Loading...
FIRE MARSHAL PLAN REVIEW ESHarnett �� COUNTY k1I�'� r.w..r>•.....oy..0.w,. walsarewtteri Plan Review, Inspection, and Permit Fees Application Number 17-so042674 $200.00 ❑ Explosive Material (90 Days) $ - $100.00 ❑ Explosive Materials (72 Hours) $ - $300.00 ❑ Fireworks Public Display $ $50.00 ❑ Final Inspection $ so.00 $35.00 +52.00 per device ❑ Fire Alarm Testing $ - $35.00 +$2.00 per nozzle ❑ Fixed Fire Suppression $ - $75.00 ❑ Insecticide Fog/Fumigation $ - $100.00 ❑ Pipe Test/UST/AGST $ - $50.00 ❑ Plans up to 5000 sq ft $ - $100.00 U Plans 5001 sq ft to 10,000 sq ft $ 100.00 $150.00 ❑ Plans 10,001 sq ft to 25,000 sq ft $ - $250.00 ❑ Plans 25,001 sq ft and over $ - $35.00 +2.00 per head ❑ Sprinkler Certification Test $ - $50.00 ❑ Standpipe Testing $ - $50.00 ❑ Special Assembly (le.amusement buildings,carnivals,fairs) $ - $75.00 Tents/Canopies/Air Supported Structure $ - $100.00 Tank Installation (charge for each tank) $ - $100.00 ❑ Tank Removal (charge for each tank) $ - Total Devices/Heads $ - Total Cost S 150.00 Code Enforcement Official Rodney Daniels 12/19/2017 toHarnett COUNTY * A �► t�oa.,ms.,,o.o.rnw.,r Ininthenettarg �FM� Fire Marshal Division December 19, 2017 Construction Systems, Inc. 6205 Raeford Road Fayetteville,NC 28304 RE: Gourd Springs Baptist Church 4575 Ray Road Spring Lake, NC 28390 Application Number—17-50042674 Mrs. Harrelson, Thank you for submitting plans for the Church. The plans have been reviewed by a qualified code enforcement official for compliance with the North Carolina Fire Prevention code and all other fire protection regulations. The following are items that will need to be addressed before a final inspection of this project can be completed. The items are listed and described below. • 906.1 Fire Extinguishers o Fire extinguishers shall be placed in approved locations and may be field verified on final inspection. The fire extinguishers provided shall have a minimum rating of 2A 10 B: C. o Fire extinguisher shall be installed not to exceed 75' distance of travel. • 1006.1/1006.2 Emergency Illumination o The means of egress shall be illuminated including the exit discharge. o Emergency illumination is required to meet minimum foot candle illumination. • 1011 Exit Signs o Exit signs shall be installed at all required exits. Exit signs shall meet all provisions of chapter 10. • 506.1 Knox Box o Keys shall be provided for fire department access. The key(s) may be placed in the existing Knox box on the main building. flHarnett COUNYY * A— ^ t ergUnion Departnat inntharnet.erg • 1004.3 Posting of occupant load. o Every room or space that is an assembly occupancy shall have the occupant load of the room or space posted in a conspicuous place, near the main exit or exit access doorway from the room or space. Posted signs shall be of an approved legible permanent design and shall be maintained by the owner or authorized agent. • An occupant load certificate will be provided by the Fire Marshal's Office. • 605.3.1 Labeling. o Doors into electrical control panel rooms shall be marked with a plainly visible and legible sign stating ELECTRICAL ROOM or similar approved wording. The disconnecting means for each service, feeder or branch circuit originating on a switchboard or panelboard shall be legibly and durably marked to indicate its purpose unless such purpose is clearly evident. Doors into electrical control panel rooms shall be marked with a plainly visible and legible sign stating ELECTRICAL ROOM or similar approved wording. The disconnecting means for each service, feeder or branch circuit originating on a switchboard or panelboard shall be legibly and durably marked to indicate its purpose unless such purpose is clearly evident. • 509.1 Control room identification. o All rooms containing controls for air conditioning equipment, sprinkler risers and valves, or other fire detection, suppression, or control elements shall by physically identified in terms of use (i.e., FACP Room, Electrical Room, Riser Room) • 907.4.1 Duct Smoke detectors. o Smoke detectors installed in ducts shall be listed for the air velocity, temperature and humidity present in the duct. Duct smoke detectors shall be connected to the building's fire alarm. • 105.7.5 Fire alarm construction permits. o A construction permit is required for the fire alarm installation. Submit complete shop drawings consistent with the architectural design documents and specifications. Shop drawings shall include detail as described in Section 907.1.2 of the NC State Fire Code. Contractor must obtain the construction permit for the fire alarm system before commencement of any work. • Notes Harnett C% COUNTY �►. e.,.�.�r s...«on.,e.,,,r A (FM o Please contact the Fire marshal's office to schedule fire final inspection when work is complete, 910-893-0743 Please review the plans and adhere to any notes and alterations that were made in addition to the original designed plans. These remarks are for the plans that were submitted and its original intent. If you have any questions please do not hesitate to contact me. We look forward to working with you during the construction period. Sincerely, Rodney Chief Deputy Fire Marshal