Plan Review, Inspection, and Permit Fees
Application Number 17-so042230
$200.00 ❑ Explosive Material (90 Days) _
$100.00 ❑ Explosive Materials (72 Hours) $ -
$100.00 ❑ Fireworks Public Display $ -
$50.00 LI Final Inspection $
$35.00 +$2.0Oper device LI Fire Alarm Testing $ 50.00
$35.00 +$2.00 per nozzle DI Fixed -
Fixed Fire Suppression $ -
$75.00 ❑ Insecticide Fog/Fumigation -
$100.00 ❑ Pipe Test/UST/AGST $ -
$50.00 ❑ Plans up to 5000 sq ft $ -
$100.00 O Plans 5001 sq ft to 10,000 sq ft $
$150.00 ❑ Plans 10,001 sq ft to 25,000 sq ft $ loo 00
$250.00 ❑ Plans 25,001 sq ft and over
$35.00 +2.00 per head ❑ $ -
Sprinkler Certification Test $ -
$50.00 ❑ Standpipe Testing
$50.00 ❑ Special Assembly
(ie.amusement buildings,carnivals,fairs) $ -
D
$75.00
Tents/Canopies/Air Supported Structure
10 $ 75.00
$100.00 Tank Installation (charge for each tank)
$100.00 ❑ Tank Removal (charge for each tank) $ -
Total Devices/Heads $
Total Cost $ 225.00
Code Enforcement Official Rodney Daniels
10/4/2017
Harnett
COUNTY ..fri1
Rap., :,6( a,n Alia*
'T.,encytenn Department
October 4, 2017
RE: Johnston-Lee-Harnett Community Action
747 Shawtown Road
Lillington, NC 27546
Re:Application Number—17-50042230
Mr. Avery,
Thank you for submitting plans for the new facility. The plans have been reviewed by a
qualified code enforcement official for compliance with the North Carolina Fire
Prevention code and all other fire protection regulations. The following are items that
will need to be addressed before a final inspection of this project can be completed. The
items are listed and described below.
• 503 Fire Department Access
o The fire department access shall extend to within 150 feet of all portions
of the facility(current driveway and parking lot may suffice).
o The fire department access road shall be of an unobstructed width of not
less than 20 feet and shall have an unobstructed vertical clearance of not
less the 13 feet 6 inches.
• 505.1 Physical Address
o The physical address of the building shall be posted in a conspicuous
place so that it can be seen on approach from the road, access road,
and/or parking lot.
o The numbers used to make up the physical address shall be at least 5
inches in height.
• 906.1 Fire Extinguishers
o Fire extinguishers shall be placed in approved locations and may be field
verified on final inspection. The fire extinguishers provided shall have a
minimum rating of 2A 10 B: C.
= Harnett
COUNTY30C—A— AO town my snati aparenbsat
vandwrmuwa
..
• 1006.1/1006.2 Emergency Illumination
o Emergency illumination is required to meet minimum foot candle
illumination.
o Emergency lighting is required. Please show locations
• 1011 Exit Signs
o Exit signs shall be installed at all required exits. Exit signs shall meet all
provisions of chapter 10.
• 506.1 Knox Box
o A Knox box is required to be installed on the building.
o An application/order form has been attached to the review comments.
• Notes
o Fire alarm and hood suppression system will require additional permits.
o Please contact the Fire marshal's office to schedule both fire alarm
system testing and fire final inspection when work is complete.
Please review the plans and adhere to any notes and alterations that were made in
addition to the original designed plans. These remarks are for the plans that were
submitted and its original intent. If you have any questions please do not hesitate to
contact me. We look forward to working with you during the construction period.
Sincerely,
Rodney Dariels
Chief Deputy Fire Marshal
Harnett
COUNTY * A (cm) A•r � M
eyScrimsDemoY
An R1) CA Rb If NA fYf
•
�I
�� CICC�I/
� Application for Plan Reviewcis s(o )
( k, I . I)u Appc`�tjon# f - cCc
Date Received: ) I� (' (� ��Received By: 0 U h.-X/,�1y,�.)j-,
Name of Project: CU `NM tf 1 LU4 e rat i x Y.1/A/l,l L r )
Physical Address of Project: 1 L-11��J.�,,,,L-haM l Q 7��r / / >(
1 L11 p) ) , NC Z1j0- (C
Plans Submitted By: C" A-vPi�
Project Phone: (1�I1V)- ,1 -/ ✓ V)&9i /
/p
Contact Person/Address: 7—/�� ` f 9
Contact Email:
Contact Phone: ( )- - ( )- -
Contractor's Name/Info:
Contractor's Phone:
• Plans that are submitted will be reviewed as quickly as possible with an average time of review
between 7-10 working days.
• Status checks may be conducted on plan reviews by visiting the website
http://hteweb.hamett.org/Click2GovBP/Index.isp or by calling the Hamett County Central Permitting
Office(910-1393-7525,Option#2), or the Hamett County Fire Marshal's Office(910-893.7580).
• Approved plans must be picked up from the Central Permitting Office and all fees paid before any
required inspections can be conducted.