FM REVIEW Harnett
COUNTYille— ♦, E•-••a,,Sant.otMrvs.t
aORTr' CAAO.:NA ® • nitiJrarMt.aa
Application for Plan ReviewIS
��J--
Alpplicatiioon# I1 - CC./-4- (6' 2C
Date Received: I • 1 Received By: di Ont'lJf
Name of Project BURGER KING RESTAURANT
Physical Address of Project: 2736 NC 24-87
CAMERON NC 28326
Plans Submitted By' ANDRES H.RIIEL,ARCHITECT
Project Phone: ( )- -
Contact PBreoNAddresa: ANDRES H. RIIEL,ARCHITECT
2644 FOREST DRIVE
HINCKLEY, OHIO 44233
Contact Email: ahiel@ameritech.net
Contact Phone: ( 440 )_ 333 _ 6900
Contractor's Namellnfo:
Contractor's Phone: ( )- -
• Plans that are submitted will be reviewed as quickly as possible with an average time of review
between 7-10 working days.
• Status checks may be conducted on plan reviews by visiting the website
htto://hteweb.hamett.org/Click2GovBP/Index.isp or by calling the Hamett County Central Permitting
Office (910-893-7525, Option#2),or the Hamett County Fire Marshal's Office (910-893-7580).
• Approved plans must be picked up from the Central Permitting Office and all fees paid before any
required inspections can be conducted.
IvHarnett
COUNTY 0 m) za..«.s*Wfl w.Kn.nr
Plan Review, Inspection, and Permit Fees
Application Number 1750041620
$200.00 ❑ Explosive Material (90 Days) $ -
$100.00 ❑ Explosive Materials (72 Hours) $ -
$100.00 ❑ Fireworks Public Display $ -
$50.00 E Final Inspection $ 50.00
$35.00 +$2.00 per device ❑ Fire Alarm Testing $ -
$35.00 +$2.00 per nozzle ❑ Fixed Fire Suppression $ -
$75.00 ❑ Insecticide Fog/Fumigation $ -
$100.00 ❑ Pipe Test/UST/AGST $ -
$50.00 El Plans up to 5000 sq ft $ 50.00
$100.00 ❑ Plans 5001 sq ft to 10,000 sq ft $ -
$150.00 ❑ Plans 10,001 sq ft to 25,000 sq ft $ -
$250.00 El Plans 25,001 sq ft and over $ -
$35.00 +2.00 per head ❑ Sprinkler Certification Test $ -
$50.00 ❑ Standpipe Testing $ -
$50.00 ❑ Special Assembly
lie.amusement buildings,carnivals,fairs) $ -
$75.00 Tents/Canopies/Air Supported Structure
$ -
111
$100.00 Tank Installation (charge for each tank) $
$100.00 ❑ Tank Removal (charge for each tank) $ -
Total Devices/Heads $ -
Total Cost $ 100.00
Code Enforcement Official Rodney Daniels 8/1/2017
Harnett
opo Einerioncy Serveces
...awnw,..o
August I, 2017
Andres H. Riiel
2644 Forest Drive
Hinckley, Ohio 44233
RE: Burger King
2738 NC 24-87
Cameron,NC 28326
Application Number 17-50041620
Mr. Riiel
Thank you for submitting the plans for the Burger King. The plans have been carefully
reviewed by a qualified code enforcement official to examine for full compliance with
the North Carolina Fire Prevention Code and all other fire protection regulatory
documents. There are some items that were found during the plan review process that
need to be addressed before a final inspection of the new facility can be given. These
items are outlined and described below.
• 906.1 Fire Extinguishers
o Fire extinguishers shall be placed in locations so that no more than 75 feet
travel to reach an extinguisher from any portion of the building,locations
will be verified at final.
o The fire extinguishers provided shall have a minimum rating of 2A1013: C
shall not be installed higher than 5 feet above the finished floor.
o Class K fire extinguisher shall be located within 30' travel distance of
commercial cooking equipment.
• 503 Fire Department Access
o The fire department access shall extend to within 150 feet of all portions
of the facility(current driveway and parking lot may suffice).
o The fire department access road shall be of an unobstructed width of not
less than 20 feet and shall have an unobstructed vertical clearance of not
less the 13 feet 6 inches.
• 507.5.1 Fire Hydrant
o A fire hydrant is required within 400' from structure.
Harnett
—IC'.
COUNTY *A oM> rwr�.�r s...n.aq.w•..
C ....wra..,
• 506.1 Knox Box
o Knox box shall be installed on exterior of building at main entrance with
5' of door and no higher than 5' high
https://www.knoxhox.com/commercial-knox-boxes
• 505.1 Physical Address
o The physical address of the building shall be posted in a conspicuous place
so that it can be seen on approach from the road, access road, and/or
parking lot.
o The numbers used to make up the physical address shall be at least 5
inches in height.
• 1006.2 Illumination Level
o The means of egress illumination level shall not be less than 1 foot-candle
at the walking surface.
Notes
• Duct detectors will be 100 % tested with smoke machine or smoke bomb
• Shop drawings for Fixed Fire Suppression to be submitted for review
• Call Fire Marshal's Office at 910-893-0743 to schedule inspections.
Thank you again for submitting the plans for the Burger King. Please review the plans
and adhere to any notes and alterations that were made in addition to the original
drawings. These remarks are for the plans that were submitted and its original intent.
These remarks do not apply if the original intent changes or what was submitted on the
above date changes. If you have any questions, please do not hesitate to call this office
Again,thank you and we look forward to working with you during the construction
period!
Sincere
i
Rodney!). els
Chief Deputy Fire Marshal