FM PLAN REVIEW APPLICATION Harnett
COUNTY .-•, oM^"�
vetrowNernattag
Plan Review, Inspection, and Permit Fees
Application Number 1750041292
$200.00 ❑ Explosive Material (90 Days) $ -
$100.00 El Explosive Materials (72 Hours) $ -
$100.00 ❑ Fireworks Public Display $ -
$50.00 0 Final Inspection $ 50.00
$35.00 +$2.00 per device ❑ Fire Alarm Testing $ -
$35.00 +$2.00 per nozzle ❑ Fixed Fire Suppression $ -
$75.00 El Insecticide Fog/Fumigation $ -
$100.00 ❑ Pipe Test/UST/AGST $ -
$50.00 El Plans up to 5000 sq ft $ 50.00
$100.00 ❑ Plans 5001 sq ft to 10,000 sq ft $ -
$150.00 ❑ Plans 10,001 sq ft to 25,000 sq ft $ -
$250.00 ❑ Plans 25,001 sq ft and over $ -
$35.00 +2.00 per head ❑ Sprinkler Certification Test $ -
$50.00 ❑ Standpipe Testing $ -
❑ Special Assembly
$50.00 (le.amusement buildings,carnivals,fairs) $ -
El
$75.00 Tents/Canopies/Air Supported Structure $
$100.00 Tank Installation (charge for each tank) $
$100.00 ❑ Tank Removal (charge for each tank) $ -
Total Devices/Heads $ -
Total Cost $ 100.00
Code Enforcement Official Rodney Daniels 5/3/2017
negroneerr ,..
:nr:..1.,. A �FM> E•-.•Kr service.n....•ran
`. • ncharnwLry
May 3, 2017
Robert Shuman
2553 Housley Road, Suite 103
Annapolis, MD 28326
RE: Dunkin Donuts/Baskin Robins
Application Number 17-50041292
Mr. Shuman,
Thank you for submitting the plans for the up fit. The plans have been carefully
reviewed by a qualified code enforcement official to examine for full compliance with
the North Carolina Fire Prevention Code and all other fire protection regulatory
documents. There are some items that were found during the plan review process that
need to be addressed before a final inspection of the new facility can be given. These
items are outlined and described below.
• 906.1 Fire Extinguishers
o A portable fire extinguisher shall be provided within a 30-foot(9144 mm)
travel distance of commercial-type cooking equipment. Cooking
equipment involving vegetable or animal oils and fats shall be protected
by a Class K rated portable extinguisher.
• 1006.1 Emergency Lighting
o All emergency lighting,provided prior to up fit, shall be in proper
operating condition at time of final inspection.
o Any changes made in illumination requirements,due to equipment
placement or storage arrangements shall be addressed before final
inspection.
o The means of egress, including the exit discharge, shall be illuminated at
all time the building space is served by the means of egress is occupied.
• Means of egress consist of three separate and distinct parts: the
exit access,the exit and the exit discharge.
o The means of egress illumination shall not be less than 1 foot-candle at
the walking surface.
• 506.1 Knox Box
Harnett
1.or. .ht:...K1 A (FM) L•r,.ar SOMOSO G..Mwt
airtharowittag
o Keys for front entrance door shall be provided to be placed in the
existing box installed on the premises.
• 505.1 Physical Address (ie: suite Number if Applicable)
o The physical address of the building shall be posted in a conspicuous place
so that it can be seen on approach from the road, access road, and/or
parking lot.
o The numbers used to make up the physical address shall be at least 5
inches in height.
o The physical address needs to be posted on the rear of the building also.
• 907.4.1 Duct Smoke detectors
o Smoke detectors installed in ducts shall be listed for the air velocity,
temperature and humidity present in the duct. Duct smoke detectors shall
be connected to the building's fire alarm control unit when a fire alarm
system is required by Section 907.2. Activation of a duct smoke detector
shall initiate a visible and audible supervisory signal at a constantly
attended location and shall perform the intended fire safety function in
accordance with this code and the International Mechanical Code. Duct
smoke detectors shall not be used as a substitute for required open area
detection.
Note: Please schedule all fire Inspections through the Fire Marshal's Office(910)893-
0743.
Thank you again for submitting the plans for the up fit. Please review the plans and
adhere to any notes and alterations that were made in addition to the original drawings.
These remarks are for the plans that were submitted and its original intent. These remarks
do not apply if the original intent changes or what was submitted on the above date
changes. If you have any questions,please do not hesitate to call this office
Again, thank you and we look forward to working with you during the construction
period!
Sincerely,
Rodney Daniels
Chief Deputy Fire Marshal