Plan Review, Inspection, and Permit Fees
Application Number 1750042621
$200.00 ❑ Explosive Material (90 Days) $ -
$100.00 ❑ Explosive Materials (72 Hours) $ -
$100.00 ❑ Fireworks Public Display $ -
$50.00 El Final Inspection $ 50.00
$35.00 +$2.00 per device ❑ Fire Alarm Testing $ -
$35.00 +$2.00 per nozzle ❑ Fixed Fire Suppression $ -
$75.00 ❑ Insecticide Fog/Fumigation $ -
$100.00 ❑ Pipe Test/UST/AGST $ -
$50.00 ❑ Plans up to 5000 sq ft $ -
$100.00 0 Plans 5001 sq ft to 10,000 sq ft $ 100.00
$150.00 ❑ Plans 10,001 sq ft to 25,000 sq ft $ -
$250.00 ❑ Plans 25,001 sq ft and over $ -
$35.00 +2.00 per head ❑ Sprinkler Certification Test $ -
$50.00 ❑ Standpipe Testing $ -
$50.00
❑ Special Assembly
(ie.amusement buildings,carnivals,fairs) $ -
O
$75.00 Tents/Canopies/Air Supported Structure $
$100.00 Tank Installation (charge for each tank) $
$100.00 ❑ Tank Removal (charge for each tank) $ -
Total Devices/Heads $ -
Total Cost S 1so.00
Code Enforcement Official Rodney Daniels 11/14/2017
r/- -N Harnett •-• E ,�rT,.nn.Oh,,nru,
Zr COUNTY * A (co n,
w•�Jwn�n.s
V
Fire Marshal Division
November 14, 201.7
Re: Campbell Convocation Center Wrestling Department Renovation&Expansion
56 Main Street
Rules Creek, NC 27506
Application Number 17-50042621
Mr. Eason,
Thank you for submitting the plans for the Convocation Center Wrestling Department
renovation & expansion. The plans have been carefully reviewed by a qualified code
enforcement official to examine for compliance with the North Carolina Fire Prevention
Code and all other fire protection regulatory documents. There are some items that
were found during the plan review process that need to be addressed before a final
inspection of the new facility can be given. These items are outlined and described
below.
• 906.1 Fire Extinguishers
o Minimum of(1) 2A10:BC fire extinguisher shall be installed not to exceed
75'distance of travel.
o All Fire extinguishers shall be properly mounted and tagged by a fire
extinguisher company.
• 1006.1 Means of Egress Illumination
o The means of egress, including the exit discharge, shall be illuminated at
all time the building space is served by the means of egress is occupied.
o Means of egress consist of three separate and distinct parts: the
exit access,the exit and the exit discharge.
o The means of egress illumination shall not be less than 1 foot-candle at
the walking surface.
• 105.7.1 Automatic fire-extinguishing systems.
o A construction permit is required for the fire sprinkler system installation
before any such work commences. Submit complete construction
documents that include the hydraulic calculations for the system. The
system shall also be designed consistent with the architectural design
� � COUNTY *A— 'N Harnett t,r„, ,.•y,,„•y.,
-� ( M�
documents and specifications. Construction documents shall include
detail as described in NEPA 13 standard for automatic sprinkler system
installation. Contractor must obtain construction permit for the fire
sprinkler system before commencement of any work.
• A rough in inspection is required.
• A final acceptance test is required.
• 105.7.5 Fire alarm construction permits.
o A construction permit is required for the fire alarm installation. Submit
complete shop drawings consistent with the architectural design
documents and specifications. Shop drawings shall include detail as
described in Section 907.1.2 of the NC State Fire Code. Contractor must
obtain the construction permit for the fire alarm system before
commencement of any work.
• A rough in inspection is required.
• A final acceptance test is required. (100%)
• 901.2.1 State of Compliance.
o Before requesting final approval of the installation, where required by
the fire code official, the installing contactor shall furnish a written
statement to the fire code official that the subject fire protection system
has been installed in accordance with the manufacture's specifications
and the appropriate installation standard. Any deviations from the design
standards shall be noted and copies of the approvals for such deviations
shall be attached to the written statement.
• 907.4.1 Duct Smoke detectors.
o Smoke detectors installed in ducts shall be listed for the air velocity,
temperature and humidity present in the duct. Duct smoke detectors
shall be connected to the building's fire alarm control unit when a fire
alarm system is required by Section 907.2. Activation of a duct smoke
detector shall initiate a visible and audible supervisory signal at a
constantly attended location and shall perform the intended fire safety
function in accordance with this code and the International Mechanical
Code. Duct smoke detectors shall not be used as a substitute for required
open area detection.
• Duct smoke detectors are required in RTU 1 & 2.
• 703.5 Identification
o Walls and partitions required to have protected openings shall be
permanently identified with signs or stencils. (Example "2- hour Fire
= COUHarnett
NTY
CouNTr �. M) IMMO o.rnb•wt
Y
Barrier Protect All Openings")
• Notes
o A final fire inspection is required.
o Schedule all fire inspections through the Fire Marshal's Office.
(919)893-0743
Thank you again for submitting the plans for the expansion and renovations. Please
review the plans and adhere to any notes and alterations that were made in addition to
the original drawings. These remarks are for the plans that were submitted and its
original intent. These remarks do not apply if the original intent changes or what was
submitted on the above date changes. If you have any questions, please do not hesitate
to call this office.
Sincerely,
kr(9-.11- 0)/i
Rodney Daniels
Chief Deputy Fire Marshal