Plan Review, Inspection, and Permit Fees
Application Number .
1750041403
$200.00 ❑ Explosive Material (90 Days) _
$100.00 ❑ Explosive Materials (72 Hours) $ _
$100.00 ❑ Fireworks Public Display $ _
$50.00 O Final Inspection $
$35.00 +$2.00 per device ❑ Fire Alarm Testing $ so.00
$35.00 +$2.00 per nozzle 1:1 Fixed Fire Suppression $
-
$75.00 ❑ $
Insecticide Fag/Fumigation -
$100.00 ❑ Pipe Test/UST/AGST $
$50.00D Plans up to 5000 sq ft $
$100.00 ❑ Plans 5001 sq ft to 10,000 sq ft $ 50.00
$150.00 ID Plans 10,001 sq ft to 25,000 sq ft $ _
$250.00 ❑ Plans 25,001 sq ft and over $
$35.00 +2.00 per head ❑ $ -
SprinklerCertification Test $ -
$50.00 ❑ Standpipe Testing
$50.00 ElSpecial Assembly
(le.amusement buildings,carnivals,fairs) $ -
❑
$75.00
Tents/Canopies/Air Supported Structure
❑ $
$100.00 Tank Installation (charge for each tank)
$100.00 ❑ Tank Removal (charge for each tank) $
Total Devices/Heads $
Total Cost $ 100.00
Code Enforcement Official Rodney Daniels
6/2/2017
=Harnett
COUNTY
-•-mow
Fire Marshal Division
June 2, 2017
Re: Central Harnett Hospital
215 Brightwater Drive
Lillington, NC 27546
Application Number 17-50041403
Mr. Kogut,
Thank you for submitting the plans for the Central Harnett Hospital renovations. The
plans have been carefully reviewed by a qualified code enforcement official to examine
for compliance with the North Carolina Fire Prevention Code and all other fire
protection regulatory documents. There are some items that were found during the
plan review process that need to be addressed before a final inspection of the new
facility can be given. These items are outlined and described below.
• 906.1 Fire Extinguishers
o Minimum of(1) 2A10:BC fire extinguisher shall be installed not to exceed
75'distance of travel.
o All Fire extinguishers shall be properly mounted and tagged by a fire
extinguisher company.
• 1006.1 Means of Egress Illumination
o The means of egress, including the exit discharge, shall be illuminated at
all time the building space is served by the means of egress is occupied.
o Means of egress consist of three separate and distinct parts: the
exit access,the exit and the exit discharge.
o The means of egress illumination shall not be less than 1 foot-candle at
the walking surface.
• 1008.1.4.4 Access-controlled egress doors.
o The entrance doors in a means of egress in buildings with an occupancy
in Group A, B, E, 1-2, M, R-1 or R-2 and entrance doors to tenant spaces in
occupancies in Groups A, 8, E, 1-2, M, R-1 and R-2 are permitted to be
equipped with an approved entrance and egress access control system
which shall be installed in accordance with all of the following criteria:
Harnett
couery .•. �
�'it*r ;nRC.:n• �f�.� "own Santos D '�rY•wt
`�. aaalarrrtt,p
1. A sensor shall be provided on the egress side arranged to
detect an occupant approaching the doors. The doors shall be
arranged to unlock by a signal from or loss of power to the sensor.
2. Loss of power to that part of the access control system which
locks the doors shall automatically unlock the doors.
3. The doors shall be arranged to unlock from a manual unlocking
device located 40 inches to 48 inches (1016mmto 1219 mm)
vertically above the floor and within 5 feet(1524 mm) of the
secured doors. Ready access shall be provided to the manual
unlocking device and the device shall be clearly identified by a
sign that reads "PUSH TO EXIT."When operated,the manual
unlocking device shall result in direct interruption of power to the
lock— independent of the access control system electronics—and
the doors shall remain unlocked for a minimum of 30 seconds.
4. Activation of the building fire alarm system, if provided, shall
automatically unlock the doors, and the doors shall remain
unlocked until the fire alarm system has been reset.
5. Activation of the building automatic sprinkler or fire detection
system, if provided, shall automatically unlock the doors. The
doors shall remain unlocked until the fire alarm system has been
reset.
• 907.1.2 Fire Alarm System Shop Drawings
o Shop drawings from the licensed installing contractor shall be submitted
prior to work beginning.
o A rough in Inspection is required.
o A final acceptance test is required. (100%)
• 901.6.1 Sprinkler System Shop Drawings
o Sprinkler system shop drawings shall be submitted by the installing
contractor prior to work beginning.
o A rough in inspection Is required.
o A final acceptance test is required.
• 703.5 Identification
o Walls and partitions required to have protected openings shall be
permanently identified with signs or stencils. (Example "2- hour Flre
Barrier Protect All Openings")
• Notes
o A final fire inspection is required.
o Schedule all fire inspections through the Fire Marshal's Office.
(919)893-0743
•
r Harnett
-� cm COUNTY
...; E....�,
Semen O...A..,r
o, :,P: . ,,,
SIT';
Thank you again for submitting the plans for the C renovations. Please review the plans
and adhere to any notes and alterations that were made in addition to the original
drawings. These remarks are for the plans that were submitted and its original intent.
These remarks do not apply if the original intent changes or what was submitted on the
above date changes. If you have any questions, please do not hesitate to call this office.
Sincerely,
Rodney Daniels
Chief Deputy Fire Marshal