APPROVED FM PLAN APPROVALApplication for Plan Review�Q�C�.
Application # f� - 5 ` t (4 �39
Date Received: `� I� Received By: l l ; 1.,� 's
Name of Project:
Physical Address of Project:
Plans Submitted By:
Campbell University, Student Union
PO Box 97
Buies Creek NC 27506
Project Phone: ( )- _ 919.890.4151
Contact Person/Address: Don Eason
Contact Email: deason@campbell.edu
Contact Phone: ( )_ _ 919.890.4151
Contractor's Name/Info:
Contractor's Phone: ( )-
• Plans that are submitted will be reviewed as quickly as possible with an average time of review
between 7-10 working days.
• Status checks may be conducted on plan reviews by visiting the website
http://hteweb.harnett.org/Click2GovBP/Index.isp or by calling the Harnett County Central Permitting
Office (910-893-7525, Option #2), or the Harnett County Fire Marshal's Office (910-893-7580).
• Approved plans must be picked up from ft Central Permitting Office and all fees paid before any
required inspections can be conducted.
ILI
riarneft
�000-�'o Ck"�'�Kh
.-flan Review, Inspection, and Permit Fees
Application Number
1750042439
$200.00
❑
Explosive Material (90 Days)
$100.00
❑
Explosive Materials (72 Hours)
$100.00
❑
Fireworks Public Display
$50.00
E
Final Inspection
$35.00 + $2.00 per device
❑
Fire Alarm Testing
$35.00 +$2.00 per nozzle
❑
Fixed Fire Suppression
$75.00
❑
Insecticide Fog/Fumigation
$100.00
❑
Pipe Test/UST/AGST
$50.00
❑
Plans up to 5000 sq ft
$100.00
❑
Plans 5001 sq ft to 10,000 sq ft
$150.00
❑
Plans 10,001 sq ft to 25,000 sq ft
$250.00
E
Plans 25,001 sq ft and over
$35.00 + 2.00 per head
❑
Sprinkler Certification Test
$50.00
❑
Standpipe Testing
$50.00
❑
Special Assembly
(ie. amusement buildings, carnivals, fairs)
$75.00 ❑
$100.00 ❑
Tents/Canopies/Air Supported Structure
Tank Installation (charge for each tank)
Tank Removal (charge for each tank)
Total Devices/Heads
Total Cost
$ 50.00
S -
S -
S -
$ 250.00
S -
.J
$ 300.00
Code Enforcement Official Rodney Daniels 12/12/2017
Harnett
COUNTY
�� Departrrvwt—A— 0 WWWAwneft,org
��:Apcn� -,&A
Fire Marshal Division
December 12, 2017
Don Eason
Re: Campbell University Student Union
Mr. Eason,
Thank you for submitting plans for the Student Union. The plans have been
carefully reviewed by a qualified code enforcement official to examine for full
compliance with the North Carolina Fire Prevention Code and all other fire
protection regulatory documents. There are some items that were found during
the plan review process that need to be addressed before a final inspection of
the new facility can be given. These items are outlined and described below.
® 105.7.1 Automatic fire -extinguishing systems.
o A construction permit is required for the fire sprinkler system
installation before any such work commences. Submit complete
construction documents that include the hydraulic calculations
for the system. The system shall also be designed consistent
with the architectural design documents and specifications.
Construction documents shall include detail as described in
NFPA 13 standard for automatic sprinkler system installation.
Contractor must obtain construction permit for the fire sprinkler
system before commencement of any work.
105.7.5 Fire alarm construction permits.
o A construction permit is required for the fire alarm installation.
Submit complete shop drawings consistent with the architectural
design documents and specifications. Shop drawings shall
include detail as described in Section 907.1.2 of the NC State
Fire Code. Contractor must obtain the construction permit for
the fire alarm system before commencement of any work.
® 105.7.6 Fire pump and related equipment.
o A construction permit is required for the installation of or
modification to fire pumps and related fuel tanks, jockey pumps,
controllers and generators. Submit complete construction
Harneft
COUNTY t
WWWAwnett.0%
documents consistent with the architectural design,
specifications and NFPA 20 standard. Contractor must obtain
the construction permit for the fire pump and related equipment
before commencement of any work.
® 505.1 Physical Address
o The physical address of the building shall be posted in a
conspicuous place so that it can be seen on approach from the
road, access road, and/or parking lot.
o The numbers used to make up the physical address shall be at
least 5 inches in height.
506.1 Knox Box
o A Knox Box secure key box shall be installed on the new
building that houses all keys to all the doors within the building
in which the fire department would need access to in the event
of an emergency. httl)s://www,knoxbox.com/commercial-knox-
boxes
o The box shall be mounted 48 — 60 inches in height. Coordinate
exact location with the Fire Marshal's Office staff.
507.3 Fire Flow (NFF)
o Provide a fire flow analysis for the building(s) and determined by
an approved method. NC Fire Code Appendix B is acceptable
method.
o Private fire service water mains shall be installed according to
NFPA 24. All fire protection water mains shall be inspected by a
fire official before covering. A contractor's underground flush
and test certificate is required at time of fire official inspection.
509.1 Control room identification.
o All rooms containing controls for air conditioning equipment,
sprinkler risers and valves, or other fire detection, suppression,
or control elements shall by physically identified in terms of use
(i.e., FACP Room, Electrical Room, Riser Room)
604.1.1 Stationary generators.
o Stationary generators and standby power generators required
by the fire code shall be listed in accordance with UL 2200.
Provide construction documents, specifications and details for
the complete installation. A construction permit is required for
the installation of a flammable/combustible liquids tank.
o The generator shall be fully tested for acceptance in accordance
with NFPA 110 and 111.
Harneft
COUNTY
901.2.1 State of Compliance.
o Before requesting final approval of the installation, where
required by the fire code official, the installing contactor shall
furnish a written statement to the fire code official that the
subject fire protection system has been installed in accordance
with the manufacture's specifications and the appropriate
installation standard. Any deviations from the design standards
shall be noted and copies of the approvals for such deviations
shall be attached to the written statement.
® 906.1 Fire Extinguishers
o Fire extinguishers shall be placed in approved locations as
drawn by the code enforcement official on the approved plans.
o The fire extinguishers provided shall have a minimum rating of
2A 10B:C and shall not be installed higher than 5 feet above the
finished floor.
o Fire extinguishers shall be serviced and tagged on a yearly
basis by an authorized company.
o A Class K fire extinguisher is required in the kitchen within 30ft.
of the cooking equipment.
o Provide fire extinguishers in all special -hazard areas, including
but not limited to laboratories, computer rooms and generator
rooms.
0 907.4.1 Duct Smoke detectors.
o Smoke detectors installed in ducts shall be listed for the air
velocity, temperature and humidity present in the duct. Duct
smoke detectors shall be connected to the building's fire alarm
control unit when a fire alarm system is required by Section
907.2. Activation of a duct smoke detector shall initiate a visible
and audible supervisory signal at a constantly attended location
and shall perform the intended fire safety function in accordance
with this code and the International Mechanical Code. Duct
smoke detectors shall not be used as a substitute for required
open area detection.
0 907.17 Acceptance tests.
o A complete acceptance test is required to be witnessed by a
representative from the fire marshal's office in conjunction with
the installing contractor for each of the following. Notify the fire
marshal's office in advance to schedule a test. (910) 893-0743.
Harneft
COUNTYc
® Visual Inspection of Underground Line (with proper
restraints)
® Hydrostatic Test and Flush of Underground Line
® Above Ceiling Inspection of ALL pipe and fittings
® Hydrostatic Test of ALL piping
® Pump Certification Test
® Flow Test of sprinkler/standpipe system
® Standpipe Certification
® 100 % test of Fire Alarm System
® Fire and Smoke Damper Testing
® Acceptance Test of Kitchen Ansul Fire Suppression
System.
® Emergency generator(s)
® 907.18 Record of completion.
o A record of completion in accordance with NFPA 72 verifying
that the system has been installed in accordance with the
approved plans and specifications shall be provided.
Notes:
913.3 Temperature of pump room.
o Suitable means shall be provided for maintaining the
temperature of the fire pump room above 40 degrees F.
o Indicate on construction documents for the fire pump installation
permit application.
1004.3 Posting of occupant load.
o Before final occupancy of all assembly spaces within the school
an occupant load posting is required to be displayed in a
prominent location for rooms >50 occupants.
Discrepancies were noted between exit sign placement and egress routes
on LSP in multi-purpose room (185) and dining room (231).
Please distribute these comments to any necessary and applicable persons
involved in the design and construction of the building and systems specified
within this letter. If you have specific questions or concerns we can be contacted
at (910) 893-0743.
Thank you again for submitting plans for the Student Union. Please review the
plans and adhere to any notes and alterations that were made in addition to the
Harnett
COUNTY t
original drawings. These remarks are for the plans that were submitted and its
original intent. These remarks do not apply if the original intent changes or what
was submitted on the above date changes. If you have any questions, please do
not hesitate to call this office.
Please schedule all fire inspections through the Fire Marshal's Office (910)
893-0743
Again, thank you and we look forward to working with you during the construction
period!
Sincerely,
Rodney D niels
Chief Deputy Fire Marshal