Loading...
FM PLAN REVIEW • ` , Harnett �..,-. -- w illt - -� , %COUNTY A .1::-. NI) ...a. c ��:nca tP.n Plan Review, Inspection, and Permit Fees Application Number : 17-50042681 $200.00 ❑ Explosive Material (90 Days) 5 - $100.00 ❑ Explosive Materials (72 Hours) $ - $100.00 ❑ Fireworks Public Display 5 - $50.00 O Final Inspection 5 50.00 5 _ $35.00 +$2.00 per device El Fire Alarm Testing 5 $35.00 +$2.00 per nozzle ❑ Fixed Fire Suppression $75.00 ❑ Insecticide Fog/Fumigation 5 - $100.00 ❑ Pipe Test/UST/AGST $ - $50.00 ❑ Plans up to 5000 sq ft $ - $100.00 ❑ Plans 5001 sq ft to 10,000 sq ft 5 - S150.00 ❑ Plans 10,001 sq ft to 25,000 sq ft 5 - $250.00 O Plans 25,001 sq ft and over 5 250.00 - $35.00 +2.00 per head El Sprinkler Certification Test $ $50.00 ❑ Standpipe Testing ❑ Special Assembly $50.00 (le.amusement buildings,carnivals,fairs) $ - II$75.00 Tents/Canopies/AirSupported Structure 5 _ $100.00 Tank Installation (charge for each tank) 5 $100.00 ❑ Tank Removal (charge for each tank) 5 - Total Devices/Heads 5 - Total Cost $ 300.00 Code Enforcement Official Rodney Daniels 11/13/2017 HarnettCOUNTY m) .., CUYT• :NRD.:UA * A `r wwwJWMt.ry November 13, 2017 RE: Harnett County Administrative Building 200 Alexander Drive Ullington, NC 27546 Re:Application Number—17-50042681 Mr.Johnson, Thank you for submitting plans for the up fit. The plans have been reviewed by a qualified code enforcement official for compliance with the North Carolina Fire Prevention code and all other fire protection regulations. The following are items that will need to be addressed before a final inspection of this project can be completed.The items are listed and described below. • 505.1 Physical Address o The physical address of the building shall be posted in a conspicuous place so that it can be seen on approach from the road, access road, and/or parking lot. o The numbers used to make up the physical address shall be at least 5 inches in height. • 906.1 Fire Extinguishers o Fire extinguishers shall be placed in approved locations and may be field verified on final inspection. The fire extinguishers provided shall have a minimum rating of 2A 10 B: C. o Fire extinguisher shall be installed not to exceed 75' distance of travel. • 1006.1/1006.2 Emergency Illumination o Emergency illumination is required to meet minimum foot candle illumination for all portions of the means of egress, including the exit discharge. • 1011 Exit Signs o Exit signs shall be installed at all required exits. Exit signs shall meet all provisions of chapter 10. Harnett •�-. �•.,,�,Sams�..�.., -4)r- COUNTY `�My • 506.1 Knox Box o A Knox box is required to be installed on the building. o An application/order form has been attached to the review comments. o https://www.knoxbox.com/commercial-knox-boxes/ • 1004.3 Posting of occupant load. o Every room or space that is an assembly occupancy shall have the occupant load of the room or space posted in a conspicuous place, near the main exit or exit access doorway from the room or space. Posted signs shall be of an approved legible permanent design and shall be maintained by the owner or authorized agent. • An occupant load certificate will be provided by the Fire Marshal's Office. • 1008.1.10 Panic and fire exit hardware. o Doors serving a Group H occupancy and doors serving rooms or spaces with an occupant load of 50 or more in a Group A or E occupancy shall not be provided with a latch or lock unless it is panic hardware or fire exit hardware. • 907.4.1 Duct Smoke detectors. o Smoke detectors installed in ducts shall be listed for the air velocity, temperature and humidity present in the duct. Duct smoke detectors shall be connected to the building's fire alarm control unit when a fire alarm system is required by Section 907.2. Activation of a duct smoke detector shall initiate a visible and audible supervisory signal at a constantly attended location and shall perform the intended fire safety function in accordance with this code and the International Mechanical Code. Duct smoke detectors shall not be used as a substitute for required open area detection. • 907.1.2 Fire Alarm System Shop Drawings o Shop drawings from the licensed installing contractor shall be submitted prior to work beginning. o A rough in inspection is required. o A final acceptance test is required. (100%) • 901.6.1 Sprinkler System Shop Drawings o Sprinkler system shop drawings shall be submitted by the installing contractor prior to work beginning. o A rough in inspection is required. l( ~ Ho u Mete I En...•cy Sammons D.»,•..rt lialtitirMittOrf o A final acceptance test is required. • • Notes o Secondary exit in meeting room shall be remotely located. See NCFPC 1015.2.1 o Please contact the Fire marshal's office to schedule fire final inspection when work is complete, 910-893-0743 Please review the plans and adhere to any notes and alterations that were made in addition to the original designed plans. These remarks are for the plans that were submitted and its original intent. If you have any questions please do not hesitate to contact me. We look forward to working with you during the construction period. Si erel , Rodney Daniels Chief Deputy Fire Marshal