Plan Review NotesHarnett
COUNTY
�OPT- "S�,KA WWWAwneworg
Fire Marshal Division
October 24, 2017
Randall A. Johnson
Campbell University
PO Box 535
Buies Creek, NC 27506
Re: Campbell University Tents - lea 20x60, lea 40x40 and lea 40x120
(Homecoming 2017, 10-26-17 thru 10-28-17)
Barker Lane Stadium (180 Wade Stewart Circle)
Lillington, NC 27546
Application Number 17-50042580
Mr. Johnson,
Thank you for submitting the plans for the tents. The plans have been carefully
reviewed by a qualified code enforcement official to examine for compliance with the
North Carolina Fire Prevention Code and all other fire protection regulatory documents.
There are some items that were found during the plan review process that need to be
addressed before a final inspection of the new facility can be given. These items are
outlined and described below.
i 2404.12 Fire Extinguishers.
o 2A -10B: C fire extinguisher shall be placed at tents/canopies with a travel
distance not to exceed 100' from any fire extinguisher.
i 2403.12.5.1 Arrangement of aisles.
o The arrangement of aisles shall be subject to the approval of the fire code
official and shall be maintained clear at all times during occupancy.
0 2403.12.6 Exit Signs
o Exits shall be clearly marked. Exit signs shall be installed at required exit
doorways and where otherwise necessary to indicate clearly the direction
of egress when the exit serves an occupant load of 50 or more.
0 2404.4 Certification
o Provide a flame propagation certificate from the tent owner/company.
0 2404.6 Smoking
o Smoking shall not be allowed under tents/canopies. "NO SMOKING "signs
shall be conspicuously posted under the tent.
0 2404.19 Generators
o Generators and other internal combustion power sources shall be
separated from tents and canopies by a minimum of 20 feet and shall be
isolated from contact with the public by approved means.
0 2404.16.2.1 LP Gas Containers
o Portable LP gas containers that are less than 500 gallons shall have
minimum separation of 10 feet between the container and the
tent/canopy.
Thank you again for submitting the plans for the tents. Please review the plans and
adhere to any notes and alterations that were made in addition to the original drawings.
These remarks are for the plans that were submitted and its original intent. These
remarks do not apply if the original intent changes or what was submitted on the above
date changes. If you have any questions, please do not hesitate to call this office.
Sincerely,
t �;�
Bili Lamm
Fire Marshal