Loading...
17-50041442, Coble Ski AGSTHarnettJEn"r9QffWV swwim Depart"WO C 0 U N WWWAO"Mm"10 Date Received: Name of Project: Physical Address of Project: Plans Submitted By: Project Phone: Contact Person/Address: Application for Plan Review Application # Received By: Ut oftly) . . ..... . ..... NC A ....... . .... . .. I E N WN Contact Entail: Contact Phone: Contractor's Name/Info: Contractor's Phone: ( - ).-.- Hold k 2 20 i5l/ 50," 2:260 5 PM • Plans that are submitted will be reviewed as quickly as possible with an average time of revi between 7-10 working d • Status checks may be conducted on plan reviews by visiting the website htto:l/hteweb.harnett,oEg/Click2GovBPlindex.ist) or by calling the Harnett County Central Permitting Office (910-893-7525, Option #2), or the Hamett County Fire Marshal's Office (910-893-7580), • Approved plans must be picked up from the Central Permitting office and all fees paid before any required inspections can be conducted. IN i i m .2 It I 0 • RA- a Ila I cj� Harneft COUNTY * A& Fire Marshal Division May 25, 2017 April Coble PO Box 2228 Lillington, NC 27546 School Re: Coble Ski .0 Coble Lillington, NC 2754f Application Number 17- 50041442 Mrs. Coble, Thank you for submitting the plans for the installation of the above ground flammable liquid storage tank. The plans have been carefully reviewed by a qualified code enforcement official to examine for compliance with the North Carolina Fire Prevention Code and all other fire protection regulatory documents. There are some items that were found during the plan review process that need to be addressed before a permit to install the tanks can be granted. These items are outlined and described below. Pending requirements before permit issuance: Submit engineered plans for the installation of each Aboveground Storage Tank (AGST) used for fleet - fueling and /or motor fuel dispensing operations. Approved and listed piping systems and all ancillary equipment for a complete installation shall be indicated on the plans as prescribed in the NC State Fire Code and NFPA 30. It is also important to remember that the NC State Board of Registration for Professional Engineers and Land Surveyors require that a Professional Engineer (PE) seal all plans regarding ASTs /USTs Installations, piping, ancillary equipment upgrades, and vapor recovery system installations. Small tanks of 1,100 gals. or less capacity for commercial or noncommercial purposes and tanks used for storing heating oil for consumptive use on the premises where stored and the storage of Class 11113 combustibles are excluded from the PE rule. o Dispensers used shall be approved and listed for appropriate fuel oil. • Provide Safety Data Sheets from the manufacture of each type of flammable or combustible liquid stored or dispensed from each tank. • Vehicle impact protection shall be installed in accordance with section 312 of NC FPC. After permit is issued and before final approval: • Installation shall be in accordance with all North Carolina Fire prevention codes and NFPA 30 standards. • All hydrostatic and pressure tests for tanks and piping shall be witnessed by the Fire Marshal's Office. • Contact the Fire Marshal's Office to witness the setting of tanks. • A final Fire inspection is required at the end of the project. • Call (910) 893 -0743 to schedule all fire inspections. Thank you again for submitting the plans for above ground storage tank installation. Please review the plans and adhere to any notes and alterations that were made in addition to the original drawings. These remarks are for the plans that were submitted and its original intent. These remarks do not apply if the original intent changes or what was submitted on the above date changes. If you have any questions, please do not hesitate to call this office. Again, thank you and we look forward to working with you during the construction period! Sincerely, f � Rodney Daniels Chief Deputy Fire Marshal