CO INSPECTION PREPARED 11/28/17, 14 :06:21 INSPECTION TICKET
Hafnett County PAGE 17
INSPECTOR: IVR DATE 11/29/17
ADDRESS . : 90 REEDY LN SUBDIV:
CONTRACTOR : NORMANS HEATING & COOLING PHONE : (252) 799-8228
OWNER . . : BELTON JAMES H & BETTY PHONE :
PARCEL . . : 09-9558- - -0019- -01-
APPL NUMBER: 17-50042808 CP STANDALONE TRADE - RESIDENTIAL
DIRECTIONS : T/S: 11/27/2017 08:41 AM LLUCAS ----
90 REEDY LANE - SANFORD
27 WEST - TURN RIGHT ONTO BARBECUE
CHURCH RD - TURN LEFT ONTO OLIVIA RD -
TURN LEFT ONTO MURCHISON RD-TURN RIGHT
ONTO REEDY LN
STRUCTURE: 000 000 HVAC CHO OUT - HT PUMP & DUCTWORK
FLOOD ZONE ' FLOOD ZONE X
PROPOSED USE - MECH/ELEC WATER SUPPLY
• UNKNOWN
PERMIT: CPMR 00 CP MECHANICAL RESIDENTIAL
REQUESTED INSP DESCRIPTION
TYP/SQ COMPLETED RESULT RESULTS/COMMENTS
R131 01 11/2 T // ONE TRADE FINAL TIME: 17:00 VRU #: 003058641
/pry/ T/S: 11/28/2017 09:37 AM LLUCAS
COMMENTS AND NOTES
cot
L PER M-r I Jon 5 oo LJ) g � Teat Date:2017-11-27
Duct Leakage
Test Report
Client Tester
Building Description James Belton Company Norman's Heating And Cooling L.
Building Address 90 Reedy Lane
Address 1135 Bdtllemine Drive
Sanford,NC 27332 Fuquay-varina,NC 27526
Contact Ronald E Norman Technician Ronald E.Nonan
Phone 9184104866 Phone (919)-410-1866
Test Type Total Duct Leakage Gauge SIN 300348
Test Equipment Retroteo DU200 Fan S/N 1LFT001341
Building and Duct Details
Conditioned Floor Area 925.0 sq ft
Air Handler Flow 787 CFM
Percentage of Duct Leakage to Outdoors 0%(estimated)
Supply Return
Average Duct Operating Pressure 0.0 Pa 0.0 Pa
Leakage Split 50% 60%
Leakage Penalty 0% 0%
Leakage Data
Baseline Pressure
Depressurization
Duct Test Pressure -25.0 Pa
Duct Leakage 1 CFM
Leakage Area 0.2 sq In
Leakage constant, C 0.14
Leakage Exponent 0.60(assumed)
Leakage Results
Total Duct Leakage 1 CFM at 26 Pa
Duct Leakage as%of Air Handler Flow 0.1%
Duct Leakage to Outdoors (estimated) 0 CFM at 26 Pa
Leakage/Conditioned Floor Area 0.001 CFM/sq ft at 26 Pa
0.1 CFM/100 sq ft at 26 Pa
1 CFM/1,000 sq ft at 26 Pa
Cost of Duct Leakage
HVAC System Efficiency Loss 0.0%
Annual Cooling Loss $0
Annual Heating Loss $0