SKM_454e17102411350CHAPTER 15
SECTION 1501
GENERAL
1501.1 Scope. This chapter shall apply to locations or areas
where any of the following activities are conducted:
1. The application of flammable or combustible paint, var-
nish, lacquer, stain, fiberglass resins or other flammable
or combustible liquid applied by means of spray appara-
tus in continuous or intermittent processes.
2. Dip -tank operations in which articles or materials are
passed through contents of tanks, vats or containers of
flammable or combustible liquids, including coating,
finishing, treatment and similar processes.
3. The application of combustible powders when applied
by powder spray guns, electrostatic powder spray guns,
fluidized beds or electrostatic fluidized beds.
4. Floor surfacing or finishing operations in areas exceed-
ing 350 square feet (32.5 m2).
5. The application of dual -component coatings or Class I or
Il liquids when applied by brush or roller in quantities
exceeding 1 gallon (4 Q.
6. Spraying and dipping operations.
1501.2 Nonapplicability. This chapter shall not apply to spray
finishing utilizing flammable or combustible liquids which dtp
not sustain combustion, including:
1. Liquids that have no fire point when tested in accordance
with ASTM D 92.
2. Liquids with a flashpoint greater than 95°F (35°C) in a
water -miscible solution or dispersion with a water and
inert (noncombustible) solids content of more than 80
percent by weight.
1501.3 Permits. Permits shall be required as set forth in Sec-
tions 105.6 and 105.7.
105.G.4I - se(";fid- O;PP.,,} /
r+�+ trnela '1
SECTION 1502 Prom. -
DEFINITIONS
1502.1 Definitions. The following words and terms shall, for
the purposes of this chapter and as used elsewhere in this code,
have the meanings shown herein.
DETERRING. A process for rapidly removing excess wet
coating material from a dipped or coated object or material by
passing it through an electrostatic field.
DIP TANK. A tank, vat or container of flammable or combus-
tible liquid in which articles or materials are immersed for the
ourpose of coating, finishing, treating and similar processes.
ELECTROSTATIC FLUIDIZED BED. A container holding
powder coating material that is aerated from below so as to
form an air -supported expanded cloud of such material that is
electrically charged with a charge opposite to that of the object
to be coated. Such object is transported through the container
immediately above the charged and aerated materials in order
to be coated.
FLAMMABLE FINISHES. Material coatings in which the
material being applied is a flammable liquid, combustible liq-
uid, combustible powder or flammable or combustible gel
coating.
FLAMMABLE VAPOR AREA. An area in which the con-
centration of flammable constituents (vapor, gas, fume, mist or
dust) in air exceeds 25 percent of their lower flammable limit
(LFL) because of the flammable finish processes operation. It
shall include:
1. The interior of spray booths.
2. The interior of ducts exhausting from spraying pro-
cesses.
3. Any area in the direct path of spray or any area contain-
ing dangerous quantities of air -suspended powder, com-
bustible residue, dust, deposits, vapor or mists as a result
of spraying operations.
4. The area in the vicinity of dip tanks, drain boards or asso-
ciated drying, conveying or other equipment during
operation or shutdown periods.
The fire code official is authorized to determine the extent of
the flammable vapor area, taking into consideration the mate-
rial characteristics of the flammable materials, the degree of
sustained ventilation and the nature of the operations.
FLUIDIZED BED. A container holding powder coating
material that is aerated from below so as to form an air -sup-
ported expanded cloud of such material through which the pre-
heated object to be coated is immersed and transported.
LIMITED SPRAYING SPACE. An area in which operations
for touch-up or spot painting of a surface area of 9 square feet
(0.84 m2) or less are conducted.
RESIN APPLICATION AREA. An area where reinforced
plastics are used to manufacture products by hand lay-up or
spray -fabrication methods.
ROLL COATING. The process of coating, spreading and
impregnating fabrics, paper or other materials as they are
passed directly through a tank or trough containing flammable
or combustible liquids, or over the surface of a roller revolving
partially submerged in a flammable or combustible liquid.
SPRAY BOOTH. A mechanically ventilated appliance of
varying dimensions and construction provided to enclose or
accommodate a spraying operation and to confine and limit the
escape of spray vapor and residue and to exhaust it safely.
2012 NORTH CAROLINA FIRE CODE 173
FLAMMABLE FINISHES
SPRAY ROOM. A room designed to accommodate spraying
operations constructed in accordance with the International
Building Code and separated from the remainder of the build-
ing by a minimum 1 -hour fire barrier.
SPRAYING SPACE. An area in which dangerous quantities
of flammable vapors or combustible residues, dusts or deposits
are present due to the operation of spraying processes. The fire
code official is authorized to define the limits of the spraying
space in any specific case.
SECTION 1503
PROTECTION OF OPERATIONS
1503.1 General. Operations covered by this chapter shall be
protected as required by Sections 1503.2 through 1503.4.4.
1503.2 Sources of ignition. Protection against sources of igni-
tion shall be provided in accordance with Sections 1503.2.1
through 1503.2.8.
1503.2.1 Electrical wiring and equipment. Electrical wir-
ing and equipment shall comply with this chapter and NFPA
70.
1503.2.1.1 Flammable vapor areas. Electrical wiring
and equipment in flammable vapor areas shall be of an
explosionproof type approved for use in such hazardous
locations. Such areas shall be considered to be Class I,
Division 1 or Class II, Division 1 hazardous locations in
accordance with NFPA 70.
1503.2.1.2 Areas subject to deposits of residues. Elec-
trical equipment, flammable vapor areas or drying oper-
ations that are subject to splashing or dripping of liquids
shall be specifically approved for locations containing
deposits of readily ignitable residue and explosive
vapors.
Exceptions:
1. This provision shall not apply to wiring in rigid
conduit, threaded boxes or fittings not contain-
ing taps, splices or terminal connections.
2. This provision shall not apply to electrostatic
equipment allowed by Section 1507.
In resin application areas, electrical wiring and equip-
ment that is subject to deposits of combustible residues
shall be listed for such exposure and shall be installed as
required for hazardous (classified) locations. Electrical
wiring and equipment not subject to deposits of combus-
tible residues shall be installed as required for ordinary
hazard locations.
1503.2.1.3 Areas adjacent to spray booths. Electrical
wiring and equipment located outside of, but within 5
feet (1524 mm) horizontally and 3 feet (914 mm) verti-
cally of openings in a spray booth or a spray room, shall
be approved for Class I, Division 2 or Class II, Division 2
hazardous locations, whichever is applicable.
1503.2.1.4 Areas subject to overspray deposits. Elec-
trical equipment in flammable vapor areas located such
that deposits of combustible residues could readily accu-
mulate thereon shall be specifically approved for loca-
tions containing deposits of readily ignitable residue am
explosive vapors in accordance with NFPA 70.
Exceptions:
1. Wiring in rigid conduit.
2. Boxes or fittings not containing taps, splices or
terminal connections.
3. Equipment allowed by Sections 1504 and 1507
and Chapter 21.
1503.2.2 Open flames and sparks. Open flames and
spark -producing devices shall not be located in flammable
vapor areas and shall not be located within 20 feet (6096
mm) of such areas unless separated by a permanent parti-
tion.
Exception: Drying and baking apparatus complying
with Section 1504.6.1.2.
1503.2.3 Hot surfaces. Heated surfaces having a tempera-
ture sufficient to ignite vapors shall not be located in flam-
mable vapor areas. Space -heating appliances, steam pipes
or hot surfaces in a flammable vapor area shall be located
such that they are not subject to accumulation of deposits of
combustible residues.
Exception: Drying apparatus complying with Section
1504.6.1.2.
1503.2.4 Equipment enclosures. Equipment or apparatu,
that is capable of producing sparks or particles of hot meta.
that would fall into a flammable vapor area shall be totally
enclosed.
1503.2.5 Grounding. Metal parts of spray booths, exhaust
ducts and piping systems conveying Class I or II liquids
shall be electrically grounded in accordance with NFPA 70.
Metallic parts located in resin application areas, including
but not limited to exhaust ducts, ventilation fans, spray
application equipment, workpieces and piping, shall be
electrically grounded.
1503.2.6 Smoking prohibited. Smoking shall be prohib-
ited in flammable vapor areas and hazardous materials stor-
age rooms associated with flammable finish processes. "No
Smoking" signs complying with Section 310 shall be con-
spicuously posted in such areas.
1503.2.7 Welding warning signs. Welding, cutting and
similar spark -producing operations shall not be conducted
in or adjacent to flammable vapor areas or dipping or coat-
ing operations unless precautions have been taken to pro-
vide safety. Conspicuous signs with the following warning
shall be posted in the vicinity of flammable vapor areas, dip-
ping operations and paint storage rooms:
NO WELDING
THE USE OF WELDING OR CUTTING
EQUIPMENT IN OR NEAR THIS AREA
IS DANGEROUS BECAUSE OF FIRE
AND EXPLOSION HAZARDS. WELDING
AND CUTTING SHALL BE DONE ONLY
UNDER THE SUPERVISION OF THE
PERSON IN CHARGE.
174 2012 NORTH CAROLINA FIRE CODE
1503.2.8 Powered industrial trucks. Powered industrial
trucks used in electrically classified areas shall be listed for
such use.
1503.3 Storage, use and handling of flammable and com-
bustible liquids. The storage, use and handling of flammable
and combustible liquids shall be in accordance with this section
and Chapter 34.
1503.3.1 Use. Containers supplying spray nozzles shall be
of a closed type or provided with metal covers, which are
kept closed. Containers not resting on floors shall be on
noncombustible supports or suspended by wire cables. Con-
tainers supplying spray nozzles by gravity flow shall not
exceed 10 gallons (37.9 L) in capacity.
1503.3.2 Valves. Containers and piping to which a hose or
flexible connection is attached shall be provided with a shut-
off valve at the connection. Such valves shall be kept shut
when hoses are not in use.
1503.3.3 Pumped liquid supplies. Where flammable or
combustible liquids are supplied to spray nozzles by posi-
tive displacement pumps, pump discharge lines shall be pro-
vided with an approved relief valve discharging to pump
suction or a safe detached location.
1503.3.4 Liquid transfer. Where a flammable mixture is
transferred from one portable container to another, a bond
shall be provided between the two containers. At least one
container shall be grounded. Piping systems for Class I and
II liquids shall be permanently grounded.
1503.3.5 Class I liquids as solvents. Class I liquids used as
solvents shall be used in spray gun and equipment cleaning
machines that have been listed and approved for such pur-
pose or shall be used in spray booths or spray rooms in
accordance with Sections 1503.3.5.1 and 1503.3.5.2.
1503.3.5.1 Listed devices. Cleaning machines for spray
guns and equipment shall not be located in areas open to
the public and shall be separated from ignition sources in
accordance with their listings or by a distance of 3 feet
(914 mm), whichever is greater. The quantity of solvent
used in a machine shall not exceed the design capacity of
the machine.
1503.3.5.2 Within spray booths and spray rooms.
When solvents are used for cleaning spray nozzles and
auxiliary equipment within spray booths and spray
rooms, the ventilating equipment shall be operated dur-
ing cleaning.
1503.3.6 Class II and III liquids. Solvents used outside of
spray booths, spray rooms or listed and approved spray gun
and equipment cleaning machines shall be restricted to
Class II and III liquids.
1503.4 Operations and maintenance. Flammable vapor
areas, exhaust fan blades and exhaust ducts shall be kept free
from the accumulation of deposits of combustible residues.
Where excessive residue accumulates in such areas, spraying
,)perations shall be discontinued until conditions are corrected.
1503.4.1 Tools. Scrapers, spuds and other tools used for
cleaning purposes shall be constructed of nonsparking
materials.
FLAMMABLE FINISHES
1503.4.2 Residue. Residues removed during cleaning and
debris contaminated with residue shall be immediately
removed from the premises and properly disposed.
1503.4.3 Waste cans. Approved metal waste cans equipped
with self-closing lids shall be provided wherever rags or
waste are impregnated with finishing material. Such rags
and waste shall be deposited therein immediately after
being utilized. The contents of waste cans shall be properly
disposed of at least once daily and at the end of each shift.
1503.4.4 Solvent recycling. Solvent distillation equipment
used to recycle and clean dirty solvents shall comply with
Section 3405.4.
SECTION 1504
SPRAY FINISHING
1504.1 General. The application of flammable or combustible
liquids by means of spray apparatus in continuous or intermit-
tent processes shall be in accordance with the requirements of
Sections 1503 and 1504.
1504.2 Location of spray -finishing operations. Spray finish-
ing operations conducted in buildings used for Group A, E, I or
R occupancies shall be located in a spray room protected with
an approved automatic sprinkler system installed in accor-
dance with Section 903.3.1.1 and separated vertically and hori-
zontally from other areas in accordance with the International
Building Code. In other occupancies, spray -finishing opera-
tions shall be conducted in a spray room, spray booth or spray-
ing space approved for such use.
Exceptions:
1. Automobile undercoating spray operations and
spray -on automotive lining operations conducted in
areas with approved natural or mechanical ventilation
shall be exempt from the provisions of Section 1504
when approved and where utilizing Class IIIA or IIIB
combustible liquids.
2. In buildings other than Group A, E, I or R occupan-
cies, approved limited spraying space in accordance
with Section 1504.9.
3. Resin application areas used for manufacturing of
reinforced plastics complying with Section 1509 shall
not be required to be located in a spray room, spray
booth or spraying space.
1504.3 Design and construction. Design and construction of
spray rooms, spray booths and spray spaces shall be in accor-
dance with Sections 1504.3 through 1504.3.3.1.
1504.3.1 Spray rooms. Spray rooms shall be constructed
and designed in accordance with this section and the Inter-
national Building Code, and shall comply with Sections
1504.4 through 1504.8.
1504.3.1.1 Floor. Combustible floor construction in
spray rooms shall be covered by approved, noncombusti-
ble, nonsparking material, except where combustible
coverings, including but not limited to thin paper or plas-
tic and strippable coatings, are utilized over noncombus-
2012 NORTH CAROLINA FIRE CODE 175
FLAMMABLE FINISHES
tible materials to facilitate cleaning operations in spray
rooms.
1504.3.2 Spray booths. The design and construction of
spray booths shall be in accordance with Sections
1504.3.2.1 through 1504.3.2.6, Sections 1504.4 through
1504.8 and NFPA 33.
1504.3.2.1 Construction. Spray booths shall be con-
structed of approved noncombustible materials. Alumi-
num shall not be used. Where walls or ceiling assemblies
are constructed of sheet metal, single -skin assemblies
shall be no thinner than 0.0478 inch (18 gage) (1.2 mm)
and each sheet of double -skin assemblies shall be no
thinner than 0.0359 inch (20 gage) (0.9 mm). Structural
sections of spray booths are allowed to be sealed with
latex -based or similar caulks and sealants.
1504.3.2.2 Surfaces. The interior surfaces of spray
booths shall be smooth; shall be constructed so as to per-
mit the free passage of exhaust air from all parts of the
interior, and to facilitate washing and cleaning; and shall
be designed to confine residues within the booth. Alumi-
num shall not be used.
1504.3.2.3 Floor. Combustible floor construction in
spray booths shall be covered by approved, noncombus-
tible, nonsparking material, except where combustible
coverings, including but not limited to thin paper or plas-
tic and strippable coatings, are utilized over noncombus-
tible materials to facilitate cleaning operations in spray
booths.
1504.3.2.4 Means of egress. Means of egress shall be
provided in accordance with Chapter 10.
Exception: Means of egress doors from premanufac-
tured spray booths shall not be less than 30 inches
(762 mm) in width by 80 inches (2032 mm) in height.
1504.3.2.5 Clear space. Spray booths shall be installed
so that all parts of the booth are readily accessible for
cleaning. A clear space of not less than 3 feet (914 mm)
shall be maintained on all sides of the spray booth. This
clear space shall be kept free of any storage or combusti-
ble construction.
Exceptions:
This requirement shall not prohibit locating a
spray booth closer than 3 feet (914 mm) to or
directly against an interior partition, wall or
floor/ceiling assembly that has afire- resistance
rating of not less than 1 hour, provided the
spray booth can be adequately maintained and
cleaned.
2. This requirement shall not prohibit locating a
spray booth closer than 3 feet (914 mm) to an
exterior wall or a roof assembly, provided the
wall or roof is constructed of noncombustible
material and the spray booth can be adequately
maintained and cleaned.
1504.3.2.6 Size. The aggregate area of spray booths in a
building shall not exceed the lesser of 10 percent of the
area of any floor of a building or the basic area allowed
for a Group H-2 occupancy without area increases, as se'
forth in the International Building Code. The area of ai.
individual spray booth in a building shall not exceed the
lesser of the aggregate size limit or 1,500 square feet
(139 m2).
Exception: One individual booth not exceeding 500
square feet (46 mz).
1504.3.3 Spraying spaces. Spraying spaces shall be
designed and constructed in accordance with the Interna-
tional Building Code and Sections 1504.3.3.1 and 1504.4
through 1504.8 of this code.
1504.3.3.1 Floor. Combustible floor construction in
spraying spaces shall be covered by approved, noncom-
bustible, nonsparking material, except where combusti-
ble coverings, such as thin paper or plastic and strippable
coatings, are utilized over noncombustible materials to
facilitate cleaning operations in spraying spaces.
1504.4 Fire protection. Spray booths and spray rooms shall be
protected by an approved automatic fire -extinguishing system
complying with Chapter 9. Protection shall also extend to
exhaust plenums, exhaust ducts and both sides of dry filters
when such filters are used.
1504.4.1 Fire extinguishers. Portable fire extinguishers
complying with Section 906 shall be provided for spraying
areas in accordance with the requirements for an extra
(high) hazard occupancy.
1504.5 Housekeeping, maintenance and storage of hazard-
ous materials. Housekeeping, maintenance, storage and use of
hazardous materials shall be in accordance with Sections
1503.3, 1503.4, 1504.5.1 and 1504.5.2.
1504.5.1 Different coatings. Spray booths, spray rooms
and spraying spaces shall not be alternately utilized for dif-
ferent types of coating materials where the combination of
materials is conducive to spontaneous ignition, unless all
deposits of one material are removed from the booth, room
or space and exhaust ducts prior to spraying with a different
material.
1504.5.2 Protection of sprinklers. Automatic sprinklers
installed in flammable vapor areas shall be protected from
the accumulation of residue from spraying operations in an
approved manner. Bags used as a protective covering shall
be 0.003 -inch -thick (0.076 mm) polyethylene or cellophane
or shall be thin paper. Automatic sprinklers contaminated
by overspray particles shall be replaced with new automatic
sprinklers.
1504.6 Sources of ignition. Control of sources of ignition shall
be in accordance with Sections 1503.2 and 1504.6.1 through
1504.6.2.4.
1504.6.1 Drying operations. Spray booths and spray
rooms shall not be alternately used for the purpose of drying
by arrangements or methods that could cause an increase ii
the surface temperature of the spray booth or spray room
except in accordance with Sections 1504.6.1.1 and
1504.6.1.2. Except as specifically provided in this section,
drying or baking units utilizing a heating system having
176 2012 NORTH CAROLINA FIRE CODE
open flames or that are capable of producing sparks shall not
be installed in a flammable vapor areas.
1504.6.1.1 Spraying procedure. The spraying proce
dure shall use low-volume spray application.
1.504.6.1.2 Drying apparatus. Fixed drying apparatus
shall comply with this chapter and the applicable provi-
sions of Chapter 21. When recirculation ventilation is
provided in accordance with Section 1504.7.2, the heat-
ing system shall not be within the recirculation air path.
1504.6.1.2.1 Interlocks. The spraying apparatus,
drying apparatus and ventilating system for the spray
booth or spray room shall be equipped with interlocks
arranged to:
1. Prevent operation of the spraying apparatus
while drying operations are in progress.
2. Purge spray vapors from the spray booth or
spray room for a period of not less than 3 min-
utes before the drying apparatus is rendered
operable.
3. Have the ventilating system maintain a safe
atmosphere within the spray booth or spray
room during the drying process and automati-
cally shut off drying apparatus in the event of a
failure of the ventilating system.
4. Shut off the drying apparatus automatically if
the air temperature within the booth exceeds
200°F (93°C).
1504.6.1.2.2 Portable infrared apparatus. When a
portable infrared drying apparatus is used, electrical
wiring and portable infrared drying equipment shall
comply with NFPA 70. Electrical equipment located
within 18 inches (457 mm) of floor level shall be
approved for Class I, Division 2 hazardous locations.
Metallic parts of drying apparatus shall be electrically
bonded and grounded. During spraying operations,
portable drying apparatus and electrical connections
and wiring thereto shall not be located within spray
booths, spray rooms or other areas where spray resi-
due would be deposited thereon.
1504.6.2 Illumination. Where spraying spaces, spray
rooms or spray booths are illuminated through glass panels
or other transparent materials, only fixed luminaires shall be
utilized as a source of illumination.
1504.6.2.1 Glass panels. Panels for luminaires or for
observation shall be of heat-treated glass, wired glass or
hammered wire glass and shall be sealed to confine
vapors, mists, residues, dusts and deposits to the flamma-
ble vapor area. Panels for luminaires shall be separated
from the luminaire to prevent the surface temperature of
the panel from exceeding 200°F (93°C).
1504.6.2.2 Exterior luminaires. Luminaires attached to
the walls or ceilings of a flammable vapor area, but out-
side of any classified area and separated from the flam-
mable vapor areas by vapor -tight glass panels, shall be
suitable for use in ordinary hazard locations. Such
FLAMMABLE FINISHES
luminaires shall be serviced from outside the flammable
vapor areas.
1504.6.2.3 Integral luminaires. Luminaires that are an
integral part of the walls or ceiling of a flammable vapor
area are allowed to be separated from the flammable
vapor area by glass panels that are an integral part of the
luminaire. Such luminaires shall be listed for use in Class
I, Division 2 or Class 11, Division 2 locations, whichever
is applicable, and also shall be suitable for accumulations
of deposits of combustible residues. Such luminaires are
allowed to be serviced from inside the flammable vapor
area.
1504.6.2.4 Portable electric lamps. Portable electric
lamps shall not be used in flammable vapor areas during
spraying operations. Portable electric lamps used during
cleaning or repairing operations shall be of a type
approved for hazardous locations.
1504.7 Ventilation. Mechanical ventilation of flammable
vapor areas shall be provided in accordance with Section 502.7
of the International Mechanical Code.
1504.7.1 Operation. Mechanical ventilation shall be kept
in operation at all times while spraying operations are being
conducted and for a sufficient time thereafter to allow
vapors from drying coated articles and finishing material
residue to be exhausted. Spraying equipment shall be inter-
locked with the ventilation of the flammable vapor areas
such that spraying operations cannot be conducted unless
the ventilation system is in operation.
1504.7.2 Recirculation. Air exhausted from spraying oper-
ations shall not be recirculated.
Exceptions:
1. Air exhausted from spraying operations is allowed
to be recirculated as makeup air for unmanned
spray operations, provided that:
1.1. The solid particulate has been removed.
1.2. The vapor concentration is less than 25
percent of the LFL.
1.3. Approved equipment is used to monitor the
vapor concentration.
1.4. When the vapor concentration exceeds 25
percent of the LFL, the following shall
occur:
a. An alarm shall sound; and
b. Spray operations shall automatically
shut down.
1.5. In the event of shutdown of the vapor con-
centration monitor, 100 percent of the air
volume specified in Section 510 of the
International Mechanical Code is auto-
matically exhausted.
2. Air exhausted from spraying operations is allowed
to be recirculated as makeup air to manned spray-
ing operations where all of the conditions provided
in Exception 1 are included in the installation and
2012 NORTH CAROLINA FIRE CODE 177
FLAMMABLE FINISHES
documents have been prepared to show that the
installation does not pose a life safety hazard to
personnel inside the spray booth, spraying space or
spray room.
1504.7.3 Air velocity. Ventilation systems shall be
designed, installed and maintained such that the average air
velocity over the open face of the booth, or booth cross sec-
tion in the direction of airflow during spraying operations,
shall not be less than 100 feet per minute (0.51 m/s).
1504.7.4 Ventilation obstruction. Articles being sprayed
shall be positioned in a manner that does not obstruct collec-
tion of overspray.
1504.7.5 Independent ducts. Each spray booth and spray
room shall have an independent exhaust duct system dis-
charging to the outside.
Exceptions:
Multiple spray booths having a combined frontal
area of 18 square feet (1.67 mz) or less are allowed
to have a common exhaust when identical spray
finishing material is used in each booth. If more
than one fan serves one booth, fans shall be inter-
connected such that all fans will operate simulta-
neously.
2. Where treatment of exhaust is necessary for air
pollution control or for energy conservation, ducts
shall be allowed to be manifolded if all of the fol-
lowing conditions are met:
2.1. The sprayed materials used are compatible
and will not react or cause ignition of the
residue in the ducts.
2.2. Nitrocellulose -based finishing material
shall not be used.
2.3. A filtering system shall be provided to
reduce the amount of overspray carried
into the duct manifold.
2.4. Automatic sprinkler protection shall be
provided at the junction of each booth
exhaust with the manifold, in addition to
the protection required by this chapter.
1504.7.6 Termination point. The termination point for
exhaust ducts discharging to the atmosphere shall not be
less than the following distances:
Ducts conveying explosive or flammable vapors,
fumes or dusts: 30 feet (9144 mm) from the property
line; 10 feet (3048 mm) from openings into the build-
ing; 6 feet (1829 mm) from exterior walls and roofs;
30 feet (9144 mm) from combustible walls or open-
ings into the building that are in the direction of the
exhaust discharge; 10 feet (3048 mm) above adjoin-
ing grade.
2. Other product -conveying outlets: 10 feet (3048 mm)
from the property line; 3 feet (914 mm) from exterior
walls and roofs; 10 feet (3048 mm) from openings
into the building; 10 feet (3048 nun) above adjoining
grade.
1504.7.7 Fan motors and belts. Electric motors drivine
exhaust fans shall not be placed inside booths or ducts. Fat,
rotating elements shall be nonferrous or nonsparking or the
casing shall consist of, or be lined with, such material. Belts
shall not enter the duct or booth unless the belt and pulley
within the duct are tightly enclosed.
1504.7.8 Filters. Air intake filters that are part of a wall or
ceiling assembly shall be listed as Class I or II in accordance
with UL 900. Exhaust filters shall be required.
1504.7.8.1 Supports. Supports and holders for filters
shall be constructed of noncombustible materials.
1504.7.8.2 Attachment. Overspray collection filters
shall be readily removable and accessible for cleaning or
replacement.
1504.7.8.3 Maintaining air velocity. Visible gauges,
audible alarms or pressure -activated devices shall be
installed to indicate or ensure that the required air veloc-
ity is maintained.
1504.7.8.4 Filter rolls. Spray booths equipped with a fil-
ter roll that is automatically advanced when the air veloc-
ity is reduced to less than 100 feet per minute (0.51 m/s)
shall be arranged to shut down the spraying operation if
the filter roll fails to advance automatically.
1504.7.8.5 Filter disposal. Discarded filter pads shall be
immediately removed to a safe, detached location o -
placed in a noncombustible container with a tight-fittinz
lid and disposed of properly.
1504.7.8.6 Spontaneous ignition. Spray booths using
dry filters shall not be used for spraying materials that are
highly susceptible to spontaneous heating and ignition.
Filters shall be changed prior to spraying materials that
could react with other materials previously collected. An
example of a potentially reactive combination includes
lacquer when combined with varnishes, stains or prim-
ers.
1504.7.8.7 Waterwash spray booths. Waterwash spray
booths shall be of an approved design so as to prevent
excessive accumulation of deposits in ducts and residue
at duct outlets. Such booths shall be arranged so that air
and overspray are drawn through a continuously flowing
water curtain before entering an exhaust duct to the
building exterior.
1504.8 Interlocks. Interlocks for spray application finishes
shall be in accordance with Sections 1504.8.1 through
1504.8.2.
1504.8.1 Automated spray application operations.
Where protecting automated spray application operations,
automatic fire -extinguishing systems shall be equipped
with an approved interlock feature that will, upon discharge
of the system, automatically stop the spraying operations
and workpiece conveyors into and out of the flammabls
vapor areas. Where the building is equipped with a fire
alarm system, discharge of the automatic fire -extinguishing
system shall also activate the building alarm notification
appliances.
178 2012 NORTH CAROLINA FIRE CODE
1504.8.1.1 Alarm station. A manual fire alarm and
emergency system shutdown station shall be installed to
serve each flammable vapor area. When activated, the
station shall accomplish the functions indicated in Sec-
tion 1504.8.1.
1504.8.1.2 Alarm station location. At least one manual
fire alarm and emergency system shutdown station shall
be readily accessible to operating personnel. Where
access to this station is likely to involve exposure to dan-
ger, an additional station shall be located adjacent to an
exit from the area.
1504.8.2 Ventilation interlock prohibited. Air makeup
and flammable vapor area exhaust systems shall not be
interlocked with the fire alarm system and shall remain in
operation during a fire alarm condition.
Exception: Where the type of fire -extinguishing system
used requires such ventilation to be discontinued, air
makeup and exhaust systems shall shut down and damp-
ers shall close.
1504.9 Limited spraying spaces. Limited spraying spaces
shall comply with Sections 1504.9.1 through 1504.9.4.
1504.9.1 Job size. The aggregate surface area to be sprayed
shall not exceed 9 square feet (0.84 m2).
1504.9.2 Frequency. Spraying operations shall not be of a
continuous nature.
1504.9.3 Ventilation. Positive mechanical ventilation pro-
viding a minimum of six complete air changes per hour shall
be installed. Such system shall meet the requirements of this
code for handling flammable vapor areas. Explosion vent-
ing is not required.
1504.9.4 Electrical wiring. Electrical wiring within 10 feet
(3048 mm) of the floor and 20 feet (6096 mm) horizontally
of the limited spraying space shall be designed for Class I,
Division 2 locations in accordance with NFPA 70.
SECTION 1505
DIPPING OPERATIONS
1505.1 General. Dip -tank operations shall comply with the
requirements of Section 1503 and this section.
1505.2 Location of dip -tank operations. Dip -tank operations
conducted in buildings used for Group A, I or R occupancies
shall be located in a room designed for that purpose, equipped
with an approved automatic sprinkler system and separated
vertically and horizontally from other areas in accordance with
the International Building Code.
1505.3 Construction of dip tanks. Dip tanks shall be con-
structed in accordance with Sections 1505.3.1 through
1505.3.4.3 and NFPA 34. Dip tanks, including drain boards,
shall be constructed of noncombustible material and their sup-
ports shall be of heavy metal, reinforced concrete or masonry.
1505.3.1 Overflow. Dip tanks greater than 150 gallons (568
L) in capacity or 10 square feet (0.93 m2) in liquid surface
area shall be equipped with a trapped overflow pipe leading
to an approved location outside the building. The bottom of
FLAMMABLE FINISHES
the overflow connection shall not be less than 6 inches (152
mm) below the top of the tank.
1505.3.2 Bottom drains. Dip tanks greater than 500 gallons
(1893 L) in liquid capacity shall be equipped with bottom
drains that are arranged to automatically and manually drain
the tank quickly in the event of a fire unless the viscosity of
the liquid at normal atmospheric temperature makes this
impractical. Manual operation shall be from a safe, accessi-
ble location. Where gravity flow is not practicable, auto-
matic pumps shall be provided. Such drains shall be trapped
and discharged to a closed, vented salvage tank or to an
approved outside location.
Exception: Dip tanks containing Class IIIB combustible
liquids where the liquids are not heated above room tem-
perature and the process area is protected by automatic
sprinklers.
1505.3.3 Dipping liquid temperature control. Protection
against the accumulation of vapors, self -ignition and exces-
sively high temperatures shall be provided for dipping liq-
uids that are heated directly or heated by the surfaces of the
object being dipped.
1505.3.4 Dip -tank covers. Dip -tank covers allowed by
Section 1505.4.1 shall be capable of manual operation and
shall be automatic closing by approved automatic -closing
devices designed to operate in the event of a fire.
1505.3.4.1 Construction. Covers shall be constructed of
noncombustible material or be of a tin -clad type with
enclosing metal applied with locked joints.
1505.3.4.2 Supports. Chain or wire rope shall be uti-
lized for cover supports or operating mechanisms.
1505.3.4.3 Closed covers. Covers shall be kept closed
when tanks are not in use.
1505.4 Fire protection. Dip -tank operations shall be protected
in accordance with Sections 1505.4.1 through 1505.4.2.
1505.4.1 Fixed fire -extinguishing equipment. An
approved automatic fire -extinguishing system or dip -tank
cover in accordance with Section 1505.3.4 shall be provided
for the following dip tanks:
1. Dip tanks less than 150 gallons (568 L) in capacity or
10 square feet (0.93 m2) in liquid surface area.
2. Dip tanks containing a liquid with a flash point below
110°F (43°C) used in such manner that the liquid tem-
perature could equal or be greater than its flash point
from artificial or natural causes, and having both a
capacity of more than 10 gallons (37.9 L) and a liquid
surface area of more than 4 square feet (0.37 in').
1505.4.1.1 Fire -extinguishing system. An approved
automatic fire -extinguishing system shall be provided
for dip tanks with a 150 -gallon (568 L) or more capacity
or 10 square feet (0.93 m2) or larger in a liquid surface
area. Fire -extinguishing system design shall be in accor-
dance with NFPA 34.
1505.4.2 Portable fire extinguishers. Areas in the vicinity
of dip tanks shall be provided with portable fire
extinguishers complying with Section 906 and suitable for
2012 NORTH CAROLINA FIRE CODE 179
FLAMMABLE FINISHES
flammable and combustible liquid fires as specified for
extra (high) hazard occupancies.
1505.5 Housekeeping, maintenance and storage of hazard-
ous materials. Housekeeping, maintenance, storage and use of
hazardous materials shall be in accordance with Sections
1503.3 and 1503.4.
1505.6 Sources of ignition. Control of sources of ignition shall
be in accordance with Section 1503.2.
1505.7 Ventilation of flammable vapor areas. Flammable
vapor areas shall be provided with mechanical ventilation ade-
quate to prevent the dangerous accumulation of vapors.
Required ventilation systems shall be arranged such that the
failure of any ventilating fan shall automatically stop the dip-
ping conveyor system.
1505.8 Conveyor interlock. Dip tanks utilizing a conveyor
system shall be arranged such that in the event of a fire, the con-
veyor system shall automatically cease motion and the required
tank bottom drains shall open.
1505.9 Hardening and tempering tanks. Hardening and tem-
pering tanks shall comply with Sections 1505.3 through
1505.3.3, 1505.4.2 and 1505.8 but shall be exempt from other
provisions of Section 1505.
1505.9.1 Location. Tanks shall be located as far as practical
from furnaces and shall not be located on or near combusti-
ble floors.
1505.9.2 Hoods. Tanks shall be provided with a
noncombustible hood and vent or other approved venting
means, terminating outside of the structure to serve as a vent
in case of a fire. Such vent ducts shall be treated as flues and
proper clearances shall be maintained from combustible
materials.
1505.9.3 Alarms. Tanks shall be equipped with a high-tem-
perature limit switch arranged to sound an alarm when the
temperature of the quenching medium reaches 50°F (10°C)
below the flash point.
1505.9.4 Fire protection. Hardening and tempering tanks
greater than 500 gallons (1893 L) in capacity or 25 square
feet (2.3 m2) in liquid surface area shall be protected by an
approved automatic fire -extinguishing system complying
with Chapter 9.
1505.9.5 Use of air pressure. Air under pressure shall not
be used to fill or agitate oil in tanks.
1505.10 Flow -coating operations. Flow -coating operations
shall comply with the requirements for dip tanks. The area of
the sump and any areas on which paint flows shall be consid-
ered to be the area of a dip tank.
1505.10.1 Paint supply. Paint shall be supplied by a gravity
tank not exceeding 10 gallons (38 L) in capacity or by direct
low-pressure pumps arranged to shut down automatically in
case of a fire by means of approved heat -actuated devices.
1505.11 Roll -coating operations. Roll -coating operations
shall comply with Section 1505.10. In roll -coating operations
utilizing flammable or combustible liquids, sparks from static
electricity shall be prevented by electrically bonding and
grounding all metallic rotating and other parts of machinery
and equipment and by the installation of static collectors, or b,
maintaining a conductive atmosphere such as a high relativr
humidity.
SECTION 1506
POWDER COATING
1506.1 General. Operations using finely ground particles of
protective finishing material applied in dry powder form by a
fluidized bed, an electrostatic fluidized bed, powder spray guns
or electrostatic powder spray guns shall comply with this sec-
tion. In addition to Section 1506, Section 1507 shall apply to
fixed electrostatic equipment used in powder coating opera-
tions.
1506.2 Location. Powder coating operations shall be con-
ducted in enclosed powder coating rooms, enclosed powder
coating facilities which are ventilated or ventilated spray
booths.
1506.3 Construction of powder coating rooms and booths.
Powder coating rooms shall be constructed of noncombustible
materials. Spray booths shall be constructed in accordance
with Section 1504.3.2.
Exception: Listed spray -booth assemblies that are con-
structed of other materials shall be allowed.
1506.4 Fire protection. Areas used for powder coating shall
be protected by an approved automatic fire -extinguishing sys-
tem complying with Chapter 9.
1506.4.1 Additional protection for fixed systems. Auto-
mated powder application equipment shall be protected by
the installation of an approved, supervised flame detection
apparatus that shall react to the presence of flame within 0.5
second and shall accomplish all of the following:
1. Shutting down of energy supplies (electrical and
compressed air) to conveyor, ventilation, application,
transfer and powder collection equipment.
2. Closing of segregation dampers in associated
ductwork to interrupt airflow from application equip-
ment to powder collectors.
3. Activation of an alarm that is audible throughout the
powder coating room or booth.
1506.4.2 Fire extinguishers. Portable fire extinguishers
complying with Section 906 shall be provided for areas used
for powder coating in accordance with the requirements for
an extra hazard occupancy.
1506.5 Operation and maintenance. Powder coating areas
shall be kept free from the accumulation of powder coating
dusts, including horizontal surfaces such as ledges, beams,
pipes, hoods, booths and floors.
1506.5.1 Cleaning. Surfaces shall be cleaned in such a man-
ner so as to avoid scattering dusts to other places or creating
dust clouds. Vacuum sweeping equipment shall be of a type
approved for use in hazardous locations.
1506.6 Sources of ignition. Control of sources of ignition shall
be in accordance with Sections 1503.2 and 1506.6.1 through
1506.6.4.