'flan Review, Inspection, and Permit Fees
Application Number
1750042737
$200.00
❑
Explosive Material (90 Days)
$ -
$100.00
❑
Explosive Materials (72 Hours)
$ -
$100.00
❑
Fireworks Public Display
$ -
$50.00
❑
Final Inspection
$ -
$35.00 + $2.00 per device
❑
Fire Alarm Testing
$ -
$35.00 + $2.00 per nozzle
❑
Fixed Fire Suppression
$ -
$75.00
❑
Insecticide Fog/Fumigation
$ -
$100.00
❑
Pipe Test/UST/AGST
$ -
$50.00
❑
Plans up to 5000 sq ft
$ -
$100.00
❑
Plans 5001 sq ft to 10,000 sq ft
$ -
$150.00
❑
Plans 10,001 sq ft to 25,000 sq ft
$ -
$250.00
❑
Plans 25,001 sq ft and over
$ -
$35.00 + 2.00 per head
2
Sprinkler Certification Test
$ 35.00
$50.00
❑
Standpipe Testing
$ -
$50.00
❑
Special Assembly
(ie. amusement buildings, carnivals, fairs)
$ -
$75.00
El
Tents/Canopies/Air Supported Structure
$ -
$100.00
Tank Installation (charge for each tank)
$ -
$100.00
❑
Tank Removal (charge for each tank)
$ -
41 Total Devices/Heads
$ 82.00
Total Cost
$ 117.00
Code Enforcement Official
Rodney Daniels
11/16/2017
riarneft
COUNTY
Fire Marshal Division
November 16, 2017
Kevin Wilder
Carolina Fire Protection, Inc.
4055 Hodges Chapel Road
Dunn, NC 28334
Re: Harnett County Admin Building
420 McKinney Parkway
Lillington, NC 27546
Application Number 17-50042737 (Sprinkler Plan Review)
Mr. Wilder,
Thank you for submitting the plans for the sprinkler up fit. The plans have been carefully
reviewed by a qualified code enforcement official to examine for compliance with the
North Carolina Fire Prevention Code and all other fire protection regulatory documents.
There are some items that were found during the plan review process that need to be
addressed before a final inspection of the new facility can be given. These items are
outlined and described below.
901.2.1 State of Compliance.
o Before requesting final approval of the installation, where required by the
fire code official, the installing contactor shall furnish a written statement
to the fire code official that the subject fire protection system has been
installed in accordance with the manufacture's specifications and the
appropriate installation standard. Any deviations from the design
standards shall be noted and copies of the approvals for such deviations
shall be attached to the written statement.
o All work shall be performed in accordance with NFPA 13 and the
NCSFC.
901.5 Installation acceptance testing.
o All piping and attached appurtenances subjected to system working
pressure shall be hydrostatically tested at 200 psi or 50 psi in excess of the
system working pressure, whichever is greater, and shall maintain that
pressure without loss for 2 hours. This test is required to be witnessed by a
representative from the Harnett County Fire Marshal's Office.
Harneft
COUNTY
o A contractor's material and test certificate shall be furnished by the
trained representative of ; Carolina Fire Protection before final
approval.
® Notes
o Layout sheet indicates SR heads. The hydraulic design information
sheet indicates QR heads. Approval .is for the QR-F1FR heads
indicated on the hydraulic design sheet.
o A sprinkler system construction permit is required.
o Please schedule all inspections through the Fire Marshal's Office.
0 910-893-0743
Thank you again for submitting the plans for the sprinkler up ht. Please review the plans
and adhere to any notes and alterations that were made in addition to the original
drawings. These remarks are for the plans that were submitted and its original intent.
These remarks do not apply if the original intent changes or what was submitted on the
above date changes. If you have any questions, please do not hesitate to call this office.