CCH, Sprinkler PRHarnett COUNTY Enw9erwy Sank" Departmat �Opik Fire Marshal Division September 28, 2017 Blackstone Fire Control 2912 Manufacturers Road Greensboro, NC 27406 Re: Central Harnett Health, Cath Lab 215 Brightwater Drive Lillington, NC 27546 Application Number 17-50041403 (Sprinkler Plan Review) Mr. Mercadante, Thank you for submitting the plans for the new Cath Lab sprinkler up fit. The plans have been carefully reviewed by a qualified code enforcement official to examine for compliance with the North Carolina Fire Prevention Code and all other fire protection regulatory documents. There are some items that were found during the plan review process that need to be addressed before a final inspection of the new facility can be given. These items are outlined and described below. ® 901.2.1 State of Compliance. o Before requesting final approval of the installation, where required by the fire code official, the installing contactor shall furnish a written statement to the fire code official that the subject fire protection system has been installed in accordance with the manufacture's specifications and the appropriate installation standard. Any deviations from the design standards shall be noted and copies of the approvals for such deviations shall be attached to the written statement. o All work shall be performed in accordance with NFPA 13 and the NCSFC. ® 901.5 Installation acceptance testing. o All piping and attached appurtenances subjected to system working pressure shall be hydrostatically tested at 200 psi or 50 psi in excess of the system working pressure, whichever is greater, and shall maintain that pressure without loss for 2 hours. This test is required to be witnessed by a representative from the Harnett County Fire Marshal's Office. Harneft COUNTY 77777 i, 77,7s o A contractor's material and test certificate shall be furnished by the trained representative of Blackstone Fire Control before final approval. • Notes o A sprinkler system construction permit is required. o Please schedule all inspections through the Fire Marshal's Office. 0 910-893-0743 Thank you again for submitting the plans for the Cath Lab sprinkler up fit. Please review the plans and adhere to any notes and alterations that were made in addition to the original drawings. These remarks are for the plans that were submitted and its original intent. These remarks do not apply if the original intent changes or what was submitted on the above date changes. If you have any questions, please do not hesitate to call this office. Sincerely, re' Rodney Da iels Chief Deputy Fire Marshal