FM REVIEW Harnett
ARN�COUNTY EMERGENCY SERVICES
Fire Marshal Division R D FOR CODE COMPLL4NCE
P.O.Box 370 •
Llllington,NC 27546
910-893-7580 A�. .APPAISM.
CO* ef''LIA` rFFICER A E
Application for Plan Review
Application p t 11 - 5004a-1 ILO
Date Received: I I S I tri Received B _
Name of Project: Harnett County School
Physical Address of Project: 2495 Ray Rd.
Spring Lake NC 28390
Plans Submitted By: Harnett County School
Project Phone: 910 893 4808
Contact Person/Address: Rodney Gregory
1500 South Main St.
Contact Phone: (910 )-985 1003 ( )
Contractor's Name/Info: Harnett County School
Contractors Phone, (910 9851003
• mass that are submitted will be reviewed as quickly as possible with an
average time of review between 7.10 working days.
• Status checks may he conducted on plan reviews by visiting the website
yftu://hteweb.hamett.oru/Click2GovBP/fndes.isg or by calling the Harnett
County Central Permitting Office(910.893.4759),or the Harnett County
Fire Marshal's Office(910-893-7580).
• Approved plans must be picked up from the Central Permitting Office and
all fees paid before any required inspections can be conducted.
ir' -, Harnett
' "IrTh COUNTY A I ■■■��• t...ea.,Same e....a enc
COo:, ft Ni.'F. set—A—
��. �
rrsLv^MFN
Plan Review, Inspection, and Permit Fees
Application Number 1750042716
$200.00 ❑ Explosive Material (90 Days) S -
$100.00 ❑ Explosive Materials (72 Hours) $ -
$100.00 ❑ Fireworks Public Display S .
$50.00 O Final Inspection $ 50.00
$35.00 +$2.00 per device ❑ Fire Alarm Testing S -
$35.00 +$2.00 per nozzle El Fixed Fire Suppression S
$75.00 ❑ Insecticide Fog/Fumigation S -
$100.00 ❑ Pipe Test/UST/AGST S -
$50.00 O Plans up to 5000 sq ft S 50.00
$100.00 ❑ Plans 5001 sq ft to 10,000 sq ft $ -
$150.00 ❑ Plans 10,001 sq ft to 25,000 sq ft $ -
$250.00 ❑ Plans 25,001 sq ft and over $ -
$35.00 +2.00 per head ❑ Sprinkler Certification Test $
$50.00 ❑ Standpipe Testing $ -
$50.00 ❑ Special Assembly
(Ie.amusement buildings,carnivals,fain) $ -
$75.00 Tents/Canopies/Air Supported Structure
S
$100.00 ❑ Tank Installation (charge for each tank)
S -
$100.00 ❑ Tank Removal (charge for each tank) $ -
Total Devices/Heads $
Total Cost $ 100.00
Code Enforcement Official Rodney Daniels 11/15/2017
Harnett
( cOUNTr ^1
%OVA .A9t•.NA (r NI
r•�wryl�wma.r�a•nt
r. watmn.a.sy
Fire Marshal Division
November 15, 2017
Rodney Gregory
1500 South Main Street
Lillington,NC 27546
Re: Harnett County Schools Huts
(Overhills)
Application Numbers- 17-50042716
Mr. Gregory,
Thank you for submitting the plans for the Harnett County School mobile classrooms.
The plans have been carefully reviewed by a qualified code enforcement official to
examine for full compliance with the North Carolina Fire Prevention Code and all other
fire protection regulatory documents. There we some items that were found during the
plan review process that need to be addressed before a final inspection of the new facility
can be given. These items are outlined and described below.
• 1003.2.11 Means of egress illumination.
o The means of egress, including the exit discharge, shall be illuminated at
all times the building space served by the means of egress is occupied
o The portion of the exterior exit discharge immediately adjacent to exit
discharge doorways in buildings required to have two or more exits.
• 906.1 Fire Extinguishers
o Fire extinguishers shall be located as not to exceed 75' of travel distance
to an extinguisher.
o The fire extinguishers provided shall have a minimum rating of 2A10:BC
and shall not be installed higher than 5 feet above the finished floor.
• 404.2 Fire Safety and Evacuation Plans
I.Hamett
courtrr
110e—A—
A ..
„a . `yev.ine �40Ir'1 •monogamy inns C.,..b.n.
o An approved fire safety and evacuation plan shall be prepared, posted and
maintained for Group E occupancies.
• Fire Department Access
o The fire department access shall extend to within 150 feet of all portions
of the facility.
o The fire department access road shall be of an unobstructed width of not
less than 20 feet and shall have an unobstructed vertical clearance of not
less the 13 feet 6 inches.
• Notes
o Please schedule all fire inspections with the Fire Marshal's Office.
o 910-893-0743
Thank you again for submitting the plans for the mobile classrooms. Please review the
plans and adhere to any notes and alterations that were made in addition to the original
drawings. These remarks are for the plans that were submitted and its original intent.
These remarks do not apply if the original intent changes or what was submitted on the
above date changes. If you have any questions, please do not hesitate to call this office
Again, thank you and we look forward to working with you during the construction
period!
Sincerely, c---_
�
>d odney D gels
Chief Deputy Fire Marshal
i