Fire Marshal Division
September 28, 2017
Blackstone Fire Control
2912 Manufacturers Road
Greensboro, NC 27406
Re: Central Harnett Health, Cath Lab
215 Brightwater Drive
Lillington, NC 27546
Application Number 17-50041403 (Sprinkler Plan Review)
Mr. Mercadante,
Thank you for submitting the plans for the new Cath Lab sprinkler up fit. The plans have
been carefully reviewed by a qualified code enforcement official to examine for
compliance with the North Carolina Fire Prevention Code and all other fire protection
regulatory documents. There are some items that were found during the plan review
process that need to be addressed before a final inspection of the new facility can be
given. These items are outlined and described below.
® 901.2.1 State of Compliance.
o Before requesting final approval of the installation, where required by the
fire code official, the installing contactor shall furnish a written statement
to the fire code official that the subject fire protection system has been
installed in accordance with the manufacture's specifications and the
appropriate installation standard. Any deviations from the design
standards shall be noted and copies of the approvals for such deviations
shall be attached to the written statement.
o All work shall be performed in accordance with NFPA 13 and the
NCSFC.
® 901.5 Installation acceptance testing.
o All piping and attached appurtenances subjected to system working
pressure shall be hydrostatically tested at 200 psi or 50 psi in excess of the
system working pressure, whichever is greater, and shall maintain that
pressure without loss for 2 hours. This test is required to be witnessed by a
representative from the Harnett County Fire Marshal's Office.
Harneft
COUNTY
77777 i, 77,7s
o A contractor's material and test certificate shall be furnished by the
trained representative of Blackstone Fire Control before final
approval.
• Notes
o A sprinkler system construction permit is required.
o Please schedule all inspections through the Fire Marshal's Office.
0 910-893-0743
Thank you again for submitting the plans for the Cath Lab sprinkler up fit. Please review
the plans and adhere to any notes and alterations that were made in addition to the
original drawings. These remarks are for the plans that were submitted and its original
intent. These remarks do not apply if the original intent changes or what was submitted
on the above date changes. If you have any questions, please do not hesitate to call this
office.
Sincerely,