCH
SEE 3/16 2-12
3/16 2-12
ADDL VERT
WALL
REINF FULL
HEIGHT
L1
LINTEL SCHEDULE
MARK D
L2
8"
16"
W
12"
12"
REINF
(2) #5
(2) #5 T&B
STEEL
-
-
NOTES:
1.ALL MASONRY BOND BEAMS TO BE FILLED WITH 3000 PSI PEA GRAVEL CONCRETE GROUT.
2.PROVIDE 2'-0" BEARING OVER MASONRY WHERE POSSIBLE (STD 90° HK IF < 2'-0" AVAILABLE).
3.PROVIDE 8" DEEP BOND BEAM w/ (2) #5 BARS FOR LINTELS NON-LOAD BEARING WALLS, SEE
ARCHITECTURAL DRAWINGS FOR LOCATIONS.
L3 24" 12"
PLATE
-
-
L4 - - - W8x18 3/8"
(2) #7 T&B
L5 - - - W8x18 -
JAMB BLOCK, TYP(1) #5 VERT, UNO
VENEER, SEE ARCHFILL BLOCK CELLS w/
GROUT FULL HEIGHT
AT REBAR CONTROL JOINT, SEE
ARCH FOR LOCATIONS
CORNERINTERSECTION
OPENING - WALL TERMINATION
VERT WALL REINF
CENTERED IN CELL,
TYP
VERT WALL REINF
CENTERED IN CELL,
TYP
VERT WALL REINF
CENTERED IN CELL,
TYP
PLAN AT CORNERPLAN AT INTERSECTION
(2) ADDL CORNER BARS AS SHOWN,
SAME SIZE AS CONT REINF
TYP30" LAP0" TYP
TYP
30" LAP
CONT BOND BEAM REINF
0" TYP
SEE PLAN
FFE
MINIMUM SEISMIC REINFORCING AT ALL MASONRY WALLS NOTES:
1.ALL MASONRY WALLS SHALL BE VERTICALLY REINFORCED CONTINUOUSLY FROM SUPPORT TO SUPPORT:
A)AT EACH CORNER
B)AT EACH SIDE OF EACH OPENING
C)AT WALL ENDS
WALLS SHALL BE REINFORCED WITH #5 BARS AT THESE LOCATIONS UNLESS OTHERWISE NOTED IN OTHER
SECTIONS AND DETAILS.
2.HORIZONTAL BOND BEAMS REINFORCED AS NOTED IN SECTIONS OR LINTEL SCHEDULE SHALL BE FURNISHED:
A)AT THE TOP AND BOTTOM OF ALL WALL OPENINGS AND SHALL EXTEND NOT LESS THAN 2'-0" PAST THE
FACE OF OPENING OR STEEL LINTEL BEARING.
B)CONTINUOUSLY AT STRUCTURALLY CONNECTED ROOF AND FLOOR LEVELS AND AT THE TOP OF ALL
WALLS.
3.ALL VERITCAL BARS SHALL BE GROUTED IN 5'-0" MAX LIFTS.
4.WHERE DETAILS SHOWN ON OTHER SHEETS NOTE REINFORCING OF GREATER SIZE AND/OR CLOSER SPACING,
THE REINFORCING REQUIREMENT IN SAID DETAIL SHALL GOVERN. THE SEISMIC REINFORCING NOTED AT WALL
OPENINGS, CORNERS AND ENDS SHALL BE IN ADDTION TO REINFORCING NOTED IN OTHER DETAILS.
5.PROVIDE CONTINUOUS HORIZONTAL JOINT REINFORCEMENT AT 16"OC, MAX VERTICAL SPACING.
SEE ARCHITECTURAL DRAWINGS AND SPECIFICATIONS.
6.SEE PLANS AND DETAILS FOR WALL REINFORCING.
7.WALL CONTROL JOINTS IN CMU AND BRICK VENEER TO BE LOCATED PER ARCHITECTURAL DRAWINGS AND AT
30'-0" OC MAX.
DWL ALL BARS TO
FTG/GRADE BEAM OR
THICKENED SLAB
CONT BOND BEAM AT T/WALL,
ALL ROOF/FLOOR LEVELS, AND
AS INDICATED
WALL CONTROL JOINT WALL REINF,
SEE NOTE 6
SEE NOTE 1-A
OPNG
OPNG
OPNG
T/WALL
1C
S2.0.1
S2.0.1
3C
1B
S2.0.1
2C
S2.0.1 S2.0.1
4C1" TYPBOND BEAM REINF AT T/WALL, ROOF, AND FLOOR
LEVELS TO BE CONT THROUGH CONTROL JOINTS
MECH OPNG
1/4"x2" RIGID STEEL
ANCHORS AT 4'-0" OC OR
INTERLOCKING COURSES
2"32"
2"
GROUT WALL SOLID
BELOW GRADE
SEE PLAN
T/FTG
MASONRY VENEER LOOSE
LINTEL SCHEDULE
MAX CLEAR SPAN LINTEL ANGLE
0' - 5' -0"L4x4x3/8
5' -1" - 8' -0"L6x4x3/8 (LLV)
NOTES:
1. USE THIS SCHEDULE AT OPENINGS IN MASONRY VENEER WHERE LINTELS ARE NOT INDICATED ON PLANS OR DETAILS.
2. BEAR LINTEL ANGLES 8" MINIMUM ON MASONRY EACH END.
3. ALL EXTERIOR LINTELS TO BE HOT-DIPPED GALVANIZED.
4. SEE ARCHITECTURAL DRAWINGS FOR OPENING LOCATIONS AND DIMENSIONS.
MASONRY WALL REINF,
SEE OTHER DETAILS
1/4" CLOSURE PL
LOOSE LINTEL, SEE
SCHD, BEAR 8" ON
MASONRY EA END
8' -1" - 10' -0"
10' -1" - 13' -4"
L7x4x3/8 (LLV)
L8x4x1/2 (LLV)
SEE ARCH
1/2" MAX
SEE ARCHROUGH OPNG3/16 2-12
BOND BEAM
LINTEL
MP1
(2) #7 TO T/WALL, DWL
TO FTG, GROUT SOLID
1' - 4"EQEQ2'-6" MIN
LAP 48 BAR Ø
MIN
2'-0" LAP
BOND BEAM REINF
Z-BAR TO MATCH
BOND BEAM REINF
w w w . l i t t l e o n l i n e . c o m
This drawing and the design shown are the property
of Little Diversified Architectural Consulting. The
reproduction, copying or other use of this drawing
without their written consent is prohibited and any
infringement will be subject to legal action.
Little 2017c
PROJECT MANAGER
DESIGN TEAM
PRINCIPAL IN CHARGE
PROJECT TEAM
REVISIONS
PROJECT NAME
SHEET TITLE
PROJECT NO.
SHEET NUMBER
ISSUE FOR
ISSUE DATE
B
1 2 3 4 5 6 7
A
C
D
E
F
410 Blackwell Street, Suite 10
Durham, NC 27701
T: 919.474.2500
10/06/2017
10/6/2017 3:53:17 PM C:\Users\carl.schuett\Documents\513.7505.00_CU_WrestlingExpansion_S-16_carl.schuett.rvt513.7505.00
10/06/2017
S2.0.1
MASONRY DETAILS
Campbell Convocation
Center Wrestling
Department Renovation
and Expansion
BID/PERMIT SET
Rob Klinedinst
Katie Buckman
David Blankfard, PE, SE
3/4" = 1'-0"S2.0.1
1C MASONRY LINTEL SECTION
3/4" = 1'-0"S2.0.1
2C STEEL INTEL SECTION
3/4" = 1'-0"S2.0.1
3C MASONRY LINTEL ELEVATION
3/4" = 1'-0"S2.0.1
4C STEEL LINTEL ELEVATION
3/4" = 1'-0"S2.0.1
1A TYPICAL LINTEL
NOT TO SCALES2.0.1
1B CMU CONTROL JOINT
NOT TO SCALES2.0.1
6C TYPICAL CMU WALL REINFORCING
NOT TO SCALES2.0.1
6D TYPICAL BOND BEAM CORNERS AND INTERSECTIONS
NOT TO SCALES2.0.1
1D TYPICAL CMU WALL REINFORCING DIAGRAM
NOT TO SCALES2.0.1
5A MASONRY VENEER LOOSE LINTEL SCHEDULE
3/4" = 1'-0"S2.0.1
2B MASONRY PILASTER DETAIL
3/4" = 1'-0"S2.0.1
6B TYPICAL STEP IN CMU BOND BEAM
NO. REASON DATE
LEVEL 1
0"
1' - 3"
3' - 6"
SEE PLAN
T/FTG
GROUT SOLID
BELOW GRADE
SOG, SEE PLAN
1/2" PJF MATERIAL
12" CMU w/ #5 AT 32" OC MOW
DWLS w/ STD 90° HK TO MATCH
VERT REINF SIZE AND SPACING
1' - 4"FINISH GRADE,
SEE CIVIL
8" CMU BELOW
GRADE, GROUT SOLID
BRICK VENEER w/
TIES, SEE ARCH
4" CMU w/ TIES
(5) #5 CONT
#5 x3'-0" LG AT 32" OC
FOM, SEE PLAN
MIN LAP48 xBAR ØCOMPACTED AGGREGATE
PIERS ENGINEERED BY FDN
CONTRACTOR AS REQD TO
PROVIDE AN ALLOWABLE
UNIFORM BRG CAPACITY OF
5500 PSF AT BOTTOF FTG
CONN BY SUPPLIER
CAST STONE,
SEE ARCH
NOTES:
1.AT SIMILAR, NO EXTERIOR BIRCK VENEER.
SEE PLAN
FFE
5/8"Ø x 1'-6" SMOOTH DWL AT 16" OC MAX;
COAT ONE END w/ GREASE TO PREVENT
BOND; CTR IN SLAB
REINF, SEE PLAN
PREVENT BOND
VAPOR BARRIER
PLANSEENOTES:
1. DO NOT RUN WWF THROUGH CONSTRUCTION JOINT.
SLAB REINF
SUPPORTS CLR1 1/2"SOG, SEE PLAN
TSEE PLAN
FFE
SAW CUT CJ 1/8" WIDE MAX
REINF, SEE PLANVAPOR BARRIER
PLANSEENOTES:
1. CUT EVERY OTHER WIRE WHERE CONTRACTION JOINTS ARE TO BE CUT.
2. SAW CUT SLAB WITHIN 8 HOURS OF CONCRETE POUR.
SLAB REINF
SUPPORTS CLR1 1/2"T/4SOG, SEE PLAN
TOR LESS
1' - 0"
EXIST CONC
SLAB
EXIST VAPOR
BARRIER
PREPARE EXIST CONC AND APPLY
BONDING AGENT, EUCOWELD BY
EUCLID CHEMICAL, THEN POUR NEW
CONC SLAB TO MATCH THICKNESS OF
EXIST (4" MIN)
NEW 15 MIL VAPOR BARRIER,
LAP w/ EXIST
EXIST VAPOR
BARRIER
NEW 15 MIL VAPOR BARRIER,
LAP w/ EXIST
POUR NEW CONC SLAB
TO MATCH THICKNESS
OF EXIST (4" MIN), REINF
w/ WWF 6x6 W2.9xW2.9
5/8"Ø x1'-6" SMOOTH DWL
AT 16" OC, DRILL AND SET
IN ADH w/ HILTI HIT-HY 200,
4" EMBED, STAGGER
AROUND PERIMETER
PREVENT BOND
5/8"Ø x1'-6" LG SMOOTH DWL AT
16" OC MAX, DRILL INTO EXIST
SLAB w/ HILTI HIT-HY 200 AND SET
IN ADH, 6" EMBED; COAT END IN
NEW SLAB w/ GREASE TO
PREVENT BOND, CTR IN SLAB
OVER 8'-0"
EXIST DRAINAGE FILL
EXIST CONC
SLAB
EXIST DRAINAGE FILL
EXIST VAPOR
BARRIER
NEW 15 MIL VAPOR BARRIER,
LAP w/ EXIST
EXIST DRAINAGE FILL
EXIST CONC
SLAB
POUR NEW CONC SLAB
TO MATCH THICKNESS OF
EXIST (4" MIN), REINF w/
WWF 6x6 W2.9xW2.9
NOTES:
1. PROVIDE A CONTRACTION JOINT AT ANY EXISTING CONTRACTION JOINT IN THE ADJACENT SLAB AND AT 15'-0" OC MAX IN ANY DIRECTION
3"PROVIDE CONT 2x4
KEY FULL WIDTH OF
FTG, CTR ON FTG
DEPTH (2x6 KEY FOR
FTG DEPTH >14")
SEE PLAN
T/FTG
(2) #5 x4'-0" MID-DEPTH OF
SLAB CTRD ON CORNER
NOTES:
1. WHERE SLAB CONTRACTION JOINT INTERSECTS RE-ENTRANT CORNER ADDED SLAB
REINFORCING IS NOT REQUIRED. SEE PLAN FOR JOINT LOCATIONS.
EOS, SEE PLAN
LEVEL 1
0"
SOG, SEE PLAN
T/EXIST FTG
DEMO EXIST CMU
WALL (1) COURSE
BELOW FFE (8" MIN)
EXIST SOG
SMOOTH DWL,
SEE /5E S3.0.1
NEW TURNED DOWN SLAB
EXIST FDN WALL
EXIST FDN
LEVEL 1
0"
SEE PLAN
T/FTG
SOG, SEE PLAN
(5) #5 CONT
#5 x3'-0" LG
AT 32" OC
EXT SLAB,
SEE CIVIL
5/8"Ø x1'-6" SMOOTH
GREASED DWL AT
16" OC AT DOOR
CTRD IN SLAB
STOREFRONT OR
DOOR, SEE ARCH
1/2" PJF MATERIAL
#5 x4'-0" w/ 180° HK AT 16" OC
(2) #5 CONT
3' - 6"1' - 4"1' - 3"COMPACTED AGGREGATE
PIERS ENGINEERED BY FDN
CONTRACTOR AS REQD TO
PROVIDE AN ALLOWABLE
UNIFORM BRG CAPACITY OF
5500 PSF AT BOTT OF FTG8"12" CMU w/ #5 AT 32" OC MOW
LEVEL 1
0"
SEE PLAN
T/FTG
GROUT SOLID
BELOW GRADE
SOG, SEE PLAN
1/2" PJF MATERIAL
12" CMU w/ #5 AT 32" OC MOW
DWLS w/ STD 90° HK TO MATCH
VERT REINF SIZE AND SPACING
FINISH GRADE,
SEE CIVIL
8" CMU BELOW
GRADE, GROUT SOLID
BRICK VENEER w/
TIES, SEE ARCH
(5) #5 CONT
#5 x3'-0" LG AT 32" OC
NOTES:
1. SEE FOR DETAILS NOT NOTED HERE./1E S3.0.1 1' - 4"1' - 3"
3' - 6"
8" DEEP BOND BEAM w/ (2) #5 CONT;
SEE FOR ADDL DETAILS/1D S2.0.1
WINDOW, SEE ARCH
MIN LAP48 xBAR ØCOMPACTED AGGREGATE
PIERS ENGINEERED BY FDN
CONTRACTOR AS REQD TO
PROVIDE AN ALLOWABLE
UNIFORM BRG CAPACITY OF
5500 PSF AT BOTT OF FTG
4" CMU w/ TIES
CAST STONE, SEE
ARCH
CONN BY SUPPLIER
CONN BY SUPPLIER
SEE ARCH
T/WALL
LEVEL 1
0"
SEE PLAN
T/FTG
GROUT SOLID
BELOW GRADE
SOG, SEE PLAN
1/2" PJF MATERIAL
FINISH GRADE,
SEE CIVIL
BASE PL, SEE
BRICK VENEER w/
TIES, SEE ARCH
(5) #5 CONT
(5) #5 x3'-0" LG AT 12" OC
CTRD UNDER COL 1' - 4"3' - 6"
COL, SEE PLAN
8" CMU BELOW
GRADE, GROUT SOLID ENCASE BASE PL AND
ANCHOR RODS w/ CONC
(3" MIN COVER)
CMU FDN WALL, CUT BLOCK
AS REQD AND ENCASE COL,
GROUT SOLID
CL
COMPACTED AGGREGATE PIERS
ENGINEERED BY FDN CONTRACTOR
AS REQD TO PROVIDE AN
ALLOWABLE UNIFORM BRG CAPACITY
OF 5500 PSF AT BOTT OF FTG
4" CMU w/ TIES
8"
/3A S3.0.1
1' - 0"1' - 2"C11"CC 9"C
6"6"7"7"5/16
TYPE 1 PROJECTION
EMBEDMENT NON-SHRINK GROUT
THICKNESS
TOP OF FDN,
PIER, OR WALL
ANCHOR RODS w/
LEVELING NUTS
3/16TACK WELD
3/16" x 3" x 3"
PL WASHER
NOTES:
1. SEE GENERAL NOTES FOR ANCHOR ROD MATERIAL.
PL WASHER T&B,
SEE SCHD
ANCHOR ROD
SCHEDULE
BOLT SIZE 3/4"Ø
DIMENSION "C"
SQUARE PL WASHER SIZE
GROUT THICKNESS
1 1/2"
1/4" x 2"
2"
EMBEDMENT 9"
PROJECTION 6"
3/16
LAP 48 BAR Ø TYP
NOTE:
1. GENERAL CONTRACTOR TO COORDINATE / VERIFY THE LOCATION OF
FOOTING STEPS WITH THE FINISHED GRADING PLAN.
2. PROVIDE 1'-4" MINIMUM COVER ABOVE TOP OF FOOTING.
3. ADDED BARS TO BE THE SAME SIZE AND QUANTITY AS CONTINOUS BARS.
CONT FTG BARS
STEP2 x STEP MIN
1' - 6"STEP/2
LEVEL 1
0"
EXIST 5" SOG
8" CMU w/ #5V AT 48" OC
MOW, SEE FOR
ADDL DETAILS
/1D S2.0.1
MIN LAP48 xBARØDWL TO MATCH VERT REINF SIZE
AND SPACING; DRILL AND SET IN
ADH w/ HILTI HIT-HY 200, 3" EMBED
w w w . l i t t l e o n l i n e . c o m
This drawing and the design shown are the property
of Little Diversified Architectural Consulting. The
reproduction, copying or other use of this drawing
without their written consent is prohibited and any
infringement will be subject to legal action.
Little 2017c
PROJECT MANAGER
DESIGN TEAM
PRINCIPAL IN CHARGE
PROJECT TEAM
REVISIONS
PROJECT NAME
SHEET TITLE
PROJECT NO.
SHEET NUMBER
ISSUE FOR
ISSUE DATE
B
1 2 3 4 5 6 7
A
C
D
E
F
410 Blackwell Street, Suite 10
Durham, NC 27701
T: 919.474.2500
10/06/2017
10/6/2017 3:53:26 PM C:\Users\carl.schuett\Documents\513.7505.00_CU_WrestlingExpansion_S-16_carl.schuett.rvt513.7505.00
10/06/2017
S3.0.1
FOUNDATION DETAILS
Campbell Convocation
Center Wrestling
Department Renovation
and Expansion
BID/PERMIT SET
Rob Klinedinst
Katie Buckman
David Blankfard, PE, SE
3/4" = 1'-0"S3.0.1
1E SECTION
3/4" = 1'-0"S3.0.1
3E SLAB ON GRADE CONSTRUCTION JOINT DETAIL
3/4" = 1'-0"S3.0.1
3F SLAB ON GRADE CONTRACTION JOINT DETAIL
NOT TO SCALES3.0.1
5E SLAB ON GRADE REPAIR DETAILS
3/4" = 1'-0"S3.0.1
5F CONTINUOUS FOOTING CONSTRUCTION JOINT DETAIL
NOT TO SCALES3.0.1
3C SLAB RE-ENTRANT CORNER REINFORCING
3/4" = 1'-0"S3.0.1
5C SECTION
3/4" = 1'-0"S3.0.1
6C SECTION
3/4" = 1'-0"S3.0.1
1C SECTION
3/4" = 1'-0"S3.0.1
1A SECTION
NOT TO SCALES3.0.1
3A BASE PLATE AND ANCHOR BOLT SCHEDULE
3/4" = 1'-0"S3.0.1
4A TYPICAL FOOTING STEP DETAIL
3/4" = 1'-0"S3.0.1
6A TYPICAL INTERIOR MASONRY WALL DETAIL
NO. REASON DATE
SEE ARCH
T/WALL
SEE PLAN
JOIST BRG
12" CMU w/ #5 AT 32" OC MOW
8" DEEP BOND BEAM w/ (2) #5 CONT
8" DEEP BOND BEAM
w/ (2) #5 CONT
BRICK VENEER w/ TIES,
SEE ARCH
CAST STONE CAP,
SEE ARCH
ROOF DECK, SEE PLAN
JOIST, SEE PLAN
1/8 3
1/8 3TYP AT EA
JOIST, UNO
PL 3/8"x6"x1'-0" w/ (2)
1/2"Ø x 4" LG HD
STUDS AT EA JOIST
CONN BY
SUPPLIER
NOTES:
1.SEE FOR ADDITIONAL CMU WALL REINFORCING DETAILS./1D S2.0.1
ROOFING, SEE ARCH
3/16
JOIST POCKET
CONT L3 1/2x3 1/2x1/4
(GALV) w/ 3/4"Ø HILTI KB-3
EXP ANCHORS AT 16" OC
(EMBED = 4 3/4")
SEE ARCH
T/WALL
VARIES
T/JOIST
12" CMU w/ #5 AT
32" OC MOW
8" DEEP BOND BEAM w/ (2) #5 CONT
8" DEEP BOND BEAM
w/ (2) #5 CONT AT
ROOF LINE
BRICK VENEER w/ TIES,
SEE ARCH
CAST STONE CAP,
SEE ARCH
WINDOW, SEE ARCH
CONN BY SUPPLIER
ROOF DECK, SEE PLANCONT L3 1/2x3 1/2x1/4
(GALV) w/ 3/4"Ø HILTI KB-3
EXP ANCHORS AT 16" OC
(EMBED = 4 3/4")
JOIST BRIDGING PER SJI
GALV BEAM, SEE PLAN
JOIST, SEE PLAN
8" DEEP BOND BEAM
w/ (2) #5 CONT ABOVE
STEEL LINTEL
PL 3/8"x1'-7 x CONT (GALV), SEE
FOR DETAILS NOT NOTED
ROOFING, SEE ARCH
MIN LAP48 x BAR ØL3x3x1/4 w/ 3/4"Ø HILTI KB-3 EXP
ANCHORS AT 8" OC INTO
GROUTED CELLS AT BRIDGING
LINE (EMBED = 4 3/4")
#5 x3'-0" DBA AT 32" OC
CONN BY
SUPPLIER
NOTES:
1.SEE FOR ADDITIONAL CMU WALL REINFORCING DETAILS.
2.SEE FOR BOND BEAM STEP DETAIL.
/1D S2.0.1
/6B S2.0.1
/1A S2.0.1
3/16 TYP
3/16 2
3/16 2 TYP
L6x6x5/16 x0'-6", TYP
L5x3x1/4 (LLV) 4 SIDES OF OPNG,
SECURE ROOF DECK TO ANGLE w/
5/8" PUDDLE WELDS AT 6" OC MAX
DECK CANTILEVER = 6"
VERIFY ROOF OPNG DIM
w/ ARCH AND MEP DWGSVERIFY ROOF OPNG DIMSw/ ARCH AND MEP DWGSNOTES:
1. FRAME ALL ROOF OPENINGS GREATER THAN 12".
2. SEE ARCHITECTURAL AND MECHANICAL DRAWINGS FOR ROOF OPENING LOCATIONS.
PROVIDE JOIST WEB REINF AT
OPNG FRAME BRG LOCATIONS
ON JOIST, SEE
CL ROOF JOIST OR BEAM, SEE PLAN
DECK SPANSIDE LAP CONNECTORS
PER JOIST SPACING
COVERAGE
ATTACHMENT AT 6" OC
ALONG EDGE OF DIAPHRAGM
ATTACHMENT PATTERN AT SUPPORTSEDGE SUPPORTSUPPORT
SUPPORT
SUPPORT
EDGE SUPPORT
ATTACHMENT
PATTERN
DECKING ATTACHMENT
DECK TYPE.........B
DECK GAGE......20 GA
DECK FINISH.......GALVANIZED
PROVIDE 36/4 ATTACHMENT PATTERN AT ALL SUPPORTS
AND AT ENDS WITH 5/8"Ø PUDDLE WELDS
PROVIDE (4) SIDELAP CONNECTORS (AT 12" OC) PER DECK
SPAN BETWEEN SUPPORTS WITH #10 TEK SCREWS
PROVIDE 5/8"Ø PUDDLE WELDS AT 6" OC AT EDGE
SUPPORTS
NOTE: CONTRACTOR OPTION TO USE HILTI MECHANICAL
FASTENERS. WHERE WELDS ARE INDICATED,
CONTRACTOR MUST PROVIDE SUBMITTAL SHOWING
EQUIVALENT CAPACITY. USE HILTI MECHANICAL DECK
FASTENER X-HSN24 WHERE THE STEEL BASE MATERIAL
THICKNESS IS 1/8"<tf<3/8" OR X-ENP-19 L15 WHERE THE
STEEL BASE MATERIAL THICKNESS IS tf>1/4". THE ACTUAL
BASE MATERIAL THICKNESS SHALL BE VERIFIED ON-SITE
PRIOR TO INSTALLING THE FASTENERS.
36/4 1 1/2"36'' COVERAGE
Ip = 0.201 IN /FT
In =0.222 IN /FT
Sp =0.234 IN³/FT
Fy =33 KSI
4
4
NEW MECH UNIT, SEE MECH
DWGS
NEW ROOF CURB, COORD w/
MECH SUPPLIER
JOIST, SEE PLAN
ROOF DECK, SEE
PLAN
L5x3x1/4 (LLV) UNDER ROOF
CURB, COORD EXACT
LOCATION w/ MECH DWGS
3/16 4
3/16 TYP
SECURE MECH UNIT TO ROOF
CURB PER MFR SPECIFICATIONS
1/2"Ø A307 GR A THRU BOLTS AT
EA CORNER AND 2'-0" OC MAX
(3 BOLTS EA SIDE MIN) PROVIDE
WOOD BLOCKING IN DECK FLUTE
AT BOLT FOR CURB BRG
NOTES:
1. ALL CONNECTIONS OF MECHANICAL EQUIPMENT TO ROOF CURB, RAILS, OR STANDS TO BE DESIGNED BY THE
EQUIPMENT SUPPLIER.
2. WHERE CURB IS PARALLEL TO DECK, PROVIDE WOOD BLOCKING IN DECK FLUTE AT BOLT FOR CURB BEARING.
3. PROVIDE L5x3x1/4 (LLV) FRAME AROUND OPENING IN ROOF DECK FOR DUCT PENETRATION SIM TO . ATTACH
ROOF DECK TO ANGLE w/ 5/8" PUDDLE WELDS AT 6" OC. MAXIMUM DECK CANTILEVER = 6"
4. THE MECHANICAL UNIT WEIGHT SHOWN ON THE ROOF FRAMING PLAN INCLUDES THE WEIGHT OF THE UNIT PLUS
ROOF CURB. GC TO VERIFY THAT THE INSTALLED WEIGHT OF THE NEW MECHANICAL UNIT AND ROOF CURB DOES NOT
EXCEED THE WEIGHT SHOWN ON THE DRAWINGS.
L6x6x5/16 x0'-6"
/6E S3.1.1
MATCH EXIST
T/BRICK RELIEF
SEE PLAN
JBE
ROOF DECK, SEE PLAN
ROOFING, SEE ARCH
JOIST, SEE PLAN
EXIST BRICK VENEER
CONT L6x6x3/8 (GALV) w/ 3/4"Ø
THREADED RODS AT 16" OC,
DRILL AND ADH IN GROUT
FILLED CELL w/ HILTI HIT-HY
70 (EMBED = 6 3/4")2"EXIST CMU WALL
L6x6x3/8 x 1'-0" LG w/ (2)
5/8"Ø THREADED RODS,
DRILL AND ADH IN GROUT
FILLED CELL w/ HILTI HIT-
HY 70 (EMBED = 5 5/8")
CONT 3 1/2x3 1/2x1/4
(GALV) w/ HILTI KB-3 EXP
ANCHORS AT 16" OC
(EMBED = 4 3/4")
GROUT SOLID BELOW
BRG PL, SEE
1/8 3
1/8 3
/1E S3.1.2
JOIST POCKET
T/STEEL
16' - 3"
1/4" CAP PL
BRICK VENEER w/
TIES, SEE ARCH
GALV STEEL, SEE PLAN COL, SEE PLAN
5"
L5x3x1/4 x0'-6"
C8, SEE PLAN
L5x3x1/4, FIELD WELD
ALL AROUND TO JOIST
T&B CHORDS
JOIST, SEE PLAN
5"
JOIST, SEE PLAN
3/16
ROOF DECK, SEE PLAN
ROOFING, SEE ARCH
3/16 4
3/16 4
3/16 4
3/16 4
1/4" CONN PL, TYP
L3 1/2x3 1/2x1/4
3/16 2
3/16 2
TYP
SEE PLAN
T/STEEL
CMU NOT SHOWN
FOR CLARITY
SEE ARCH
T/WALL
SEE PLAN
JOIST BRG
12" CMU w/ #5 AT
32" OC MOW
8" DEEP BOND BEAM w/ (2) #5 CONT
BRICK VENEER w/ TIES,
SEE ARCH
CAST STONE CAP,
SEE ARCH
WINDOW, SEE ARCH
CONN BY SUPPLIER
ROOF DECK, SEE PLAN
CONT L3 1/2x3 1/2x1/4 (GALV) w/ 3/4"Ø
HILTI KB-3 EXP ANCHORS AT 16" OC
(EMBED = 4 3/4")
JOIST, SEE PLAN
BOND BEAM w/ (2) #5
CONT
ROOFING, SEE ARCH
LOOSE LINTEL,
SEE SCHD
NOTES:
1.SEE FOR ADDITIONAL CMU WALL REINFORCING DETAILS.
2.NO WINDOW AT SIM SECTION.
/1D S2.0.1
CONN BY SUPPLIER
SEE FOR ATTACHMENT/3E S3.1.1
BRIDGING PER SJI
EXIST CMU WALL
MATCH EXIST
T/BRICK RELIEF
ROOF DECK, SEE PLAN
ROOFING, SEE ARCH
EXIST BRICK VENEER
CONT L6x6x3/8 (GALV) w/ 3/4"Ø
THREADED RODS AT 16" OC,
DRILL AND ADH IN GROUT
FILLED CELL w/ HILTI HIT-HY 70
(EMBED = 6 3/4")2"CONT L3 1/2x3 1/2x1/4
(GALV) w/ 3/4"Ø HILTI
KB-3 EXP ANCHORS AT
16" OC (EMBED = 4 3/4")
SEE PLAN
VARIES
w w w . l i t t l e o n l i n e . c o m
This drawing and the design shown are the property
of Little Diversified Architectural Consulting. The
reproduction, copying or other use of this drawing
without their written consent is prohibited and any
infringement will be subject to legal action.
Little 2017c
PROJECT MANAGER
DESIGN TEAM
PRINCIPAL IN CHARGE
PROJECT TEAM
REVISIONS
PROJECT NAME
SHEET TITLE
PROJECT NO.
SHEET NUMBER
ISSUE FOR
ISSUE DATE
B
1 2 3 4 5 6 7
A
C
D
E
F
410 Blackwell Street, Suite 10
Durham, NC 27701
T: 919.474.2500
10/06/2017
10/6/2017 3:53:34 PM C:\Users\carl.schuett\Documents\513.7505.00_CU_WrestlingExpansion_S-16_carl.schuett.rvt513.7505.00
10/06/2017
S3.1.1
FRAMING DETAILS
Campbell Convocation
Center Wrestling
Department Renovation
and Expansion
BID/PERMIT SET
Rob Klinedinst
Katie Buckman
David Blankfard, PE, SE
3/4" = 1'-0"S3.1.1
1E SECTION
3/4" = 1'-0"S3.1.1
3E SECTION
NOT TO SCALES3.1.1
6E ROOF OPENING PLAN DETAIL
NOT TO SCALES3.1.1
1C PLAN VIEW OF DECK ATTACHMENT
NOT TO SCALES3.1.1
3C ROOF DECK ATTACHMENT SCHEDULE
NOT TO SCALES3.1.1
4E SECTION AT ROOFTOP MECHANICAL UNIT
3/4" = 1'-0"S3.1.1
6C SECTION
3/4" = 1'-0"S3.1.1
1A SECTION
3/4" = 1'-0"S3.1.1
4A SECTION
3/4" = 1'-0"S3.1.1
4C SECTION
NO. REASON DATE
NOTES:
1. EXISTING BRICK VENEER NOT SHOWN FOR CLARITY.
LINTEL, SEE PLAN
AND SCHD
GROUT CMU SOLID UNDER
BRG PL 16" WIDE x 24"
DEEP w/ 3000 PSI PEA
GRAVEL CONC OR GROUT
EA END
EXIST CMU WALL
1/2"Ø x5" HD STUD
AT 24" OC (2 MIN),
SHOP WELDED
BRG PL 3/8x8x0'-8"
w/ (2)1/2"Ø x5" LG
HD STUDS EA END
3/16
3/16
8" MIN BRG
MAX
1/2"
1/4" END PL
EA END
GROUNT SOLID
AROUND LINTEL
2' - 0"MATCH EXIST, VIF
JBE, SEE PLAN
ROOF DECK, SEE PLAN
ROOFING, SEE ARCH
1/8 3
1/8 3
TYP
EXIST ROOF DECK
DEMO EXIST PARAPET TO JBE
LAP NEW ROOF DECK w/ EXIST ROOF
DECK AND PROVIDE SIDE LAP
FASTENERS PER /3C S3.1.1
JOIST, SEE PLAN
EXIST JOIST
EXIST BOND
BEAM, VIF
EXIST CMU
WALL
DESIGN JOIST
SEAT FOR
ROLLOVER
FORCE = XXk
DEMO EXIST
VENEER
BRG PL 3/8x6x1'-0" w/ (2)
5/8"Ø THREADE RODS, DRILL
AND ADH w/ HILTI HIT-HY-70
(EMBED = 5 5/8")1' - 0"3"3"TYP1 1/2"BRG PL
EXIST BEAM
L3x3x1/4 x 1'-0" AT EA
BEAM (TIGHT TO WALL)
NON LOAD-BEARING
CMU WALL
NOTE:
BUILD CMU WALL
WITH 1" CLEAR
AROUND
WALL PERPENDICULAR TO BEAM
PARTITIONS TO UNDERSIDE OF DECK
L4x4x1/4
AT 6'-0" OC
L3x3x1/4 x 1'-0"
(TIGHT TO WALL)
WALL PARALLEL TO JOIST
EXIST
FLOOR SLAB
L6x4x5/16 x 1'-0"(LLV)
AT EA BEAM (TIGHT
TO WALL)
WALL PERPENDICULAR TO JOIST
EXIST
FLOOR SLAB
PARTITIONS STOPPING BELOW BEAM
3/16 2
3/16 2
TYP
3/16 2
3/16 2 TYP
1/8 2
TYP
EXIST
FLOOR SLAB
NON LOAD-BEARING
CMU WALL1" MINEXIST BEAM
NON LOAD-BEARING
CMU WALL
3/16 2
3/16 2
TYP
L4x4x1/4
AT 6'-0" OC
WALL PARALLEL TO JOIST
3/16 2
3/16 2
TYP
3/16 2
TYP
EXIST
FLOOR SLAB
L6x4x5/16 x 1'-0"(LLV) AT EA
L4x4 (TIGHT TO WALL)
NON LOAD-BEARING
CMU WALL3" MAX3" MAX1" MINSEE PLAN
JBE
ROOFING, SEE ARCH
ROOF DECK, SEE PLAN
JOIST, SEE PLAN
BOND BEAM LINTEL,
SEE PLAN AND
SCHD
LOOSE LINTEL, SEE SCHD
BRICK VENEER w/ TIES, SEE ARCH
JOIST, SEE PLAN
8" DEEP BOND
BEAM w/ (2) #5 CONT
BRG PL, SEE
/3E S3.1.2
1/8 3
1/8 3
TYP
w w w . l i t t l e o n l i n e . c o m
This drawing and the design shown are the property
of Little Diversified Architectural Consulting. The
reproduction, copying or other use of this drawing
without their written consent is prohibited and any
infringement will be subject to legal action.
Little 2017c
PROJECT MANAGER
DESIGN TEAM
PRINCIPAL IN CHARGE
PROJECT TEAM
REVISIONS
PROJECT NAME
SHEET TITLE
PROJECT NO.
SHEET NUMBER
ISSUE FOR
ISSUE DATE
B
1 2 3 4 5 6 7
A
C
D
E
F
410 Blackwell Street, Suite 10
Durham, NC 27701
T: 919.474.2500
10/06/2017
10/6/2017 3:53:36 PM C:\Users\carl.schuett\Documents\513.7505.00_CU_WrestlingExpansion_S-16_carl.schuett.rvt513.7505.00
10/06/2017
S3.1.2
FRAMING DETAILS
Campbell Convocation
Center Wrestling
Department Renovation
and Expansion
BID/PERMIT SET
Rob Klinedinst
Katie Buckman
David Blankfard, PE, SE
3/4" = 1'-0"S3.1.2
1E SECTION
3/4" = 1'-0"S3.1.2
3E SECTION
NOT TO SCALES3.1.2
1B TYPICAL NON LOAD-BEARING CMU WALL BRACING
3/4" = 1'-0"S3.1.2
4E SECTION
NO. REASON DATE
VENT THROUGH ROOF - DIAGRAMMATIC (VTR)
SHOCK ARRESTOR (SA)'A'
WATER VALVE BOXWVB
DOMESTIC COLD WATER
DOMESTIC HOT WATER (110°F)
DOMESTIC HOT WATER RECIRCULATING (110°F)
GALLONS PER MINUTEGPM
AIR GAP FITTING
UNION
WALL HYDRANT (WH)
HOSE BIBB (HB)
VENT PIPING
PIPE TURNING DOWN
PIPE TURNING UP
NATURAL GASG
AMERICANS WITH DISABILITY ACT
SUMP PUMP DISCHARGE
MIXING VALVE
ADA
SPD
MV
ACCESS PANEL
ABOVE FINISHED FLOOR
ABOVE FINISHED GRADE
AP
AFF
AFG
RECIRCULATION PUMP
GAS WATER HEATER
RP
GWH-1
WASTE STACK VENT
SHOCK ABSORBER AND SIZE
WSV
SA 'A'
WALL CLEANOUTWCO
CLEANOUT PLUGCOP
AUTOMATIC AIR VENT
VALVES AND ACCESSORIES
AUTOMATIC FLOW CONTROL VALVE
BACKFLOW PREVENTER (BFP)
BALL VALVE
BUTTERFLY VALVE
CAPPED PIPE
CHECK VALVE
CONCENTRIC REDUCER
DIRECTION OF FLOW
ECCENTRIC REDUCER
FLANGED CONNECTION
FLEXIBLE CONNECTION
FLOW METER
GATE VALVE
MANUAL AIR VENT
METERED BALANCING VALVE
W/PRESSURE TAPS
GAS COCK
PIPE SLEEVE
PRESSURE REDUCING VALVE
PRESSURE RELIEF VALVE
PRESSURE GAUGE WITH GAUGE COCK
SQUARE HEAD COCK
STRAINER
STRAINER W/BLOW DOWN VALVE
THERMOMETER
VACUUM BREAKER
ABBREVIATIONSGENERAL
LEGEND
ACCESS DOORAD
ARCHITECTURALARCH
DIAMETERDIA
DRAWINGDWG
GAUGEGA
MISCELLANEOUSMISC
TYPICALTYP
UNLESS OTHERWISE NOTEDUON
GALVANIZEDGALV
SANITARY SEWER
FLOOR DRAIN WITH DEEP SEAL P-TRAPFD
CLEANOUT, YARD TYPEYCO
CLEANOUT, FLOOR TYPEFCO
CLEANOUTCO
BRANCH SIDE CONNECTION
BRANCH TOP CONNECTION
BRANCH BOTTOM CONNECTION
FINISHED FLOORFF
HOSE BIBBHB
FLOOR SINKFS
VENT THRU ROOFVTR
INVERT ELEVATIONI.E.
SOLENOID VALVE.
LIMIT OF DEMOLITION WORK
CONNECT TO EXISTING
FLOOR DRAIN WITH TRAP PRIMERFD
TP
VENT STACKVS
WASTE STACKWS
GREASE DRAINAGE
ACID WASTEAS
GS
SS
GLOBE VALVE
DOMESTIC HOT WATER (140°F)
DOMESTIC HOT WATER RECIRCULATING (140°F)HWR
110°
110°
DRAINAGE FIXTURE UNITSDFU
COLD WATER SUPPLY
FIXTURE UNITSCWSFU
HOT WATER SUPPLY
FIXTURE UNITSHWSFU
FLOOR DRAINFD
GENERAL NOTES
1.OPENINGS THRU WALLS, FLOORS AND ROOFS SHALL BE FLASHED AND SEALED WATER TIGHT. PENETRATIONS THROUGH SMOKE OR FIRE-RATED WALLS
AND/OR PARTITIONS SHALL BE SEALED TO MAINTAIN RATING PER ASTM E-814 AND BUILDING CODE REQUIREMENTS.
2.INTERRUPTIONS OF SERVICES SHALL BE COORDINATED WITH THE OWNER AT LEAST 48 HOURS IN ADVANCE OF THE WORK BEING PERFORMED.
DISRUPTION TIME SHALL BE KEPT TO A MINIMUM.
3.UNLESS OTHERWISE INDICATED, ALL PIPING SHALL BE RUN IN CONCEALED SPACES IN WALLS, IN CHASES OR BETWEEN CEILINGS AND INSULATION ABOVE.
PIPES SHALL BE RUN AT RIGHT ANGLES OR PARALLEL LINES WITH BUILDING WALLS AND ROUTED WITH STRUCTURAL MEMBERS IN EXPOSED AREAS.
PLUMBING SHALL COORDINATE WITH MECHANICAL DUCTWORK IN ALL CHASES. SUPPORT ALL INTERIOR PIPING FROM BUILDING STRUCTURE BY MEANS OF
PIPE STANDS, HANGERS OR INSERTS TO MAINTAIN REQUIRED GRADING AND PITCHING OF LINES, TO PREVENT VIBRATION AND TO SECURE PIPING IN PLACE.
SOIL WASTE AND VENT STACKS SHALL BE SUPPORTED AT THE BASE BY MEANS OF PIERS OR HEAVY-DUTY RISER CLAMPS CLOSE TO THE BOTTOM OF RISERS
AND SECURED AT EACH FLOOR BY MEANS OF HEAVY-DUTY IRON RISER CLAMPS. PROTECT COPPER PIPING AGAINST CONTACT WITH MASONRY OR DISSIMILAR
METALS. COPPER PIPING HANGERS, SUPPORTS, ANCHORS AND CLIPS SHALL BE COPPER OR COPPER PLATED. PROVIDE CLEANOUTS AT THE BASE OF EACH
WASTE OR INTERIOR STORM DRAINAGE STACK. WCO AND COP AT BASE OF STACKS SHALL BE 12" TO 15" AFF. FLAT WALL CLEANOUT COVERS SHALL BE
FLUSH WITH FINISHED WALL SURFACE. DEEP COVERS ARE NOT ACCEPTABLE. EXPOSED PIPING SHALL BE LABELED WITH SERVICE AND DIRECTION OF FLOW
EVERY 20 FEET, AND IN EACH ROOM. ALL VALVES SHALL BE TAGGED. EXPOSED PIPING CONNECTIONS IN OCCUPIED SPACES SHALL BE CHROME PLATED.
4.IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO VERIFY THE ITEMS TO BE FURNISHED FIT THE SPACE AVAILABLE. CONTRACTOR TO VERIFY
LOCATIONS OF ALL EXISTING SERVICES AND CONNECTION POINTS. CONTRACTOR SHALL FIELD CONFIRM ALL PIPE SIZES AND LOCATIONS, AND ALL DIMENSIONS
AND ELEVATIONS. CONTRACTOR SHALL BE RESPONSIBLE FOR CONTACTING AND PAYING ALL FEES FOR UTILITY LOCATOR SERVICE TO LOCATE PUBLIC AND
PRIVATE UTILITIES AND UNDERGROUND STRUCTURES BEFORE DIGGING. CONTRACTOR SHALL BE RESPONSIBLE FOR ANY DAMAGES INCURRED AS A RESULT
OF THIS WORK. ALL DISCOVERIES SHALL BE ACCURATELY SHOWN ON THE RECORD DRAWINGS.
5.THE DRAWINGS ARE INTENDED TO COVER THE COMPLETE PLUMBING SYSTEMS. HOWEVER, THE DRAWINGS MAY NOT SHOW COMPLETE OR ACCURATE
DETAILS OF THE BUILDING OR SYSTEMS IN EVERY RESPECT. IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO CONFIRM FIELD CONDITIONS AND OBTAIN ANY
ADDITIONAL INFORMATION AS REQUIRED. DO NOT SCALE FROM CONTRACT DRAWINGS.
6.THE ENGINEER SHALL NOT BE RESPONSIBLE FOR THE MEANS, METHODS, TECHNIQUES, SEQUENCES OR PROCEDURES OF CONSTRUCTION SELECTED BY
THE CONTRACTOR OR OF THE SAFETY PRECAUTIONS AND PROGRAMS INCIDENTAL TO THE WORK OF THE CONTRACTOR TO PERFORM THE CONSTRUCTION
WORK IN ACCORDANCE WITH OSHA, APPLICABLE CODES, THE DRAWINGS AND SPECIFICATIONS.
7.PROVIDE DIELECTRIC UNIONS AS REQUIRED.
8.SANITARY TIE-INS SHALL BE MADE WITH SANITARY TEES IN THE VERTICAL AND WYES IN THE HORIZONTAL. TIE BRANCH CONNECTIONS TO SEWER MAINS IN
UPPER HALF OF MAIN. UNLESS NOTED OTHERWISE ON THE DRAWINGS. SANITARY PIPE CONNECTIONS SHALL NOT BE REDUCED IN SIZE WITHOUT PRIOR
APPROVAL OF THE A/E. IF EXISTING IS FOUND TO BE OF DISSIMILAR METALS, PROVIDE DIELECTRIC UNIONS OR OTHER NON-CONDUCTIVE MEANS TO PREVENT
ELECTROLYSIS.
9.CONTRACTOR SHALL INSTALL FIXTURES, EQUIPMENT AND MATERIALS IN ACCORDANCE WITH THE MANUFACTURER'S WRITTEN INSTRUCTIONS, AND
APPLICABLE CODES. INSTALL ADA FIXTURES AT THE HEIGHTS PRESCRIBED BY THE CODE HAVING JURISDICTION. MAKE PROPER PIPING CONNECTIONS TO
FIXTURES AND EQUIPMENT EVEN THOUGH BRANCH MAINS, ELBOWS AND CONNECTIONS ARE NOT SHOWN. COORDINATE WITH ARCHITECTURAL DRAWINGS
BEFORE ROUGHING-IN PLUMBING FIXTURES. PROVIDE STOPS ON ALL PLUMBING FIXTURE WATER SUPPLIES. SENSOR OPERATED FLUSH VALVES SHALL BE
MOUNTED AT A HEIGHT WHEREAS RAISED WATER CLOSET SEATS SHALL NOT INTERFERE WITH FLUSH VALVE OPERATION.
10. PROVIDE 4" HIGH (MIN.) CONCRETE HOUSEKEEPING PADS FOR ALL FLOOR MOUNTED EQUIPMENT, PAD SHALL BE A MINIMUM OF 6" LARGER IN ALL
DIRECTIONS THAN THE EQUIPMENT.
11.LOCATE ALL VALVES ABOVE ACCESSIBLE CEILING WHERE POSSIBLE. PROVIDE ACCESS DOORS FOR ALL CONCEALED VALVES IN INACCESSIBLE
LOCATIONS.
12.INSTALL EQUIPMENT TO FACILITATE SERVICING, MAINTENANCE, AND REPAIR OR REPLACEMENT OF EQUIPMENT COMPONENTS. AS MUCH AS PRACTICAL,
CONNECT EQUIPMENT FOR EASE OF DISCONNECTING, WITH A MINIMUM OF INTERFERENCE WITH OTHER INSTALLATIONS. PIPING SHALL NOT INTERFERE WITH
COMPONENT CLEARANCES. UNIONS AND/OR FLANGES SHALL BE INSTALLED AT EACH PIECE OF EQUIPMENT TO PERMIT DISASSEMBLY FOR ALTERATION AND
REPAIRS. PROVIDE FLEXIBLE CONNECTIONS IN PIPING SYSTEMS CONNECTED TO PUMPS AND OTHER EQUIPMENT REQUIRING VIBRATION ISOLATION AS CLOSE
TO EQUIPMENT AS POSSIBLE, UNLESS SHOWN OTHERWISE ON DRAWINGS.
13.ALL ABANDONED SANITARY, VENT AND STORM PIPING SHALL BE CAPPED AT BOTH ENDS WITH A GAS/WATER TIGHT FITTING. AREAS NOT ASSOCIATED
WITH THE RENOVATION SHALL NOT BE DISTURBED. WHERE ABANDONED PIPING IS LOCATED WITHIN AREAS SUCH AS WALLS, AND CEILINGS THAT ARE NOT
PART OF THE RENOVATION SCOPE, THEN BOTH ENDS OF DRAINAGE, WASTE AND VENT AND STORM PIPING SHALL BE CAPPED AS STATED ABOVE.
14.ANY ITEMS NOT SHOWN TO BE DEMOLISHED, THAT ARE DAMAGED, SHALL BE REPAIRED BY THE CONTRACTOR.
15.NO PENETRATIONS SHALL BE MADE IN THE EXISTING ROOF. ALL PIPE ROUTING SHALL BE MADE WITH EXISTING VENT-THROUGH-ROOF PENETRATIONS.
WHERE VENT PIPING IS REMOVED AND NO NEW PIPING IS CONNECTED TO EXISTING VENT-THROUGH-ROOF PENETRATIONS. THE ABANDONED VENT-THROUGH-
ROOF SHALL BE CAPPED ABOVE THE ROOF ABD BELOW THE ROOF IN THE CEILING SPACE. THIS VERTICAL PIPE SHALL BE SECURED TO STRUCTURE IN AN
APPROVED MANNER. ALL PIPING CAPS SHALL BE WATER AND GAS TIGHT CONNECTIONS IN A PERMANENT PIPING ARRANGEMENT.
16.NEW FIXTURES SHALL TIE IN TO EXISTING PIPING IF PIPE SIZING MEETS CODE MINIMUM SIZES. NEW FIXTURES INSTALLED WHERE NONE ARE EXISTING
SHALL MEET SCHEDULED PIPE REQUIREMENTS.
17.CONTRACTOR RESPONSIBLE NOT TO ALLOW ON-SITE ACCUMULATION OF DEBRIS OR DEMOLISHED MATERIALS. PROMPTLY AND LEGALLY TRANSPORT AND
DISPOSE OF MATERIALS OFF-SITE. DO NOT BURN DEBRIS OR DEMOLISHED MATERIALS. ALL DISPOSAL COSTS TO BE BORNE BY CONTRACTOR.
18.CONTRACTOR SHALL COORDINATE HIS/HER WORK WITH THAT OF OTHER TRADES. INTERRUPTIONS OF SERVICES SHALL BE COORDINATED WITH THE
OWNER AT LEAST 48 HOURS IN ADVANCE OF THE WORK BEING PERFORMED. DISRUPTION TIME SHALL BE KEPT TO A MINIMUM.
19.THE CONTRACTOR SHALL MAKE A PERSONAL INSPECTION OF THE SITE AND INCLUDE PERFORMING ALL WORK REQUIRED BY THE DRAWINGS AND
SPECIFICATIONS. FIELD VERIFY INFORMATION PROVIDED ON THE DRAWINGS AND EXISTING CONDITIONS, INCLUDING: LOCATIONS, ELEVATIONS, DIMENSIONS
AND QUANTITIES REQUIRED FOR THE WORK. NOTIFY A/E IN WRITING OF ANY ADDITIONAL WORK THAT MAY BE REQUIRED TO ACCOMPLISH THE SCOPE OF
WORK AND/OR ACCOMMODATE FIELD INCONSISTENCIES WITH OR IN THE DRAWINGS AND/OR SPECIFICATIONS.
20.THESE DRAWINGS ARE BASED ON FIELD OBSERVATIONS AND EXISTING DRAWINGS PROVIDED TO THE A/E BY THE OWNER. THE DRAWINGS ARE FROM
PREVIOUS PROJECT(S), WHEN AVAILABLE. FIELD OBSERVATIONS, HOWEVER, PROVIDED LITTLE DATA, AS MOST OF THE INSTALLATIONS WERE INACCESSIBLE
FOR VISUAL CONFIRMATION. THE INTENT OF THESE DRAWINGS IS TO PROVIDE AS MUCH INFORMATION TO THE CONTRACTOR AS POSSIBLE. HOWEVER, IT IS
THE CONTRACTOR'S RESPONSIBILITY TO CONFIRM ACTUAL FIELD CONDITIONS AND INFORMATION PROVIDED HEREIN.
21.AS EXISTING PIPING IS ENCOUNTERED, THE CONTRACTOR SHALL ASSESS THE CONDITION OF THE PIPING BEFORE TIE-INS ARE MADE. IF THE PIPING IS
BELIEVED TO BE IN POOR CONDITION OR NOT ADEQUATE FOR USE AS INTENDED, THE CONTRACTOR SHALL IMMEDIATELY REPORT SUCH TO THE A/E. TIE-INS
ARE NOT TO PROCEED UNTIL CONTRACTOR HAS RECEIVED A RESPONSE FROM THE A/E.
22.WHEN CONSTRUCTION IS COMPLETE, CONTRACTOR SHALL THOROUGHLY CLEAN ALL FIXTURES, EQUIPMENT AND SYSTEMS BEFORE PLACING IN
OPERATION OR TURN OVER TO THE OWNER. RESTORE FINISHED SURFACES IF DAMAGED AND DELIVER THE ENTIRE INSTALLATION IN AN APPROVED
CONDITION.
23.ADEQUATE PROTECTION SHALL BE PROVIDED FOR THE BUILDING(S) AND CONTENTS DURING THE PERFORMANCE OF THE WORK. TRASH REMOVAL SHALL
BE PERFORMED DAILY AND COORDINATED WITH THE OWNER'S REPRESENTATIVE TO PREVENT IT'S ACCUMULATION, TO ENSURE PROPER DISPOSAL OF
MATERIALS, AND TO PROTECT THE PROPERTY. CONTRACTOR SHALL CONTROL DUST AND DEBRIS TO PREVENT SPREAD INTO THE BUILDING(S).
24.NEATLY CORE-DRILL AND/OR SAW-CUT FLOORS, WALLS, SIDEWALKS AND PAVING AS REQUIRED. INSTALL NEW FIXTURES AND APPROPRIATE PIPING AND
REPAIR FINISHES TO MATCH EXISTING. CORE-DRILL AND/OR SAW-CUT HOLES AND SLOTS AS SMALL AS POSSIBLE. DO NOT CUT STRUCTURAL MEMBERS
WITHOUT PRIOR WRITTEN APPROVAL OF THE A/E.
25. FOR ALL INVERT ELEVATIONS, FINISHED FLOORS SHALL BE ASSUMED TO BE 0'-0"
28.UNLESS OTHERWISE NOTED ON PLANS ALL HOT WATER SUPPLY AND RETURN SHALL BE 140°.
29. P.C. SHALL BALANCE HOT WATER RETURN SYSTEM TO INSURE ADEQUATE FLOW OF HOT WATER TO EACH FIXTURE REQUIRING HOT WATER, PER PLAN(S).Plumbing Equipment Schedule
GASREMARKS
VENTCOLDHOTWATERINDIRECTWASTEWATERITEM FIXTURE
ROUGH-IN SERVICES
WASTEFD-1 FLOOR DRAIN
ZURN FLOOR DRAIN MODEL NO. Z-415-6B, CAST IRON BODY, COMBINATION CLAMP
AND ADJUSTABLE COLLAR, 2", 3" or 4" BOTTOM OUTLET WITH 6" ROUND NICKEL
BRONZE STRAINER AND TRAP PRIMER CONNECTION.
--2"2"--WITH DEEP
SEAL P-TRAP
MANUFACTURER/MODEL
FCO JAY R. SMITH FLOOR CLEANOUT MODEL NO. 4040. FLOOR CLEANOUT NICKEL
BRONZE TOP----SEE
PLANS -
YCO JAY R SMITH CLEANOUT 42223SG CAST IRON WITH ROUND ADJUSTABLE CAST IRON
TRAFFIC LOAD TOP IN CONCRETE SLAB.YARD CLEANOUT ----4"-
FLOOR CLEANOUT
YCO YARD CLEANOUT ----SEE
PLANS -
----8"-
FROET COMBINATION ROOF DRAIN AND OVERFLOW, 100C8-OFS-DMP WITH CAST
IRON DOMES OVER DRAIN AND OVERFLOW. 8" ROOF DRAIN, 8" OVERFLOW, DECK
MOUNTING PLATE, AND NO HUB.
RD-1 ROOF DRAIN
TP "PRIME-EZE" WATER SAVER TRAP PRIMER EQUAL TO J.R. SMITH MODEL NO. 2698.
UNIT SHALL BE APPROVED BY LOCAL AHJ.1/2"-----TRAP PRIMER
MV-1 THERMOSTATIC MIXING
VALVE (POINT OF USE)WATTS THEMOSTATIC MIXING VALVE LFUSG-B, WITH MIN. FLOW OF .25 GPM
SET TO 110°
1/2"1/2"----
EXISTING TO BE RELOCATEDHB-1 HOSE BIBB - EXTERIOR 3/4"-----
----6"-RD-2 ROOF DRAIN
FROET COMBINATION ROOF DRAIN AND OVERFLOW, 100C6-OFS-DMP WITH CAST
IRON DOMES OVER DRAIN AND OVERFLOW. 6" ROOF DRAIN, 6" OVERFLOW, DECK
MOUNTING PLATE, AND NO HUB.
ZURN Z199 DOWNSPOUT NOZZLE, FOR EMERGENCY OVERFLOW ROOF DRAINAGE.DN-1 DOWNSPOUT NOZZLE ----10"-
Plumbing Fixture Schedule
GASREMARKS
VENTCOLDHOTWATERINDIRECTWASTEWATERITEM FIXTURE
ROUGH-IN SERVICES
WASTEHANDICAP TYPEP10
AMERICAN STANDARD ELONGATED BOWL #2854.111 MADERA FLOWWISE, FLOOR
MOUNTED WATER CLOSET, ADA HIEGHT, WHITE COLOR EVERCLEAN FINISH, OPEN
FRONT SEAT, SLOAN ROYAL 111-1.28 FLUSHOMETER, 1.28 GPF.
WATER CLOSET (ADA)1"-3"2"--
MANUFACTURER/MODEL
P30
LAVATORY, KOHLER SOHO WALL MOUNTED SINK #K-2053-0 WHITE, WITH CONCEALLED
ARM CARRIER J.R.SMITH 0700. FAUCET, DELTA 590-PLGHDF BATTERY OPERATED, 0.5
GPM. 1-1/2"x1-1/4" P-TRAP, AND GRID STRAINER. PROVIDE PLUMBEREX "HANDY
SHIELD" ON EXPOSED PIPING.
LAVATORY 1/2"1/2"2"1 1/2"--HANDICAP TYPE
P40 SHOWER - ADA 1/2"1/2"2"1 1/2"--
SHOWER STALL, AKER OPS-3636-141277-R/L, WHITE WITH STRAIGHT VERTICAL
AND L-SHAPED HORIZONTAL GRAB BARS, L-SHAPED FOLD DOWN PHENOLIC
SEAT. DELTA FAUCET T13H333 ADJUSTIBLE HEAD/HANDSET SINGLE LEVER
HANDLE, POLISHED CHROME WITH INTEGRAL CHECK/STOPS, DIVERTER VALVE,
AND 1.5 GPM RESTRICTOR.
HANDICAP TYPE
MANUFACTURER OR EQUAL
ZURN, SMITH, PPI, SIOUX-CHIEF
SHOCK ARRESTORS SHALL BE SAME SIZE AS PIPE INSTALLED ON, MINIMUM.
PROVIDE SHOCK ARRESTORS AS INDICATED ON THE DRAWINGS.
LOCATE SHOCK ARRESTORS IN AN ACCESSIBLE LOCATION, OR PROVIDE
SHOCK ARRESTOR SCHEDULE
12 - 32SA'B'
61 - 113
33 - 60
114 - 154
155 - 330
SIOUX-CHIEF SHOCK ARRESTORS ONLY.
SA'F'
SA'E'
SA'D'
SA'C'
FIXTURE UNITS
1 - 11SA'A'
P.D.I. SIZE
"
"
"
"
"VARIESUNDERGROUND PIPING
1/8 BEND
FLOOR
SCORIATED COVER
TAPER THREAD
CLEANOUT PLUG
CLEANOUT BOX
REDUCER AS
REQUIRED
LONG SWEEP
90 OR WYE
DEEP SEAL "P" TRAP
FINISHED FLOOR
FLOOR DRAINGRATE
CAULK OUTLET
1/2" TRAP PRIMER (TP), TAP
WHERE SPECIFIED
VARIESUNDERGROUND PIPING
1/8 BEND
GRADE
SCORIATED COVER
TAPER THREAD
CLEANOUT PLUG
CLEANOUT BOX
REDUCER AS
REQUIRED
LONG SWEEP 90
OR WYE
TRAP
PRIMING
VALVE
SERVICE
VALVE
UNION 9 1/2"1/2" PIPE TO DRAIN
MAXIMUM PIPE/TUBING SUPPORT SPACING, FEET
NOM. SIZE THRU 3/4
PIPE
TUBING
1 1 1/4 1 1/2 2 3 4 5 6 8 10 12 14 16 18 20 22
7 FT 7 7 9 10 12 14 16 17 19 22 23 25 27 28 30 32
5 FT 6 7 8 8 10 12 13 14 16 -------
NOTE: FOR TRAPEZE HANGER - TAKE SPACING OF SMALLEST SIZE ON TRAPEZE.
HANGER ROD
INSULATION (VAPOR BARRIER TYPE REQUIRED FOR
LOW TEMP. PIPE)
PROVIDE HIGH COMPRESSIVE STRENGTH INSULATION. INSERT
BLOCKS UNDER INSULATION-PRE INSULATED CALCIUM SILICATE
SHIELD
INSULATION SHIELD AT HANGER OR
PRE-INSULATED CALCIUM SILICATE
SHIELD
HANGER ROD
INSULATION
WELD
SADDLE OR PRE-INSULATED
CALCIUM SILICATE SHIELD
PROVIDE INSULATION SHIELD AND
INSERT FOR ALL PIPING 8" MAX.
1" MAX.
1-5/8" 12 GAUGE CHANNEL
OR 2"x2"x1/4" ANGLE
ADJUSTABLE CLEVIS
HANGER PART 1
ADJUSTABLE ROLLER
HANGER TYPE 43
TRAPEZE HANGER FOR UP TO
1000 POUND UNIFORM LOAD
2 1/2
11
9
w w w . l i t t l e o n l i n e . c o m
This drawing and the design shown are the property
of Little Diversified Architectural Consulting. The
reproduction, copying or other use of this drawing
without their written consent is prohibited and any
infringement will be subject to legal action.
Little 2017c
PROJECT MANAGER
DESIGN TEAM
PRINCIPAL IN CHARGE
PROJECT TEAM
REVISIONS
PROJECT NAME
SHEET TITLE
PROJECT NO.
SHEET NUMBER
ISSUE FOR
ISSUE DATE
B
1 2 3 4 5 6 7
A
C
D
E
F
410 Blackwell Street, Suite 10
Durham, NC 27701
T: 919.474.2500
10/6/2017 2:35:58 PM C:\Users\fred.josey\Documents\513.7505.00_CU_WrestlingExpansion_-P16_fred.josey.rvt513.7505.00
10/06/17
P0.0.1
PLUMBING GENERAL
NOTES, SCHEDULES,
AND DETAILS
Campbell Convocation
Center Wrestling
Department Renovation
and Expansion
BID/PERMIT SET
Rob Klinedinst
Katie Buckman
DG
1 : 1P0.0.1
4 FLOOR CLEANOUT DETAIL
1 : 1P0.0.1
5 FLOOR DRAIN DETAIL
1 : 1P0.0.1
6 YARD CLEANOUT DETAIL
12" = 1'-0"P0.0.1
7 TRAP PRIMER DETAIL
1/8" = 1'-0"P0.0.1
8 PIPE HANGAR DETAILS
NO. REASON DATE
eG
e10
eE.6
eE
eF
YCO
YCO
EX.
HB-1
RD-1 RD-1
RD-1
1
2
3
4
5 5 5
6
7
EX.
WCO
EX.
WCO
EX.
WCO
8
9
w w w . l i t t l e o n l i n e . c o m
This drawing and the design shown are the property
of Little Diversified Architectural Consulting. The
reproduction, copying or other use of this drawing
without their written consent is prohibited and any
infringement will be subject to legal action.
Little 2017c
PROJECT MANAGER
DESIGN TEAM
PRINCIPAL IN CHARGE
PROJECT TEAM
REVISIONS
PROJECT NAME
SHEET TITLE
PROJECT NO.
SHEET NUMBER
ISSUE FOR
ISSUE DATE
B
1 2 3 4 5 6 7
A
C
D
E
F
410 Blackwell Street, Suite 10
Durham, NC 27701
T: 919.474.2500
10/6/2017 2:36:05 PM C:\Users\fred.josey\Documents\513.7505.00_CU_WrestlingExpansion_-P16_fred.josey.rvt513.7505.00
10/06/17
PD101
PLUMBING DEMOLITION
FLOOR PLAN
Campbell Convocation
Center Wrestling
Department Renovation
and Expansion
BID/PERMIT SET
Rob Klinedinst
Katie Buckman
DG
PLAN
NORTHN
X KEY NOTES
3/16" = 1'-0"PD101
1 PLUMBING DEMOLITION PLAN
1 CAP EXISTING PIPES AFTER ISOLATION VALVES.
2 EXISTING OIL SEPERATOR AND MOP SINK SHALL REMAIN.
3 REMOVE EXISTING HOSE BIBB AND REUSE IN NEW
CONSTRUCTION.
4 DEMO EXISTING YCO.
5 DEMO EXISTING 4" SD PIPE AT EXISTING WALL.
6 P.C. SHALL FIELD VERIFY EXACT SIZE AND CONFIGURATION OF
EXISTING SD PIPING.
7 DEMOLISH EXISTING 2" VENT TO THIS POINT FOR EXISTING MOP
SINK AND OIL INTERCEPTOR.
8 EXISTING PIPING SHALL REMAIN.
9 REMOVE EXISTING SEG OF COLD WATER PIPE TO EXISTING
HOSE BIBB. RELOCATE EXISTING HOSE BIBB.
NO. REASON DATE
FECFECeG
e10
eE.6
eE
eF
6" SS
4" SS
FCO
4" SS
3" SS
2" V
FCO
P40 P10
P30
EX.
WCO EX.
WCO
EX.
WCO
WCO
6" SD 6" SD 6" SD
6" SD
6" SD
EX. 4" TO
RD-1 EX. 4" TO
RD-2
EX. 4" TO
RD-2
4" TO
RD-2
EX.
FCO
2" SS
YCO
8" SD
8" SD
YCO
2" SS
EXIST. SUMP
PUMP
EX.
EX.
EX.
2" V
EX.
EX.
FD-1
TP
8" SD
1 2
3
4 5 6 7
8
9
8" ORL10" ORLCOP
COP
10
11 11 11
DN-1
6" ORL 6" ORL
12
6" SD
(3,390 SF.)
8" SD
(5,771 SF)(8,094 SF)(10,041 SF)
2" V
2" SS
2" V
2" V
13
14
X KEY NOTES
KEY PLAN
w w w . l i t t l e o n l i n e . c o m
This drawing and the design shown are the property
of Little Diversified Architectural Consulting. The
reproduction, copying or other use of this drawing
without their written consent is prohibited and any
infringement will be subject to legal action.
Little 2017c
PROJECT MANAGER
DESIGN TEAM
PRINCIPAL IN CHARGE
PROJECT TEAM
REVISIONS
PROJECT NAME
SHEET TITLE
PROJECT NO.
SHEET NUMBER
ISSUE FOR
ISSUE DATE
B
1 2 3 4 5 6 7
A
C
D
E
F
410 Blackwell Street, Suite 10
Durham, NC 27701
T: 919.474.2500
10/6/2017 2:36:00 PM C:\Users\fred.josey\Documents\513.7505.00_CU_WrestlingExpansion_-P16_fred.josey.rvt513.7505.00
10/06/17
P1.1.1
PLUMBING DRAINAGE
PLAN - LEVEL 1
Campbell Convocation
Center Wrestling
Department Renovation
and Expansion
BID/PERMIT SET
Rob Klinedinst
Katie Buckman
DG
1 REPLACE EXISTING ELBOW WITH NEW "TEE".
2 EXISTING MOP SINK AND OIL SEPERATOR AND ALL ASSOCIATED
PIPING SHALL REMAIN.
3 REPLACE EXISTING YCO WITH NEW FCO.
4 P.C. SHALL REPLACE EXISTING ROOF DRAIN WITH RD-1.
REWORK EXISTING PIPING TO 1/4" SLOPE (MIN) FROM RISER TO
DRAIN, 3390 S.F.
5 P.C. SHALL REPLACE EXISTING ROOF DRAIN WITH RD-2.
REWORK EXISTING PIPING TO 1/4" SLOPE (MIN) FROM RISER TO
DRAIN, 2381 S.F.
6 P.C. SHALL REPLACE EXISTING ROOF DRAIN WITH RD-2.
REWORK EXISTING PIPING TO 1/4" SLOPE (MIN) FROM RISER TO
DRAIN, 2323 S.F.
7 NEW ROOF DRAIN, RD-2, 1947 S.F.
8 CONNECT 6" SD PIPE TO EXISTING 4" SD AT BUILDINGS EDGE
AND ROUTE PER PLAN (1/8" SLOPE).
9 VERIFY EXISTING SD PIPE IS 8". IF NOT, THEN DEMO AND
EXTEND NEW 8" SD PIPE TO EXISTING SD MAN HOLE
CONNECTION AND MODIFY AS REQUIRED. (10,041 SF)
10 CONNECT 8" ORL UP TO OVERFLOW CONNECTION ON RD-1.
11 CONNECT 6" ORL UP TO OVERFLOW CONNECTION ON RD-2.
12 TERMINATE OVERFLOW DRAINAGE OUTSIDE EXTERIOR WALL.
OVERFLOW DRAINAGE SHALL PENETRATE EXTERIOR WALL
ABOVE CEILING HEIGHT.
13 EXTEND EXISTING VENT TO NEW "WYE". VERIFY EXACT SIZE IN
FIELD.
14 PC SHALL ENSURE THAT STORM DRAINAGE PIPE SHALL NOT
PENETRATE WALL CLOSER THAN 16" (MIN.) FROM ROOF
3/16" = 1'-0"P1.1.1
1 PLUMBING PLAN - DRAINAGE
ADDITION
NOT TO SCALE
EXISTING BUILDING
NO. REASON DATE
FECeG
e10
eE.6
eE
eF
3/4" HW
HB-1
P40 P10
P30
1 1/2" CW
1 1/4" CW
1" CW3/4" HWR
2 1/2" CW
2" HW
1" HWR
EX.
EX.
EX.
1
2
3
4
5
6
w w w . l i t t l e o n l i n e . c o m
This drawing and the design shown are the property
of Little Diversified Architectural Consulting. The
reproduction, copying or other use of this drawing
without their written consent is prohibited and any
infringement will be subject to legal action.
Little 2017c
PROJECT MANAGER
DESIGN TEAM
PRINCIPAL IN CHARGE
PROJECT TEAM
REVISIONS
PROJECT NAME
SHEET TITLE
PROJECT NO.
SHEET NUMBER
ISSUE FOR
ISSUE DATE
B
1 2 3 4 5 6 7
A
C
D
E
F
410 Blackwell Street, Suite 10
Durham, NC 27701
T: 919.474.2500
10/6/2017 2:36:02 PM C:\Users\fred.josey\Documents\513.7505.00_CU_WrestlingExpansion_-P16_fred.josey.rvt513.7505.00
10/06/17
P1.2.1
PLUMBING PIPING
PLAN - LEVEL 1
Campbell Convocation
Center Wrestling
Department Renovation
and Expansion
BID/PERMIT SET
Rob Klinedinst
Katie Buckman
DG
X KEY NOTES
KEY PLAN
1 EXTEND EXISTING HOT AND COLD WATER PIPING TO NEW
MAINS.
2 PROVIDE NEW SHOCK ABSORBER SA"B".
3 TAP EXISTING WATER LOOP WITH NEW 1-1/2" CW, 3/4" HW, AND
1/2" HWR.
4 SET BALANCING VALVE AT 0.5 GPM.
5 INSTALL RELOCATED HOSE BIBB IN NEW WALL, EXTEND
EXISTING 3/4" CW PIPE TO NEW LOCATION.
6 VERIFY IN FIELD EXACT LOCATION OF EXISTING 3/4" CW PIPIE,
EXTEND NEW 3/4" CW MAIN AND CONNECT IN RESTROOM SIDE
OF WALL.
3/16" = 1'-0"P1.2.1
1 PLUMBING PLAN - PIPING
EX. 3/4" CW
ADDITION
NOT TO SCALE
EXISTING BUILDING
NO. REASON DATE
eG
e10
eE.6
eE
eF
RD-1 RD-2 RD-2 RD-2
1 2 3 4
w w w . l i t t l e o n l i n e . c o m
This drawing and the design shown are the property
of Little Diversified Architectural Consulting. The
reproduction, copying or other use of this drawing
without their written consent is prohibited and any
infringement will be subject to legal action.
Little 2017c
PROJECT MANAGER
DESIGN TEAM
PRINCIPAL IN CHARGE
PROJECT TEAM
REVISIONS
PROJECT NAME
SHEET TITLE
PROJECT NO.
SHEET NUMBER
ISSUE FOR
ISSUE DATE
B
1 2 3 4 5 6 7
A
C
D
E
F
410 Blackwell Street, Suite 10
Durham, NC 27701
T: 919.474.2500
10/6/2017 2:36:03 PM C:\Users\fred.josey\Documents\513.7505.00_CU_WrestlingExpansion_-P16_fred.josey.rvt513.7505.00
10/06/17
P1.3.1
PLUMBING ROOF PLAN
Campbell Convocation
Center Wrestling
Department Renovation
and Expansion
BID/PERMIT SET
Rob Klinedinst
Katie Buckman
DG
X KEY NOTES
KEY PLAN
1/8" = 1'-0"P1.3.1
1 PLUMBING PLAN - ROOF
ADDITION
NOT TO SCALE
EXISTING BUILDING
1 P.C. SHALL REPLACE EXISTING ROOF DRAIN WITH RD-1.
REWORK EXISTING PIPING TO 1/4" SLOPE (MIN) FROM RISER TO
DRAIN, 3390 S.F.
2 P.C. SHALL REPLACE EXISTING ROOF DRAIN WITH RD-2.
REWORK EXISTING PIPING TO 1/4" SLOPE (MIN) FROM RISER TO
DRAIN, 2381 S.F.
3 P.C. SHALL REPLACE EXISTING ROOF DRAIN WITH RD-2.
REWORK EXISTING PIPING TO 1/4" SLOPE (MIN) FROM RISER TO
DRAIN, 2323 S.F.
4 NEW ROOF DRAIN, RD-2, 1947 S.F.
NO. REASON DATE
FCO
FCO
EX. SP-1
EX. OI-1
EX. FCO
6" SS
4" SS
3" SS
2" SS
2" V
2" V
2" SS
4" SS
FD-1
P40
P30 P10
2" SS
2" V
3" SS3" SS
EX.
EX.
EX.
EX.
EX.
EX.
2" V
2" V
2" SS
HB-2
P30
P10
P40
3/4" HW
1 1/4" CW
3/4" CW
1 1/2" CW
EX.3/4" CW
EX. MOP
BASIN
3/4" HWR
3/4" HW
BALANCE TO 0.5 GPM
SA'B'
1" CW
CAP EXIST. PIPING AT
EXIST. VALVES.
EXIST. HOT, COLD
AND HOT WATER
RETURN PIPING
3/4" CW
w w w . l i t t l e o n l i n e . c o m
This drawing and the design shown are the property
of Little Diversified Architectural Consulting. The
reproduction, copying or other use of this drawing
without their written consent is prohibited and any
infringement will be subject to legal action.
Little 2017c
PROJECT MANAGER
DESIGN TEAM
PRINCIPAL IN CHARGE
PROJECT TEAM
REVISIONS
PROJECT NAME
SHEET TITLE
PROJECT NO.
SHEET NUMBER
ISSUE FOR
ISSUE DATE
B
1 2 3 4 5 6 7
A
C
D
E
F
410 Blackwell Street, Suite 10
Durham, NC 27701
T: 919.474.2500
10/6/2017 2:36:04 PM C:\Users\fred.josey\Documents\513.7505.00_CU_WrestlingExpansion_-P16_fred.josey.rvt513.7505.00
06/22/17
P7.1.1
PLUMBING RISER
Campbell Convocation
Center Wrestling
Department Renovation
and Expansion
BID/PERMIT SET
Rob Klinedinst
Katie Buckman
DG
NOT TO SCALEP7.1.1
2 PLUMBING PLAN - DRAINAGE RISER
NOT TO SCALEP7.1.1
1 PLUMBING PLAN - PIPING RISER
NO. REASON DATE
FECFECeG
e10
eE.6
eE
eF
1
2 4" FS
34
4" FS
5
5
6
7
78
9
1.SCOPE OF WORK: PROVIDE A COMPLETE WET PIPE AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE WITH NFPA 13, NFPA 14, & NFPA
20 2012. THE WORK SHALL INCLUDE ALL WORK NECESSARY TO PROVIDE COMPLETE SPRINKLER COVERAGE FOR THE ENTIRE BUILDING.
2.SPRINKLERS SHALL BE HYDRAULICALLY DESIGNED TO PROVIDE COVERAGE FOR LIGHT HAZARD OCCUPANCY (0.10 GPM/SF OVER THE
HYDRAULICALLY MOST REMOTE 1500 SF) UNLESS NOTED OTHERWISE OR REQUIRED BY NFPA 13. THE CONTRACTOR SHALL PROVIDE ALL
NECESSARY SPRINKLER HYDRAULIC CALCULATIONS.
3.THE CONTRACTOR SHALL OBTAIN CURRENT (LESS THAN ONE-YEAR OLD) HYDRAULIC DATA REQUIRED TO PREPARE THE HYDRAULIC
CALCULATIONS.
4.SUBMITTALS: THE CONTRACTOR SHALL SUBMIT HYDRAULIC CALCULATIONS AND ALL PRODUCT DATA FOR REVIEW AND ACCEPTANCE
BY THE ENGINEER. THE SYSTEM SHALL BE DESIGNED BY A REGISTERED PROFESSIONAL ENGINEER OR NICET DESIGNER (LEVEL III OR
HIGHER) AND SHALL BEAR THE SEAL OF THE DESIGNER. THE CONTRACTOR SHALL BE PROCEEDING AT THEIR OWN RISK IF THE
CONTRACTOR CHOOSES TO PROCEED WITH THE WORK PRIOR TO ACCEPTANCE OF THE MATERIALS AND EQUIPMENT BY THE ENGINEER.
PRODUCTS:
1.ALL EQUIPMENT SHALL BE UL-LISTED AND/OR FM-APPROVED.
2.SPRINKLER PIPING SHALL BE SCHEDULE 40 BLACK STEEL WITH THREADED FITTINGS. PIPING 2-1/2" AND LARGER SHALL BE SCHEDULE
10 BLACK STEEL WITH GROOVED FITTINGS.
3.HANGERS SHALL BE FLAT-BAND, GALVANIZED.
INSTALLATION:
1.SPRINKLERS SHALL BE LOCATED IN THE CENTERS OF CEILING TILES AND SYMMETRICALLY ALIGNED ON THE CEILING.
2.MAXIMUM SPRINKLER SPACING SHALL NOT EXCEED THE LIMITS OF NFPA 13 AND THE LISTINGS OF SPRINKLERS.
3.PROVIDE AUXILIARY DRAINS WHERE REQUIRED TO DRAIN ALL PORTIONS OF THE PIPING SYSTEM.
4.COORDINATION WITH ELEVATORS:
4.1.PROVIDE SPRINKLERS IN LOCATIONS REQUIRED BY NFPA 13. THE HEADS SHALL BE STANDARD RESPONSE HEADS (NOT QUICK
RESPONSE) AND SHALL HAVE AN INTERMEDIATE TEMPERATURE RATING OF 212-DEGREES F UNLESS A DIFFERENT RATING IS
WARRANTED BY SHAFT ENVIRONMENTAL CONDITIONS.
4.2.THESE HEADS SHALL BE SUPPLIED DIRECTLY FROM THE WET PIPE SPRINKLER SYSTEM FOR THE RESPECTIVE FLOOR. ONE
SPRINKLER LINE SHALL SERVE BOTH THE MACHINE RO AND ADJACENT HOISTWAY OF THE RESPECTIVE FLOOR, AND SHALL NOT
SERVE ANY OTHER NON-ELEVATOR SPACE. ROUTING PIPES INSIDE THE HOISTWAY SHALL COMPLY WITH ASME A17.1.
4.3.A FLOW SWITCH, AND APPROPRIATE MEANS FOR TESTING AND DRAINING, SHALL BE PLACED IN AN ACCESSIBLE LOCATION
OUTSIDE OF THE MACHINE ROOM AND/OR HOISTWAY WHERE SPRINKLERS ARE INSTALLED. ONE FLOW SWITCH SHALL SERVE
BOTH THE MACHINE ROOM AND HOISTWAY.
4.4.THE FLOW SWITCH SHALL NOT HAVE A MEANS TO CREATE A TIME DELAY; IT MUST ACTIVATE IMMEDIATELY.
4.5.ACTIVATION OF A FLOW SWITCH SHALL:
A. IMMEDIATELY DISCONNECT MAIN LINE POWER.
B. ACTIVATE THE BUILDING’S FIRE ALARM SYSTEM, IF PRESENT.
5.ARMOVER PIPING SHALL BE 1" MINIMUM.
6.HYDROSTATICALLY TEST THE SYSTEM IN ACCORDANCE WITH NFPA 13.
7.OBTAIN ALL APPROVALS OF AUTHORITIES HAVING JURISDICTION.
8.PROVIDE CLOSE-OUT DOCUMENTS TO THE OWNER INCLUDING RECORD DRAWINGS, HYDRAULIC CALCULATIONS, PRODUCT DATA, AND
INSPECTION, TESTING AND MAINTENANCE INFORMATION.
FIRE PROTECTION GENERAL NOTES
w w w . l i t t l e o n l i n e . c o m
This drawing and the design shown are the property
of Little Diversified Architectural Consulting. The
reproduction, copying or other use of this drawing
without their written consent is prohibited and any
infringement will be subject to legal action.
Little 2017c
PROJECT MANAGER
DESIGN TEAM
PRINCIPAL IN CHARGE
PROJECT TEAM
REVISIONS
PROJECT NAME
SHEET TITLE
PROJECT NO.
SHEET NUMBER
ISSUE FOR
ISSUE DATE
B
1 2 3 4 5 6 7
A
C
D
E
F
410 Blackwell Street, Suite 10
Durham, NC 27701
T: 919.474.2500
10/6/2017 2:35:54 PM C:\Users\fred.josey\Documents\513.7505.00_CU_WrestlingExpansion_-P16_fred.josey.rvt513.7505.00
10/06/17
FS1.0.1
FIRE PROTECTION
PLAN - LEVEL 1
Campbell Convocation
Center Wrestling
Department Renovation
and Expansion
BID/PERMIT SET
Rob Klinedinst
Katie Buckman
DG
3/16" = 1'-0"FS1.0.1
1 FIRE SUPPRESSION PIPING PLAN
X KEY NOTES
KEY PLAN
1 REMOVE AND RELOCATE EXISTING VALVE CABINET. EXTEND
EXISTING FIRE SUPPRESSION PIPE TO NEW LOCATION.
2 PROVIDE NEW 4" AP INTO EXISTING 6" FIRE SUPPRESSION
LOOP. ROUTE 4" LINE TO NEW VALVE BOX.
3 PROVIDE NEW HOSE VALVE BOX. INSTALL PER LOCAL AND
STATE CODES.
4 RELOCATE AND EXTEND EXISTING SPRINKLER ASSEMBLY TEST
DRAIN FROM EXISTING WALL TO NEW WALL, EXTEND EXISTING
PIPE.
5 SPRINKLER HEAD LOCATIONS AND COVERAGE BY FIRE
SPRINKLER CONTRACTOR.
6 CONTRACTOR SHALL VERIFY EXACT LOCATION, AND
CONFIGURATION OF EXISTING SPRINKLER TEST ASSEMBLY
DRAIN LINE, AND MAKE CORRECTIONS AS REQUIERD.
COORDINATE WITH GC TO INSURE NO CONFLICTS.
7 EXISTING SPRINKLER SYSTEM TO REMAIN.
8 REWORK EXISTING SPRINKLERS TO COVER EXPANDED SPACE.
9 ROUTE NEW FIRE SUPPRESSION PIPE UP OVER EXISTING HVAC
DUCT AND ROUTE AS SHOWN ON PLAN.
ADDITION
NOT TO SCALE
EXISTING BUILDING
NO. REASON DATE
1.GENERAL NOTES ON THIS DRAWING ARE APPLICABLE TO EACH MECHANICAL DRAWING OF THIS SET. NOTES SPECIFIC TO INDIVIDUAL MECHANICAL
DRAWINGS WILL BE SHOWN ON THE RESPECTIVE MECHANICAL DRAWING.
2.THE CONTRACTOR SHALL PROVIDE A COMPLETE HVAC SYSTEM TO INCLUDE ALL LABOR, MATERIALS, TOOLS, AND EQUIPMENT FOR A COMPLETE AND
FUNCTIONAL SYSTEM INCLUDING ALL NECESSARY APPURTENANCES CUSTOMARILY INCLUDED IF NOT SPECIFICALLY CALLED OUT. ALL WORK SHALL BE
GUARANTEED IN WRITING AGAINST DEFECTIVE WORKMANSHIP AND MATERIALS FOR A PERIOD OF ONE YEAR FROM TURN OVER TO OWNER.
3.ENTIRE INSTALLATION, INCLUDING MATERIALS, EQUIPMENT, AND WORKMANSHIP, SHALL CONFORM WITH ALL APPLICABLE LAWS, CODES, AND
REGULATIONS OF MUNICIPAL, STATE AND FEDERAL AUTHORITIES.
4.ALL WORK SHALL CONFORM TO APPLICABLE ASHRAE, NFPA, AND SMACNA STANDARDS AND OTHER REGULATORY BODIES HAVING JURISDICTION OVER
THE CLASS OF WORK. ALL MATERIALS AND EQUIPMENT SHALL HAVE APPROPRIATE STAMPS/SEALS OF AHRI, ASME, U.L., AND ASTM.
5.THE CONTRACTOR SHALL OBTAIN AND PAY FOR ALL PERMITS, LICENSES, DOCUMENTS, AND SERVICES RELATED TO INSTALLATION OF THE WORK. THE
CONTRACTOR SHALL MAKE TESTS FOR ACCEPTANCE AND APPROVAL AS REQUIRED BY CODE AND THE REQUIREMENTS OF APPLICABLE REGULATORY
AGENCIES. REQUIRED TESTS SHALL BE PERFORMED IN THE PRESENCE OF THE OWNER'S REPRESENTATIVE UNLESS OTHERWISE WAIVED IN WRITING.
6.THE MECHANICAL CONTRACTOR SHALL COORDINATE ALL MECHANICAL WORK WITH ALL OTHER TRADES IN ORDER TO RESOLVE ANY CONFLICT THAT
MIGHT ARISE IN THE FIELD.
7.EQUIPMENT OF DIFFERING CHARACTERISTICS MAY BE PROVIDED IF SUCH PROPOSED ALTERNATE EQUIPMENT IS SUBMITTED TO AND APPROVED BY
THE ENGINEER OF RECORD AND OWNER'S REPRESENTATIVE IN WRITING. THE MECHANICAL CONTRACTOR SHALL RESPONSIBLE FOR COORDINATING
WITH ALL IMPACTED TRADES, AND ANY SUBSEQUENT COSTS OF THE ALTERNATE EQUIPMENT SHALL BE PROVIDE AT NO COST TO THE OWNER.
8.NO EQUIPMENT, PIPING, OR DUCTWORK SHALL BE INSTALLED OVER ANY ELECTRICAL EQUIPMENT OR ELECTRICAL SERVICE SPACE.
9.LAYOUT OF DUCTWORK IS DIAGRAMMATIC IN NATURE. MECHANICAL CONTRACTOR SHALL ALLOW FOR RISES, DROPS AND OFFSETS AS
REQUIRED FOR PROPER INSTALLATION, OPERATION, AND MAINTENANCE. INSTALL MECHANICAL EQUIPMENT TO FACILITATE SERVICING, MAINTENANCE,
AND REPAIR/REPLACEMENT OF COMPONENTS, INCLUDING ACCESS TO UNIT PANELS, CONTROLS, ETC. AS MUCH AS PRACTICAL, CONNECT
EQUIPMENT FOR EASE OF DISCONNECTING, WITH A MINIMUM OF INTERFERENCE WITH OTHER INSTALLATIONS. DUCTWORK SHALL NOT
INTERFERE WITH FILTER ACCESS.
10.PROVIDE VIBRATION ISOLATION AS REQUIRED FOR MECHANICAL EQUIPMENT TO PREVENT TRANSMISSION OF VIBRATION TO BUILDING STRUCTURE AND
SYSTEMS. PROVIDE FLEXIBLE CONNECTIONS IN ALL DUCTWORK AND PIPING SYSTEMS CONNECTED TO MECHANICAL EQUIPMENT WHICH REQUIRE
VIBRATION ISOLATION. FLEXIBLE CONNECTIONS SHALL BE PROVIDED AT THE POINT OF CONNECTION TO THE EQUIPMENT UNLESS OTHERWISE
INDICATED.
11.PROVIDE ALL CONTROL DEVICES, SUCH AS TEMPERATURE SENSORS, RELAYS, PRESSURE SWITCHES WHICH ARE ASSOCIATED WITH MECHANICAL
EQUIPMENT AND ASSOCIATED CONTROL WIRING FROM STARTER TO THE CONTROL DEVICE. ALL CONTROL DEVICES SHALL BE POWERED AND
OPERATED BY LOW VOLTAGE POWER (>24V) UNLESS OTHERWISE NOTED.
12.EXCEPT IN EQUIPMENT ROOMS, ALL CONTROL WIRING SHALL BE RUN CONCEALED. ALL CONTROL WIRING SHALL BE PLENUM RATED AND ROUTED IN
CONDUIT. J-HOOKS ARE AN ACCEPTABLE ALTERNATE METHOD TO CONDUIT WITH WRITTEN APPROVAL BY OWNER. CONTROL WIRING SHALL NOT BE
ROUTED WITHOUT CONDUIT OR J-HOOKS
13.ALL SPACE MOUNTED CONTROL DEVICES (THERMOSTATS, SWITCHES, HUMIDISTATS, ETC.) SHALL BE MOUNTED AT 4'-0" ABOVE FINISHED FLOOR
UNLESS OTHERWISE NOTED. THE MECHANICAL CONTRACTOR SHALL COORDINATE THE LOCATION OF SPACE MOUNTED CONTROL DEVICES WITH THE
ARCHITECT, GENERAL CONTRACTOR, AND OTHER TRADES BEFORE ROUGHING-IN OF WALLS HAS BEGUN.
14.TESTING, ADJUSTING, AND BALANCING AGENCY SHALL BE A MEMBER OF THE ASSOCIATED AIR BALANCE COUNCIL (AABC) OR THE NATIONAL
ENVIRONMENTAL BALANCING BUREAU (NEBB). TESTING, ADJUSTING, AND BALANCING SHALL BE PERFORMED IN ACCORDANCE WITH THE AABC OR NEBB
STANDARDS.
15.ALL PENETRATIONS THROUGH THE BUILDING ENVELOPE SHALL BE COORDINATED IN THE FIELD BY THE GENERAL CONTRACTOR. ROOF MOUNTED
EQUIPMENT SHALL BE INSTALLED ON PREFABRICATED CURBS OR RAILS, WITH ROOF PATCHED AND FLASHED TO PREVENT MOISTURE INTRUSION.
1.RUN ALL CONCEALED HORIZONTAL PIPING AND DUCTWORK ABOVE CEILING, TIGHT TO STRUCTURE UNLESS OTHERWISE NOTED. RUN ALL EXPOSED
PIPING AND DUCTWORK AS HIGH AS POSSIBLE UNLESS OTHERWISE NOTED.
2.DUCTWORK SIZES ARE SHEET METAL DIMENSIONS. PROVIDE DUCT LINER ONLY WHERE INDICATED OR NOTED ON PLANS. PIPE SIZES ARE NOMINAL
DIAMETERS.
3.PROVIDE ESCUTCHEON PLATES WHERE DUCTS OR PIPES PENETRATE ASSEMBLIES IN FINISHED AREAS EXPOSED TO VIEW. ESCUTCHEONS FOR DUCTS
SHALL BE CONSTRUCTED OF THE SAME MATERIAL AS DUCT. PIPE ESCUTCHEONS SHALL BE CHROME-PLATED BRASS. PIPE, CONDUIT AND DUCT
OPENINGS THROUGH ASSEMBLIES AROUND MECHANICAL ROOMS SHALL BE PACKED WITH MINERAL WOOL AND SEALED.
4.LOCATE ALL CONTROL DEVICES (TEMPERATURE, PRESSURE, AND FLOW MEASURING, ETC.)IN ACCESSIBLE LOCATIONS WITH STRAIGHT SECTION OF
PIPE OR DUCT UPSTREAM AND DOWNSTREAM AS REQUIRED BY THE MANUFACTURER FOR GOOD ACCURACY.
5.PENETRATIONS THROUGH RATED ASSEMBLIES (DUCTWORK, PIPING, ETC.) SHALL BE PROTECTED WITH A U.L. LISTED PENETRATION DETAIL. THE
GENERAL CONTRACTOR IS RESPONSIBLE FOR VERIFYING CONDITIONS IN FIELD AND SUBMITTING A U.L. DETAIL FOR APPROVAL OF THE ARCHITECT AND
ENGINEER OF RECORD.
6.CONCEALED DUCTWORK SHALL BE INSULATED USING EXTERIOR DUCT WRAP INSULATION. WRAPPED INSULATION SHALL BE 2 INCH THICK GLASS FIBER
FLEXIBLE DUCT INSULATION, 0.75 POUND DENSITY WITH U.L. APPROVED FSK JACKET. SECURE WITH ADHESIVE APPLIED DIRECTLY TO THE DUCT IN 4
INCH WIDE STRIPS AROUND THE DUCT ON 12 INCH CENTERS AND TAPE ALL JOINTS. WHERE REQUIRED, ACOUSTICAL DUCT LINING SHALL BE 1-1/2 INCH
THICK RIGID DUCTBOARD AND SHALL COMPLY WITH FIRE CLASSIFICATION REQUIREMENTS OF NFPA 90A AND 90B. ADHERE LINER TO DUCT WITH FIRE
RESISTANT ADHESIVE AND WELDED PIN TYPE MECHANICAL FASTENERS AS INDICATED IN SMACNA STANDARDS.
7.EXPOSED ROUND AND FLAT OVAL DUCTWORK IN FINISHED SPACES SHALL BE DOUBLEWALL SPIRAL DUCT WITH 2" FIBERGLASS INSULATION BETWEEN
THE DUCT WALLS. WHERE DOUBLE WALL DUCT REQUIRES SOUND ATTENUATION, A PERFORATED INTERIOR WALL SHALL BE USED.
8.FLEXIBLE DUCT LENGTH SHALL NOT EXCEED 5 FEET, AND SHALL ONLY BE INSTALLED IN CONCEALED SPACES.
9.ACOUSTICAL LINING SHALL BE PROVIDED ON THE FIRST 15'-0" OF SUPPLY AND RETURN DUCT CONNECTED TO AIR HANDLING UNITS.
10.ALL DUCT PENETRATIONS OF WALLS SHALL BE MADE WITH RIGID METAL DUCTS. FLEXIBLE DUCT PENETRATIONS OF WALLS ARE NOT ACCEPTABLE.
11.REFER TO ARCHITECTURAL REFLECTED CEILING PLANS FOR EXACT LOCATION OF DIFFUSERS, REGISTERS, AND GRILLES. FINISH AND COLOR TO BE
SELECTED FROM MANUFACTURER'S STANDARD PALETTE AND APPROVED BY ARCHITECT UNLESS OTHERWISE NOTED.
12.ALL ELBOWS IN DUCTWORK SHALL BE RADIUS ELBOWS UNLESS OTHERWISE NOTED. WHERE SQUARE ELBOWS ARE SHOWN, OR WHERE FIELD
CONDITIONS PREVENT USE OF RADIUS ELBOWS, INSTALL AIRFOIL TYPE TURNING VANES IN ACCORDANCE WITH SMACNA STANDARDS.
13.PROVIDE LOCKING OPPOSED BLADE MANUAL VOLUME DAMPERS WHERE INDICATED ON THE DUCT PLANS, AT SUPPLY, RETURN, AND EXHAUST BRANCH
DUCTS, AND IN EACH RUNOUT TO AIR TERMINALS, UNLESS DAMPER IS SPECIFIED AT TERMINAL. BRANCH DUCT DAMPERS SHALL BE AS CLOSE TO MAIN
TRUNK DUCT AS POSSIBLE. VOLUME DAMPERS ABOVE INACCESSIBLE CEILINGS SHALL BE PROVIDED WITH REMOTE CABLE CONTROLS WITH ALL
NECESSARY HARDWARE, TERMINATING 3" ACCESS PORT WITH FINAL LOCATION COORDINATED IN FIELD BY ARCHITECT.
14.FIRE, SMOKE, AND FIRE-SMOKE DAMPERS SHALL BE INSTALLED IN COMPLETE ACCORDANCE WITH THE MANUFACTURER'S U.L. LISTING AND
INSTALLATION INSTRUCTIONS. DAMPERS SHALL HAVE SPECIFIC U.L. LISTING FOR THE CONSTRUCTION IN WHICH THEY ARE INSTALLED. PROVIDE
DYNAMIC FIRE DAMPERS WITH BLADES OUT OF THE AIRSTREAM. INSTALL DUCTS THROUGH FIRE AND SMOKE RATED ASSEMBLIES AND PARTITIONS TO
LEAVE A MINIMUM OF 2 INCHES AROUND THE DUCT TO SEAL THE ASSEMBLY. DO NOT INSTALL FLEXIBLE DUCT THROUGH FIRE AND SMOKE RATED
ASSEMBLIES AND PARTITIONS.
15.DUCT MOUNTED SMOKE DETECTORS SHALL BE FURNISHED AND WIRED BY THE ELECTRICAL CONTRACTOR AND INSTALLED BY MECHANICAL
CONTRACTOR.
16.PROVIDE PIANO-HINGED DUCT ACCESS DOORS AT ALL DUCT ACCESSORIES (MOTOR OPERATED DAMPERS, FIRE DAMPERS, ETC.) REQUIRING
MAINTENANCE AND SERVICE, AND WHERE REQUIRED FOR OPERATION, ADJUSTMENT, AND MAINTENANCE OF MECHANICAL EQUIPMENT. WHERE ACCESS
DOORS ARE LOCATED ABOVE AN INACCESSIBLE CEILING, PROVIDE AN ACCESS DOOR IN THE CEILING. PROVIDE RATED ACCESS PANELS AS REQUIRED
TO MAINTAIN ASSEMBLY RATING.
17.BEFORE FABRICATING DUCTWORK, THE MECHANICAL CONTRACTOR IS RESPONSIBLE FOR COORDINATING THE LOCATION AND SIZE WITH ALL OTHER
TRADES.
18.EXTEND CONDENSATE DRAIN PIPING TO NEAREST DRAIN UNLESS OTHERWISE NOTED. ALL CONDENSATE PIPING SHALL BE TRAPPED AND PITCHED AT A
MINIMUM OF 1/8" PER LINEAR FOOT TOWARDS THE ROOF DRAIN.
1.PRIOR TO SUBMITTING A PROPOSAL THE CONTRACTOR IS STRONGLY ENCOURAGED TO VISIT THE SITE AND THOROUGHLY INSPECT ALL EXISTING
CONDITIONS TO INSURE THAT THE WORK REPRESENTED ON THE DRAWINGS CAN BE INSTALLED AS INDICATED.
2.INFORMATION ON EXISTING CONDITIONS (DUCT, PIPE, EQUIPMENT, ETC.) IS NOTED FOR THE CONVENIENCE OF THE CONTRACTOR ONLY AND IS NOT
WARRANTED TO BE CORRECT. THE CONTRACTOR IS RESPONSIBLE FOR VERIFYING EXISTING CONDITIONS PRIOR TO PROCEEDING WITH ANY
ASSOCIATED WORK OR ORDERING EQUIPMENT.
3.CUT OPENINGS AS REQUIRED IN THE EXISTING CONSTRUCTION FOR THE INSTALLATION OF PIPING, DUCTWORK, AND EQUIPMENT. PATCH AND REPAIR
TO MATCH THE EXISTING ADJACENT CONSTRUCTION.
4.ALL EQUIPMENT REMOVED FROM THE BUILDING DURING DEMOLITION SHALL BECOME THE PROPERTY OF THE CONTRACTOR AND SHALL BE REMOVED
FROM THE SITE UNLESS OTHERWISE NOTED.
5.PRIOR TO PERFORMING ANY WORK THE MECHANICAL CONTRACTOR SHALL INSPECT THE EXISTING DUCTWORK, PIPING, AND EQUIPMENT FOR
DEFECTS AND REPORT TO THE ENGINEER OF RECORD, GENERAL CONTRACTOR, AND OWNER ANY DEFICIENCIES FOUND. CONTRACTOR SHALL
CLEAN EXISTING DUCTWORK AND AIR TERMINALS PRIOR TO INSTALLING THE NEW WORK.
GENERAL NOTESDUCT & PIPING NOTES
EXISTING CONDITIONS & DEMOLITION
EXHAUST AIR DUCT TURNING UP
THERMOSTAT
EA
SUPPLY AIR DUCT TURNING UP
SA
CLASS 1 COMBINATION FIRE & SMOKE DAMPER
WITH DUCT ACCESS DOOR AND DUCT
MOUNTED ACTUATOR. REFER TO ELECTRICAL
PLANS FOR POWER REQUIREMENTS.
RADIUS DUCT ELBOW. RADIUS ELBOWS
SHALL BE 1.5W/1.5D ELBOWS UNLESS
OTHERWISE NOTED.
MITERED ELBOW WITHOUT TURNING
VANES AND WITH LINER.
MITERED ELBOW WITH TURNING VANES.
CONNECT TO EXISTING
CLASS 1 MOTORIZED DAMPER. REFER
TO ELECTRICAL PLANS FOR POWER
REQUIREMENTS.
CO2 CARBON DIOXIDE
SP STATIC PRESSURE
DP DIFFERENTIAL PRESSURE
SD SMOKE DETECTOR
CO CARBON MONOXIDE
SUPPLY AIR DUCT TURNING DOWN
RETURN AIR DUCT TURNING UP
RA
RETURN AIR DUCT TURNING DOWN
EXHAUST AIR DUCT TURNING DOWN
OVALRECTANGULARROUND
CLASS 1 SMOKE DAMPER WITH DUCT ACCESS
DOOR AND DUCT MOUNTED ACTUATOR.
REFER TO ELECTRICAL PLANS FOR POWER
REQUIREMENTS.
DYNAMIC TYPE B FIRE DAMPER WITH DUCT
ACCESS DOOR. COORDINATE DAMPER RATING
WITH ARCHITECTURAL WALL SCHEDULE.
GORED ELBOW (OVAL DUCT)
OVAL DUCT
ROUND DUCT
RECTANGULAR DUCT12x10
12/10
12ø
LIMIT OF DEMOLITION
FLEXIBLE DUCT. MAXIMUM LENGTH 6'-0".
FSD
SD
FD
MD
EXISTING CONDITIONS
NEW CONSTRUCTION
SYMBOL DESCRIPTIONABBR.
TEMPORARY WORK
DEMOLITION WORK
HUMIDISTAT
T
H
LOCKING MANUAL OPPOSED BLADE
BALANCING DAMPERBD
DIFFUSER TAGA10
325
NUMERAL INDICATES
NECK DIAMETER.
AIR FLOW AT DESIGN.
LETTER INDICATES
DIFFUSER TYPE
METHOD OF COMPLIANCE:
Prescriptive
Energy Cost Budget
Climate Zone:
Exterior Design Conditions:
winter dry bulb:
summer dry bulb:
Interior Design Conditions:
winter dry bulb:
summer dry bulb:
relative humidity:
Building Heating Load:
Building Cooling Load:
Mechanical Spacing Conditioning System:
Unitary:
description of unit:
heating efficiency:
cooling efficiency:
cooling output:
heating output:
Boiler:
Chiller:
Number of poles:
Motor type:
Minimum efficiency:
Number of phases:
Motor horsepower:
List equipment efficiencies:
No Change to Existing Systems
Mechanical system motors:
Mechanical Systems, Service Systems and Equipment
Performance
summer wet bulb:
Cooling Efficiency:
Heating Efficiency:
Oversizing reason:
Boiler output:
Oversizing reason:
Chiller output:
4A
18 °F
94 °F 75 °F
68 °F
76 °F
45-60%
62,300.0 Btu/h
148,300.0 Btu/h
AIR COOLED (HEATING & COOLING)
SINGLE PACKAGE
REFER TO MECHANICAL SCHEDULES
REFER TO MECHANICAL SCHEDULES
REFER TO MECHANICAL SCHEDULES
REFER TO MECHANICAL SCHEDULES
N/A
REFER TO MECHANICAL SCHEDULES
N/A
REFER TO MECHANICAL SCHEDULES
N/A
N/A
REFER TO MECHANICAL SCHEDULES
REFER TO MECHANICAL SCHEDULES
REFER TO MECHANICAL SCHEDULES
REFER TO MECHANICAL SCHEDULES
REFER TO MECHANICAL SCHEDULES
REFER TO MECHANICAL SCHEDULES
REFER TO MECHANICAL SCHEDULES
w w w . l i t t l e o n l i n e . c o m
This drawing and the design shown are the property
of Little Diversified Architectural Consulting. The
reproduction, copying or other use of this drawing
without their written consent is prohibited and any
infringement will be subject to legal action.
Little 2017c
PROJECT MANAGER
DESIGN TEAM
PRINCIPAL IN CHARGE
PROJECT TEAM
REVISIONS
PROJECT NAME
SHEET TITLE
PROJECT NO.
SHEET NUMBER
ISSUE FOR
ISSUE DATE
B
1 2 3 4 5 6 7
A
C
D
E
F
410 Blackwell Street, Suite 10
Durham, NC 27701
T: 919.474.2500
10/6/2017 2:33:35 PM C:\Users\rob.bell\Documents\513.7505.00_CU_WrestlingExpansion_M-16_rob.bell.rvt513.7505.00
10/06/17
M0.0.1
MECHANICAL GENERAL
NOTES & LEGEND
Campbell Convocation
Center Wrestling
Department Renovation
and Expansion
BID/PERMIT SET
Rob Klinedinst
Katie Buckman
M.GRUBBS, R.BELL
NO. REASON DATE
FIRE BARRIER FIRE & SMOKE BARRIER
1-HOUR
2-HOUR
3-HOUR
0.5-HOUR
1-HOUR
FIRE PARTITIONFIRE WALL
2-HOUR
3-HOUR
4-HOUR
1-HOUR
2-HOUR
3-HOUR
0-HOUR 1-HOUR
SMOKE BARRIERSMOKE PARTITION
1.PROVIDE BALANCING DAMPERS ON ALL BRANCH RUNOUTS TO DIFFUSERS.
2.FLEX DUCTS SHALL BE SIZED TO MATCH DIFFUSER NECK SIZE.
eG
eF
eE.6
e10
LOUNGE
108
FITNESS
107
STOR.
106
COACH
105
CONF.
104
ASST.
COACH
OFFICES
103
RECEP.
102
CORRIDOR
102.1
WRESTLING
GYM
101
WRESTLING
GYM
ADDITION
101.1
C14
600
A8
200
A8
200 A8
200
A12
425
A12
425
C15
850
C15
850
C6
100
C14
600
C12
500
C10
250
C10
250
C14
800
A12
400
A12
400
A8
150
A8
175
A8
175
A10
250
A10
250
A10
300
A10
300
A6
100
A12
425
A12
425
10"x16"14"x18"10"x18"
12"x10"
6"x10"
14"x14"18"x14"14"x14"
8"x14"18"x12"10"x12"
8"x16"
12"x18"
10"x18"
22"x18"
22"x18"
22"x18"
22"x18"
6"x8"
14"x14"10"x14"
10"x16"
T RTU-1
AVG
T RTU-1
AVG
TRTU-2
AVG
T RTU-2
AVG
03
04
04
04
--
B16x8
--
B16x8
--
XS18x10
--
XS18x10
--
XS18x10
--
XS18x10
20"ø
--
XS18x10--
XS18x10
26"ø
--
XS18x10
--
XS18x10
--
XR18x12
--
XR18x12
--
XR18x12
--
XR18x12
--
XR18x12
26"ø26"ø 20"ø 16"ø
16"ø 14"ø
0506
0606
06
06
06
06
07
06
SD
--
B16x8
TRTU-2
AVG
T RTU-2
AVG
03
--
XS18x10 --
XS18x100606
06 06
06
--
D18x12
--
D18x12
--
D18x1207070707070707
05
SD
14"ø
eF
eE.6
eE
e10
10"x8"
8"x10"
XE-10
300
XS-6
130
XE-6
100
XS-10
400
E6x6
100XS-6
125
E8x8
200
XR-8
255 XS-6
130
26"ø
24"x20"24"x20"60"x20"60"x20"12"x10"18"x18"02
02
02
02
02
02
02
eF
eE.6
eE
e1024"x20"24"x20"
26"ø 18"x18"12"x10"8"x8"10"x8"60"x20"01
01
01
01
01
01
01
w w w . l i t t l e o n l i n e . c o m
This drawing and the design shown are the property
of Little Diversified Architectural Consulting. The
reproduction, copying or other use of this drawing
without their written consent is prohibited and any
infringement will be subject to legal action.
Little 2017c
PROJECT MANAGER
DESIGN TEAM
PRINCIPAL IN CHARGE
PROJECT TEAM
REVISIONS
PROJECT NAME
SHEET TITLE
PROJECT NO.
SHEET NUMBER
ISSUE FOR
ISSUE DATE
B
1 2 3 4 5 6 7
A
C
D
E
F
410 Blackwell Street, Suite 10
Durham, NC 27701
T: 919.474.2500
10/6/2017 2:33:37 PM C:\Users\rob.bell\Documents\513.7505.00_CU_WrestlingExpansion_M-16_rob.bell.rvt513.7505.00
06/22/17
M1.1.1
MECHANICAL
DUCTWORK PLAN -
LEVEL 1
Campbell Convocation
Center Wrestling
Department Renovation
and Expansion
BID/PERMIT SET
Rob Klinedinst
Katie Buckman
M.GRUBBS, R.BELL
01 AIR TERMINAL TO BE RELOCATED. CONTRACTOR SHALL RETAIN UNTIL
INSTALLATION.
02 RELOCATED AIR TERMINAL. NEW FLEX DUCT SHALL MATCH DIFFUSER
NECK.
03 SUPPLY AND RETURN AIR DUCT UP THROUGH ROOF TO RTU.
COORDINATE OPENINGS WITH STRUCTURAL FRAMING.
04 ROUTE DUCT UP ABOVE HIGHER CEILING.
05 REMOVE EXISTING CAP AND ATTACH NEW TRANSITION TO EXISTING
DUCTWORK.
06 REBALANCE ALL SUPPLY DIFFUSSERS EQUALLY IN THIS AREA.
07 REBALANCE ALL RETURN GRILLES EQUALLY IN THIS AREA.
X KEY NOTES
KEY PLAN
GENERAL SHEET NOTES
WALL RATING LEGEND
3/16" = 1'-0"M1.1.1
1A CONVOCATION AREA C - ADDITION DUCT PLAN
ADDITION
NOT TO SCALE
EXISTING BUILDING
3/16" = 1'-0"M1.1.1
4D CONVOCATION AREA C - LOCKER ROOM DUCT PLAN
3/16" = 1'-0"M1.1.1
1D CONVOCATION AREA C - LOCKER ROOM DEMOLITION DUCT PLAN
NO. REASON DATE
FIRE BARRIER FIRE & SMOKE BARRIER
1-HOUR
2-HOUR
3-HOUR
0.5-HOUR
1-HOUR
FIRE PARTITIONFIRE WALL
2-HOUR
3-HOUR
4-HOUR
1-HOUR
2-HOUR
3-HOUR
0-HOUR 1-HOUR
SMOKE BARRIERSMOKE PARTITION
eG
e10
eE.6
eF
eG
eF
eE.6
e10
01
RTU-1 RTU-2
02 02
w w w . l i t t l e o n l i n e . c o m
This drawing and the design shown are the property
of Little Diversified Architectural Consulting. The
reproduction, copying or other use of this drawing
without their written consent is prohibited and any
infringement will be subject to legal action.
Little 2017c
PROJECT MANAGER
DESIGN TEAM
PRINCIPAL IN CHARGE
PROJECT TEAM
REVISIONS
PROJECT NAME
SHEET TITLE
PROJECT NO.
SHEET NUMBER
ISSUE FOR
ISSUE DATE
B
1 2 3 4 5 6 7
A
C
D
E
F
410 Blackwell Street, Suite 10
Durham, NC 27701
T: 919.474.2500
10/6/2017 2:33:37 PM C:\Users\rob.bell\Documents\513.7505.00_CU_WrestlingExpansion_M-16_rob.bell.rvt513.7505.00
06/22/17
M1.1.2
MECHANICAL PLAN -
ROOF
Campbell Convocation
Center Wrestling
Department Renovation
and Expansion
BID/PERMIT SET
Rob Klinedinst
Katie Buckman
M.GRUBBS, R.BELL
X KEY NOTES
KEY PLAN
WALL RATING LEGEND
3/16" = 1'-0"M1.1.2
1A CONVOCATION AREA C - ADDITION ROOF PLAN
ADDITION
NOT TO SCALE
EXISTING BUILDING
01 EXISTING EXHAUST FAN. REBALANCE TO PROVIDE AN ADDITIONAL 300
CFM OF EXHAUST (TOTAL EXHAUST 2225 CFM). RESHEAVE AS
NECESSARY. CONTRACTOR SHALL REBALANCETHIS EXHAUST SYSTEM
AS A PART OF THE TAB WORK.
02 COORDINATE EXACT ROUTING OF DUCTWORK AND PIPING DOWN INTO
CEILING PLENUM BELOW WITH STRUCTURAL ELEMENTS. MAINTAIN A
MINIMUM OF 15'-0" FROM THE OUTSIDE AIR INTAKE TO ANY SOURCES
OF EXHAUST, INCLUDING PLUMBING VENTS.
NO. REASON DATE
KEYED NOTES:
EQUIPMENT WITH
INTEGRAL
DISCONNECT
SWITCH
JB
STARTER
OR VFD
MOTOR
CONTROL
CENTER
LEGEND:
BY ELECTRICAL (DIVISION 26)
CONDUIT & WIRING OR CABLE BY MECHANICAL CONTRACTOR, CONTROLS CONTRACTOR, OR OTHER
TRADES. IN ALL CASES THE EQUIPMENT CONTRACTOR (DIVISION 23) SHALL MAKE FINAL CONNECTIONS, START
UP EQUIPMENT AND TEST EQUIPMENT. COORDINATE CONNECTIONS WITH DIV 26.
IF ANY ADDITIONAL DISCONNECTS ARE REQUIRED BY NEC, IT SHALL BE PROVIDED AND INSTALLED BY THE
EQUIPMENT CONTRACTOR (DIVISION 23).
A COMBINATION STARTER OR VFD MAY BE USED IN LIEU OF A SEPARATE DISCONNECT SWITCH AND STARTER. FACTORY MOUNT
OR LOCATE ADJACENT TO EQUIPMENT AND PROVIDED BY EQUIPMENT CONTRACTOR.
A JUNCTION BOX MAY BE SHOWN ON THE ELECTRICAL PLANS FOR SOME EQUIPMENT. IF NO STARTER OR
DISCONNECT IS SUPPLIED, A JUNCTION BOX SHALL BE INSTALLED ADJACENT TO EQUIPMENT. THE
ELECTRICAL CONTRACTOR SHALL PROVIDE LINE SIDE WIRING TO JUNCTION BOX. LOAD SIDE WIRING
WILL BE PROVIDED BY MECHANICAL CONTRACTOR OR OTHER TRADES.
FOR PROJECTS UTILIZING MOTOR CONTROL CENTERS (MCC), THE STARTER, CB, OR VFD IN THE MCC ARE
PROVIDED BY THE ELECTRICAL CONTRACTOR.
DIVISION 26 EQUIPMENT
BY MECHANICAL (DIVISION 23)
GENERAL NOTES:
1.ALL POWER WIRING ASSOCIATED WITH DIVISION 23 (MECHANICAL) SHALL BE PERFORMED UNDER THE SCOPE OF
WORK OF THE CONTRACTOR SUPPLYING THE EQUIPMENT AND SHALL BE COORDINATED WITH THE DIVISION 26
(ELECTRICAL) CONTRACTOR.
2.ALL POWER DISCONNECT SWITCHES, VFDS, AND SINGLE SPEED MANUAL STARTING SWITCHES ASSOCIATED
WITH DIVISION 23 SHALL BE PROVIDED UNDER THE SCOPE OF WORK OF THE CONTRACTOR SUPPLYING THE
EQUIPMENT AND SHALL BE COORDINATED WITH THE DIVISION 26 CONTRACTOR.
3.EXCEPT AS MAY BE INDICATED ON THE DRAWINGS AND/OR HEREINAFTER NOTED, ALL LOW VOLTAGE
CONTROL WIRING, (INCLUDING ALL TEMPERATURE CONTROL WIRING, INTERLOCKING, START-STOP WIRING,
TOGETHER WITH CONDUIT FOR SAME) SHALL BE PROVIDED UNDER DIVISION 23 BY THE CONTRACTOR
SUPPLYING THE EQUIPMENT. THIS INCLUDES, BUT IS NOT LIMITED TO, WIRING TO LOW VOLTAGE
THERMOSTATS, DAMPER MOTORS, AQUASTATS, FIRESTATS, PUSH BUTTONS, SELECTOR SWITCHES, AND
CONTROL PANELS. ALL DISCONNECT SWITCHES FOR CONTROL WIRING SHALL BE PROVIDED UNDER
DIVISION 23 BY THE CONTRACTOR SUPPLYING THE EQUIPMENT.
4.WORK OF DIVISION 23 SHALL INCLUDE FURNISHING AND SETTING MOTORS.
5.ALL MAGNETIC STARTERS AND OVERLOAD ELEMENTS WILL BE PROVIDED UNDER DIVISION 23 BY THE
CONTRACTOR SUPPLYING THE EQUIPMENT AND SHALL BE COORDINATED WITH THE DIVISION 26
CONTRACTOR. OVERLOAD ELEMENTS IN ALL STARTERS SHALL BE SELECTED ACCORDING TO ACTUAL MOTOR
NAMEPLATE FULL LOAD CURRENT. RESPONSIBILITY FOR THIS COORDINATION SHALL LIE WITH THE DIVISION
UNDER WHICH THE PARTICULAR STARTER WAS FURNISHED.
6.FIRESTATS AND WALL MOUNTED THERMOSTATS WHICH INTERRUPT LINE VOLTAGE POWER CIRCUITS
TO MOTORS SHALL BE PROVIDED UNDER DIVISION 23, AND ELECTRICALLY CONNECTED IN THE
BRANCH CIRCUIT WIRING AS WORK OF DIVISION 26.
7.ALL POWER AND CONTROL CONDUIT ROUTED TO EXTERIOR ON-GRADE MECHANICAL EQUIPMENT SHALL BE
ROUTED BELOW GRADE UNLESS OTHERWISE NOTED. COORDINATE STUB-UP LOCATIONS PRIOR TO ROUGH-IN.
8.ALL POWER AND CONTROL CONDUIT ROUTED TO ROOF MECHANICAL EQUIPMENT SHALL BE COORDINATED
WITH ARCHITECT AND GENERAL CONTRACTOR TO LIMIT THE NUMBER OF ROOF PENETRATIONS. COORDINATE
STUB-UP LOCATIONS PRIOR TO ROUGH-IN.
DIVISION 23 (MECHANICAL) EQUIPMENT
FEEDER CIRCUIT WIRING AND CONDUIT BY ELECTRICAL CONTRACTOR.
7 8
7
8
6
5
4
3
2
1
3
2
1
2
4
2
2
1
PANELBOARD/
SWITCHBOARD
8
3
55
6
1
2
3
EQUIPMENT WITHOUT
INTEGRAL
DISCONNECT
SWITCH
2
1
3
SPLIT SYSTEM
CONDENSING
UNIT
(EXTERIOR)
1 2
SPLIT SYSTEM
EVAPORATOR
UNIT
(INTERIOR)
3
1
ROOF
SILICONE UV
STABLE SEALANT DUCT
BUTLE CAULK
20 GA GALVANIZED STEEL
COUNTER FLASHING
SHEET METAL
SCREW 8" OC
LOW EXPANSION FOAM
NON-SHRINK GROUT
(ALL AROUND)
DUCT
CAULK AIR TIGHT
BETWEEN SLEEVE
& DUCT (TYPICAL)
DUCT SLEEVE
WALL
UNINSULATED
SILICONE CAULK CONTINUOUS
BEAD PRIOR TO ANGLE BEING
INSTALLED
1 1/2" X 1 1/2" X 1/8"
GALVANIZED CLOSED
ANGLE ALL SIDES WITH
SCREWS 12" OC MINIMUM 2
PER SIDE
NON-SHRINK GROUT
(ALL AROUND)
DUCT
FIELD APPLIED
DUCT INSULATION.
RUN CONTINUOUS
THRU WALL DUCT SLEEVE
WALL
INSULATED
SILICONE CAULK CONTINUOUS
BEAD PRIOR TO ANGLE BEING
INSTALLED
1 1/2" X 1 1/2" X 1/8"
GALVANIZED CLOSED
ANGLE ALL SIDES WITH
SCREWS 12" OC MINIMUM 2
PER SIDE
MAIN DUCT
STRAIGHT
3/4 D THROAT
RADIUS
MAY BE USED ANYWHERE 45°D-3/4 D HEEL R
BRANCH DUCT
BALANCING DAMPER (BD)
MAIN DUCT
6"
45°
BRANCH DUCT
BALANCING DAMPER (BD)
USE ONLY AT LAST TAKEOFF BEFORE OUTLETS & THEN ONLY WHERE
RECTANGULAR RUNOUTS ARE INDICATED ON DRAWINGS
MAIN DUCT
6"
45°
BRANCH DUCT
BALANCING DAMPER (BD)RECTANGULAR
ROUND
USE ONLY AT LAST TAKEOFF BEFORE OUTLETS & THEN ONLY
WHERE ROUND RUNOUTS ARE INDICATED ON DRAWINGS
THIS CONNECTION SHALL BE USED AT ALL BRANCHES FROM MAINS AND SUB-MAINS. BALANCING
DAMPERS SHALL BE PROVIDED AS SHOWN IN ADDITION TO THOSE INDICATED ON THE PLANS.
METAL STUD
RECTANGULAR OR
ROUND DUCTWORK
SHEETMEAL
SAFING ALL AROUND
(MIN. 22 GA.)
ACOUSTIC LINING
WHERE REQUIRED
SECURE SLEEVE TO SAFING
SHEETMEAL SLEEVE (MIN. 22 GA.)
ALL AROUND FOR DUCTS WITH
EXTERNAL INSULATION DRYWALL PARTITION
INSULATED TIGHT
TO SLEEVE
EXTERNAL INSULATION
WHERE REQUIRED
RECTANGULAR OR
ROUND DUCTWORK
CAULK ALL AROUND
COUNTER FLASHING
PREFABRICARED, INSULATED
CURB, MOUNT AND SECURE
ON WOOD NAILER.(BASE)
BASE FLASHING
INSULATION
BUILT UP
ROOF
WOOD
NAILER
SHEETMETAL
SAFING TIGHT
TO DUCT
CONCRETE DECK
WOOD NAILER
DUCT SUPPORT
INSULATION
WHERE REQUIRED
12"
MIN.
NON-SHRINK GROUT
(ALL AROUND)
RECTANGULAR
DUCT
FIELD APPLIED
DUCT INSULATION.
RUN CONTINUOUS
THRU WALL
DUCT SLEEVE
BLOCK WALL
INSULATED
UNION
REMOVABLE CAP
FULL SIZE
OF DRAIN
CONNECTION
DRAIN PAN
EACH DIMENSION IS
EQUAL TO FAN NEGATIVE
STATIC PRESSURE
APPROVED
AIR CAP
HEIGHT
LOCAL ROOF DRAIN
FLOOR DRAIN, OR
FLOOR SINK.
STIFFEN
BLADE AS
REQUIRED INSULATION
DUCT
INSULATION
STAND-OFF
DAMPER BLADE
HANDLE WITH
LOCKING
QUADRANT
INSIDE END
BEARING
1/8" CLEARANCE
ALL AROUND
1/2" ROUND
ROD PIN
OUTSIDE END BEARING
SIDE ELEVATION SECTION
DELETE INSULATION STAND-OFF ON DUCTWORK WITHOUT EXTERIOR INSULATION.
DETAIL SHOWS SINGLE BLADE DAMPER. DAMPER INSTALLATION SHALL BE SIMILAR
FOR MULTI-BLADE DAMPERS & ROUND DAMPERS.
1.
2.
NOTE:
DUCT
COLLAR
FLEX DUCT MAX. 6'-0"
FLEX DUCT SIZE SHALL
MATCH DIFFUSERR NECK SIZE
LAY-IN T-BAR
OR GWB
CEILING
OPPOSED BLADE
DAMPER (WHEN
SCHEDULED)
CEILING DIFFUSER
DRAW BAND WITH SILICONE SEALER
MANUAL VOLUME DAMPER WITH LOCKING
QUADRANT. PROVIDE ACCESS DOOR WHEN
LOCATED ABOVE GWB CEILING OR OTHER
INACCESSIBLE LOCATION
SUPPORT STRAPS FROM CEILING
TO PREVENT KINKING OR LAYING
ON CEILING.
SUPPLY AIR
DUCT
RETURN AIR
DUCT
ROOF
CURB CONDENSATE
TRAP AND DRAIN
TO POWER
SUPPLY
CONTROL
WIRING
TO INDOOR
THERMOSTAT
FIELD SUPPLIED FUSED
DISCONNECT SWITCH
ECONOMIZER HOOD
DUCT MOUNTED SMOKE DETECTOR
(FURNISHED BY E.C., INSTALLED BY
M.C., WIRED BY E.C.)
w w w . l i t t l e o n l i n e . c o m
This drawing and the design shown are the property
of Little Diversified Architectural Consulting. The
reproduction, copying or other use of this drawing
without their written consent is prohibited and any
infringement will be subject to legal action.
Little 2017c
PROJECT MANAGER
DESIGN TEAM
PRINCIPAL IN CHARGE
PROJECT TEAM
REVISIONS
PROJECT NAME
SHEET TITLE
PROJECT NO.
SHEET NUMBER
ISSUE FOR
ISSUE DATE
B
1 2 3 4 5 6 7
A
C
D
E
F
410 Blackwell Street, Suite 10
Durham, NC 27701
T: 919.474.2500
10/6/2017 2:33:38 PM C:\Users\rob.bell\Documents\513.7505.00_CU_WrestlingExpansion_M-16_rob.bell.rvt513.7505.00
06/22/17
M5.0.1
MECHANICAL DETAILS
Campbell Convocation
Center Wrestling
Department Renovation
and Expansion
BID/PERMIT SET
Rob Klinedinst
Katie Buckman
M.GRUBBS, R.BELL
NOT TO SCALEM5.0.1
4D EQUIPMENT POWER CONNECTION DETAIL
NOT TO SCALEM5.0.1
3E ROOF CURB DETAIL
NOT TO SCALEM5.0.1
1C DUCT PENETRATION DETAIL
NOT TO SCALEM5.0.1
4A BRANCH CONNECTION DETAILS
NOT TO SCALEM5.0.1
1E DUCT PENETRATION THROUGH NON FIRE RATED WALL
NOT TO SCALEM5.0.1
4C DUCT PENETRATION THROUGH ROOF
NOT TO SCALEM5.0.1
6A RECTANGULAR DUCT WALL PENETRATION DETAIL
NOT TO SCALEM5.0.1
6B CONDENSATE DRAIN TO TERMINATION DETAIL
NOT TO SCALEM5.0.1
3D VOLUME DAMPER DETAIL
NOT TO SCALEM5.0.1
6C TYPICAL DIFFUSER CONNECTION
NOT TO SCALEM5.0.1
2A ROOFTOP PACKAGED HVAC UNIT DETAIL
NO. REASON DATE
NOTES:
1.PROVIDE UNIT WITH MANUFACTURER'S INSULATED ROOF CURB.
2.UNIT SHALL BE CAPABLE OF FULL ECONOMIZER OPERATION
3.CONNECT UNIT INTO EXISTING CONTROL SYSTEM AND BAS. COORDINATE WITH FACILITIES STAFF. ALL CONTROLS AND SENSORS SHALL BE FACTORY MOUNTED.
4.PROVIDE WITH SINGLE POINT ELECTRICAL CONNECTION AND INTEGRAL, NON-FUSED DISCONNECT.
5.ELECTRICAL CONTRACTOR SHALL FURNISH RETURN AIR SMOKE DETECTOR, TO BE INSTALLED BY MECHANICAL CONTRACTOR AND WIRED BY ELECTRICAL CONTRACTOR.
6.PROVIDE INSULATED CASE WITH R-13 INSULATION.
7.FANS SHALL BE INTERNALLY ISOLATED.
8.COIL CONDENSATE PAN SHALL BE STAINLESS STEEL CONSTRUCTION. ROUTE CONDENSATE TO NEAREST ROOF DRAIN.
9.PROVIDE MANUFACTURER'S HOT GAS REHEAT OPTION WITH HUMIDISTAT IN RETURN AIR DUCT.
NOTES:
1.REFER TO ARCHITECTURAL CEILING PLANS FOR EXACT LOCATION OF ALL AIR DEVICES
2.PROVIDE MANUFACTURER'S FACE ACCESSED BALANCING DAMPER OPTION FOR ALL AIR DEVICES MOUNTED IN HARD CEILINGS.
3.PROVIDE MANUFACTURER'S INTEGRAL AIR SCOOP AND BALANCING DAMPER FOR ALL AIR DEVICES MOUNTED ON EXPOSED DUCTWORK.
4.SUBMIT MANUFACTURER'S COLOR PALLETTE FOR APPROVAL BY ARCHITECT.
5.DIFFUSERS EXPOSED IN GYM SHALL BE PROVIDED WITH MANUFACTURER'S PRIME COAT ONLY. DUCT, DIFFUSERS, AND GRILLES SHALL BE PAINTED BY GENERAL CONTRACTOR.
6.EXISTING AIR DEVICE TO BE RELOCATED, SHOWN FOR COORDINATION ONLY.
AIR HANDLING UNITS:
1.THE AIR HANDLING UNITS SHALL BE PROVIDED WITH PROGRAMMABLE THERMOSTATS - REFER TO
SPECIFICATIONS AND EQUIPMENT SCHEDULES.
2.IF SMOKE IS DETECTED IN THE DUCT MOUNTED SMOKE DETECTORS LOCATED IN RETURN DUCTWORK
SERVING RTU-1 OR RTU-2, A SIGNAL SHALL BE SENT TO THE FACP, THE UNIT SHALL BE DE-ENERGIZED,
3.UNOCCUPIED MODE:
i.THE SUPPLY FAN SHALL BE OFF AND THE OUTDOOR AIR DAMPER SHALL BE CLOSED.
ii.ON A CALL FOR COOLING, THE SUPPLY FAN SHALL START AND THE SYSTEM SHALL UTILIZE
INTERNAL CONTROL LOGIC TO ENERGIZE THE COMPRESSOR TO MAINTAIN SPACE TEMPERATURE.
ONCE SPACE TEMPERATURE IS SATISFIED, THE SUPPLY FAN AND COMPRESSOR SHALL STOP.
iii.ON A CALL FOR HEATING, THE SUPPLY FAN SHALL START AND THE SYSTEM SHALL UTILIZE
INTERNAL CONTROL LOGIC TO ENERGIZE THE COMPRESSOR TO MAINTAIN SPACE TEMPERATURE.
ONCE SPACE TEMPERATURE IS SATISFIED, THE SUPPLY FAN AND COMPRESSOR SHALL STOP. IF
THE COMPRESSOR ALONE CANNOT MAINTAIN SPACE TEMPERATURE, THE ELECTRIC HEATING
ELEMENT SHALL BE UTILIZED.
iv.AN OVERRIDE SWITCH SHALL INITIATE OVERRIDE OF UNOCCUPIED MODE TO OCCUPIED MODE WHEN
ACTIVATED BY THE OCCUPANT. THE OVERRIDE SHALL BE LIMITED TO 2-HOURS (ADJUSTABLE).
4.OCCUPIED MODE:
i.THE SUPPLY FAN SHALL BE ON AND THE OUTDOOR AIR DAMPER SHALL BE OPEN TO MINIMUM
POSITION.
ii.ON A CALL FOR COOLING, THE SYSTEM SHALL UTILIZE INTERNAL CONTROL LOGIC TO ENERGIZE THE
COMPRESSOR TO MAINTAIN SPACE TEMPERATURE. ONCE SPACE TEMPERATURE IS SATISFIED THE
COMPRESSOR SHALL STOP.
iii.ON A CALL FOR HEATING, THE SYSTEM SHALL UTILIZE INTERNAL CONTROL LOGIC TO ENERGIZE THE
COMPRESSOR TO MAINTAIN SPACE TEMPERATURE. ONCE SPACE TEMPERATURE IS SATISFIED THE
COMPRESSOR SHALL STOP.
iv.THE ELECTRIC HEATING ELEMENT SHALL BE ENERGIZED TO SUPPLEMENT THE COMPRESSOR WHEN
THE COMPRESSOR ALONE CANNOT MAINTAIN SPACE SETPOINT. PROVIDE CONTROLS TO PREVENT
THE ELECTRIC HEATER FROM BEING ENERGIZED WHEN THE HEATPUMP CAN MEET THE HEATING
LOAD - EXCEPT DURING DEFROST. PROVIDE ADDITIONAL CONTROLS TO PREVENT THE ELECTRIC
HEATER FROM BEING ENERGIZED IF OUTDOOR AIR TEMPERATURE IS ABOVE 40°F.
SEQUENCE OF OPERATION
RAEA
OA
THSD
M
N.C.
BI - RA SMOKE DETECTOR
AI - RA HUMIDITY
AI - RA TEMP
M N.O.AO - MIXED AIR DAMPERS
M
N.C.
DP
AI - PREFILTER
DIFFERENTIAL PRESSURE
T
AI - MIXED AIR TEMP
T
BI - FREEZESTAT
BI - FAN STATUS
BO - FAN START/STOP
CT
STARTER
BO - COOLING STAGE 1
BO - HEATING STAGE 1
DX
DP
AI - FINAL FILTER
DIFFERENTIAL PRESSURE
T
AI - SA TEMP
ELEC
BO - ELECTRIC HEATING STAGE 1
BO - ELECTRIC HEATING STAGE 2
SA
H
AI - MIXED AIR HUMIDITY
BI - OCCUPANT OVERRIDE
AI - SPACE TEMP
T
w w w . l i t t l e o n l i n e . c o m
This drawing and the design shown are the property
of Little Diversified Architectural Consulting. The
reproduction, copying or other use of this drawing
without their written consent is prohibited and any
infringement will be subject to legal action.
Little 2017c
PROJECT MANAGER
DESIGN TEAM
PRINCIPAL IN CHARGE
PROJECT TEAM
REVISIONS
PROJECT NAME
SHEET TITLE
PROJECT NO.
SHEET NUMBER
ISSUE FOR
ISSUE DATE
B
1 2 3 4 5 6 7
A
C
D
E
F
410 Blackwell Street, Suite 10
Durham, NC 27701
T: 919.474.2500
10/6/2017 2:33:39 PM C:\Users\rob.bell\Documents\513.7505.00_CU_WrestlingExpansion_M-16_rob.bell.rvt513.7505.00
06/22/17
M6.0.1
MECHANICAL
SCHEDULES AND
CONTROL DIAGRAM
Campbell Convocation
Center Wrestling
Department Renovation
and Expansion
BID/PERMIT SET
Rob Klinedinst
Katie Buckman
M.GRUBBS, R.BELL
DIFFUSERS, REGISTERS, & GRILLES SCHEDULE
MARK SERVICE
AIR PERFORMANCE CONSTRUCTION
MANUFACTURER MODEL NOTES
MINIMUM
FLOW
MAXIMUM
FLOW
PRESSURE
DROP
THROW AT 100
FPM
SOUND
RATING (NC)MOUNTING FACE TYPE NECK SIZE FACE SIZE MATERIAL COLOR
A6 SUPPLY 80 CFM 140 CFM 0.03 in-wg 3' - 0" 15 SURFACE SQUARE PLAQUE 6" 24"x24" ALUMINUM WHITE PRICE ASPD 1-2, 4
A8 SUPPLY 140 CFM 245 CFM 0.06 in-wg 4' - 0" 15 SURFACE SQUARE PLAQUE 8" 24"x24" ALUMINUM WHITE PRICE ASPD 1-2, 4
A10 SUPPLY 220 CFM 380 CFM 0.09 in-wg 6' - 0" 18 SURFACE SQUARE PLAQUE 10" 24"x24" ALUMINUM WHITE PRICE ASPD 1-2, 4
A12 SUPPLY 315 CFM 550 CFM 0.13 in-wg 7' - 0" 21 SURFACE SQUARE PLAQUE 12" 24"x24" ALUMINUM WHITE PRICE ASPD 1-2, 4
B16x8 SUPPLY 155 CFM 260 CFM 0.02 in-wg 23' - 0" 15 SIDEWALL DOUBLE DEFLECTION 16"x8" 18"x10" ALUMINUM WHITE PRICE 620-D
C6 RETURN 15 CFM 100 CFM 0.04 in-wg 0" 15 SURFACE PERFORATED FACE 6"ø 24"x24" ALUMINUM WHITE PRICE APDDR 1-2, 4
C10 RETURN 110 CFM 275 CFM 0.04 in-wg 0" 15 SURFACE PERFORATED FACE 10"ø 24"x24" ALUMINUM WHITE PRICE APDDR 1-2, 4
C12 RETURN 150 CFM 400 CFM 0.04 in-wg 0" 15 SURFACE PERFORATED FACE 12"ø 24"x24" ALUMINUM WHITE PRICE APDDR 1-2, 4
C14 RETURN 200 CFM 515 CFM 0.04 in-wg 0" 15 SURFACE PERFORATED FACE 14"ø 24"x24" ALUMINUM WHITE PRICE APDDR 1-2, 4
C15 RETURN 245 CFM 610 CFM 0.04 in-wg 0" 15 SURFACE PERFORATED FACE 15"ø 24"x24" ALUMINUM WHITE PRICE APDDR 1-2, 4
D18x12 RETURN 270 CFM 540 CFM 0.06 in-wg 0" 21 SIDEWALL LOUVERED 18"x12" 20"x14" ALUMINUM PRIME COAT PRICE 635-D 1, 3, 5
E6x6 EXHAUST 15 CFM 125 CFM 0.04 in-wg 0" 15 SURFACE PERFORATED FACE 6"x6" 24"x24" ALUMINUM WHITE PRICE APDDR 1-2, 4
E8x8 EXHAUST 15 CFM 225 CFM 0.04 in-wg 0" 15 SURFACE PERFORATED FACE 8"x8" 24x24 ALUMINUM WHITE PRICE APDDR
XE-6 EXHAUST 15 CFM 125 CFM 0.04 in-wg 0" 15 SURFACE PERFORATED FACE 6"x6" 24"x24" ALUMINUM WHITE PRICE APDDR 6
XE-10 EXHAUST 140 CFM 350 CFM 0.04 in-wg 0" 15 SURFACE PERFORATED FACE 10"x10" 24"x24" ALUMINUM WHITE PRICE APDDR 6
XR-8 RETURN 70 CFM 175 CFM 0.04 in-wg 0" 15 SURFACE PERFORATED FACE 8"ø 24"x24" ALUMINUM WHITE PRICE APDDR 6
XS-6 SUPPLY 80 CFM 140 CFM 0.03 in-wg 3' - 0" 15 SURFACE SQUARE PLAQUE 6" 24"x24" ALUMINUM WHITE PRICE ASPD 6
XS-10 SUPPLY 220 CFM 380 CFM 0.09 in-wg 6' - 0" 18 SURFACE SQUARE PLAQUE 10" 24"x24" ALUMINUM WHITE PRICE ASPD 6
PACKAGED ROOFTOP UNIT SCHEDULE - HEAT PUMP
MARK
COMPRESSOR DATA PERFORMANCE DATA
SOUND
RATING
SUPPLY FAN EVAPORATOR COIL AUXILIARY HEAT AIR FILTRATION ELECTRICAL DATA
MANUFACTURER MODEL NOTES
TYPE QUANTITY HP
REFRIGERANT
TYPE
COOLING
STAGES EER COP
PEAK
AIRFLOW
VENTILATION
AIRFLOW ESP TYPE MOTOR VFD/ECM?
COOLING OPERATION HEAT PUMP OPERATION
POWER STAGES
PREFILTER FINAL FILTER
VOLTAGE PHASE FREQUENCYTOTAL
CAPACITY
SENSIBLE
CAPACITY
ENTERING AIR LEAVING AIR TOTAL
HEATING
CAPACITY
AIR TEMPERATURE
EFFICIENCY TYPE EFFICIENCY TYPEDB WB DB WB
ENTERING
DB
LEAVING
DB
RTU-1 SCROLL 1 7.3 hp R-410A 1 11.1 3.4 89 2400 CFM 220 CFM 1.00 in-wg FC CENTRIFUGAL 1 hp No 94,800.0 Btu/h 54,100.0 Btu/h 75 °F 62 °F 55 °F 52 °F 92,100 Btu/h 68 °F 77 °F 27 kW 2 MERV 8 PLEATED MERV 13 PLEATED 480 V 3 60 Hz TRANE WSC-090 1-8
RTU-2 SCROLL 1 7.3 hp R-410A 1 11.1 3.4 89 2400 CFM 350 CFM 1.00 in-wg FC CENTRIFUGAL 1 hp No 94,800.0 Btu/h 54,100.0 Btu/h 75 °F 62 °F 55 °F 52 °F 92,100 Btu/h 68 °F 77 °F 27 kW 2 MERV 8 PLEATED MERV 13 PLEATED 480 V 3 60 Hz TRANE WSC-090 1-8
NOT TO SCALEM6.0.1
2 PACKAGED ROOFTOP HEAT PUMP CONTROLS SCHEMATIC
NO. REASON DATE
COMMUNICATIONS OUTLETS:
TELE/DATA OUTLETS
ABOVE COUNTER TOPS
LIGHT SWITCHES/OCCUPANCY WALL SWITCHES
ABOVE 36" COUNTER TOPS
GENERAL
RECEPTACLES:
UNLESS OTHERWISE NOTED
UNLESS OTHERWISE NOTED
UNLESS OTHERWISE NOTED
48"
44"
SAME AS ADJACENT RECEPTACLE
44"
18"
(DISTANCE FROM FINISHED FLOOR TO CENTER OF DEVICE, UNLESS OTHERWISE NOTED)
CABLE TV OUTLETS SAME AS ADJACENT RECEPTACLE
ABOVE OR ADJACENT TO LAVATORIES UNLESS OTHERWISE NOTED44"
BEHIND REFRIGERATORS UNLESS OTHERWISE NOTED52"
BEHIND WASHERS/DRYERS UNLESS OTHERWISE NOTED44"
NOTE: FOR ALL DEVICES LOCATED IN CMU WALL, INSTALL BOXES AS FOLLOWS: THE TOP OF THE BOX
SHALL MATCH THE TOP OF THE BLOCK COURSING. MOUNT BOXES AT 48" TO TOP FOR SWITCHES AND
16" TO BOTTOM OF BOXES FOR OUTLETS. WHERE OUTLETS ARE SHOWN TO BE MOUNTED HIGH,
ADJUST HEIGHT AS REQUIRED TO TOP OF BLOCK COURSING.
A AMPERES
AC ALETERNATING CURRENT OR
ABOVE COUNTER
A/E ARCHITECT/ENGINEER
AF AMPERE FRAME
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AHJ AUTHORITY HAVING JURISDICTION
AHU AIR HANDLING UNIT
ANSI AMERICAN NATIONAL STANDARDS
INSTITUTES, INC.
AT AMPERE TRIP
ASTM AMERICAN SOCIETY FOR TESTING
AND MATERIALS
ATS AUTOMATIC TRANSFER SWITCH
AWG AMERICAN WIRE GAUGE
BAS BUILDING AUTOMATION SYSTEM
BC BARE COPPER
BPS BOLTED PRESSURE SWITCH
C CONDUIT
CB CIRCUIT BREAKER
CBM CERTIFIED BALLAST MANUFACTURERS
CATV COMMUNITY ANTENNA TELEVISION
CCTV CLOSED CIRCUIT TELEVISION
cd CANDELA RATING
CFL COMPACT FLUORESCENT
CKT CIRCUIT
CLG CEILING
CT CURRENT TRANSFORMER
CU COPPER
DB DIRECT BURIAL
dBA DECIBEL LEVEL
DC DIRECT CURRENT
DISP GARBAGE DISPOSAL
DN DOWN
DWG DRAWING
E.C.ELECTRICAL CONTRACTOR
EC EMPTY CONDUIT
EF EXHAUST FAN
EG EQUIPMENT GROUND
ELBU EMERGENCY LIGHTING BATTERY UNIT
EM EMERGENCY
EMR EQUIPMENT MANUFACTURER REQUIREMENT
EMT ELECTRIC METALLIC TUBING
ETR EXISTING TO REMAIN
EUH ELECTRIC UNIT HEATER
EWC ELECTRIC WATER COOLER
EX EXISTING
F FUSE
FA FIRE ALARM
FAAP FIRE ALARM ANNUNCIATOR PANEL
FACP FIRE ALARM CONTROL PANEL
FCU FAN COIL UNIT
FDAS FIRE DETECTION ALARM SYSTEM
FLUOR FLUORESCENT
FPVAV FAN POWERED VARIABLE AIR VOLUME BOX
G.C.GENERAL CONTRACTOR
GF,GFI GROUND FAULT CIRCUIT INTERRUPTER
GFR GROUND FAULT RELAY
G, GND GROUND
HH HANDHOLE
HOA HAND OFF AUTOMATIC
HP HORSEPOWER
HZ HERTZ
IG ISOLATED GROUND
IMC INTERMEDIATE METAL CONDUIT
JB JUNCTION BOX
KCMIL THOUSAND CIRCULAR MILS
KW KILOWATT
KV KILO VOLT
KVA KILO VOLT-AMPERE
L LOCKING
LCP LIGHTING CONTROL PANEL
LV LOW VOLTAGE
MATV MASTER ANTENNA TELEVISION
M.C.MECHANICAL CONTRACTOR
MCB MAIN CIRCUIT BREAKER
MCC MOTOR CONTROL CENTER
MDP MAIN DISTRIBUTION PANEL
MDS MAIN DISTRIBUTION SWITCHBOARD
MLO MAIN LUGS ONLY
MH MANHOLE
MSP MOTOR STARTER PANEL
MT MOUNT
MTS MANUAL TRANSFER SWITCH
MHT MOUNTING HEIGHT
MV MEDIUM VOLTAGE
MW MICROWAVE
N NEUTRAL
NC NORMALLY CLOSED
NEC NATIONAL ELECTRICAL CODE
NEMA NATIONAL ELECTRICAL MANUFACTURERS
ASSOCIATION
NIC NOT IN CONTRACT
NF NON FUSED
NFPA NATIONAL FIRE PROTECTION ASSOCIATION
NL NIGHT LIGHT
NO NORMALLY OPEN
NTS NOT TO SCALE
PA PUBLIC ADDRESS
PB PULLBOX
PH.PHASE
P POLE
PNL PANLEBOARD
PT POTENTIAL TRANSFORMER
PWR POWER
Q QUARTS RESTRIKE LAMP
R RACEWAY
REC.RECEPTACLE
RECEPT.
REF REFRIGERATOR
RL RELOCATE EXISTING
RM ROOM
RMC RIGID METAL CONDUIT
RS RAPID START
RV REMOVE EXISTING
SA SURGE ARRESTOR
SN SOLID NEUTRAL
SPD SURGE PROTECTION DEVICE
SS SAFETY SWITCH
SW SWITCH
SWBD SWITCHBOARD
SWGR SWITCHGEAR
TTB TELEPHONE TERMINAL BOARD
TTC TELEPHONE TERMINAL CABINET
TEL TELEPHONE
TV TELEVISION
TVSS TRANSIENT VOLTAGE SURGE SUPPRESSOR
TYP TYPICAL
UC UNDER COUNTER
UH UNIT HEATER
UL UNDERWRITERS' LABORATORIES, INC.
UON UNLESS OTHERWISE NOTED
UPS UNINTERRUPTIBLE POWER SUPPLY
V VOLTS
VP VAPOR PROOF
VAV VARIABLE AIR VOLUME BOX
VFD VARIABLE FREQUENCY DRIVE
W WIRE, WATTS
WAP WIRELESS ACCESS POINT
WH WATER HEATER
WP WEATHERPROOF
XFMR TRANSFORMER
METHOD OF COMPLIANCE:
ELECTRICAL SYSTEM AND EQUIPMENT
PerformanceEnergy Code:
PerformanceASHRAE 90.1:
SEE LIGHTING FIXTURE SCHEDULElamp type required in fixture
minimum exterior source efficacy specified vs allowed
506.2.3 Energy Recovery Ventilation System
506.2.2 Reduced Lighting Power Density
506.2.1 More Efficient Mechanical Equipment
Additional Prescriptive Compliance
total interior wattage specified vs allowed (whole building or space by space)
total wattage per fixture
number of ballasts in fixture
ballast type used in the fixture
number of lamps in fixture
506.2.5 On-Site Supply of Renewable Energy
506.2.4 Higher Efficiency Service Water Heating
MIN. 60 LUMENS/WATT
Lighting schedule
SEE LIGHTING FIXTURE SCHEDULE
SEE LIGHTING FIXTURE SCHEDULE
SEE LIGHTING FIXTURE SCHEDULE
SEE LIGHTING FIXTURE SCHEDULE
10,645 WATTS / 6792 WATTS
506.2.6 Automatic Daylighting Control Systems
ALL WORK SHALL BE IN ACCORDANCE WITH THE NATIONAL ELECTRICAL CODE (NFPA 70 - 2014 EDITION), THE NATIONAL FIRE ALARM CODE (NFPA 72),
THE NATIONAL LIFE SAFETY CODE (NFPA 101), THE AMERICANS WITH DISABILITIES ACT (ADA), ALL OTHER APPLICABLE LOCAL, STATE, AND NATIONAL
CODES, AND ALL AUTHORITIES HAVING JURISDICTION.
CONTRACTOR SHALL OBTAIN ALL PERMITS AND PAY SUCH FEES AS MAY BE NECESSARY FOR INSPECTIONS, TESTS, AND OTHER SERVICES NEEDED
FOR THE COMPLETION OF WORK.
IT IS THE INTENT OF THESE DRAWINGS AND OTHER RELATED DOCUMENTS TO PRODUCE A COMPLETE AND FUNCTIONING ELECTRICAL SYSTEM. THE
CONTRACTOR SHALL PROVIDE ALL LABOR, MATERIALS, AND OTHER SERVICES AS MAY BE NECESSARY TO ACHIEVE THIS PRODUCT. IT SHALL BE THE
RESPONSIBILITY OF THE CONTRACTOR TO BRING TO THE ATTENTION OF THE ENGINEER ANY DISCREPANCIES IN THE PLANS AND SPECIFICATIONS THAT
WILL AFFECT THE WORK, PRIOR TO SUBMISSION OF THE PRICE.
ALL MATERIAL SHALL BE NEW AND BEAR THE UL LABEL INDICATING THE LISTING FOR ITS INSTALLED APPLICATION.
CONTRACTOR SHALL UTILIZE ARCHITECTURAL REFLECTED CEILING PLANS FOR EXACT LOCATIONS OF LIGHTING FIXTURES AND ALL OTHER
LIGHTING/ELECTRICAL/SPECIAL SYSTEMS CEILING DEVICES.
CONTRACTOR SHALL UTILIZE MECHANICAL/PLUMBING PLANS FOR EXACT LOCATIONS OF ALL MECHANICAL/PLUMBING EQUIPMENT.
ELECTRICAL DRAWINGS ARE DIAGRAMMATIC. DO NOT SCALE DRAWINGS EXCEPT WHERE DIMENSIONS ARE SHOWN.
CONTRACTOR TO CONSULT PLANS OF ALL OTHER TRADES FOR COORDINATION AND FOR RELATED AND ADJOINING WORK.
CONTRACTOR TO CONSULT ARCHITECTURAL AND STRUCTURAL PLANS AND DETAILS FOR CONSTRUCTION TYPE, HEADROOM, CEILINGS, FINISHES, ETC.
CONTRACTOR TO COORDINATE ALL CONDUITS AND ELECTRICAL DEVICES/BOXES WITH ARCHITECT AS RELATED TO WALL CONSTRUCTION TYPE PRIOR
TO INSTALLATION.
ALL CONDUCTORS IN ELECTRICAL SYSTEM SHALL BE NO. 12 AWG COPPER MINIMUM UNLESS SPECIFICALLY LABELED OTHERWISE OR AS REQUIRED BY
SPECIFICATIONS OR CODE. THE CORRECT NUMBER OF WIRES MAY NOT BE INDICATED FOR ALL CIRCUITS, ONLY THOSE WHERE CLARIFICATION IS
NECESSARY. THE CONTRACTOR SHALL PROVIDE ALL WIRES NECESSARY FOR THE PROPER FUNCTION OF THE SYSTEM.
ALL EMPTY CONDUIT RUNS IN EXCESS OF 10 FEET SHALL BE PROVIDED WITH A PULL STRING OR FISH TAPE.
RACEWAYS SHALL BE CONCEALED IN FINISHED SPACES AND AS PER SPECS. WHERE APPLICABLE, EXPOSED CONDUITS MOUNTED TO STRUCTURE
SHALL BE RUN AS INCONSPICUOUSLY AS POSSIBLE, AND SHALL BE PAINTED TO MATCH SURFACE TO WHICH THEY ARE MOUNTED. CONDUITS SHALL
RUN PARALLEL TO BUILDING LINES. ALL EXPOSED JUNCTION BOXES SHALL BE WEATHERPROOF, WITH NO KNOCKOUT.
ALL DEVICES INDICATED AS REQUIRING AN ISOLATED GROUND CONNECTION SHALL BE SERVED VIA A BRANCH CIRCUIT CONTAINING AN INSULATED
ISOLATED GROUND CONDUCTOR IN ADDITION TO AN INSULATED EQUIPMENT GROUNDING CONDUCTOR. THE ISOLATED GROUND CONDUCTOR SHALL BE
CONNECTED TO THE ISOLATED GROUND BUS IN THE PANELBOARD SERVING THE DEVICE.
PROVIDE "LOCKING" TYPE DEVICES ON ALL CIRCUIT BREAKERS THAT WILL SERVE EMERGENCY LIGHTING, SIGNS, FIRE ALARM SYSTEMS, AND
SECURITY SYSTEMS.
PROVIDE COMPLIANCE WITH ANSI A117.1 FOR ADA REQUIREMENTS.
CONTRACTOR SHALL INCREASE WIRE SIZE AS REQUIRED TO MAINTAIN A 5-PERCENT WORST CASE VOLTAGE DROP, FROM SERVICE ENTRANCE TO
FURTHEST DEVICE.
FOR MULTI-WIRE BRANCH CIRCUITS, CIRCUITS MUST BE PROVIDED WITH A MEANS TO DISCONNECT ALL PHASE CONDUCTORS SIMULTANEOUSLY AT THE
POINT OF ORIGINATION. IN COMPLIANCE WITH NFPA 70:210.4 (A) AND (B), MULTIWIRE BRANCH CIRCUITS, PROVIDE FOR ALL CIRCUITS IN EACH MULTI-
WIRE CIRCUIT TO BE CONNECTED TO SINGLE POLE BRANCH BREAKERS THAT ARE ADJACENT AND CONSECUTIVELY STACKED IN THE PANEL, AND
PROVIDE A HANDLE-TIE ON EACH GROUP OF SINGLE POLE BRANCH BREAKERS FORMING A MULTI-WIRE CIRCUIT.
IN COMPLIANCE WITH NFPA 70:210.4 (D), MULTI-WIRE BRANCH CIRCUITS, PROVIDE FOR ALL CIRCUIT CONDUCTORS OF EACH MULTI-WIRE BRANCH CIRCUIT
TO BE GROUPED AND TIED TOGETHER IN AT LEAST ONE LOCATION IN THE PANEL, UNLESS GROUPING IS OBVIOUS BY THE CONDUIT ENTRANCE.
MULTI-WIRE BRANCH CIRCUITS SHALL ONLY SERVE SINGLE POLE LINE-TO-NEUTRAL LOADS.
PROVIDE A #10 NEUTRAL CONDUCTOR FOR ALL MULTI-WIRE RECEPTACLE BRANCH CIRCUITS.
POWER RATINGS INDICATED ON DRAWINGS MAY DIFFER FROM THE ACTUAL EQUIPMENT FURNISHED. IF FURNISHED EQUIPMENT DIFFERS FROM
RATINGS ON THE DRAWINGS, CONTRACTOR SHALL NOTIFY ENGINEER FOR APPROPRIATE ACTION TO BE TAKEN.
HORSEPOWER RATINGS INDICATED ON DRAWINGS MAY DIFFER FROM THE ACTUAL EQUIPMENT FURNISHED. IF FURNISHED EQUIPMENT DIFFERS FROM
RATINGS ON THE DRAWINGS, THE CONTRACTOR SHALL NOTIFY ENGINEER FOR APPROPRIATE ACTION TO BE TAKEN.
PROVIDE APPROVED "HACR" TYPE CIRCUIT BREAKERS FOR ALL HEATING, AIR CONDITIONING, AND REFRIGERATION EQUIPMENT THAT IS INDICATED FOR
CONNECTION ON THE ELECTRICAL DRAWINGS.
THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE PROPER SIZING OF ALL MOTOR OVERLOAD DEVICES IN STARTERS, BASED ON ACTUAL
NAMEPLATE RATINGS ON THE MOTORS BEING INSTALLED.
CONTRACTOR SHALL NOTE UL LABELS ON PACKAGE-TYPE MECHANICAL EQUIPMENT. IF UL LABEL ON MECHANICAL EQUIPMENT CALLS FOR THE
OVERCURRENT PROTECTIVE DEVICE TO BE FUSES, THE CONTRACTOR SHALL PROVIDE A FUSED DISCONNECT SWITCH WITH PROPERLY SIZED FUSES
AT THE SWITCH LOCATION INDICATED ON THE DRAWINGS.
CONTRACTOR SHALL VERIFY WIRE SIZES, FUSE RATINGS, AND CIRCUIT BREAKER RATINGS FOR ALL HVAC EQUIPMENT, AND SHALL BRING TO THE
ATTENTION OF THE ENGINEER ANY DISCREPANCIES AFFECTING THE WORK, PRIOR TO PROCEEDING.
ALL ELECTRIC DRINKING FOUNTAINS SHALL BE PROTECTED WITH GROUND-FAULT CIRCUIT-INTERRUPTER PROTECTION. PROVIDE GFCI TYPE CIRCUIT
BREAKERS FEEDING ELECTRIC DRINKING FOUNTAINS (EWC).
ALL EXTERIOR RECEPTACLES SHALL BE LISTED WEATHER-RESISTANT TYPE, BE GFI PROTECTED AND HAVE AN ENCLOSURE/COVERPLATE THAT IS
WEATHERPROOF (WITH THE ATTACHMENT PLUG CAP INSERTED OR REMOVED). REFER TO SPECIFICATIONS.
ALL DEVICES (INCLUDING LIGHT SWITCH BOXES, ELECTRICAL OUTLET BOXES, AND FIRE ALARM PULL STATIONS) SHALL NOT BE RECESSED INTO THE
OUTER MEMBRANE OF EXIT STAIR ENCLOSURES. LOCATE THESE DEVICES AS REQUIRED. THERE SHALL BE NO PENETRATIONS INTO AND OPENINGS
THROUGH AN EXIT ENCLOSURE ASSEMBLY PER NFPA 101: 7.1.3.2.1(9).
ALL 125V, SINGLE PHASE, 15- AND 10-AMPERE RECEPTACLES INSTALLED IN THE LOCATIONS SPECIFIED BELOW SHALL HAVE GROUND-FAULT CIRCUIT-
INTERRUPTER PROTECTION FOR PERSONNEL: BATHROOMS, KITCHENS, BREAKROOMS, WITHIN 6' FEET OF SINKS, AND DISHWASHERS.
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
16.
17.
18.
19.
20.
21.
22.
23.
24.
25.
26.
27.
28.
29.
30.
WALL-MOUNTED OCCUPANCY SENSOR WITH (1) BUTTON, ON/OFF. EATON MODEL# OSP10M.M
LV
LV1
DECORATOR SWITCH, ON/OFF. EATON MODEL# 7601.
EXTERIOR LIGHTING FIXTURE, POST TOP MOUNTED OR BOLLARD, SUBSCRIPT
INDICATES TYPE (SEE LIGHTING FIXTURE SCHEDULE)
EXTERIOR POLE MOUNTED LIGHTING FIXTURE, SUBSCRIPT INDICATES TYPE (SEE
LIGHTING FIXTURE SCHEDULE)
WALL-MOUNTED OCCUPANCY SENSOR WITH RAISE/LOWER DIMMING. EATON MODEL# OS10D7.M1
DIMMER SWITCH, ALL ON/ALL OFF/RAISE/LOWER. EATON MODEL# WBSD-010DEC-C1.
T
30/3
3
3
30/3/3R
30/3/30/3R
-
PB
J J
J
J ******J
CP
MOTOR STARTER OR CONTROLLER. SUBSCRIPT INDICATES NEMA MOTOR SIZE.
COMBINATION MOTOR STARTER. FUSE SIZE AS INDICATED ON DRAWINGS. SUBSCRIPT
INDICATES NEMA MOTOR SIZE
MOTOR CONNECTION - HP AS INDICATED
DRY-TYPE DISTRIBUTION TRANSFORMER; FLOOR MTD or TRAPEZE / WALL
HUNG AS INDICATED ON PLANS
AV
JUNCTION BOX, CEILING-MOUNTED AND WALL-MOUNTED RESPECTIVELY
BRANCH CIRCUIT CONDUIT CONCEALED IN CEILING OR WALL (OR EXPOSED, WHERE
BRANCH CIRCUIT CONDUIT CONCEALED IN FLOOR OR UNDERGROUND
DUPLEX RECEPTACLE MOUNTED HIGH, ABOVE COUNTER / BACKSPLASH OR AS INDICATED
HOMERUN TO PANELBOARD - NUMBER OF ARROWS INDICATES NUMBER OF CIRCUITS
QUADRAPLEX RECEPTACLE, 20 AMP, 120V
CONCEALMENT IS NOT POSSIBLE)
CONDUIT TURNED UP
CONDUIT TURNED DOWN
480Y/277V PANELBOARD
208Y/120V PANELBOARD
SERVICE OR EQUIPMENT GROUND
POWER:
PULLBOX
GENERAL:
REPRESENTS FACE. PROVIDE WITH ARROWS AS INDICATED
EXIT SIGN, SINGLE-FACED AND DOUBLE-FACED RESPECTIVELY. SHADED AREA
LIGHTING:
DEDICATED WALL PHONE OUTLET, MOUNTED AT 44" AFF
SAME AS EXCEPT MOUNTED HIGH ABOVE COUNTER / BACKSPLASH, OR HEIGHT INDICATED
QUADRAPLEX RECEPTACLE MOUNTED ABOVE COUNTER OR BACKSPLASH
FUSED SAFETY SWITCH. SUBSCRIPT, IF USED, INDICATES AMPERAGE RATING/POLES/FUSE
SIZE/NEMA RATING
NON-FUSED SAFETY SWITCH. SUBSCRIPT, IF USED, INDICATES AMPERAGE
RATING/POLES/NEMA RATING
CIRCUIT BREAKER MOUNTED IN ENCLOSURE. FLUSH-MOUNTED OR SURFACE-MOUNTED
AS NOTED. SUBSCRIPT, IF USED, INDICATES TRIP RATING/POLES. AIC RATING AS
INDICATED ON DRAWINGS
4" SQUARE BOX WITH SINGLE-GANG OPENING AND PLASTER RING FOR A/V WITH 1-1/2"C
STUBBED OUT ABOVE NEAREST ACCESSIBLE CEILING, OR AS INDICATED ON DRAWINGS.
TERMINATE CONDUIT WITH PLASTIC PROTECTIVE RING AND PROVIDE PULL STRING
CEILING MOUNTED OCCUPANCY SENSOR. EATON MODEL# OAC-DT-2000-R.
COMBINATION TELEPHONE/DATA OUTLET. PROVIDE SINGLE-GANG BOX 18" AFF UON AND
1"C STUBBED OUT ABOVE ACCESSIBLE CEILING WITH PULLSTRINGS. PROVIDE 6-PORT RJ-45
** TYPICAL FOR ALL COMMUNICATIONS OUTLETS: TP = TAMPERPROOF C = CEILING MOUNTED
SUBSCRIPT, IF SHOWN, INDICATES # OF RJ-45 CONNECTIONS
DUPLEX RECEPTACLE, 20 AMP, 120V
LUMINAIRE, SUBSCRIPT INDICATES TYPE (SEE LIGHTING FIXTURE SCHEDULE)
SC
CONNECTION TO CEILING MOUNTED PROJECTION SCREEN. COORDINATE EXACT LOCATION
AND REQUIREMENTS WITH MANUFACTURER'S INSTALLATION REQUIREMENTS PRIOR TO
ROUGH-IN
** TYPICAL FOR ALL RECEPTACLES:
GFI = GROUND FAULT INTERRUPTER TYPE T = TVSS WP = WEATHERPROOF
EWC = ELECTRIC WATER COOLER IG = ISOLATED GROUND TP = TAMPERPROOF
TV = POWER FOR TELEVISION USB = DUPLEX WITH (2) USB PORTS
CR
SINGLE-GANG BOX FOR CARD READER WITH 1/2"C, REFER TO DETAIL 5/E5.1.2 FOR
ADDITIONAL POWER REQUIREMENTS
FLUSH MOUNTED FLOOR DEVICE WITH NUMBER OF RECEPTACLES AS INDICATED,
BLACK FINISH,SUBSCRIPT INDICATES TYPE. WHERE REQUIRED PROVIDE (1) 2" FOR
A/V, (1) 3/4" FOR POWER AND (1) 1-1/4" FOR TELE/DATA
TYPE A1: FLOOR BOX WITH AV PROVISIONS, TWO DUPLEX RECEPTACLES, AND DATA
CONNECTIONS: LEGRAND (BASIS OF DESIGN) WIREMOLD #RFB9-OG WITH (2)
#RFB119-SD, (2) #RFB119-SGFI, (2) #RFB119-AAP, (1) #RFB119-SB AND (1) RFB119CTCBK
OR APPROVED EQUAL BY HUBBELL OR LEVITON.
DROP CORD RECEPTACLE - SUBSCRIPT INDICATES AMPERAGE/NEMA
RATING; RECEPTACLE TO HANG AT 8'-0" AFF UON
PROJECTOR CEILING BOX WITH RECEPTACLES, REMOVABLE SHELVES, PROJECTOR
MOUNT; WIREMOLD #ECB2SP-RLNK
OCC
THREE WAY SWITCH (LOWERCASE SUBSCRIPT, IF SHOWN, INDICATES FIXTURE
CONTROLLED)3a
FOUR WAY SWITCH, EATON MODEL# 1224.4a
DAYLIGHT DIMMING SENSORDDS
WALL MOUNTED OCCUPANCY SENSOR, SEE SPECIFICATIONS
PHOTOCELL AND RELAYDEDICATED RECEPTACLE, SUBSCRIPT INDICATES AMPERAGE/NEMA RATING
SWITCHED RECEPTACLE
TRACK LIGHTING, LENGTH AS SHOWN ON DRAWINGS, QUANTITY OF HEADS AS SHOWN
ON DRAWINGS
EMERGENCY BATTERY PACK UNIT
COMBINATION EXIT/ EMERGENCY BATTERY PACK UNIT
POWER PACKPP*PC
TYPICAL CIRCUITING:
PP-5
HP-5
F2
CIRCUIT DESIGNATION
FIXTURE TYPE
CIRCUIT DESIGNATION
TYPICAL LIGHT FIXTURE
TYPICAL RECEPTACLE OR DEVICE
5
a
SWITCH DESIGNATION (IF MORE THAN ONE
SWITCH IN ROOM/AREA)
OR
OR
ALL F2
5HP-5
*FIXTURE TYPE APPLICABLE TO ROOM
CIRCUIT DESIGNATION*P D FURNITURE SYSTEMS POWER FEED, FLOOR MOUNTED, # OF CIRCUITS AS SHOWN
ON PLANS, WIREMOLD FURNITURE FEED 4FFATCA, PROVIDE CAT6 CABLES AS
REQUIRED FOR FURNITURE SYSTEMS. PROVIDE BUILDING STANDARD BACK TO
NEAREST IT ROOM
PFURNITURE SYSTEMS POWER FEED, THRU-WALL, # OF CIRCUITS AS SHOWN ON
PLANS
DFURNITURE SYSTEMS DATA FEED, WALL MOUNTED SINGLE GANG BOX, PROVIDE
CAT6 CABLES AS REQUIRED TO FURNITURE SYSTEMS, PER BUILDING STANDARD
BACK TO NEAREST IT ROOM
COAX OUTLET. PROVIDE SINGLE-GANG BOX 18" AFF UON AND 1"C STUBBED OUT ABOVE
ACCESSIBLE CEILING WITH PULLSTRINGS.
D
C CEILING MOUNTED DUPLEX RECEPTACLE, 20 AMP, 120V
OC or
DS or
WR = WEATHER RESISTANT
COMMUNICATIONS:
REF = REFRIGERATOR
MW = MICROWAVE UC = UNDERCOUNTER
FACEPLATE.
3LV 3 WAY DECORATOR SWITCH, ON/OFF. EATON MODEL# 7603.
CONTRACTOR SHALL VISIT THE SITE AND EXAMINE CONDITIONS OF THE PREMISES AND THE CHARACTER AND EXTENT OF WORK REQUIRED,
PRIOR TO SUBMITTING PRICING. ANY DIFFICULTIES IN COMPLYING WITH THE DRAWINGS AND SPECIFICATIONS SHALL BE BROUGHT TO THE
ATTENTION OF THE ENGINEER, BEFORE BEGINNING WORK.
ALL WORK SHALL BE DONE AT SUCH TIMES AND IN SUCH A MANNER AS WILL LEAST INTERFERE WITH THE MAINTENANCE AND OPERATION OF
ALL RELATED OR AFFECTED SYSTEMS. ALL POWER OUTAGES SHALL BE COORDINATED WITH OWNER.
EXISTING BOXES, CONDUIT, AND WIRING SHALL BE REUSED TO FURTHEST EXTENT PRACTICAL. SUPPLEMENT WHERE NEEDED.
WHERE EXISTING CIRCUITS ARE EXTENDED TO SERVE NEW OR RELOCATED DEVICES OR FIXTURES, PROVIDE TYPE AND SIZE OF
CONDUCTORS TO MATCH EXISTING.
EXISTING CIRCUITING SHALL BE FIELD VERIFIED AND ADJUSTMENTS SHALL BE MADE, IF NECESSARY, TO THE CIRCUITING SHOWN ON THE
PLANS AS REQUIRED BY FIELD CONDITIONS.
WHERE ELECTRICAL WORK PENETRATES EXISTING FIRE-RATED BARRIERS (WALLS, FLOORS, AND CEILINGS), SEAL OPENING AROUND
ELECTRICAL WORK WITH U.L. LISTED FIRE STOPPING MATERIAL TO MAINTAIN THE FIRE RATING OF THE BARRIER.
1.
2.
3.
4.
5.
6.
REMOVE ALL EXISTING FIXTURES, WIRING DEVICES, ELECTRICAL EQUIPMENT AND BRANCH CIRCUIT WIRING, AS REQUIRED BY THE
ARCHITECTURAL DEMOLITION WORK IN THE AREA TO BE RENOVATED. REMOVE WIRING BACK TO THE NEAREST POINT OF USAGE (SOURCE
OF VOLTAGE). FOR ITEMS TO BE REMOVED, REMOVE THE ENTIRE ELECTRICAL INSTALLATION, INCLUDING ALL ASSOCIATED CONDUIT,
JUNCTION BOXES, WIRING AND FITTINGS, INCLUDING CABLING AND SUPPORTS, SURFACE RACEWAY, ETC. REUSE EXISTING BOXES AND
CONDUIT WHERE PRACTICAL. ALL CONDUIT NOT TO BE REUSED SHALL BE REMOVED.
WHERE EXISTING FIXTURES, WIRING DEVICES, AND ELECTRICAL EQUIPMENT ARE REMOVED, RECONNECT CIRCUITING AS REQUIRED TO
MAINTAIN CONTINUITY TO OUTLETS REMAINING ON THE CIRCUIT WITHIN OCCUPIED SPACES.
WHERE REQUIRED BY NEW CONSTRUCTION, PROVIDE EXTENSION RINGS, COVERPLATES, OR ACCESS PLATES AS REQUIRED TO MAINTAIN
ACCESS TO EXISTING WIRING.
FIELD VERIFY LOCATIONS OF EXISTING OUTLETS. WHERE NEW CONSTRUCTION CONFLICTS WITH EXISTING OUTLETS, REMOVE WIRING
DEVICES OR RELOCATE FIXTURES AS REQUIRED.
WHERE EXISTING WIRING DEVICES ARE REMOVED AND JUNCTION BOXES ARE NOT REUSED, PROVIDE BLANK COVERPLATES.
WHERE EXISTING CIRCUITS ARE EXTENDED TO SERVE NEW OR RELOCATED DEVICES OR FIXTURES, PROVIDE TYPE AND SIZE OF
CONDUCTORS TO MATCH.
PROVIDE CUTTING AND PATCHING AS REQUIRED VERIFY EXTENT OF NEW AND EXISTING PARTITIONS WITH ARCHITECTURAL DRAWINGS.
EXISTING CIRCUITING SHALL BE FIELD VERIFIED AND ADJUSTMENTS SHALL BE MADE IF NECESSARY TO THE CIRCUITING SHOWN ON THE
PLANS, AS REQUIRED BY FIELD CONDITIONS.
1.
2.
3.
4.
5.
6.
7.
8.
w w w . l i t t l e o n l i n e . c o m
This drawing and the design shown are the property
of Little Diversified Architectural Consulting. The
reproduction, copying or other use of this drawing
without their written consent is prohibited and any
infringement will be subject to legal action.
Little 2017c
PROJECT MANAGER
DESIGN TEAM
PRINCIPAL IN CHARGE
PROJECT TEAM
REVISIONS
PROJECT NAME
SHEET TITLE
PROJECT NO.
SHEET NUMBER
ISSUE FOR
ISSUE DATE
B
1 2 3 4 5 6 7
A
C
D
E
F
410 Blackwell Street, Suite 10
Durham, NC 27701
T: 919.474.2500
10/6/2017 4:23:40 PM C:\Users\brenden.elliott\Documents\513.7505.00_CU_WrestlingExpansion_E-16_brenden.elliott.rvt513.7505.00
10/6/17
E0.0.0
ELECTRICAL
COVERSHEET
Campbell Convocation
Center Wrestling
Department Renovation
and Expansion
BID/PERMIT SET
Rob Klinedinst
Katie Buckman
LITTLE
GENERAL NOTES ABBREVIATIONS
ENERGY CODE
MOUNTING HEIGHTS
ELECTRICAL SYMBOL SCHEDULE
GENERAL NOTES (RENOVATION)
GENERAL NOTES (DEMOLITION)
NOTE: ALL SYMBOLS MAY NOT BE USED.NOTE: ALL ABBREVIATIONS MAY NOT BE USED.
NO. REASON DATE
CORPORATE LICENSE #F-0467
FIRE BARRIER FIRE & SMOKE BARRIER
1-HOUR
2-HOUR
3-HOUR
0.5-HOUR
1-HOUR
FIRE PARTITIONFIRE WALL
2-HOUR
3-HOUR
4-HOUR
1-HOUR
2-HOUR
3-HOUR
0-HOUR 1-HOUR
SMOKE BARRIERSMOKE PARTITION
REMOVE ALL ELECTRICAL DEVICES LOCATED ON WALLS TO BE
DEMOLISHED, INCLUDING RECEPTACLES AND TELEPHONE/DATA
OUTLETS, SURFACE RACEWAY, JUNCTION BOXES, AND ALL
ASSOCIATED CONDUIT AND WIRING, UNLESS OTHERWISE NOTED.
DEVICES SHOWN ARE MEANT TO AID THE CONTRACTOR AND ARE NOT
INTENDED TO SHOW EVERY DEVICE TO BE REMOVED.
FOR ITEMS TO BE REMOVED, REMOVE THE ENTIRE ELECTRICAL
INSTALLATION, INCLUDING ALL ASSOCIATED CONDUIT, JUNCTION
BOXES, WIRING AND FITTINGS, INCLUDING TELECOMMUNICATIONS
CABLING AND SUPPORTS, SURFACE RACEWAY, ETC. UNLESS NOTED
OTHERWISE. ALL CONDUIT NOT TO BE REUSED SHALL BE REMOVED.
REUSE EXISTING BOXES AND CONDUIT WHERE PRACTICAL.
EXISTING ELECTRICAL DEVICES, INCLUDING RECEPTACLES AND
TELEPHONE/DATA OUTLETS, LOCATED ON WALLS TO REMAIN SHALL
REMAIN, UNLESS NOTED OTHERWISE. DEVICES SHOWN ARE MEANT
TO AID THE CONTRACTOR AND ARE NOT INTENDED TO SHOW EVERY
DEVICE TO REMAIN.
PROVIDE CUTTING AND PATCHING AS REQUIRED. VERIFY EXTENT OF
NEW AND EXISTING PARTITIONS WITH ARCHITECTURAL DRAWINGS.
REMOVE ALL EXISTING WI-FI CEILING DEVICES AND PROTECT DURING
CONSTRUCTION. REINSTALL DEVICES IN NEW CEILING. COORDINATE
ASSOCIATED WORK WITH OWNER AND ARCHITECT. MAINTAIN
EXISTING SYSTEM'S COVERAGE AND OPERATIONAL INTEGRITY.
DEVICES SHOWN ARE MEANT TO AID THE CONTRACTOR AND ARE NOT
INTENDED TO SHOW EVERY DEVICE.
A.
B.
C.
D.
E.
F.
WRESTLING
GYM
101
WRESTLING
LOCKERS
111
Room
105
VESTIBULE
110
STAIR
103.3
RV
RV
EX
RV
RV
EX
RV
RV
RV
EX
EXEXEX
EX
EX
RV
RV
RV
RV
RV
RV
RV
RV
RV
RV
RV
RV
RV
RV
RV
RV
RV
RV
RV
eG
eF
eE.6
eE
e109
w w w . l i t t l e o n l i n e . c o m
This drawing and the design shown are the property
of Little Diversified Architectural Consulting. The
reproduction, copying or other use of this drawing
without their written consent is prohibited and any
infringement will be subject to legal action.
Little 2017c
PROJECT MANAGER
DESIGN TEAM
PRINCIPAL IN CHARGE
PROJECT TEAM
REVISIONS
PROJECT NAME
SHEET TITLE
PROJECT NO.
SHEET NUMBER
ISSUE FOR
ISSUE DATE
B
1 2 3 4 5 6 7
A
C
D
E
F
410 Blackwell Street, Suite 10
Durham, NC 27701
T: 919.474.2500
10/6/2017 4:23:50 PM C:\Users\brenden.elliott\Documents\513.7505.00_CU_WrestlingExpansion_E-16_brenden.elliott.rvt513.7505.00
10/6/17
ED1.1.1
DEMOLITION POWER
PLAN - CONVOCATION
AREA C
Campbell Convocation
Center Wrestling
Department Renovation
and Expansion
BID/PERMIT SET
Rob Klinedinst
Katie Buckman
LITTLE
X KEY NOTES
KEY PLAN
GENERAL SHEET NOTES
RATED WALL LEGEND
DEMO
EXISTING BUILDING
3/16" = 1'-0"ED1.1.1
1 CONVOCATION AREA C - DEMOLIITON POWER PLAN
NO. REASON DATE
CORPORATE LICENSE #F-0467
3 33
3333FIRE BARRIER FIRE & SMOKE BARRIER
1-HOUR
2-HOUR
3-HOUR
0.5-HOUR
1-HOUR
FIRE PARTITIONFIRE WALL
2-HOUR
3-HOUR
4-HOUR
1-HOUR
2-HOUR
3-HOUR
0-HOUR 1-HOUR
SMOKE BARRIERSMOKE PARTITION
WRESTLING
GYM
101
WRESTLING
LOCKERS
111
Room
105
RL
RL
RL
RL
RL
RL
RL
RV
RV
RV
RVRV
RV
RV
RV
RV
RV RL
RL
RV RV
RL
RL
RV
RL
EX
eG
eF
eE.6
eE
e10
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
9
EX
EX
REMOVE ALL LIGHTING SWITCHES LOCATED ON WALLS TO BE
DEMOLISHED, INCLUDING SURFACE RACEWAY, JUNCTION BOXES, AND
ALL ASSOCIATED CONDUIT AND WIRING, UNLESS OTHERWISE NOTED.
DEVICES SHOWN ARE MEANT TO AID THE CONTRACTOR AND ARE NOT
INTENDED TO SHOW EVERY DEVICE TO BE REMOVED.
FOR ITEMS TO BE REMOVED, REMOVE THE ENTIRE LIGHTING
INSTALLATION, INCLUDING ALL ASSOCIATED CONDUIT, JUNCTION
BOXES, WIRING AND FITTINGS, SURFACE RACEWAY, ETC. UNLESS
NOTED OTHERWISE. ALL CONDUIT NOT TO BE REUSED SHALL BE
REMOVED. REUSE EXISTING BOXES AND CONDUIT WHERE PRACTICAL.
EXISTING LIGHTING SWITCHES AND FIXTURES LOCATED ON WALLS OR
CEILINGS TO REMAIN SHALL REMAIN, UNLESS NOTED OTHERWISE.
DEVICES SHOWN ARE MEANT TO AID THE CONTRACTOR AND ARE NOT
INTENDED TO SHOW EVERY DEVICE TO REMAIN.
PROVIDE CUTTING AND PATCHING AS REQUIRED. VERIFY EXTENT OF
NEW AND EXISTING PARTITIONS WITH ARCHITECTURAL DRAWINGS.
DEVICES SHOWN ARE MEANT TO AID THE CONTRACTOR AND ARE NOT
INTENDED TO SHOW EVERY DEVICE.
A.
B.
C.
D.
E.
w w w . l i t t l e o n l i n e . c o m
This drawing and the design shown are the property
of Little Diversified Architectural Consulting. The
reproduction, copying or other use of this drawing
without their written consent is prohibited and any
infringement will be subject to legal action.
Little 2017c
PROJECT MANAGER
DESIGN TEAM
PRINCIPAL IN CHARGE
PROJECT TEAM
REVISIONS
PROJECT NAME
SHEET TITLE
PROJECT NO.
SHEET NUMBER
ISSUE FOR
ISSUE DATE
B
1 2 3 4 5 6 7
A
C
D
E
F
410 Blackwell Street, Suite 10
Durham, NC 27701
T: 919.474.2500
10/6/2017 4:23:51 PM C:\Users\brenden.elliott\Documents\513.7505.00_CU_WrestlingExpansion_E-16_brenden.elliott.rvt513.7505.00
10/6/17
ED1.2.1
DEMOLITION LIGHTING
PLAN - CONVOCATION
AREA C
Campbell Convocation
Center Wrestling
Department Renovation
and Expansion
BID/PERMIT SET
Rob Klinedinst
Katie Buckman
LITTLE
X KEY NOTES
KEY PLAN
GENERAL SHEET NOTES
RATED WALL LEGEND
DEMO
EXISTING BUILDING
3/16" = 1'-0"ED1.2.1
1 CONVOCATION AREA C - DEMOLITION LIGHTING PLAN
NO. REASON DATE
CORPORATE LICENSE #F-0467
CORRIDOR
1015
STAIR B
1020
FIRE PUMP
1016
ELECTRICAL
1017
BOILER
1014
CUSTODIAL
OFFICE
1018
ELEV
1019
ELEC.
1111
MENS
1112
FECFEC
J PDJ JJ
CORRIDOR
1108
STORAGE
MECHANICAL
1013
TELECOM
1106
ATS
1107SUPPLY
1105
MAINTENANCE
1104
CUSTODIAL
1103
HEAD COACH
OFFICE
1102
ASST COACH
OFFICE
1100
FIRE BARRIER FIRE & SMOKE BARRIER
1-HOUR
2-HOUR
3-HOUR
0.5-HOUR
1-HOUR
FIRE PARTITIONFIRE WALL
2-HOUR
3-HOUR
4-HOUR
1-HOUR
2-HOUR
3-HOUR
0-HOUR 1-HOUR
SMOKE BARRIERSMOKE PARTITION
MAINTAIN CIRCUITRY OF ALL EXISTING OUTLETS TO REMAIN, UNLESS
INDICATED OTHERWISE. PROVIDE ALL NECESSARY SUPPLEMENTAL
WIRING AND CONDUIT AS REQUIRED.
WHERE EXISTING CIRCUITRY IS REUSED, CONTRACTOR SHALL VERIFY
LOAD DOES NOT EXCEED 1,920 VA @ 120V (OR 4,432 VA @ 277V).
CONTRACTOR SHALL REUSE EXISTING BACKBOXES, CONDUIT AND
WIRING TO FURTHEST EXTENT PRACTICAL. SUPPLEMENT WHERE
NEEDED.
ALL NEW RECEPTACLES, TELEPHONE/DATA, AND COAX OUTLETS
SHALL BE FLUSH-MOUNTED. ALL NEW CONDUIT AND RACEWAY SHALL
BE CONCEALED. PROVIDE CUTTING AND PATCHING AS REQUIRED.
VERIFY EXTENT OF NEW AND EXISTING PARTITIONS WITH
ARCHITECTURAL DRAWINGS.
CONTRACTOR TO VERIFY ALL COAX AND TELE/DATA LOCATIONS WITH
OWNER, PRIOR TO ROUGH-IN. ALL COAX AND TELE/DATA CABLES TO
BE IN CONDUIT OR EXISTING CABLE TRAY SYSTEM. ALL COAX AND
DATA CABLING SHALL BE PER BUILDING STANDARD.
CONTRACTOR TO COORDINATE RECEPTACLE LOCATIONS IN STORAGE
106 WITH SHELVING.
A.
B.
C.
D.
E.
F.
MAIN SWITCHBOARD
(EXISTING)
FIRE ALARM
CONTROL PANEL
(EXISTING)
LIGHTING
CONTACTOR
(EXISTING)
ATS
SCRBD
1PLN3
1PLN2
1PLN1
1DLN
OS1DHN
(EXISTING)
(EXISTING)
(EXISTING)
(EXISTING)
(EXISTING)
(EXISTING)EX
1TN1 (EXISTING)
1DLN1
DISC.
(EXISTING)
1TN(EXISTING)
1LHN(EXISTING)
e10
1DLN1
(EXISTING)
1SLN1 (EXISTING)
1TN2
1PLN5 (NEW)
(NEW)
TRAPEZE HUNG
OVER PANEL '1PLN5'
EXISTING
GENERATOR
CONCRETE PAD.
CONTRACTOR
NOT TO USE.
eG
e10
eE.6
eE
eF
FITNESS
107
WRESTLING
GYM
101
COACH
105
ASST.
COACH
OFFICES
103
LOUNGE
108
CORRIDOR
102.1
RECEP.
102
CONF.
104
STOR.
106
COACH
LOCKERS
109
WRESTLING
LOCKERS
111
Room
105
VESTIBULE
110
TOILET
109.1
WRESTLING
GYM
ADDITION
101.1
STAIR
103.3
REF
AV
GFI
GFI
GFI
GFI
GFI
GFI
GFI
CR
CR
EX
EX
EXEXEX
EX
EX
ALL RECEPTACLES IN ROOM
SHALL BE GFCI PROTECTED
TYPE
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
GFI,WR
A1
54" AFF
54" AFF
54" AFF
54" AFF
eG
eF
eE.6
eE
e10
1PLN5-1
1PLN5-1
1PLN5-1
1PLN5-21PLN5-7
1PLN5-2
1PLN5-2
1PLN5-5
1PLN5-3
1PLN5-3
1PLN5-2
1PLN5-4
1PLN5-4
1PLN5-4
1PLN5-4
1PLN5-5
1PLN5-5
1PLN5-5
1PLN5-14
1PLN5-13
1PLN5-8
1PLN5-12
1PLN5-111PLN5-10
1PLN5-6 1PLN5-6
1PLN5-8 1PLN5-6
1PLN5-18
1PLN5-171PLN5-161PLN5-15
1PLN5-19
1PLN5-19
1PLN5-20
1PLN5-19
1PLN5-19
1PLN5-21
1PLN5-22
1PLN5-23
1PLN5-23
1PLN5-271PLN5-27
1PLN5-28
1PLN5-28
1PLN5-30
1PLN5-30
1PLN5-30
1PLN5-29
1PLN5-29
1PLN5-29
1PLN5-29
1PLN5-24
1PLN5-24
1PLN5-24
1PLN5-25
1PLN5-25
1PLN5-25
1PLN5-25
1PLN5-26
1PLN5-26
1PLN5-26
1PLN5-26
1PLN5-26
1PLN5-31,33,35 E1
ALL RECEPTACLES IN ROOM
SHALL BE GFCI PROTECTED
TYPE
1PLN5-30
1PLN5-28
1PLN5-32
1PLN5-32
1PLN5-32
1PLN5-5
72" AFF
72" AFF
72" AFF
E2
E1DHN
(EX)
E1LHN
E1TN
(EX)
E1PLN
(EX)
ATS #1
(EX)(EX)
1MHN1(EX)
w w w . l i t t l e o n l i n e . c o m
This drawing and the design shown are the property
of Little Diversified Architectural Consulting. The
reproduction, copying or other use of this drawing
without their written consent is prohibited and any
infringement will be subject to legal action.
Little 2017c
PROJECT MANAGER
DESIGN TEAM
PRINCIPAL IN CHARGE
PROJECT TEAM
REVISIONS
PROJECT NAME
SHEET TITLE
PROJECT NO.
SHEET NUMBER
ISSUE FOR
ISSUE DATE
B
1 2 3 4 5 6 7
A
C
D
E
F
410 Blackwell Street, Suite 10
Durham, NC 27701
T: 919.474.2500
10/6/2017 4:23:43 PM C:\Users\brenden.elliott\Documents\513.7505.00_CU_WrestlingExpansion_E-16_brenden.elliott.rvt513.7505.00
10/6/17
E1.1.1
POWER PLAN -
CONVOCATION AREA C
Campbell Convocation
Center Wrestling
Department Renovation
and Expansion
BID/PERMIT SET
Rob Klinedinst
Katie Buckman
LITTLE
X KEY NOTES
KEY PLAN
GENERAL SHEET NOTES
RATED WALL LEGEND
1/8" = 1'-0"E1.1.1
2 CONVOCATION ELECTRICAL ROOM 1017 - POWER PLAN
1/8" = 1'-0"E1.1.1
3
CONVOCATION ELECTRICAL ROOM 1111 -
POWER PLAN
ADDITION
EXISTING BUILDING
ELEC 1111
ELEC. 1017
MECH 1013 & ATS 1107
3/16" = 1'-0"E1.1.1
1 CONVOCATION AREA C - POWER PLAN
1/8" = 1'-0"E1.1.1
4 CONVOCATION ATS 1107 & MECHANICAL 1013 - POWER PLAN
E1 PROVIDE POWER TO OWNER'S EQUIPMENT. COORDINATE
LOCATION OF CONTOLLER WITH OWNER PRIOR TO ROUGH-IN.
PROVIDE 3P, 50A CIRCUIT BREAKER WITH 4#8, #10(G) IN 1"C.
PROVIDE ALL NECESSARY CONDUIT AND WIRING FOR
COMPLETE INSTALLATION. COORDINATE REQUIREMENTS WITH
OWNER AND MANUFACTURER.
E2 PROVIDE TELECOM AND AV PROVISIONS AS REQUIRED TO
POKE-THRU. PROVIDE 2" CONDUIT FROM POKE-THRU TO A/V
BOX ON WALL (VERIFY WITH VENDOR). PROVIDE WIREWAY AND
ALL NECESSARY COMPONENTS FOR COMPLETE INSTALLATION.
PROVIDE ALL REQUIRED RACEWAY TO ACCOMMODATE AV
VENDOR'S CABLING.
NO. REASON DATE
CORPORATE LICENSE #F-0467
FECFEC
OSLV OS
OSLV LVOS OS
LV1 LV1
LVLVLV
OS
OS
OS
OS
OS
LV
M
33
3344
3LVOS OS OS OS
OSOS
33
OS
LV1
3LV
OS33 33
44
FIRE BARRIER FIRE & SMOKE BARRIER
1-HOUR
2-HOUR
3-HOUR
0.5-HOUR
1-HOUR
FIRE PARTITIONFIRE WALL
2-HOUR
3-HOUR
4-HOUR
1-HOUR
2-HOUR
3-HOUR
0-HOUR 1-HOUR
SMOKE BARRIERSMOKE PARTITION
CONTRACTOR SHALL REUSE EXISTING CONDUIT AND WIRING TO
FURTHEST EXTENT PRACTICAL. SUPPLEMENT WHERE NEEDED.
ALL EXIT SIGNS AND NIGHT LIGHTS ('NL') SHALL BE ON UNSWITCHED
"HOT" LEG SERVING THE AREA, CONNECTED AHEAD OF SWITCH
SERVING AREA/ROOM. RECONNECT EXISTING FIXTURES TO REMAIN
OR TO BE RELOCATED TO NEAREST 277V EMERGENCY CIRCUIT IN
SAME ROOM.
WHERE EXISTING CIRCUITRY IS REUSED, CONTRACTOR SHALL
VERIFY EXISTING LOAD DOES NOT EXCEED 1,440 VA @ 120V (OR
3,324 VA @277V).
ALL LIGHT SWITCHES SHOWN ARE NEW, UNLESS NOTED
OTHERWISE. REUSE EXISTING BACKBOXES, CONDUIT, AND WIRING
WHERE PRACTICAL.
ALL NEW WIRING DEVICES SHALL BE RECESSED IN NEW OR
EXISTING WALLS AS INDICATED. ALL CONDUIT SHALL BE
CONCEALED. PROVIDE CUTTING AND PATCHING AS REQUIRED.
VERIFY EXTENT OF NEW AND EXISTING PARTITIONS WITH
ARCHITECTURAL DRAWINGS.
ALL EXIT SIGNS SHALL BE INSTALLED AS PER NFPA. WALL
MOUNTED EXIT SIGNS SHALL BE MOUNTED SO THAT THE BOTTOM
EDGE OF THE SIGN IS 2" CLEAR OF THE DOOR LINTEL OR FINISHED
DOOR TRIM. WHERE WALL MOUNTING AFFECTS FIRE RATING OF
THE AREA (SUCH AS STAIR ENCLOSURES), EXIT SIGN SHALL BE
CEILING MOUNTED. THE BOTTOM OF THE SIGN MUST BE OUT OF
THE EGRESS PATH OR ABOVE THE MINIMUM HEADROOM HEIGHT.
CONTRACTOR SHALL COORDINATE NUMBER AND LOCATION OF
OCCUPANCY SENSORS AS PER MANUFACTURER
RECOMMENDATIONS TO ASSURE COVERAGE IN ALL OCCUPIABLE
AREAS OF ROOMS COVERED. CONNECT LINE VOLTAGE SENSORS
AND POWER PACKS TO ADJACENT LIGHT FIXTURE CIRCUIT.
PROVIDE POWER PACKS AS REQUIRED. PROVIDE 4"X4" JUNCTION
BOX AS REQUIRED. REFER TO SPECIFICATIONS FOR ADDITIONAL
REQUIREMENTS.
REFER TO SHEET E1.1.1 FOR LOCATIONS OF PANEL '1LHN1 (ROOM
1017) & PANEL 'E1LHN' (ROOM 1111).
A.
B.
C.
D.
E.
F.
G.
H.
FITNESS
107
WRESTLING
GYM
101
COACH
105
ASST.
COACH
OFFICES
103
LOUNGE
108
CORRIDOR
102.1
RECEP.
102
CONF.
104
STOR.
106
COACH
LOCKERS
109
WRESTLING
LOCKERS
111
Room
105
VESTIBULE
110
TOILET
109.1
WRESTLING
GYM
ADDITION
101.1
RL RL
RL RL
RL RL
RL
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
RL
RL
EX
F2
F2
F2
F2
F6
F6
F6
F6 F6 F6 F6 F6 F6 F6 F6 F6 F6 F6 F6 F6
F6F6F6F6F6F6F6F6F6F6F6F6
F6F6F6F6F6F6F6F6F6F6F6F6
F6F6F6F6F6F6F6F6F6F6F6F6
F2 F2
F2
EX1
F1 F1
F1
F1
F1
F1
F1
F1F1
F1
F1
F1
F1
F1
F1
F1F1
F1
F1
EX
F1
F1
F1
F1
F1F1
F1
F1
F1
F2
EX1
eG
eF
eE.6
eE
e10
F1
EX2
9
F6F6 EMEM EM EM EM
F1
1LHN - 17 E1LHN - 6 1LHN - 17 1LHN - 17 E1LHN - 6 1LHN - 17 1LHN - 17 E1LHN - 6 1LHN - 17 1LHN - 17 E1LHN - 6 1LHN - 17 1LHN - 17
1LHN - 171LHN - 171LHN - 171LHN - 171LHN - 171LHN - 171LHN - 171LHN - 171LHN - 171LHN - 171LHN - 171LHN - 171LHN - 17
1LHN - 17 E1LHN - 6 1LHN - 17 1LHN - 17 E1LHN - 6 1LHN - 17 1LHN - 17 E1LHN - 6 1LHN - 17 1LHN - 17 E1LHN - 6 1LHN - 17 1LHN - 17
1LHN - 171LHN - 171LHN - 171LHN - 171LHN - 171LHN - 171LHN - 171LHN - 171LHN - 171LHN - 171LHN - 171LHN - 171LHN - 17
E1LHN - 8 1LHN - 15
1LHN - 151LHN - 15
1LHN - 151LHN - 15
1LHN - 15 1LHN - 15
1LHN - 15
1LHN - 15
1LHN - 15
1LHN - 151LHN - 15
1LHN - 15
1LHN - 151LHN - 15
1LHN - 151LHN - 15
1LHN - 151LHN - 15
1LHN - 151LHN - 15
1LHN - 15
1LHN - 15
1LHN - 15
1LHN - 15
F2
F2
F2
1LHN - 15
1LHN - 15
1LHN - 15 1LHN - 15
1LHN - 151LHN - 15
1LHN - 15
EM EM EM EM
EM EM EM EM
E1LHN - 6
E1LHN - 6
E1LHN - 6
E1LHN - 6
E1LHN - 6
E1LHN - 6
E1LHN - 6
E1LHN - 8
E1LHN - 8
E1LHN - 8
E1LHN - 8E1LHN - 8
E1LHN - 8
E1LHN - 8
E1LHN - 8
L1
EM
EM
EM
EM
EM
EM
EM EM
EM
EM
EM
EM
EM
EM
EM
F6A
F6
1LHN - 15
F6
E1LHN - 8
F6 F6 F6 F6 F6 F6 F6 F6
E1LHN - 81LHN - 15E1LHN - 81LHN - 151LHN - 15E1LHN - 81LHN - 151LHN - 15
EX1
EX1
L2(TYP.)
RL
L3 L4
L5
L3
L3
L4
L5L3
EM
EM
L6
w w w . l i t t l e o n l i n e . c o m
This drawing and the design shown are the property
of Little Diversified Architectural Consulting. The
reproduction, copying or other use of this drawing
without their written consent is prohibited and any
infringement will be subject to legal action.
Little 2017c
PROJECT MANAGER
DESIGN TEAM
PRINCIPAL IN CHARGE
PROJECT TEAM
REVISIONS
PROJECT NAME
SHEET TITLE
PROJECT NO.
SHEET NUMBER
ISSUE FOR
ISSUE DATE
B
1 2 3 4 5 6 7
A
C
D
E
F
410 Blackwell Street, Suite 10
Durham, NC 27701
T: 919.474.2500
10/6/2017 4:23:45 PM C:\Users\brenden.elliott\Documents\513.7505.00_CU_WrestlingExpansion_E-16_brenden.elliott.rvt513.7505.00
10/6/17
E1.2.1
LIGHTING PLAN -
CONVOCATION AREA C
Campbell Convocation
Center Wrestling
Department Renovation
and Expansion
BID/PERMIT SET
Rob Klinedinst
Katie Buckman
LITTLE
X KEY NOTES
KEY PLAN
GENERAL SHEET NOTES
RATED WALL LEGEND
3/16" = 1'-0"E1.2.1
1 CONVOCATION AREA C - LIGHTING PLAN
ADDITION
EXISTING BUILDING
L1 NEW LIGHTING FIXTURES IN AREA SHALL BE MOUNTED
ADJACENT AND AT THE SAME HEIGHT AS EXISITNG FIXTURES.
L2 CONTRACTOR SHALL COORDINATE SWITCH LOCATION, DO NOT
MOUNT SWITCH BEHIND DOOR SWING.
L3 CONTRACTOR TO CONNECT NEW/RELOCATED/EXISTING
SWITCHES TO EXISTING LIGHTING CIRCUITS SERVING THIS
AREA.
L4 PROVIDE NEW SWITCH TO CONTROL FIXTURES 'F6' CONNECTED
TO '1LHN-17'.
L5 PROVIDE NEW SWITCH TO CONTROL FIXTURES 'F6' CONNECTED
TO 'E1LHN-6'.
L6 CONTRACTOR TO CONNECT NEW LED WALLPACK TO EXISTING
EMERGENCY CIRCUIT SERVING EXTERIOR LIGHTS. FIXTURE
SHALL BE MOUNTED AT SAME HEIGHT AS EXISTING EXTERIOR
FIXTURES.
STAIR A
1047
NO. REASON DATE
CORPORATE LICENSE #F-0467
ALL POWER AND CONTROL CONDUIT ROUTED TO ROOF
MECHANICAL EQUIPMENT SHALL BE COORDINATED WITH
ARCHITECT AND GENERAL CONTRACTOR TO LIMIT THE NUMBER
OF ROOF PENETRATIONS. COORDINATE STUB-UP LOCATIONS
PRIOR TO ROUGH-IN.
A.
FIRE BARRIER FIRE & SMOKE BARRIER
1-HOUR
2-HOUR
3-HOUR
0.5-HOUR
1-HOUR
FIRE PARTITIONFIRE WALL
2-HOUR
3-HOUR
4-HOUR
1-HOUR
2-HOUR
3-HOUR
0-HOUR 1-HOUR
SMOKE BARRIERSMOKE PARTITION
e10
RTU-1
RTU-2
GFI, WPGFI, WP
1MHN1-1,3,5 1MHN1-2,4,6
1PLN5-341PLN5-34
EQUIPMENT
WITH
BUILT-IN
SWITCH
JB
STARTER
PANELBOARD/
OUTDOOR
UNIT
INDOOR
UNIT
GENERAL NOTES:
SWITCHBOARD
LEGEND:
BY ELECTRICAL (DIV. 26)
BY CONTRACTOR SUPPLYING EQUIPMENT
(DIV. 22, 23, OTHERS)
55
6
22 2
2
3
33
2
1
1 1
1
1
4
ALL POWER WIRING ASSOCIATED WITH DIVISION 22/23 (PLUMBING/MECHANICAL) SHALL BE DONE UNDER THE
SCOPE OF WORK OF THE CONTRACTOR SUPPLYING THE EQUIPMENT.
ALL POWER DISCONNECT SWITCHES AND SINGLE SPEED MANUAL STARTING SWITCHES ASSOCIATED WITH
DIVISION 22/23 (PLUMBING/MECHANICAL) SHALL BE FURNISHED AND INSTALLED UNDER THE SCOPE OF
WORK OF THE CONTRACTOR SUPPLYING THE EQUIPMENT.
EXCEPT AS MAY BE INDICATED ON THE DRAWINGS AND/OR HEREINAFTER NOTED, ALL CONTROL WIRING,
INCLUDING ALL TEMPERATURE CONTROL WIRING, INTERLOCKING, START-TOP WIRING, TOGETHER WITH
CONDUIT FOR SAME WILL BE FURNISHED AND INSTALLED UNDER DIVISION 22/23 BY THE CONTRACTOR
SUPPLYING THE EQUIPMENT. THIS INCLUDES, BUT IS NOT LIMITED TO, WIRING TO LOW VOLTAGE
THERMOSTATS, DAMPER MOTORS, AQUASTATS, FIRESTATS, PUSHBUTTONS, SELECTOR SWITCHES, AND
CONTROL PANEL. ALL DISCONNECT SWITCHES FOR CONTROL WIRING SHALL BE FURNISHED AND INSTALLED
UNDER DIVISION 22/23 BY THE CONTRACTOR SUPPLYING THE EQUIPMENT.
WORK OF OTHER DIVISIONS SHALL INCLUDE FURNISHING AND SETTING MOTORS.
ALL MAGNETIC STARTERS AND OVERLOAD ELEMENTS WILL BE FURNISHED UNDER DIVISION 22/23 BY THE
CONTRACTOR SUPPLYING THE EQUIPMENT. OVERLOAD ELEMENTS IN ALL STARTERS SHALL BE SELECTED
ACCORDING TO ACTUAL MOTOR NAMEPLATE FULL LOAD CURRENT. RESPONSIBILITY FOR THIS
COORDINATION SHALL LIE WITH THE DIVISION UNDER WHICH THE PARTICULAR STARTER WAS FURNISHED.
FIRESTATS AND WALL MOUNTED THERMOSTATS WHICH INTERRUPT LINE VOLTAGE POWER CIRCUITS TO
MOTORS WILL BE FURNISHED AND SET UNDER DIVISION 23, AND ELECTRICALLY CONNECTED IN THE BRANCH
CIRCUIT WIRING AS WORK OF DIVISION 26.
ALL POWER AND CONTROL CONDUIT ROUTED TO EXTERIOR ON-GRADE MECHANICAL EQUIPMENT SHALL BE
ROUTED UNDERGROUND UNLESS OTHERWISE NOTED. COORDINATE STUB-UP LOCATIONS PRIOR TO ROUGH-
IN.
ALL POWER AND CONTROL CONDUIT ROUTED TO ROOF MECHANICAQL EQUIPMENT SHALL BE COORDINATED
WITH ARCHITECT AND GENERAL CONTRACTOR TO LIMIT THE NUMBER OF ROOF PENETRATIONS.
COORDINATED STUB-UP LOCATIONS PRIOR TO ROUGH-IN.
1.
2.
3.
4.
5.
6.
7.
8.
EQUIPMENT OF TRADES OTHER THAN ELECTRICAL.
FEEDER CIRCUIT WIRING AND CONDUIT BY ELECTRICAL CONTRACTOR.
KEYED NOTES:
1
2
3
4
5
6
CONDUIT & WIRING OR CABLE BY MECHANICAL CONTRACTOR, CONTROLS CONTRACTOR, OR OTHER
TRADES. IN ALL CASES THE EQUIPMENT CONTRACTOR (DIV. 22/23) SHALL MAKE FINAL CONNECTIONS,
START UP EQUIPMENT AND TEST EQUIPMENT. COORDINATE CONNECTIONS WITH DIV 26.
IF ANY ADDITIONAL DISCONNECTS ARE REQUIRED BY NEC, IT SHALL BE PROVIDED AND INSTALLED BY
THE EQUIPMENT CONTRACTOR (DIV. 22/23).
A COMBINATION STARTER OR VFD MAY BE USED IN LIEU OF A SEPARATE DISCONNECT SWITCH AND
STARTER. LOCATED ADJACENT TO EQUIPMENT AND PROVIDED BY EQUIPMENT CONTRACTOR.
A JUNCTION BOX MAY BE SHOWN ON THE ELECTRICAL PLANS FOR SOME EQUIPMENT. IF NO STARTER
OR DISCONNECT IS SUPPLIED, A JUNCTION BOX SHALL BE INSTALLED ADJACENT TO EQUIPMENT. THE
ELECTRICAL CONTRACTOR SHALL PROVIDE LINE SIDE WIRING TO JUNCTION BOX. LOAD SIDE WIRING
WILL BE PROVIDED BY MECHANICAL CONTRACTOR OR OTHER TRADES.
w w w . l i t t l e o n l i n e . c o m
This drawing and the design shown are the property
of Little Diversified Architectural Consulting. The
reproduction, copying or other use of this drawing
without their written consent is prohibited and any
infringement will be subject to legal action.
Little 2017c
PROJECT MANAGER
DESIGN TEAM
PRINCIPAL IN CHARGE
PROJECT TEAM
REVISIONS
PROJECT NAME
SHEET TITLE
PROJECT NO.
SHEET NUMBER
ISSUE FOR
ISSUE DATE
B
1 2 3 4 5 6 7
A
C
D
E
F
410 Blackwell Street, Suite 10
Durham, NC 27701
T: 919.474.2500
10/6/2017 4:23:46 PM C:\Users\brenden.elliott\Documents\513.7505.00_CU_WrestlingExpansion_E-16_brenden.elliott.rvt513.7505.00
10/6/17
E1.3.1
MECHANICAL POWER
PLAN - CONVOCATION
AREA C
Campbell Convocation
Center Wrestling
Department Renovation
and Expansion
BID/PERMIT SET
Rob Klinedinst
Katie Buckman
LITTLE
X KEY NOTES
KEY PLAN
GENERAL SHEET NOTES
RATED WALL LEGEND
1/8" = 1'-0"E1.3.1
2 CONVOCATION ROOF - MECHANICAL POWER PLAN
ADDITION
EXISTING BUILDING
MECHANICAL EQUIPMENT SCHEDULE
EQUIP. HP KW FLA MCA MOCP VOLT PHASE VFD DISCONNECT SIZE CONDUCTORS COMMENTS
RTU-1 47 A 60 A 70 A 480 V 3 No 100/3/EMR/3R 3#4, #8(G), 1-1/2"C
RTU-2 47 A 60 A 70 A 480 V 3 No 100/3/EMR/3R 3#4, #8(G), 1-1/2"C
NOT TO SCALEE1.3.1
1 EQUIPMENT CONNECTION DETAIL (TYPICAL)
NO. REASON DATE
CORPORATE LICENSE #F-0467
ANSI/UL1479 (ASTM E814)
F Rating — 3 Hr
T Rating — 0 Hr
L Rating At Ambient — Less Than 1 CFM/sq ft
L Rating At 400 F — 4 CFM/sq ft
SECTION A-A
A
A
2
34B
3
14B
4A
1. Floor or Wall Assembly — Min 4-1/2 in. (114 mm) thick reinforced lightweight or normal weight (100-150 pcf or 1600-2400 kg/m³) concrete. Wall
may also be constructed of any UL Classified Concrete Blocks*. Max diam of opening is 32 in. (813 mm).
2. Metallic Sleeve — (Optional) Nom 32 in. (813 mm) diam (or smaller) Schedule 40 (or heavier) steel sleeve cast or grouted into floor or wall
assembly, flush with floor or wall surfaces or extending a max of 3 in. (76 mm) above floor or beyond both surfaces of wall.
2A. Sheet Metal Sleeve — (Optional) Max 6 in. (152 mm) diam, min 26 ga. galv steel provided with a 26 ga galv steel square flange spot welded to
the sleeve at approx mid-height, or flush with bottom of sleeve in floors, and sized to be a min of 2 in. (51 mm) larger than the sleeve diam. The
sleeve is to be cast in place and may extend a max of 4 in. (102 mm) below the bottom of the deck and a max of 1 in. (25 mm) above the top
surface of the concrete floor.
2B. Sheet Metal Sleeve — (Optional) - Max 12 in. (305 mm) diam, min 24 ga galv steel provided with a 24 ga galv steel square flange spot welded
to the sleeve at approx mid-height, or flush with bottom of sleeve in floors, and sized to be a min of 2 in. (51 mm) larger than the sleeve diam. The
sleeve is to be cast in place and may extend a max of 4 in. (102 mm) below the bottom of the deck and a max of 1 in. (25 mm) above the top
surface of the concrete floor.
3. Through-Penetrant — One metallic pipe, tube or conduit to be installed either concentrically or eccentrically within the firestop system. The
annular space between penetrant and periphery of opening shall be min 0 in. (point contact) to max 1-7/8 in. (48 mm). Penetrant may be installed
with continuous point contact. Penetrant to be rigidly supported on both sides of floor or wall assembly. The following types and sizes of metallic
penetrants may be used:
A. Steel Pipe — Nom 30 in. (762 mm) diam (or smaller) Schedule 10 (or heavier) steel pipe.
B. Iron Pipe — Nom 30 in. (762 mm) diam (or smaller) cast or ductile iron pipe.
C. Copper Pipe — Nom 6 in. (152 mm) diam (or smaller) Regular (or heavier) copper pipe.
D. Copper Tubing — Nom 6 in. (152 mm) diam (or smaller) Type L (or heavier) copper tubing.
E. Conduit — Nom 6 in. (152 mm) diam (or smaller) steel conduit.
F. Conduit — Nom 4 in. (102 mm) diam (or smaller) steel electrical metallic tubing (EMT).
4. Firestop System — The firestop system shall consist of the following:
A. Packing Material — Min 4 in. (102 mm) thickness of min 4 pcf (64 kg/m³) mineral wool batt insulation firmly packed into opening as a
permanent form. Packing material to be recessed from top surface of floor or sleeve or from both surfaces of wall or sleeve as required to
accommodate the required thickness of fill material.
B. Fill, Void or Cavity Material* — Sealant — Min 1/4 in. (6 mm) thickness of fill material applied within the annulus, flush with top surface of
floor or sleeve or with both surfaces of wall or sleeve. At the point or continuous contact locations between penetrant and concrete or sleeve,
a min 1/4 in. (6 mm) diam bead of fill material shall be applied at the concrete or sleeve/ pipe penetrant interface on the top surface of floor
and on both surfaces of wall.
HILTI CONSTRUCTION CHEMICALS, DIV OF HILTI INC — FS-One Sealant or FS-ONE MAX Intumescent Sealant
* Indicates such products shall bear the UL or cUL Certification Mark for jurisdictions employing the UL or cUL Certification (such as Canada),
respectively.
System No. C-AJ-1226 ANSI/UL1479 (ASTM E814)
F Rating — 2 Hr
T Ratings — 0 and 1 Hr (See Items 2 and 4)
L Rating At Ambient — 4 CFM/sq ft
L Rating At 400 F — Less Than 1 CFM/sq ft
SECTION A-A
A
A
12
5B
4
3
5A
1. Floor or Wall Assembly — Min 4-1/2 in. (114 mm) thick reinforced lightweight or normal weight (100-150 pcf or 1600-2400 kg/m³) concrete. Wall
may also be constructed of any UL Classified Concrete Blocks*. Max diam of opening is 29 in. (737 mm).
See Concrete Blocks (CAZT) category in the Fire Resistance directory for names of manufacturers.
2. Metallic Sleeve — (Optional) — Nom 30 in. (762 mm) diam (or smaller) Schedule 10 (or heavier) steel pipe sleeve cast or grouted into floor or
wall assembly, flush with floor or wall surfaces or extending a max of 3 in. (76 mm) above floor or beyond both surfaces of wall. If the steel sleeve
extends beyond the top surface of the floor or both surfaces of the wall, the T Rating of the firestop system is 0 hr.
2A. Sheet Metal Sleeve — (Optional) - Max 6 in. (152 mm) diam, min 26 ga galv steel provided with a 26 ga galv steel square flange spot welded to
the sleeve at approximately mid- height, or flush with bottom of sleeve in floors, and sized to be a min of 2 in. (51 mm) larger than the sleeve
diam. The sleeve is to be cast in place flush with bottom surface of floor and may extend a max of 1 in. (25 mm) above the top surface of the
floor.
2B. Sheet Metal Sleeve — (Optional) - Max 12 in. (305 mm) diam, min 24 ga galv steel provided with a 24 ga galv steel square flange spot welded
to the sleeve at approximately mid- height, or flush with bottom of sleeve in floors, and sized to be a min of 2 in. (51 mm) larger than the sleeve
diam. The sleeve is to be cast in place flush with bottom surface of floor and may extend a max of 1 in. (25 mm) above the top surface of the floor.
3. Through Penetrants — One metallic pipe or tubing to be installed either concentrically or eccentrically within the firestop system. Pipe or tubing
to be rigidly supported on both sides of floor or wall assembly. The following types and sizes of metallic pipes or tubing may be used:
A. Steel Pipe — Nom 12 in. (305 mm) diam (or smaller) Schedule 10 (or heavier) steel pipe.
B. Iron Pipe — Nom 12 in. (305 mm) diam (or smaller) cast or ductile iron pipe.
C. Copper Pipe — Nom 6 in. (152 mm) diam (or smaller) Regular (or heavier) copper pipe.
D. Copper Tubing — Nom 6 in. (152 mm) diam (or smaller) Type L (or heavier) copper tubing.
4. Pipe Covering — Min 1/2 in. (13 mm) to max 2 in. (51 mm) thick hollow cylindrical heavy density (min 3.5 pcf or 56 kg/m³) glass fiber units
jacketed on the outside with an all-service jacket. Longitudinal joints sealed with metal fasteners or factory-applied, self-sealing lap tape.
Transverse joints secured with metal fasteners or with butt tape supplied with the product. The annular space between the insulated pipe and the
edge of the periphery of the opening shall be min 1/2 in. (13 mm) to max 12 in. (305 mm). When thickness of pipe covering is less than 2 in. (51
mm), the T Rating for the firestop system is 0 hr.
See Pipe Equipment Covering — Materials — (BRGU) category in the Building Materials Directory for names of manufacturers. Any pipe
covering material meeting the above specifications and bearing the UL Classification Marking with a Flame Spread Index of 25 or less and
a Smoke Developed Index of 50 or less may be used.
4A. Pipe Covering — (Not Shown) — As an alternate to Item 4, max 2 in. (51 mm) thick cylindrical calcium silicate (min 14 pcf or 224 kg/m³) units
sized to the outside diam of the pipe or tube may be used. Pipe insulation secured with stainless steel bands or min 18 AWG stainless steel wire
spaced max 12 in. (305 mm) OC. The annular space shall be min 1/2 in. (13 mm) to max 12 in. (305 mm).
5. Firestop System — The firestop system shall consist of the following:
A. Packing Material — Min 4 in. (102 mm) thickness of min 4 pcf (64 kg/m³) mineral wool batt insulation firmly packed into opening as a
permanent form. Packing material to be recessed from top surface of floor or from both surfaces of wall as required to accommodate the
required thickness of fill material.
B. Fill, Void or Cavity Material* — Sealant — Min 1/2 in. (13 mm) thickness of fill material applied within the annulus, flush with top surface of
floor or with both surfaces of wall.
HILTI CONSTRUCTION CHEMICALS, DIV OF HILTI INC — FS-One Sealant or FS-ONE MAX Intumescent Sealant
* Indicates such products shall bear the UL or cUL Certification Mark for jurisdictions employing the UL or cUL Certification (such as Canada),
respectively.
System No. C-AJ-5091
ANSI/UL1479 (ASTM E814)
F Ratings —1 and 2 Hr (See Items 1 and 3)
T Rating — 0 Hr
L Rating at Ambient — Less Than 1 CFM/sq ft
L Rating at 400 F — Less Than 1 CFM/sq ft
SECTION A-A
A
A
1A
3
2 1B
1. Wall Assembly — The 1 or 2 hr fire-rated gypsum wallboard/stud wall assembly shall be constructed of the materials and in the manner specified
in the individual U300 or U400 Series Wall and Partition Designs in the UL Fire Resistance Directory and shall include the following construction
features:
A. Studs — Wall framing may consist of either wood studs or steel channel studs. Wood studs to consist of nom 2 by 4 in. (51 by 102 mm)
lumber spaced 16 in. (406 mm) OC. Steel studs to be min 2-1/2 in. (64 mm) wide and spaced max 24 in. (610 mm) OC. When steel studs are
used and the diam of opening exceeds the width of stud cavity, the opening shall be framed on all sides using lengths of steel stud installed
between the vertical studs and screw-attached to the steel studs at each end. The framed opening in the wall shall be 4 to 6 in. (102 to 152
mm) wider and 4 to 6 in. (102 to 152 mm) higher than the diam of the penetrating item such that, when the penetrating item is installed in the
opening, a 2 to 3 in. (51 to 76 mm) clearance is present between the penetrating item and the framing on all four sides.
B. Gypsum Board* — 5/8 in. (16 mm) thick, 4 ft (122 cm) wide with square or tapered edges. The gypsum board type, thickness, number of
layers, fastener type and sheet orientation shall be as specified in the individual U300 or U400 Series Design in the UL Fire Resistance
Directory. Max diam of opening is 32-1/4 in. (819 mm) for steel stud walls. Max diam of opening is 14-1/2 in. (368 mm) for wood stud walls.
The F and FH Ratings of the firestop system are equal to the fire rating of the wall assembly.
2. Through-Penetrants — One metallic pipe, conduit or tubing to be installed either concentrically or eccentrically within the firestop system. The
annular space shall be min 0 in. to max 2-1/4 in. (57 mm). Pipe may be installed with continuous point contact. Pipe, conduit or tubing to be rigidly
supported on both sides of wall assembly. The following types and sizes of metallic pipes, conduits or tubing may be used:
A. Steel Pipe — Nom 30 in. (762 mm) diam (or smaller) Schedule 10 (or heavier) steel pipe.
B. Iron Pipe — Nom 30 in. (762 mm) diam (or smaller) cast or ductile iron pipe.
C. Conduit — Nom 4 in. (102 mm) diam (or smaller) steel electrical metallic tubing or 6 in. (152 mm) . diam steel conduit.
D. Copper Tubing — Nom 6 in. (152 mm) diam (or smaller) Type L (or heavier) copper tubing.
E. Copper Pipe — Nom 6 in. (152 mm) diam (or smaller) regular (or heavier) copper pipe.
3. Fill, Void or Cavity Material* — Sealant — Min 5/8 in. (16 mm) thickness of fill material applied within the annulus, flush with both surfaces of
wall. At the point or continuous contact locations between pipe and wall, a min 1/2 in. (13 mm) diam bead of fill material shall be applied at the
pipe wall interface on both surfaces of wall.
HILTI CONSTRUCTION CHEMICALS, DIV OF HILTI INC — FS-One Sealant or FS-ONE MAX Intumescent Sealant
* Indicates such products shall bear the UL or cUL Certification Mark for jurisdictions employing the UL or cUL Certification (such as Canada),
respectively.
System No. W-L-1054
ANSI/UL1479 (ASTM E814)
F Ratings — 1, 2 and 3 Hr (See Items 1, 3 and 4)
T Ratings — 0, 1/2, 1 and 1-1/4 Hr (See Item 3)
L Rating At Ambient — 4 CFM/Sq Ft
L Rating At 400 F — Less Than 1 CFM/Sq Ft
SECTION A-A
A
A
2
4 3
2
3
4
5
1
1. Wall Assembly — The 1, 2 or 3 hr fire-rated gypsum board/stud wall assembly shall be constructed of the materials and in the manner specified
in the individual U300, U400, V400 or W400 Series Wall and Partition Designs in the UL Fire Resistance Directory and shall include the following
construction features:
A. Studs — Wall framing may consist of either wood studs or steel channel studs. Wood studs to consist of nom 2 by 4 in. (51 by 102 mm)
lumber spaced 16 in. (406 mm) OC. Steel studs to be min 2-1/2 in. (64 mm) wide for 1 and 2 hr F and FH rating and 3-1/2 in. (89 mm) wide
for 3 hr F and FH rating and spaced max 24 in. (610 mm) OC.
B. Gypsum Board* — Min 5/8 in. (16 mm) thick with square or tapered edges. The gypsum board type, thickness, number of layers, fastener
type and sheet orientation shall be as specified in the individual Wall and Partition Design. Max diam of opening is 18-5/8 in. (473 mm).
The hourly F and FH Ratings of the firestop system are equal to the hourly fire rating of the wall assembly in which it is installed.
2. Through Penetrants — One metallic pipe or tubing to be installed within the firestop system. Pipe or tubing to be rigidly supported on both sides
of wall assembly. The following types and sizes of metallic pipes or tubing may be used:
A. Steel Pipe — Nom 12 in. (305 mm) diam (or smaller) Schedule 10 (or heavier) steel pipe.
B. Iron Pipe — Nom 12 in. (305 mm) diam (or smaller) cast or ductile iron pipe.
C. Copper Tubing — Nom 6 in. (152 mm) diam (or smaller) Type L (or heavier) copper tubing. When the hourly F or FH Rating of the firestop
system is 3 hr, the nom diam of copper tube shall not exceed 4 in. (102 mm).
D. Copper Pipe — Nom 6 in. (152 mm) diam (or smaller) Regular (or heavier) copper pipe. When the hourly F or FH Rating of the firestop
system is 3 hr, the nom diam of copper pipe shall not exceed 4 in. (102 mm).
3. Pipe Covering* — Nom 1, 1-1/2 or 2 in. (25, 38 or 51 mm) thick hollow cylindrical heavy density (min 3.5 pcf or 56 kg/m3) glass fiber units
jacketed on the outside with an all service jacket. Longitudinal joints sealed with metal fasteners or factory-applied self-sealing lap tape.
Transverse joints secured with metal fasteners or with butt tape supplied with the product. For 1 and 2 hr F and FH Ratings, the annular space
between insulated penetrant and periphery of opening shall be min 0 in. (point contact) to max 1-7/8 in. (48 mm). For 3 hr F and FH Ratings, the
annular space shall be min 0 in. (point contact) to max 1-1/4 in. (32 mm).
See Pipe and Equipment Covering — Materials (BRGU) category in the Building Material Directory for the names of manufacturers. Any pipe
covering material meeting the above specifications and bearing the UL Classification Marking with a Flame Spread Index of 25 or less and a
Smoke Developed Index of 50 or less may be used.
The hourly T, FT, FTH Ratings of the firestop system are 1/2 hr for 1 hr rated walls and 1 hr for 2 hr rated walls. For 3 hr rated walls, the hourly T,
FT and FTH Ratings when steel and iron pipes are used are 1 hr. For 3 hr rated walls, the hourly T, FT and FTH Ratings when copper penetrants
are used are 1-1/4 hr for 2 in. (51 mm) thick pipe covering and 0 hr for pipe covering thickness less than 2 in. (51 mm).
3A. Pipe Covering* — (Not Shown) — As an alternate to Item 3, max 2 in. (51 mm) thick cylindrical calcium silicate (min 14 pcf) units sized to the
outside diam of the pipe or tube may be used. Pipe insulation secured with stainless steel bands or min 18 AWG stainless steel wire spaced max
12 in. (305 mm) OC. When the alternate pipe covering is used, the T and FT Rating shall be as specified in item 3 above.
See Pipe and Equipment Covering — Materials (BRGU) category in the Building Materials Directory for names of manufacturers. Any pipe
covering material meeting the above specifications and bearing the UL Classification Marking with a Flame Spread Index of 25 or less and a
Smoke Developed Index of 50 or less may be used.
4. Fill, Void or Cavity Material* — Sealant — For 1 and 2 hr F and FH Rating, min 5/8 in. (16 mm) thickness of fill material applied within the
annulus, flush with both surfaces of wall. For 3 hr F and FH Rating, min 1 in. (25 mm) thickness of fill material applied within the annulus, flush
with both surfaces of wall. At the point contact location between pipe covering and gypsum board, a min 1/2 in. (13 mm) diam bead of fill material
shall be applied at the pipe covering/gypsum board interface on both surfaces of wall.
HILTI CONSTRUCTION CHEMICALS, DIV OF HILTI INC — FS-One Sealant or FS-ONE MAX Intumescent Sealant
* Indicates such products shall bear the UL or cUL Certification Mark for jurisdictions employing the UL or cUL Certification (such as Canada),
respectively.
System No. W-L-5029
CP 617 or CFS-P PA Firestop Putty Pads, for use with max 4 by 3-3/4 by 3 in. deep UL Listed Nonmetallic Outlet Boxes manufactured by Allied
Molded Products, Inc., made from fiber reinforced thermoplastic and bearing a 2 hr rating under the "Outlet Boxes and Fittings Classification
for Fire Resistance" category in the Fire Resistance Directory. Putty pads and boxes for use in 1 hr fire rated gypsum wallboard assemblies,
framed with min 3-1/2 in. deep wood studs and constructed as specified in the individual U300 Series Wall and Partition Designs in the Fire
Resistance Directory. Outlet box secured to wood stud by means of two nailing tabs supplied with the outlet box. Putty pads shall lap min 1/2
in. onto the stud and gypsum board within the stud cavity. Outlet boxes installed with plastic cover plates.
CP 617 or CFS-P PA Firestop Putty Pads, for use with max 4 by 4 in. by 1-½ in. deep flush device UL Listed Metallic Outlet Boxes installed with
steel cover plates in 1 hr. fire rated gypsum wallboard wall assemblies framed with min 3-1/2 in. deep wood or steel studs and constructed as
specified in the individual U300, U400 or V400 Series Wall and Partition Designs in the Fire Resistance Directory. The boxes are installed
back to back with 5 in. by 4 in. UL Classified fire block, FS 657, CP 657 or CFS-BL Firestop Block installed in the cavity between the two
boxes
.
CP 617 or CFS-P PA Firestop Putty Pads, for use with max 14 by 4 by max 2-1/2 in. flush device UL Listed Metallic Outlet Boxes installed with
steel cover plates in 1 and 2 hr. fire rated gypsum board wall assemblies framed with min 5-1/2 in. deep wood or steel studs for 2 hr fire rated
walls and min 3-1/2 in. deep wood or steel studs for 1 hr fire rated walls. Walls constructed as specified in the individual U300, U400 or V400
Series Wall and Partition Designs in the Fire Resistance Directory. Stud cavity insulation is required and shall consist of min 5-1/2 in. (2 hr
rated walls) or min 3-1/2 in. (1 hr rated walls) thick fiberglass (min 0.8 pcf) or mineral fiber (min 4 pcf). Putty pads shall lap min 1/2 in. onto the
stud and gypsum board within the stud cavity. When boxes are interconnected by means of electrical metallic tube (EMT) or conduit, a ball of
putty pad material shall be used to completely plug the open end of each EMT or conduit within the box.
CP 617 or CFS-P PA Firestop Putty Pads, for use with max 4-11/16 by 4-11/16 by max 2-1/8 in. flush device UL Listed Metallic Outlet Boxes
installed with steel or plastic cover plates for use in 1 and 2 hr fire rated gypsum board wall assemblies framed with min 5-1/2 in. deep steel
studs and constructed of the materials and in the manner specified in the individual U400 or V400 Series Wall and Partition Designs in the
Fire Resistance Directory. Putty pads shall lap min 1/2 in. onto the stud and gypsum board within the stud cavity. When boxes are
interconnected by means of electrical metallic tube (EMT) or conduit, a ball of putty pad material shall be used to completely plug the open
end of each EMT or conduit within the outlet boxes. Metallic outlet boxes may be provided with steel attachment brackets which offset box
min 1/4 in. from stud. When steel attachment brackets are used, putty pad to be affixed to the back and all four sides of the box.
CFS-P PA Moldable Putty Pads, for use with max 4-11/16 by 4-11/16 in. by max 2-1/8 in. flush device UL Listed Metallic Outlet Boxes installed
with steel cover plates in 2 hr fire rated gypsum board wall assemblies framed with min 3-1/2 in. deep steel studs and constructed of the
materials and in the manner specified in the individual U400 and V400 Series Wall and Partition Designs in the Fire Resistance Directory. An
additional 3/4 in. ball of putty pad material shall be used to plug the end of each electrical metallic tube or conduit at its connection to the box.
CFS-P PA Moldable Putty Pads, for use with max 4 by 4 by 2-1/8 in. flush device UL Listed Metallic Outlet Boxes installed with steel or plastic
cover plates in 2 hr fire rated gypsum board wall assemblies framed with min 3-1/2 in. deep steel studs and constructed of the materials and
in the manner specified in the individual U400 and V400 Series Wall and Partition Designs in the Fire Resistance Directory. An additional 3/4
in. ball of putty pad material shall be used to plug the end of each electrical metallic tube or conduit at its connection to the box.
CFS-P PA Moldable Putty Pads, for use with max 14-1/4 by 4-1/2 by 2-1/2 in. flush device UL Listed Metallic Outlet Boxes installed with steel
cover plates in 2 hr fire rated gypsum board wall assemblies framed with min 3-1/2 in. deep steel studs and constructed of the materials and
in the manner specified in the individual U400 and V400 Series Wall and Partition Designs in the Fire Resistance Directory. An additional 3/4
in. ball of putty pad material shall be used to plug the end of each electrical metallic tube or conduit at its connection to the box.
CP 617 or CFS-P PA Firestop Putty Pads and HILTI Firestop Box Inserts, for use with maximum 4 by 4 by 1-1/2 in. (102 by 102 by 38 mm)
deep flush device UL Listed Metallic Outlet Boxes installed with steel mud rings and with steel or plastic faceplates in 1 or 2 hr fire rated
gypsum board wall assemblies constructed with min 3-1/2 in. (89 mm) wide wood or steel studs. When both protective materials are used with
outlet boxes on both sides of the wall as directed, the boxes may be installed back-to-back provided that the backs of the boxes are minimum
1/2 in. (13 mm) apart and provided that the boxes are not interconnected. Adjoining pieces of moldable putty pads to be overlapped approx
1/2 in. (13 mm) at the seam. An insert pad shall be installed to completely cover the back inside surface of each outlet box.
CP 617 or CFS-P PA Firestop Putty Pads, for use with flush device UL Listed Metallic Outlet Boxes installed with steel mud rings or UL Listed
Nonmetallic Outlet Boxes in framed wall assemblies as specified below. When protective material is used on outlet boxes on both sides of the
wall as directed, the horizontal separation between outlet boxes on opposite sides of the wall may be less than 24 in. provided that the boxes are
not installed back-to-back (unless otherwise indicated). Installation shall comply with the National Electrical Code (NFPA 70). Min 1/8 in. thick (CP
617) or min 0.2 in. (CFS-P PA) thick moldable putty pads are to be installed to completely cover the exterior surfaces of the outlet box (except for
the side of the outlet box against the stud) and conduit fittings/connectors and to completely seal against the stud and gypsum board in the wall
cavity unless otherwise noted below. When CFS-P PA is used, the putty pads may be installed with the release liner intact on the outside of the
pad with the exception of any overlaps, in which case the liner is to be removed from the bottom layer at the overlap location. The box
composition, max device dimensions, hourly rating, type of stud and type of faceplate are specified below.
CP 617 or CFS-P PA Firestop Putty Pads, for use with max 4 by 4 by max 2-1/8 in. flush device UL Listed Metallic Outlet Boxes installed with steel
cover plates in 1 and 2 hr. fire rated gypsum wallboard wall assemblies framed with min 3-1/2 in. deep wood or steel studs and constructed as
specified in the individual U300, U400 or V400 Series Wall and Partition Designs in the Fire Resistance Directory.
CP 617 or CFS-P PA Firestop Putty Pads, for use with max 4-11/16 by 4-11/16 by max 2-1/8 in., or max 4-3/8 by 4-7/8 by max 2-1/8 in., flush
device UL Listed Metallic Outlet Boxes installed with steel cover plates for use in 1 hr fire rated V446 gypsum board/steel stud or U341 gypsum
board/wood stud Wall and Partition Design No. in the Fire Resistance Directory. When U341 wall design is used, wall shall be sheathed with 5/8
in. gypsum board, and glass or mineral fiber batt insulation shall be installed in stud cavities in accordance with U341 design. Boxes may be
installed back-to-back.
CP 617 or CFS-P PA Firestop Putty Pads, for use with max 4-11/16 by 4-11/16 by max 2-1/8 in. flush device UL Listed Metallic Outlet Boxes
installed with steel cover plates for use in 1 and 2 hr fire rated gypsum board wall assemblies framed with min 3-1/2 in. deep wood or steel studs
and constructed of the materials and in the manner specified in the individual U300, U400 or V400 Series Wall and Partition Designs in the Fire
Resistance Directory. Min 0.8 pcf density fiberglass batt insulation is to be installed within the wall cavity required for 1 hr fire rated gypsum board
wall assemblies and optional in 2 hr fire rated gypsum wallboard assemblies.
CP 617 or CFS-P PA Firestop Putty Pads, for use with max 4 by 3-3/4 by 3 in. deep UL Listed Nonmetallic Outlet Boxes manufactured by Carlon
Electrical Products, made from polyvinyl chloride, and bearing a 2 hr rating under the "Outlet Boxes and Fittings Classification for Fire
Resistance" category in the Fire Resistance Directory. Putty pads and boxes for use in 1 and 2 hr fire rated gypsum wallboard assemblies,
framed with min 3-1/2 in. deep wood studs and constructed as specified in the individual U300 Series Wall and Partition Designs in the Fire
Resistance Directory. Outlet box secured to wood stud by means of two nailing tabs supplied with the outlet box. Putty pads shall lap min 1/2 in.
onto the stud and gypsum board within the stud cavity. Outlet boxes installed with steel or plastic cover plates.
CP 617 or CFS-P PA Firestop Putty Pads, for use with max 4 by 4 by 2-7/8 in. deep UL Listed Nonmetallic Outlet Boxes manufactured by Carlon
Electrical Products, made from polyvinyl chloride, and bearing a 2 hr rating under the "Outlet Boxes and Fittings Classification for Fire
Resistance" category in the Fire Resistance Directory. Putty pads and boxes for use in the 1 hr fire rated V446 gypsum board/steel stud or U341
gypsum board/wood stud Wall and Partition Design in the Fire Resistance Directory. When U341 wall design is used, wall shall be sheathed with
5/8 in. gypsum board, and glass or mineral fiber batt insulation shall be installed in stud cavities in accordance with U341 design. Outlet box
secured to steel stud by means of fastening tab supplied with the outlet box. Putty pads shall lap min 1/2 in. onto the stud and gypsum board
within the stud cavity. Outlet boxes installed with steel or plastic cover plates. Boxes may be installed back to back.
CP 617 Firestop Putty Pads, for use with max 2-1/4 by 3-3/4 by 2-3/4 in. deep UL Listed Nonmetallic Outlet Boxes manufactured by Pass and
Seymore, Inc., and bearing a 2 hr rating under the "Outlet Boxes and Fittings Classification for Fire Resistance" category in the Fire Resistance
Directory. Putty pads and boxes for use in 1 and 2 hr fire rated gypsum wallboard assemblies, framed with min 3-1/2 in. deep wood studs and
constructed as specified in the individual U300 Series Wall and Partition Designs in the Fire Resistance Directory. Outlet box secured to wood
stud by means of two nailing tabs supplied with the outlet box.Putty pads shall lap min 1/2 in. onto the stud and gypsum board within the stud
cavity. Outlet boxes installed with steel or plastic cover plates.
Wall Opening Protective Materials (CLIV, CLIV7)
w w w . l i t t l e o n l i n e . c o m
This drawing and the design shown are the property
of Little Diversified Architectural Consulting. The
reproduction, copying or other use of this drawing
without their written consent is prohibited and any
infringement will be subject to legal action.
Little 2017c
PROJECT MANAGER
DESIGN TEAM
PRINCIPAL IN CHARGE
PROJECT TEAM
REVISIONS
PROJECT NAME
SHEET TITLE
PROJECT NO.
SHEET NUMBER
ISSUE FOR
ISSUE DATE
B
1 2 3 4 5 6 7
A
C
D
E
F
410 Blackwell Street, Suite 10
Durham, NC 27701
T: 919.474.2500
10/6/2017 4:23:47 PM C:\Users\brenden.elliott\Documents\513.7505.00_CU_WrestlingExpansion_E-16_brenden.elliott.rvt513.7505.00
10/6/17
E5.1.1
ELECTRICAL DETAILS
Campbell Convocation
Center Wrestling
Department Renovation
and Expansion
BID/PERMIT SET
Rob Klinedinst
Katie Buckman
LITTLE
NO. REASON DATE
CORPORATE LICENSE #F-0467
151-600
0-150
3. EXPOSED LIVE PARTS ON BOTH SIDES OF THE WORK SPACE (NOT GUARDED AS
2. EXPOSED LIVE PARTS ON ONE SIDE AND GROUNDED PARTS ON THE OTHER SIDE.
1. EXPOSED LIVE PARTS ON ONE SIDE AND NO LIVE OR GROUNDED PARTS ON
3 3 1/2 4
3 3 3
PROVIDED IN CONDITION 1) WITH THE OPERATOR BETWEEN.
300 VOLTS SHALL NOT BE CONSIDERED LIVE PARTS.
MATERIALS. INSULATED WIRE OR INSULATED BUSBARS OPERATING AT NOT OVER
BOTH SIDES EFFECTIVELY GUARDED BY SUITABLE WOOD OR OTHER INSULATING
THE OTHER SIDE OF THE WORKING SPACE, OR EXPOSED LIVE PARTS ON
WHERE THE "CONDITIONS" ARE AS FOLLOWS:
CONCRETE, BRICK OR TILE SHALL BE CONSIDERED AS GROUNDED.
S E E TA B L E "A "T H IS D IS TA N C E
VOLTAGE TO GROUND, NOMINAL
OR WIDTH
OF
EQUIP.
30" MIN.6 FT. 6 INCHES MIN.DEDICATED SPACE CONTINUES
THROUGH SUSPENDED CEILING
PER NEC ARTICLE 110-26.f
SUSPENDED
CEILING6 ft. MIN.WALL
LIGHT FIXTURE
PANEL
EXCLUSIVELY
DEDICATED SPACE
WALL
NOTE:
THIS FIGURE ILLUSTRATES THE
ADDITIONAL EXCLUSIVELY DEDICATED
CODE.
THE PANELBOARD FOR THE CABLES,
RACEWAYS, ETC. TO AND FROM THE
PANELBOARD REQUIRED BY SECTION
110-26, f OF THE NATIONAL ELECTRICAL
SPACE REQUIRED OVER AND UNDER
LIGHT FIXTURE
PANEL
PLANE OF FRONT
EDGE OF PANEL
EXCLUSIVELY
DEDICATED SPACE
NOTE:
THIS FIGURE ILLUSTRATES THE
WORKING SPACE IN FRONT OF
THE PANELBOARD REQUIRED
BY SECTION 110-26 OF THE
NATIONAL ELECTRICAL CODE.
SUSPENDED
CEILING
STRUCTURAL
CEILING
TABLE 110-26,(a) WORKING SPACES
CONDITION: 1 2 3
MINIMUM CLEAR DISTANCE (FEET)
STRUCTURAL
CEILING
NOTE:
NO PIPING, DUCTS OR EQUIPMENT FOREIGN TO THE ELECTRICAL
EQUIPMENT OR ARCHITECTURAL APPURTENANCES SHALL BE
PERMITTED TO BE INSTALLED IN OR PASS THROUGH THE
DEDICATED SPACES SHOWN ABOVE WITHOUT THE WRITTEN
PERMISSION OF THE DESIGN ENGINEER AND THE AUTHORITY
HAVING JURISDICTION.
EXCLUSIVELY
DEDICATED SPACE
GENERAL NOTES:
1.MAINTAIN A MINIMUM CLEARANCE OF 305mm (12") ON ALL SIDES OF ROOF
PENETRATION FROM WALLS, CURBS, AND OTHER PROJECTIONS TO FACILITATE
PROPER FLASHING.
2.FLANGES OF ADJACENT FLASHINGS SHALL NOT BE CUT OR OVERLAPPED.
3.VERIFY ROOF & STRUCTURAL SYSTEM WITH ARCHITECT.
4.COORDINATE FLASHING INSTALLATION WITH ROOFING CONTRACTOR TO
ENSURE PROPER METHODS & MATERIALS ARE USED TO MAINTAIN ROOF
WARRANTY.
PREFABRICATED RUBBER
BOOT CAP WITH GRADUATED
STEPS & WEATHER-PROOF
PRESSURE SEAL TO COLLAR
SEALANT AT PENETRATION
TO MEMBRANE JUNCTUREBY
ROOFING CONTRACTOR MULTIPLE MEMBRANE STRIPPING
PLIES FEATHERED AT FIELD OF
ROOF BY ROOFING CONTRACTOR.
PRIME FLANGE BEFORE STRIPPING.
PREFABRICATED FORMED 1.52mm
(0.06") THICK ALUMINUM FLASHING
ROUND COLLAR WITH MIN. 76mm
(3") WIDE FLANGE. ATTACH TO
ROOF PER MANUFACTURER'S
INSTRUCTIONS
CONDUIT CLAMP. SIZE AS
REQUIRED
BATT INSULATION
ROOF MEMBRANE
WATER CUT-OFF
MASTIC COMPATIBLE
WITH ROOF MEMBRANE
STAINLESS CLAMP, TYP.
9.52mm (3/8")
MIN GALVANIZED
THREADED ROD,
TYP.
SEAL-OFF
FITTING,
TYP.
ROOF
STEEL
EXPANSION
ANCHOR
INTEGRAL GALVANIZED
LIPPED STEEL
MOUNTING CHANNEL
CONDUIT,
TYP.
CONDUIT
CLAMP. SIZE
AS REQUIRED
LOCKING
SQUARE
WASHER &
LOCKNUT
GROUND BUS
NEUTRAL BUS
CONDUIT BONDING
GROUNDING
ELECTRODE
CONDUTOR
GROUND BUS
GROUNDING
CONDUCTOR
NEUTRAL BUS
CONDUIT BONDING
BOND TO BUILDING STEEL. IF STEEL
IS NOT AVAILABLE, BOND TO MDS
480V, 3PH, 3W PHASE
CONDUCTORS
DRY TYPE TRANSFORMER
PHASE
CONDUCTORS
BRANCH CIRCUIT CONDUIT
MAKE CIRCUIT JOINT
WITH TWIST-ON
CONNECTOR AND
CONNECT TO DEVICE
WITH SINGLE LEADS
1#12 AWG SOLID
COPPER GREEN
INSULATED JUMPER TO
BOX BONDING SCREW
DEVICE TRIM PLATE
BOX DEVICE COVER WITH RAISED
RING OF PROPER DEPTH AND TYPE
FOR WALL CONSTRUCTION. RING
TO FINISH FLUSH WITH WALL
4" SQUARE
DEVICE BOX
1#12 AWG SOLID
COPPER GREEN
INSULATED JUMPER TO
DEVICE GROUNDING
SCREW
NOTES: (ACCESS CONTROL SYSTEM)
1.THIS IS A GENERAL SERVICE SCHEMATIC WITH TYPICAL
DEVICE AND WIRING RELATIONSHIPS OF A NEW ACCESS
CONTROL SYSTEM TO SERVE THE FACILITY, INTENDED TO
CONVEY THE BASIS OF DESIGN.
2. REFER TO PLANS AND DETAILS FOR QUANTITIES OF
DEVICES AND GENERAL EQUIPMENT, LOCATIONS AND
CABLING DETAILS. PROVIDE ALL NECESSARY AND
REQUIRED HARDWARE, RACEWAY SYSTEMS, CABLING,
CIRCUITRY, BONDING, GROUNDING, ETC.
3.EXACT LOCATIONS AND QUANTITIES OF ACCESS DEVICES,
ETC. TO BE COORDINATED WITH OWNER REPRESENTATIVE
PRIOR TO ROUGH IN AND LAYOUT.
4.ALL EQUIPMENT, ETC. INSTALLED IN OR OPEN TO THE
CEILING CAVITY ENVIRONMENTAL AIR PLENUM WILL BE
RATED AND U.L. LISTED FOR SUCH INSTALLATIONS. ALL
SURVEILLANCE AND RELATED COMMUNICATION WIRING
SHALL BE IN EMT.
5.SYSTEMS TO BE COORDINATED WITH OWNER
REPRESENTATIVE PRIOR TO COMMENCING WORK.
PROVIDE ALL NECESSARY AND REQUIRED COMPONENTS,
CABINETS, DEVICES, APPLIANCES, CABLING AS PER
MANUFACTURER.
ELECTRIC STRIKE,
COORDINATE WITH
ARCHITECT FOR
HARDWARE
COMPATIBILITY AND
MOUNTING DETAILS
TYPICAL ACCESS CONTROLLED DOOR
CARD READER
ON ENTRY SIDE OF DOOR
1/2"C
#18 AWG
#16 AWG
DOOR CONTACTS
GENERAL NOTES:
1.ALL COMPONENTS AND WIRING
PROVIDED BY THE CONTRACTOR
EXCEPT AS NOTED.
2.ALL CONDUITS SHALL BE SEALED.
CEILING
MOTION SENSOR
ON EGRESS SIDE
OF DOOR,
CONNECTED FOR
FREE EGRESS
#16 AWG
CAT 6A CABLING TO PATCH PANEL
120V POWER CIRCUITRY
12"X12"X6" GALVANIZED STEEL
JUNCTION BOX WITH SCREW
COVER, LOCATED ABOVE
NEAREST ACCESSIBLE
CEILING ON THE SECURE SIDE
OF DOOR. PROVIDE 3/4"C WITH
INSULATED BUSHING FOR
CONTROL WIRING BACK TO
ELECTRICAL ROOM ON 1ST
FLOOR.
CONTROLLER(S), MOUNTED IN
ELECTRICAL ROOM (FURNISHED BY
OWNER) INSTALLED BY CONTRACTOR
38"w w w . l i t t l e o n l i n e . c o m
This drawing and the design shown are the property
of Little Diversified Architectural Consulting. The
reproduction, copying or other use of this drawing
without their written consent is prohibited and any
infringement will be subject to legal action.
Little 2017c
PROJECT MANAGER
DESIGN TEAM
PRINCIPAL IN CHARGE
PROJECT TEAM
REVISIONS
PROJECT NAME
SHEET TITLE
PROJECT NO.
SHEET NUMBER
ISSUE FOR
ISSUE DATE
B
1 2 3 4 5 6 7
A
C
D
E
F
410 Blackwell Street, Suite 10
Durham, NC 27701
T: 919.474.2500
10/6/2017 4:23:47 PM C:\Users\brenden.elliott\Documents\513.7505.00_CU_WrestlingExpansion_E-16_brenden.elliott.rvt513.7505.00
10/6/17
E5.1.2
ELECTRICAL DETAILS
Campbell Convocation
Center Wrestling
Department Renovation
and Expansion
BID/PERMIT SET
Rob Klinedinst
Katie Buckman
LITTLE
NOT TO SCALEE5.1.2
1 ELECTRICAL WORKING CLEARANCES DETAIL
NOT TO SCALEE5.1.2
2 CONDUIT ROOF PENETRATION DETAIL
NOT TO SCALEE5.1.2
4 TRANSFORMER BONDING DETAIL
NOT TO SCALEE5.1.2
3 RECEPTACLE GROUNDING DETAIL
NOT TO SCALEE5.1.2
5 DOOR ACCESS CONTROL DETAIL
NO. REASON DATE
CORPORATE LICENSE #F-0467
33 eE.6
eE
RL
EX
EX2
PRACTICE
GYMNASIUM
1036
OS
EATON
OAC-DT-2000-R
(QTY. INDICATED
ON PLANS)
H
N
NORMAL
POWER
H
N
EMERGENCY
POWER
EATON
7601
POWER
PACKSWITCH
"S-LV"
NORMAL
LIGHTING
LOAD
EMERG
POWER
TRANSFER
EATON
CEPC-1-D
EMERGENCY
LIGHTING
LOAD
FIXTURES 'F6'
OR 'F2'
FIXTURES 'F6'
OR 'F2'
EATON
SP20-MV
OS
EATON
OAC-DT-2000-R
(QTY. INDICATED
ON PLANS)
H
N
NORMAL
POWER
H
N
EMERGENCY
POWER
EATON
WBSD-010DEC-C1
POWER
PACK
DIMMER
SWITCH
"S-LV1"
NORMAL
LIGHTING
LOAD
EMERG
POWER
TRANSFER
EATON
CEPC-1-D
EMERGENCY
LIGHTING
LOAD
FIXTURES 'F1'
FIXTURES 'F1'
EATON
SP20-MV
OS
EATON
OAC-DT-2000-R
(QTY. INDICATED
ON PLANS)
H
N
NORMAL
POWER
EATON
WBSD-010DEC-C1
POWER
PACK
DIMMER
SWITCH
"S-LV1"
NORMAL
LIGHTING
LOAD
FIXTURES 'F1'
EATON
SP20-MV
w w w . l i t t l e o n l i n e . c o m
This drawing and the design shown are the property
of Little Diversified Architectural Consulting. The
reproduction, copying or other use of this drawing
without their written consent is prohibited and any
infringement will be subject to legal action.
Little 2017c
PROJECT MANAGER
DESIGN TEAM
PRINCIPAL IN CHARGE
PROJECT TEAM
REVISIONS
PROJECT NAME
SHEET TITLE
PROJECT NO.
SHEET NUMBER
ISSUE FOR
ISSUE DATE
B
1 2 3 4 5 6 7
A
C
D
E
F
410 Blackwell Street, Suite 10
Durham, NC 27701
T: 919.474.2500
10/6/2017 4:23:48 PM C:\Users\brenden.elliott\Documents\513.7505.00_CU_WrestlingExpansion_E-16_brenden.elliott.rvt513.7505.00
10/6/17
E6.0.0
LIGHTING FIXTURE
SCHEDULE
Campbell Convocation
Center Wrestling
Department Renovation
and Expansion
BID/PERMIT SET
Rob Klinedinst
Katie Buckman
LITTLE
LIGHTING FIXTURE SCHEDULE
TYPE DESCRIPTION MANUFACTURER MODEL ALTERNATE MANUFACTURER
LAMP
INFORMATION
VOLT
APPARENT
LOAD MOUNTING COMMENTSTYPE.
EX1 EXIT SIGN - CEILING MOUNTED SURE-LITES ELX6-X-G-X-C ACUITY - APPROVED EQUAL
HUBBELL - APPROVED EQUAL
LED 277 V 5 VA CEILING
EX2 EXIT SIGN - WALL MOUNTED SURE-LITES ELX6-X-G-X-W ACUITY - APPROVED EQUAL
HUBBELL - APPROVED EQUAL
LED 277 V 5 VA SURFACE
F1 2'x4' LED TROFFER LITHONIA 2BLT4-30L-ADSM-277-EZ1-L835 EATON - APPROVED EQUAL
HUBBELL - APPROVED EQUAL
LED 277 V 34 VA RECESSED
F2 2'x2' LED TROFFER LITHONIA 2BLT2-20L-ADSM-277-EZ1-L835 EATON - APPROVED EQUAL
HUBBELL - APPROVED EQUAL
LED 277 V 20 VA RECESSED
F6 4' LED LINEAR FIXTURE EATON 4SLSTP4040DD-UNV ACUITY - APPROVED EQUAL
HUBBELL - APPROVED EQUAL
LED 277 V 43 VA SUSPENDED
F6A 4' LED LINEAR FIXTURE EATON 4SLSTP2040DD-UNV ACUITY - APPROVED EQUAL
HUBBELL - APPROVED EQUAL
LED 277 V 20 VA SUSPENDED
F7 EXTERIOR WALL FIXTURE LITHONIA TWR1-LED-3-40K-MVOLT EATON - APPROVED EQUAL
HUBBELL - APPROVED EQUAL
LED 277 V 49 VA WALL
1/8" = 1'-0"E6.0.0
3 CONVOCATION PRACTICE GYM - LIGHTING PLAN
NOT TO SCALEE6.0.0
1
LIGHTING CONTROL DIAGRAM - LOCKER ROOMS, LOUNGE, FITNESS,
CORRIDOR, AND RECEPTION (TYPICAL)
NOT TO SCALEE6.0.0
2 LIGHTING CONTROL DIAGRAM - CONFERENCE ROOM 104 & OFFICE 103
GENERAL NOTES (LIGHTING CONTROL DIAGRAMS):
A. ALL ROOM CONTROLLERS SHALL BE LOCATED ABOVE THE CEILING AT ENTRY DOOR. PROVIDE
MARK OR LABEL ON CEILING GRID DIRECTLY BELOW THE CONTROLLER, COORDINATE TYPE OF
IDENTIFICATION WITH OWNER AND ARCHITECTS PRIOR TO INSTALLATION.
B. THE DIAGRAMS ON THIS SHEET ARE GENERAL SCHEMATICS INTENDED TO CONVEY THE BASIS
OF DESIGN. IF ANOTHER MANUFACTURER IS USED, CONTRACTOR IS RESPONSIBLE FOR PROVIDING
ALL NECESSARY EQUIPMENT, DEVICES, WIRING, ETC. TO ENSURE ACTUAL INSTALLATIONS AND
PERFORMANCE OF THE SYSTEM MEETS THE DESIGN INTENT.
NOT TO SCALEE6.0.0
4 LIGHTING CONTROL DIAGRAM - COACH OFFICE 105
NOTE: CONTRACTOR TO VERIFY EXISTING LAMP COLOR TEMPERATURE AND MATCH NEW TO EXISTING.
NO. REASON DATE
CORPORATE LICENSE #F-0467
70/3 70/3
1
1
1
1TN2 (NEW)
45 KVA
PRIMARY: 480V
SEC: 208/120V
3#4,#8(G) IN 1"C
4#1/0,#6(G) IN 2"C
#6 CU, 1/2"C
4#3,#8(G) IN
1-1/4"C
4#3,#8(G) IN
1-1/4"C
2 SETS OF:
4#500,#1/0(G) IN 3-1/2"C
150/3
150A
70A
GENERATOR
45KW
FIRE PUMP
CONTROLLER WITH
TRANSFER SWITCHL
#2#1
L
#2#1 ATS-2
L
#2#1 ATS-1
G
M MM M
M MM M M M
VFD VFD
M M
VFD VFD
M
VFD
M M M M M M M M
M
M MM M M M M M
VFD VFD
M M
VFD VFD
M
VFD
M M
VFD VFD
M M
VFD VFD
M
VFD
M
M MMMM
M M
GFP 100% RATED
480/277V SEC., 3PH, 4W
UTILITY XFMR
3200/3
MAIN SWITCHBOARD MDSB
100/3800/3 800/3
800A BUS
PANEL 1MHN1
3PH, 4W
480/277V,
2TS
400/3AF
2DLS
PANEL
GROUND BAR
NEUT.
GND.
250/3 100/3 100/3 100/3
100/3
100A
2PLS1
PANEL
100/3
100A
2PLS2
PANEL
250/3AF
480/277V, 3PH, 4W
PANEL 2DHS
250A BUS
100A
ELEVATOR 1002
100A
ELEVATOR 1019
100/3
100A
2PLS3
PANEL
3LHN1
PANEL
3LHN2
PANEL
3LHN3
PANEL
100A 100A 100A
80A
COOLING TOWER
100A
ELEVATOR 1044
70/3
CWP-2
40/3
PCHP-1
70/3
CWP-1 PCHP-2 SCHP-1 SCHP-2 HP-1 HP-2
100/3 90/3 100/3
AHU-1
RETURN
AHU-1
SUPPLY
AHU-2
SUPPLY
90/3
AHU-2
RETURN
20/3
COOLING
TOWER
BASIN
VF-1 CAF-1COOLING
TOWER
BASIN
CAF-1
J
1TN
400/3AF
1DLN
PANEL
225A
150/3
225A
1PLS1
PANEL
225A
1PLS2
PANEL
1TS
250/3AF
150A
1DLS
PANEL
100A
1LHN
PANEL
100A
1LHS
PANEL
100/3
100/3
100A
1SLN1
PANEL
200/3
1TN1
250/3AF
150A
1DLN1
PANEL
150/3
100A
SCRBD
PANEL
100/3
100A
1PLN1
PANEL
100/3
100A
1PLN2
PANEL
100/3
100A
1PLN3
PANEL
100/3
100A
1PLN4
PANEL
150/3
400A 200A 200A 100A
'CAMLOK'
PLUGS
PD-1
CHILLER
CH-1
70/3 40/3 100/3 90/3 100/3 90/3 20/3 20/3
400A BUS
PANEL 1MHN2
3PH, 4W
480/277V,
BOILER
B-1
BOILER
B-2
AHU-4
SUPPLY
AHU-4
RETURN
AHU-7
SUPPLY
AHU-7
RETURN
AHU-3
SUPPLY
AHU-5
SUPPLY
AHU-5
RETURN
AHU-6
SUPPLY
AHU-8
SUPPLY
AHU-8
RETURN
AHU-3
RETURN
AHU-6
RETURN
125A 100A 100A
FIRE
PUMP
400/3 100/3
20/3
OS1DHN
PANEL
35/3 20/3
REF-1 JOCKEY PUMP
DOMESTIC
WATER
BOOSTER
PUMP
E1TN
50/3
30/3 100A 100A 40/3
E3LLS
PANEL
E1LHN
PANEL
125A 125A
E1DHN
PANEL
40/3 40/3 40/3 40/3 40/3 20/3 20/3 20/3 20/3 20/3 20/3 20/3 20/3 20/3 20/3
60/3
E1PLN1
PANEL
100A
MINI
POWER
ZONE
225/3
RTU-1 RTU-2
20/3
PANEL
1PLN5 (NEW)
42 CKT.
LOAD SUMMARY - "MSBD"
3200
OVERCURRENT PROTECTION
EXISTING LOAD (FROM RECORD
DRAWINGS)
NEW LOAD
EQUIPMENT BUS RATING AMPS
AMPS
KVA
KVA
3200
2231.8
117.19
2825.4 AMPS
TOTAL CONNECTED LOAD 2349 KVA
EXISTING DEMAND LOAD
ADDED LOAD
AMPS
AMPS
2307.1
+133.2
TOTAL DEMAND LOAD 2440.3 AMPS
w w w . l i t t l e o n l i n e . c o m
This drawing and the design shown are the property
of Little Diversified Architectural Consulting. The
reproduction, copying or other use of this drawing
without their written consent is prohibited and any
infringement will be subject to legal action.
Little 2017c
PROJECT MANAGER
DESIGN TEAM
PRINCIPAL IN CHARGE
PROJECT TEAM
REVISIONS
PROJECT NAME
SHEET TITLE
PROJECT NO.
SHEET NUMBER
ISSUE FOR
ISSUE DATE
B
1 2 3 4 5 6 7
A
C
D
E
F
410 Blackwell Street, Suite 10
Durham, NC 27701
T: 919.474.2500
10/6/2017 4:23:49 PM C:\Users\brenden.elliott\Documents\513.7505.00_CU_WrestlingExpansion_E-16_brenden.elliott.rvt513.7505.00
10/6/17
E7.0.0
SINGLE LINE DIAGRAM
Campbell Convocation
Center Wrestling
Department Renovation
and Expansion
BID/PERMIT SET
Rob Klinedinst
Katie Buckman
LITTLE
NOT TO SCALEE7.0.0
1 SINGLE LINE DIAGRAM
GENERAL NOTES:
1.EXISTING FEEDER SIZES ARE FROM RECORD DRAWINGS.
2.ALL EQUIPMENT, ASSOCIATED FEEDERS, AND CIRCUIT BREAKERS ARE EXISTING
TO REMAIN, UNLESS OTHERWISE NOTED. ALL NEW WORK ASSOCIATED WITH
PANELS IS SPECIFICALLY INDICATED ON THE PLANS, POWER RISER DIAGRAM
AND/OR THE PANEL SCHEDULES. SCOPE OF WORK INCLUDES NEW XFMR '1TN2'
& PANEL '1PLN5' AND MODIFICATIONS TO '1LHN', 'E1LHN', AND '1MHN1'.
3.UPDATE ALL PANEL DIRECTORIES PER RENOVATION WORK. PROVIDE NEW,
TYPED DIRECTORIES FOR ALL AFFECTED PANELS. NO HANDWRITTEN MARKS.
4.FOR ALL EXISTING LOADS REMOVED, AS A RESULT OF DEMOLITION
WORK, RELABEL CIRCUIT BREAKERS AS "SPARE" IN EXISTING PANELS.
PROVIDE UPDATED TYPED DIRECTORY. FOR PANELS AFFECTED,
CONTRACTOR SHALL TRACE CIRCUITS AS REQUIRED TO PROVIDE
UPDATED DIRECTORY.
5.ALL NEW CIRCUIT BREAKERS SHALL MATCH EXISTING AIC RATINGS.
REFERENCE NOTES (SINGLE LINE DIAGRAM):
ADDING LOAD TO EXISTING PANELS. SEE PANEL SCHEDULES E7.0.1.1
NO. REASON DATE
CORPORATE LICENSE #F-0467
LOAD SUMMARY - "1LHN"
125
OVERCURRENT PROTECTION
EXISTING LOAD (FROM RECORD
DRAWINGS)
ADDED LOAD (NEW LIGHTING)
EQUIPMENT BUS RATING AMPS
AMPS
KVA
KVA
100
39
+3.79
51.5 AMPS
TOTAL CONNECTED LOAD 42.79 KVA
EXISTING DEMAND LOAD
ADDED LOAD
AMPS
AMPS
46.92
+5.7
TOTAL DEMAND LOAD 52.62 AMPS
LOAD SUMMARY - "E1LHN"
125
OVERCURRENT PROTECTION
EXISTING LOAD (FROM RECORD
DRAWINGS)
ADDED LOAD (NEW LIGHTING)
EQUIPMENT BUS RATING AMPS
AMPS
KVA
KVA
100
15.54
+1.00
20 AMPS
TOTAL CONNECTED LOAD 16.54 KVA
EXISTING DEMAND LOAD
ADDED LOAD
AMPS
AMPS
18.5
+2
TOTAL DEMAND LOAD 20.5 AMPS
LOAD SUMMARY - "E1DHN"
125
OVERCURRENT PROTECTION
EXISTING LOAD (FROM RECORD
DRAWINGS)
PANEL E1LHN (NEW LOAD)
EQUIPMENT BUS RATING AMPS
AMPS
KVA
KVA
100
27.89
+1.00
34.75 AMPS
TOTAL CONNECTED LOAD 28.89 KVA
EXISTING DEMAND LOAD
ADDED LOAD
AMPS
AMPS
32.96
+1.25
TOTAL DEMAND LOAD 34.23 AMPS
LOAD SUMMARY - "1MHN1"
800
OVERCURRENT PROTECTION
EXISTING LOAD (FROM RECORD
DRAWINGS)
ADDED LOAD (RTU-1 & RTU-2)
EQUIPMENT BUS RATING AMPS
AMPS
KVA
KVA
800
420.04
+78.16
599.2 AMPS
TOTAL CONNECTED LOAD 498.2 KVA
EXISTING DEMAND LOAD
ADDED LOAD
AMPS
AMPS
505.47
+94
TOTAL DEMAND LOAD 599.5 AMPS
w w w . l i t t l e o n l i n e . c o m
This drawing and the design shown are the property
of Little Diversified Architectural Consulting. The
reproduction, copying or other use of this drawing
without their written consent is prohibited and any
infringement will be subject to legal action.
Little 2017c
PROJECT MANAGER
DESIGN TEAM
PRINCIPAL IN CHARGE
PROJECT TEAM
REVISIONS
PROJECT NAME
SHEET TITLE
PROJECT NO.
SHEET NUMBER
ISSUE FOR
ISSUE DATE
B
1 2 3 4 5 6 7
A
C
D
E
F
410 Blackwell Street, Suite 10
Durham, NC 27701
T: 919.474.2500
10/6/2017 4:23:50 PM C:\Users\brenden.elliott\Documents\513.7505.00_CU_WrestlingExpansion_E-16_brenden.elliott.rvt513.7505.00
10/6/17
E7.0.1
PANEL SCHEDULES
Campbell Convocation
Center Wrestling
Department Renovation
and Expansion
BID/PERMIT SET
Rob Klinedinst
Katie Buckman
LITTLE
**1: CONTRACTOR TO INSTALL NEW CIRCUIT BREAKER TO MATCH EXISTING TYPE AND AIC RATING.
Notes:
Total Est. Demand Current:5 A
Total Conn. Current:4 A
Total Est. Demand:4 kVA
Total Conn. Load:3.2 kVA
Lighting 3.2 kVA 125.00% 4 kVA (NEW LOAD ONLY)
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Legend:
Total Amps:0 A 5 A 8 A
Total Load:0 kVA 1.31 kVA 1.89 kVA
29 EXISTING 20 A 1 0 0 1 20 A EXISTING 30
27 Space -- -- 0 0 -- -- Space 28
25 Space -- -- 0 0 -- -- Space 26
23 Space -- --0 0 -- -- Space 24
21 Space -- -- 0 0 1 20 A EXISTING 22
19 Space -- -- 0 0 1 20 A EXISTING 20
17 LTG - WRESTLING GYM ADDITION **1 20 A 1 1.89 0 -- -- Space 18
15 LTG - WRESTL. LOCKERS, ROOMS 102-108 **1 20 A 1 1.31 0 -- -- --16
13 EXISTING 20 A 1 0 0 -- -- --14
11 EXISTING 20 A 1 0 0 3 20 A EXISTING 12
9 EXISTING 20 A 1 0 0 1 20 A EXISTING 10
7 EXISTING 20 A 1 0 0 1 20 A EXISTING 8
5 EXISTING 20 A 1 0 0 -- -- Space 6
3 EXISTING 20 A 1 0 0 1 20 A EXISTING 4
1 EXISTING 20 A 1 0 0 -- -- Space 2
CKT Circuit Description Trip Poles
A B C
Poles Trip Circuit Description CKT
ALL CIRCUIT BREAKERS SHOWN ARE EXISTING UNLESS OTHERWISE NOTED.
Notes:
Enclosure:Type 1 MCB Rating:
Mounting:Surface Wires:4 Mains Rating:125 A
Supply From:Phases:3 Mains Type:MLO
Location:Volts:480/277 Wye A.I.C. Rating:
Branch Panel: 1LHN
**1: CONTRACTOR TO INSTALL NEW CIRCUIT BREAKER TO MATCH EXISTING TYPE AND AIC RATING.
Notes:
Total Est. Demand Current:2 A
Total Conn. Current:1 A
Total Est. Demand:1.25 kVA
Total Conn. Load:1 kVA
Lighting 1 kVA 125.00% 1.25 kVA (NEW LOAD ONLY)
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Legend:
Total Amps:2 A 0 A 2 A
Total Load:0.46 kVA 0 kVA 0.54 kVA
29 Space -- --0 0 -- -- Space 30
27 Space -- -- 0 0 -- -- Space 28
25 Space -- -- 0 0 -- -- Space 26
23 Space -- --0 0 -- -- Space 24
21 Space -- -- 0 0 -- -- Space 22
19 Space -- -- 0 0 -- -- Space 20
17 Space -- --0 0 -- -- Space 18
15 Space -- -- 0 0 -- -- Space 16
13 Space -- -- 0 0 -- -- Space 14
11 Space -- --0 0 -- -- Space 12
9 EXISTING 20 A 1 0 0 -- -- Space 10
7 EXISTING 20 A 1 0 0.46 1 20 A LTG - ROOMS 102-108 8
5 EXISTING 20 A 1 0 0.54 1 20 A LTG - WRESTL. LOCKER RMS & GYM **1 6
3 EXISTING 20 A 1 0 0 1 20 A EXISTING 4
1 EXISTING 20 A 1 0 0 1 20 A EXISTING 2
CKT Circuit Description Trip Poles
A B C
Poles Trip Circuit Description CKT
ALL CIRCUIT BREAKERS SHOWN ARE EXISTING UNLESS OTHERWISE NOTED.
Notes:
Enclosure:Type 1 MCB Rating:
Mounting:Surface Wires:4 Mains Rating:125 A
Supply From:Phases:3 Mains Type:MLO
Location:Volts:480/277 Wye A.I.C. Rating:
Branch Panel: E1LHN
Notes:
Total Est. Demand Current:87 A
Total Conn. Current:95 A
Power 9.01 kVA 100.00% 9.01 kVA Total Est. Demand:31.5 kVA
Receptacle 15.48 kVA 82.30% 12.74 kVA Total Conn. Load:34.24 kVA
Other 9.75 kVA 100.00% 9.75 kVA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Legend:
Total Amps:94 A 98 A 93 A
Total Load:11.3 kVA 11.79 kVA 11.14 kVA
41 Spare 20 A 1 0 0 1 20 A Spare 42
39 Spare 20 A 1 0 0 1 20 A Spare 40
37 Spare 20 A 1 0 0 1 20 A Spare 38
35 ---- --3 0 1 20 A Spare 36
33 ---- -- 3 0.36 1 20 A REC: EXTERIOR ROOF 34
31 OWNER EQUIPMENT 30 A 3 3 0.9 1 20 A REC: WRESTLING LOCAKERS - 111 32
29 REC: WRESTLING LOCAKERS - 111 20 A 1 0.72 1.08 1 20 A REC: WRESTLING LOCAKERS - 111 30
27 REC: WRESTLING LOCAKERS - 111 20 A 1 1.08 1.08 1 20 A REC: WRESTLING LOCAKERS - 111 28
25 REC: COACH'S LOCKERS 109 & TOILET 109.1 ... 20 A 1 0.72 0.9 1 20 A REC: COACH'S LOCKERS 109 26
23 REC: LOUNGE 108 - COUNTERTOP 20 A 1 0.36 0.54 1 20 A REC: WRESTLING GYM EXPANSION - 101.1 24
21 REC: LOUNGE 108 - REF 20 A 1 0.75 0.18 1 20 A REC: LOUNGE 108 - COUNTERTOP 22
19 REC: LOUNGE 108 20 A 1 0.72 0.18 1 20 A REC: LOUNGE 108 - TV 20
17 REC: FITNESS 107 - STATIONARY BIKE 20 A 1 1 1 1 20 A REC: FITNESS 107 - STATIONARY BIKE 18
15 REC: FITNESS 107 - STATIONARY BIKE 20 A 1 1 1 1 20 A REC: FITNESS 107 - STATIONARY BIKE 16
13 REC: FITNESS 107 - TREADMILL 20 A 1 1 1 1 20 A REC: FITNESS 107 - ELLIPTICAL 14
11 REC: FITNESS 107 - TREADMILL 20 A 1 1 1 1 20 A REC: FITNESS 107 - TREADMILL 12
9 REC: ASST. COACH 103 - FURNITURE CONN #2 20 A 1 1.08 1 1 20 A REC: FITNESS 107 - TREADMILL 10
7 REC: ASST. COACH 103 - FURNITURE CONN #1 20 A 1 1.08 0.36 1 20 A REC: FITNESS 107 - TV's 8
5 REC: STOR 106 & CORRIDOR 102.1 20 A 1 0.9 0.54 1 20 A REC: FITNESS 107 6
3 REC: CONF 104 20 A 1 0.36 0.9 1 20 A REC: CONF 104 4
1 REC: RECEP. 102 20 A 1 0.72 0.72 1 20 A REC: ASST. COACH OFFICES 103 2
CKT Circuit Description Trip Poles
A B C
Poles Trip Circuit Description CKT
Notes:
Enclosure:Type 1 MCB Rating:
Mounting:Surface Wires:4 Mains Rating:150 A
Supply From:Phases:3 Mains Type:MLO
Location:Volts:120/208 Wye A.I.C. Rating:10,000
Branch Panel: 1PLN5(MODIFIED)
(MODIFIED)
(NEW)
**1: CONTRACTOR TO INSTALL NEW CIRCUIT BREAKER TO MATCH EXISTING TYPE AND AIC RATING.
Notes:
Total Est. Demand Current:94 A
Total Conn. Current:94 A
Total Est. Demand:78.16 kVA
Total Conn. Load:78.16 kVA
HVAC 78.16 kVA 100.00% 78.16 kVA (NEW LOAD ONLY)
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Legend:
Total Amps:94 A 94 A 94 A
Total Load:26.05 kVA 26.05 kVA 26.05 kVA
65 ---- --0 0 -- -- --66
63 ---- -- 0 0 -- -- --64
61 EXISTING 20 A 3 0 0 3 20 A EXISTING 62
59 ---- --0 0 -- -- --60
57 ---- -- 0 0 -- -- --58
55 EXISTING 20 A 3 0 0 3 20 A EXISTING 56
53 ---- --0 0 -- -- --54
51 ---- -- 0 0 -- -- --52
49 EXISTING 20 A 3 0 0 3 20 A EXISTING 50
47 ---- --0 0 -- -- --48
45 ---- -- 0 0 -- -- --46
43 EXISTING 20 A 3 0 0 3 20 A EXISTING 44
41 ---- --0 0 -- -- --42
39 ---- -- 0 0 -- -- --40
37 EXISTING 20 A 3 0 0 3 20 A EXISTING 38
35 ---- --0 0 -- -- --36
33 ---- -- 0 0 -- -- --34
31 EXISTING 20 A 3 0 0 3 20 A EXISTING 32
29 ---- --0 0 -- -- --30
27 ---- -- 0 0 -- -- --28
25 EXISTING 20 A 3 0 0 3 20 A EXISTING 26
23 ---- --0 0 -- -- --24
21 ---- -- 0 0 -- -- --22
19 EXISTING 20 A 3 0 0 3 20 A EXISTING 20
17 ---- --0 0 -- -- --18
15 ---- -- 0 0 -- -- --16
13 EXISTING 20 A 3 0 0 3 20 A EXISTING 14
11 Space -- --0 0 -- -- Space 12
9 Space -- -- 0 0 -- -- Space 10
7 Space -- -- 0 0 -- -- Space 8
5 ---- --13.03 13.03 -- -- --6
3 ---- -- 13.03 13.03 -- -- --4
1 RTU-1 **1 70 A 3 13.03 13.03 3 70 A RTU-2 **1 2
CKT Circuit Description Trip Poles
A B C
Poles Trip Circuit Description CKT
ALL CIRCUIT BREAKERS SHOWN ARE EXISTING UNLESS OTHERWISE NOTED.
Notes:
Enclosure:Type 1 MCB Rating:
Mounting:Surface Wires:4 Mains Rating:800 A
Supply From:Phases:3 Mains Type:MLO
Location:Volts:480/277 Wye A.I.C. Rating:
Branch Panel: 1MHN1
ELEC. 1111
MDSB
NO. REASON DATE
CORPORATE LICENSE #F-0467
FS
TS
SDSD
SDSD
SDSD
MM
C
F
HEAT DETECTOR
EV ELEVATOR LOBBY SMOKE DETECTOR
DUCT MOUNTED SMOKE DETECTOR WITH REMOTE LED INDICATOR
TP TAMPERPROOF SMOKE DETECTOR. IONIZATION TYPE.
TAMPER SWITCH
FLOW SWITCH
FIRE ALARM PULL STATION. SEE SPECIFICATIONS FOR DEVICE TYPE.
AS INDICATED ON PLANS. SEE SPECS FOR TYPE.
VISUAL FIRE ALARM NOTIFICATION APPLIANCE. (15 CANDELAS UNLESS
OTHERWISE NOTED). WALL-MOUNTED OR CEILING-MOUNTED AS INDICATED ON
PLANS.
COMBINATION AUDIBLE/VISUAL FIRE ALARM NOTIFICATION APPLIANCE.
(15 CANDELAS UNLESS OTHERWISE NOTED). WALL-MOUNTED OR CEILING-MOUNTED
CEILING OR WALL MOUNTED SMOKE DETECTOR
CONTROL MODULE
MONITOR MODULE
HD
AUDIBLE NOTIFICATION APPLIANCE. WALL-MOUNTED OR CEILING MOUNTED AS INDICATED
ON PLANS.
or SDSD
DD
A
F
V
Aor
Vor
For
R
DMP
M
FIRE/SMOKE DAMPER - FIRE ALARM CONNECTION
FIRE ALARM CONTROL PANEL
FIRE ALARM ANNUNCIATOR PANEL
FIRE ALARM ADDRESSABLE RELAY. COORDINATE CONNECTIONS TO MECHANICAL
EQUIPMENT WITH DIVISION 23 CONTRACTOR TO ENSURE PROPER OPERATION OF
MECHANICAL EQUIPMENT.
DOOR HOLD OPEN DEVICE PROVIDED UNDER GENERAL CONTRACT. PROVIDE 120V
AC CONNECTION TO FURNISHED POWER SUPPLY ABOVE ACCESSIBLE CEILING.
PROVIDE 3/4"C AND WIRING PER MANUFACTURER REQUIREMENTS BETWEEN POWER
SUPPLY AND HOLD OPEN DEVICE(S) AT DOOR.
POST INDICATOR VALVEPIV
BEAM DETECTOR
FACP
FAA
DUCT DETECTOR REMOTE INDICATOR LIGHT (MOUNTED IN NEAREST COMMON AREA)LI
MOUNT ON
APPROVED BOX
SMOKE/HEAT
DETECTOR
INSTALL PER
NATIONAL ELECTRIC CODE
CONDUIT
AIR SUPPLY DIFFUSER OR
OR RETUN AIR OPENING
MOUNT AUDIBLE
& VISUAL DEVICES
ON APPROVED
BOXED.
0'-6" MIN3'-0" MIN0'-4" MIN 1'-0" MAX
HORN
SMOKE/HEAT
DETECTOR
STROBE
FINISHED FLOOR
HINGED SIDE
MANUAL PULL
STATION
HORN/STROBE
5'-0" MAX
(3'-6" MIN,
4'0" MAX)
3'-8"
80" MIN
BOTTOM OF DEVICE
96" MAX
TOP OF
DEVICE
EXIT
5'-6"
A B C D E F G H I J K L M N O P Q R S T U V W X Y
A B C D E F G H I J K L M N O P Q R S T U V W X Y
1
2
3
4
5
6
7
8
9
10
FIRE ALARM SYSTEM AC POWER FAILURE
SYSTEM INPUTS
11
12
13
14
15
16
17
18
19
20
21
22
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
FIRE ALARM SYSTEM LOW BATTERY
OPEN CIRCUIT
GROUND FAULT
NOTIFICATION APPLIANCE CIRCUIT SHORT
BUILDING MANUAL PULL STATIONS
CORRIDOR SMOKE DETECTORS
AREA SMOKE DETECTORS
HVAC AIR DUCT SMOKE DETECTORS
SPRINKLER TAMPER SWITCH
SPRINKLER WATER FLOW IN BUILDING
SPRINKLER WATER FLOW IN ELEVATOR EQUIPMENT ROOM OR SHAFT
ELEVATOR EQUIPMENT ROOM AREA SMOKE DETECTOR
ELEVATOR SHAFT AND ELEVATOR EQUIPMENT ROOM HEAT DETECTORS
ELEVATOR LOBBY SMOKE DETECTORS - UPPER FLOORS
ELEVATOR LOBBY SMOKE DETECTORS - RECALL FLOOR
ELEVATOR CONTROLLER POWER SHUNT TRIP STATUS
FIRE PUMP POWER FAILURE/PHASE REVERSAL
FIRE PUMP RUNNING
FIRE PUMP SYSTEN NOT IN AUTOMATIC
--
AREA OF REFUGE TWO-WAY COMMUNICATIONS STATUS
FIRE ALARM
SYSTEM MATRIX
SPRINKLERED BUILDING
SYSTEM OUTPUTSACTUATE COMMON ALARM SI
GNAL I
NDI
CATORACTUATE AUDI
BLE SUPERVI
SORY SI
GNALACTUATE AUDI
BLE ALARM SI
GNALACTUATE ZONE OR DEVI
CE ADDRESS ALARM I
NDI
CATORACTUATE COMMON SUPERVI
SORY SI
GNAL I
NDI
CATORACTUATE AUDI
BLE TROUBLE SI
GNALACTUATE COMMON TROUBLE SI
GNAL I
NDI
CATORACTUATE GENERAL EVACUATI
ON SI
GNALDI
SPLAY CHANGE OF STATUSTRANSMI
T FI
RE ALARM SI
GNAL TO CENTRAL STATI
ONTRANSMI
T SUPERVI
SORY SI
GNAL TO CENTRAL STATI
ONTRANSMI
T TROUBLE SI
GNAL TO CENTRAL STATI
ONRELEASE MAGNETI
CALLY HELD DOORSRECALL ELEVATOR TO RECALL FLOORRECALL ELEVATOR TO ALTERNATE RECALL FLOORACTUATE WARNI
NG TO ELEVATOR CABSDELAYED REMOVAL OF POWER FROM ELEVATORSUNLOCK EXI
TS AND CONTROL DOORSSHUT DOWN RESPECTI
VE AI
R HANDLI
NG EQUI
PMENT-
-
-
-
FACP ANNUNCIATION NOTIFICATION REQUIRED FIRE SAFETY CONTROL
NOTE: EXISTING BUILDING’S SEQUENCE OF OPERATION IS FOR REFERENCE ONLY.
CONTRACTOR TO VERIFY EXISTING BUILDING’S SEQUENCE OF OPERATIONS.
THE EXISTING SYSTEM CONSISTS OF INITIATION, NOTIFICATION, AND DETECTION (PULL STATIONS, AUDIBLE/VISUAL, VISUAL, SMOKE
DETECTORS, DUCT DETECTORS). ALL EXISTING DEVICES AND EQUIPMENT TO REMAIN AS INSTALLED UNLESS INDICATED OTHERWISE ON
DRAWINGS. MAINTAIN OPERATIONAL INTEGRITY OF ALL EXISTING DEVICES AND EQUIPMENT TO REMAIN. REPLACE ANY COMPONENT NOT IN
PROPER OPERATING ORDER.
REFER TO PLANS AND DETAILS FOR QUANTITIES AND LOCATIONS OF NEW DEVICES AND EQUIPMENT. ALL NEW DEVICES/EQUIPMENT SHALL
BE COMPATIBLE WITH, AND INTERFACED WITH THE EXISTING FIRE ALARM SYSTEM.
PROVIDE ALL REQUIRED AND NECESSARY APPLIANCES, WIRING, RE-PROGRAMMING, RACEWAYS, BACKBOXES, AND TESTING FOR A
COMPLETE OPERATING SYSTEM IN COMPLIANCE WITH NFPA 101, 70, 72 AND OTHER RELATED CODES.
A CERTIFIED FIRE ALARM SYSTEM REPRESENTATIVE SHALL FURNISH AND INSTALL CABLES, CONTROL MODULES, CONTROL/RELAY
MODULES, MONITOR MODULES, SIGNALING LINE CIRCUIT MODULES, SYNCHRONIZATION MODULES, AND ALL RELATED AND NECESSARY RE-
PROGRAMMING, FUNCTIONAL TESTING, ETC. AS REQUIRED TO ACCOMMODATE THE NEW NOTIFICATION APPLIANCES, INITIATION DEVICES,
ETC. FOR A COMPLETE WORKING FIRE ALARM SYSTEM.
ACTIVATION OF THE NEW FIRE ALARM SYSTEM NOTIFICATION APPLIANCES, INITIATING DEVICES, CONTROL/RELAY MODULES, MONITOR
MODULES, ETC. SHALL BE PER THE BUILDING'S FIRE ALARM SYSTEM CONTROL PANEL SEQUENCE OF EVENTS AND OPERATION.
EXACT LOCATIONS AND QUANTITIES OF APPLIANCES, PANELS, ETC. TO BE COORDINATED WITH AE TEAM AND WITH LOCAL AHJ PRIOR TO
ROUGH-IN AND LAYOUT.
PROVIDE DETAILED SHOP DRAWING SUBMITTAL, INCLUDING BUT NOT LIMITED TO, A LAYOUT PLAN OF ALL APPLIANCES, CABLING, AND
EQUIPMENT, INCLUDING POINT TO POINT WIRING DIAGRAM, BATTERY AND VOLTAGE DROP CALCULATIONS, FOR SUBMITTAL TO AND
REVIEW AND APPROVAL BY AE TEAM AND OSFM PRIOR TO COMMENCING WORK OR ORDERING MATERIAL.
ALL EQUIPMENT, ETC INSTALLED IN OR OPEN TO THE CEILING CAVITY ENVIRONMENTAL AIR PLENUM SHALL BE RATED AND U.L. LISTED FOR
SUCH INSTALLATIONS.
FIRE ALARM SYSTEM CABLING TYPE, RATING, SIZE AND QUANTITIES, TO BE AS DICTATED BY FIRE ALARM AND FIRE SUPPRESSION
SYSTEM'S MANUFACTURERS.
QUANTITIES OF NOTIFICATION APPLIANCES, INITIATING DEVICES, ETC., SHALL BE AS DELINEATED ON THE PLANS AND AS REQUIRED BY THE
OFFICE OF THE STATE FIRE MARSHAL.
QUANTITIES OF POWER SUPPLY UNITS, MODULES, CONTROLLERS, CARDS, RELAYS, ETC., SHALL BE PROVIDED AS DICTATED BY APPLIANCE
LOADS.
CEILING MOUNTED SMOKE/HEAT DETECTORS SHALL BE A MINIMUM OF 2' AWAY FROM LIGHT FIXTURES AND A MINIMUM OF 3' AWAY FROM
AIR DISTRIBUTION DEVICES. RELOCATE EXISTING DEVICES IN NEW CEILING(S) AS REQUIRED.
CANDELA RATINGS INDICATED ON DRAWINGS ARE THE REQUIRED MINIMUM CANDELA. ALL 15 CANDELA FIRE ALARM STROBES SHALL BE
RATED FOR 15/75 CANDELAS.
WHERE NEW AND EXISTING VISUAL NOTIFICATION APPLIANCES ARE WITHIN THE SAME FIELD OF VIEW, PROVIDE FLASH SYNCHRONIZATION
OF ALL APPLIANCES.
AUDIBLE SIGNAL SOUND LEVEL SHALL BE AT LEAST 15dBA ABOVE THE AVERAGE AMBIENT SOUND LEVEL OR 5dBA ABOVE THE MAXIMUM
SOUND LEVEL HAVING A DURATION OF 60 SECONDS MINIMUM, WHICHEVER IS LOUDER, MEASURED FIVE FEET ABOVE THE FLOOR IN THE
OCCUPIABLE AREA. AMBIENT SOUND LEVEL IS CONSIDERED AT 60dBA. COMPLY WITH 2012 NC FIRE CODE 907.6.2.1.1.
INTERRUPTION OF EXISTING FIRE-ALARM SERVICE: DO NOT INTERRUPT FIRE-ALARM SERVICE TO FACILITIES OCCUPIED BY OWNER UNLESS
PERMITTED UNDER THE FOLLOWING CONDITIONS AND THEN ONLY AFTER ARRANGING TO PROVIDE TEMPORARY GUARD SERVICE OR FIRE
WATCH ACCORDING TO REQUIREMENTS INDICATED:
1. NOTIFY OWNER IN ADVANCE OF PROPOSED INTERRUPTION OF FIRE-ALARM SERVICE.
2. DO NOT PROCEED WITH INTERRUPTION OF FIRE-ALARM SERVICE WITHOUT OWNER'S WRITTEN PERMISSION.
PROTECT EXISTING DEVICES DURING CONSTRUCTION, UNLESS DEVICES ARE PLACED IN SERVICE TO PROTECT THE FACILITY DURING
CONSTRUCTION.
MAINTAIN EXISTING EQUIPMENT FULLY OPERATIONAL UNTIL NEW EQUIPMENT HAS BEEN TESTED AND ACCEPTED. AS NEW EQUIPMENT IS
INSTALLED, LABEL IT "NOT IN SERVICE" UNTIL IT IS ACCEPTED. REMOVE LABELS FROM NEW EQUIPMENT/DEVICES WHEN PUT INTO SERVICE.
LABEL EXISTING FIRE-ALARM EQUIPMENT/DEVICES "NOT IN SERVICE" UNTIL REMOVED FROM THE BUILDING. AFTER ACCEPTANCE OF NEW
FIRE-ALARM SYSTEM, REMOVE EXISTING DISCONNECTED FIRE-ALARM EQUIPMENT AND WIRING.
ALL WIRING SHALL BE IN 1/2" DEDICATED CONDUIT.
ALL FIRE ALARM SYSTEM WORK SHALL BE APPROVED BY THE LOCAL AHJ PRIOR TO COMMENCING ANY FIRE ALARM WORK.
ALL NEW FIRE ALARM APPLIANCES SHALL BE RED FINISH.
A.
B.
C.
D.
E.
F.
G.
H.
I.
J.
K.
L.
M.
N.
O.
P.
Q.
R.
S.
T.
U.
EXISTING FIRE ALARM CONTROL
PANEL (SIMPLEX 4100U) LOCATED ON
LEVEL 1
F
TYPICAL NEW DEVICES, SEE PLAN FOR LOCATION
EXISTING
PREACTION
RELEASE
PANEL
CONTROL
EXISTING
ELEVATOR
RECALL
TO FAN SHUT
DOWN CONTROL
(EXISTING)
EXISTING CIRCUIT FOR MECHANICAL
EQUIPMENT SHUTDOWN AT ALARM
CONDITION (COMMONS AREA UNITS)
SUPPLY (EXISTING)
24VDC CHARGER/POWER
EXISTING NOTIFICATION APPLIANCE CIRCUIT LOOP EXISTING INITIATION CIRCUIT LOOP
EXISTING SPRINKLER FLOW
ALARM SWITCHES AND VALVE
SUPERVISORY SWITCHES
120V CIRCUIT (EXISTING)
EXISTING
FIRE
ALARM
PANEL
ANNUNCIATOR
SERVICE, PER NFPA 72 (EXISTING)
TO U.L. LISTED 24-HOUR MONITORING
C
FLFL TSTS
SD SD
DD
LI
A FF T
NOTE:
THIS IS A GENERAL SERVICE SCHEMATIC WITH TYPICAL BOARD AND DEVICE WIRING
RELATIONSHIPS OF THE EXISTING FIRE ALARM AND DETECTION CONTROL SYSTEM
SERVING THE FACILITY.
F V A
F AFVA
TYPICAL NOTIFICATION
BOOSTER APPLIANCE
PANEL
TYPICAL NEW DEVICES, SEE PLAN FOR LOCATION
DD
w w w . l i t t l e o n l i n e . c o m
This drawing and the design shown are the property
of Little Diversified Architectural Consulting. The
reproduction, copying or other use of this drawing
without their written consent is prohibited and any
infringement will be subject to legal action.
Little 2017c
PROJECT MANAGER
DESIGN TEAM
PRINCIPAL IN CHARGE
PROJECT TEAM
REVISIONS
PROJECT NAME
SHEET TITLE
PROJECT NO.
SHEET NUMBER
ISSUE FOR
ISSUE DATE
B
1 2 3 4 5 6 7
A
C
D
E
F
410 Blackwell Street, Suite 10
Durham, NC 27701
T: 919.474.2500
10/6/2017 4:23:52 PM C:\Users\brenden.elliott\Documents\513.7505.00_CU_WrestlingExpansion_E-16_brenden.elliott.rvt513.7505.00
10/6/17
FA0.0.0
FIRE ALARM
COVERSHEET
Campbell Convocation
Center Wrestling
Department Renovation
and Expansion
BID/PERMIT SET
Rob Klinedinst
Katie Buckman
LITTLE
FIRE ALARM GENERAL NOTES FIRE ALARM SYMBOL LEGEND NOTE: ALL SYMBOLS MAY NOT BE USED.
NOT TO SCALEFA0.0.0
2 FIRE ALARM MOUNTING DETAIL
NOT TO SCALEFA0.0.0
3 FIRE ALARM RISER DIAGRAM
NO. REASON DATE
CORPORATE LICENSE #F-0467
F
F F
FF
F
FF
SD FFFIRE BARRIER FIRE & SMOKE BARRIER
1-HOUR
2-HOUR
3-HOUR
0.5-HOUR
1-HOUR
FIRE PARTITIONFIRE WALL
2-HOUR
3-HOUR
4-HOUR
1-HOUR
2-HOUR
3-HOUR
0-HOUR 1-HOUR
SMOKE BARRIERSMOKE PARTITION
WRESTLING
GYM
101
WRESTLING
LOCKERS
111
STAIR
103.3
RV
RL
EX
EX EX
EX
EX
EX
EX
EX
eG
eF
eE.6
eE
e109
RV
w w w . l i t t l e o n l i n e . c o m
This drawing and the design shown are the property
of Little Diversified Architectural Consulting. The
reproduction, copying or other use of this drawing
without their written consent is prohibited and any
infringement will be subject to legal action.
Little 2017c
PROJECT MANAGER
DESIGN TEAM
PRINCIPAL IN CHARGE
PROJECT TEAM
REVISIONS
PROJECT NAME
SHEET TITLE
PROJECT NO.
SHEET NUMBER
ISSUE FOR
ISSUE DATE
B
1 2 3 4 5 6 7
A
C
D
E
F
410 Blackwell Street, Suite 10
Durham, NC 27701
T: 919.474.2500
10/6/2017 4:23:54 PM C:\Users\brenden.elliott\Documents\513.7505.00_CU_WrestlingExpansion_E-16_brenden.elliott.rvt513.7505.00
10/6/17
FAD1.1.1
FIRE ALARM
DEMOLITION PLAN -
CONVOCATION AREA C
Campbell Convocation
Center Wrestling
Department Renovation
and Expansion
BID/PERMIT SET
Rob Klinedinst
Katie Buckman
LITTLE
X KEY NOTES
KEY PLAN
GENERAL SHEET NOTES
RATED WALL LEGEND
DEMO
EXISTING BUILDING
3/16" = 1'-0"FAD1.1.1
1
CONVOCATION AREA C - DEMOLITION
FIRE ALARM PLAN
NO. REASON DATE
CORPORATE LICENSE #F-0467
FECFEC
SD
F
AF
F
F
F
F
FFFF
F F
FF
F
F
FF
SD F F
F
FF
F
V
CORRIDOR
1015
STAIR B
1020
FIRE PUMP
1016
ELECTRICAL
1017
BOILER
1014
CUSTODIAL
OFFICE
1018
ELEV
1019
FIRE BARRIER FIRE & SMOKE BARRIER
1-HOUR
2-HOUR
3-HOUR
0.5-HOUR
1-HOUR
FIRE PARTITIONFIRE WALL
2-HOUR
3-HOUR
4-HOUR
1-HOUR
2-HOUR
3-HOUR
0-HOUR 1-HOUR
SMOKE BARRIERSMOKE PARTITION
eG
e10
eE.6
eE
eF
FITNESS
107
WRESTLING
GYM
101
COACH
105
ASST.
COACH
OFFICES
103
LOUNGE
108
CORRIDOR
102.1
RECEP.
102
CONF.
104
STOR.
106
COACH
LOCKERS
109
WRESTLING
LOCKERS
111
Room
105
VESTIBULE
110
TOILET
109.1
WRESTLING
GYM
ADDITION
101.1
STAIR
103.3
EX
EX EX
EX
RL
EX
15
30
30
30
30
15
15151515
110
110
EX
EX
DD
LI
eG
eF
eE.6
eE
e10
15 15
15
30
RTU-1 (ON THE
ROOF)
RTU-2 (ON THE
ROOF)
DD
LI
15
110110
110 110
RA RA
FIRE ALARM
CONTROL PANEL
(EXISTING)
w w w . l i t t l e o n l i n e . c o m
This drawing and the design shown are the property
of Little Diversified Architectural Consulting. The
reproduction, copying or other use of this drawing
without their written consent is prohibited and any
infringement will be subject to legal action.
Little 2017c
PROJECT MANAGER
DESIGN TEAM
PRINCIPAL IN CHARGE
PROJECT TEAM
REVISIONS
PROJECT NAME
SHEET TITLE
PROJECT NO.
SHEET NUMBER
ISSUE FOR
ISSUE DATE
B
1 2 3 4 5 6 7
A
C
D
E
F
410 Blackwell Street, Suite 10
Durham, NC 27701
T: 919.474.2500
10/6/2017 4:23:54 PM C:\Users\brenden.elliott\Documents\513.7505.00_CU_WrestlingExpansion_E-16_brenden.elliott.rvt513.7505.00
10/6/17
FA1.1.1
FIRE ALARM PLAN -
CONVOCATION AREA C
Campbell Convocation
Center Wrestling
Department Renovation
and Expansion
BID/PERMIT SET
Rob Klinedinst
Katie Buckman
LITTLE
X KEY NOTES
KEY PLAN
GENERAL SHEET NOTES
RATED WALL LEGEND
ADDITION
EXISTING BUILDING
ELEC. 1017
3/16" = 1'-0"FA1.1.1
1
CONVOCATION AREA C - FIRE ALARM
PLAN
1/8" = 1'-0"FA1.1.1
2 CONVOCATION ELECTRICAL ROOM 1017 - FIRE ALARM PLAN
NO. REASON DATE
CORPORATE LICENSE #F-0467