FM REVIEW n- HarnettCOUNTY
*__A__ (FMS ` a.nr. War=r .�t
WY'JIMMngrg
Application for Plan Review
Application # _
Date Received: 23 7
Received By:
Name of Project: CarolinaL a( Arts
/� It r
Physical Address of Project: ► &)C 2 'z7
NC 51_ _
Plans Submitted By: I a U
-Mita A a,
Project Phone: (g�)- g I O- )aQ I I
Contact Person/Address: -��r--��.—
Contact Email: CD% 1.9 N
t(VaI vile I ' vie, IVK.
Contact Phone: ( )
} -
Contractor's Name/Info:
Contractor's Phone:
• Plans that are submitted will be reviewed as quickly as possible with an average time of review
between 7-10 working days,
• Status checks may be conducted on plan reviews by visiting the website
http.lmteweb.harnett.orq/Click2GovBP/Index.isp or by calling the Harnett County Central Permitting
Office(910-893-7525, Option#2), or the Harnett County Fire Marshal's Office(910-893-7580).
• Approved plans must be picked up from the Central Permitting Office and all fees paid before any
required inspections can be conducted.
Harnett
couNVV
,_„r.z_..,., as(N+>
inowansettarg
Plan Review, Inspection, and Permit Fees
Application Number .
1750041691
$200.00 ❑ Explosive Material (90 Days)
$100.00 ElExplosive Materials (72 Hours) $
$100.00 I:3 Fireworks Public Display $
$50.00 O Final Inspection $
$35.00 +$2.00 per device ❑ Fire Alarm Testing $ sum
$35.00 +$2.00 per nozzle El Fixed Fire Su $
$75.o0 ❑ Suppression $
Insecticide Fog/Fumigation
$100.00 ❑ Pipe Test/UST/AGST $
$50.00 O Plans up to 5000 sq ft $
$100.00 ❑ Plans 5001 sq ft to 10,000 sq ft $ 50.00
$150.00 ❑ Plans 10,001 sq ft to 25,000 sq ft $ --
$250.00 ❑ Plans 25,001 sq ft and over $
$35.00 +2.00 per head ❑ Sprinkler Certification Test $
$50.00 ❑ Standpipe Testing $ -
$50.00 ❑ Special Assembly $
(ie.amusement buildings,carnivals,fairs) $
❑ -
$75.00 Tents/Canopies/Air Supported Structure
$
$100.00 ❑
Tank Installation (charge for each tank)
$100.00 ❑ Tank Removal (charge for each tank) $ -
Total Devices/Heads
Total Cost $
$ 100.00
Code Enforcement Official Rodney Daniels
6/30/2017
( \ Harnett
• COUNTY
heh • Uh Af1.1 ® 11
wrnaornenary
Fire Marshal Division
June 29, 2017
Commercial Building, Inc.
910-818-6811
RE: Carolina Performing Arts
1482 NC 24-87
Cameron,NC 28326
Application Number 17-50041691
To whom it may concern,
Thank you for submitting the plans for the up fit. The plans have been carefully
reviewed by a qualified code enforcement official to examine for full compliance with
the North Carolina Fire Prevention Code and all other fire protection regulatory
documents. There are some items that were found during the plan review process that
need to be addressed before a final inspection of the new facility can be given. These
items are outlined and described below.
• 906.1 Fire Extinguishers
o A portable fire extinguisher shall be provided within a 30-foot(9144 mm)
travel distance of commercial-type cooking equipment. Cooking
equipment involving vegetable or animal oils and fats shall be protected
by a Class K rated portable extinguisher.
• 1006.1 Emergency Lighting
o All emergency lighting, provided prior to up fit, shall be in proper
operating condition at time of final inspection.
o Any changes made in illumination requirements, due to equipment
placement or storage arrangements shall be addressed before final
inspection.
o The means of egress, including the exit discharge, shall be illuminated at
all time the building space is served by the means of egress is occupied.
• Means of egress consist of three separate and distinct parts: the
exit access, the exit and the exit discharge.
o The means of egress illumination shall not be less than 1 foot-candle at
the walking surface.
• 506.1 Knox Box
flHarnett
COUNTY
�Ur.. . r:. �. * k4 IFMA
hael
o Keys for front entrance door shall be provided to be placed in the enren .in
existing box installed on the premises.
• 505.1 Physical Address (ie: suite Number if Applicable)
o The physical address of the building shall be posted in a conspicuous place
so that it can be seen on approach from the road, access road, and/or
parking lot.
o The numbers used to make up the physical address shall be at least 5
inches in height.
o The physical address needs to be posted on the rear of the building also.
• 907.4.1 Duct Smoke detectors (If greater than 2000 cfm's)
o Smoke detectors installed in ducts shall be listed for the air velocity,
temperature and humidity present in the duct. Duct smoke detectors shall
be connected to the building's fire alarm control unit when a fire alarm
system is required by Section 907.2. Activation of a duct smoke detector
shall initiate a visible and audible supervisory signal at a constantly
attended location and shall perform the intended fire safety function in
accordance with this code and the International Mechanical Code. Duct
smoke detectors shall not be used as a substitute for required open area
detection.
Note: Please schedule all fire Inspections through the Fire Marshal's Office(910)893-
0743.
Thank you again for submitting the plans for the up fit. Please review the plans and
adhere to any notes and alterations that were made in addition to the original drawings.
These remarks are for the plans that were submitted and its original intent. These remarks
do not apply if the original intent changes or what was submitted on the above date
changes. If you have any questions, please do not hesitate to call this office
Again, thank you and we look forward to working with you during the construction
period!