FM PLAN REVIEW Harnett
")( COUNTY
® ,
0o<<. .. . A lFM> ._•.. ,..insD...._t
May 24,2017
RLT&Associates, Inc.
III Tasha Lane
Fuquay Varina,NC 27526
Re: AGST Removal
Harnett County Vehicle Maintenance Building
1100 East McNeill Street
Lillington,NC 27546
Application Number 17-50041444
Mr. Temple,
Thank you for submitting the plans for the tank removal. The plans have been carefully
reviewed by a qualified code enforcement official to examine for compliance with the
North Carolina Fire Prevention Code and all other fire protection regulatory documents.
There are some items that were found during the plan review process that need to be
addressed before a final inspection of the new facility can be given. These items are
outlined and described below.
• Guidance
o The removal of the tanks shall follow the applicable requirements in
NFPA 30(Annex C.5), API 2015,NFPA 226,and the Fire Code.
• Procedures
o Combustible liquids shall be removed from the tank and connected piping.
o Piping at tank openings that is not to be used further shall be disconnected.
o Piping shall be removed from the ground(if applicable)or filled with
concrete.
o Tank openings shall be capped or plugged, leaving a ve to 'h inch gap for
pressure equalization.
o Tanks shall be purged of vapor and inerted prior to removal, until an LEL
of 10%or lower is achieved
o All tanks shall be marked indicating type of product that was stored,date
of removal,and the word"EMPTY"
Harnett
oan
® (FM) us," Deplanes,
rOrr'r INA CArb_INA
• Closure Report
o A closure report shall be submitted to the Fire Marshal's Office after the
removal of the tanks. The closure report shall detail any possible
contamination of the property resulting from the tanks and the appropriate
response. The destination of the removed tanks must also be noted.
Tanks to be Removed (1 tanks total):
3000 Gallon Gasoline
General Notes
Contact our office to witness the setting/removal of the tanks and the tests associated with
the tanks and piping attached to tanks. A Fire Inspector must be onsite to perform these
tests.
Thank you again for submitting the plans for tank removal. Please review the plans and
adhere to any notes and alterations that were made in addition to the original drawings.
These remarks are for the plans that were submitted and its original intent. These remarks
do not apply if the original intent changes or what was submitted on the above date
changes. If you have any questions,please do not hesitate to call this office.
Again, thank you and we look forward to working with you during the construction
period!
Sincerely,
Rodney
Chief Deputy Fire Marshal
HCFM
Office of the Fire Marshal
P.O. Box 370
Lillington, N.C. 27548
(910)493.7580
Permit Certificate
Business Name: HARNETT COUNTY GARAGE
Address: 1100 E MCNEIL ST
LILLINGTON, NC 27545
Phone:
The following permit has been issued: Permit No. 1750041444
Type: 035 Above Ground Tank Removal
Issued Date: 05/24/2017
Effective Date: 06/24/2017
Expiration Date: 05/25/2017
This permit certificate has been issued for[ ]construction/ [ ]operational purposes located
at the above business location.This permit has been issued and will be enforced in accordance
with section log of the N.C.State Fire Prevention Code. Please contact our office for any further
questions regarding this permit.
Inspector: 'kodney Keith Daniels Date
05/24/2017 Page 1