FM REVIEW Harnett �FMf Ein. -�
�� C O U N T Y s +w.hrnM•°'9
Rnp:'= fRr C:'MM1
Application for Plan fR^eview
Application# \ c
�- oOA1112-. �
2I Il
Date ReceivedReceived By. • CQ_ ��I.
'. �I I C
Si( 1 ' - Qs CA/+u1 Sb e S
Name of Project:
Physical Address of Project
fl)mune \ OaOAA0. , NC 27S21e
Plans Submitted By: !y'1 7`5 pp�g4
Project Phone: ( -11 'I )-� ,
Contact PeraonlAtldress:
Ltc 2ev\S
rvauII \iav,na NC 215
Contact Email:
( �I gl S .-)359e_ ( )--
Contact Phone:
Contractor's Namellnfo: 1
Contractor's Phone:
• Plans that are submitted will be reviewed as quickly as possible with an average time of re=iew
between 7between 1Jaysi
• Status checks may be conducted on plan reviews by visiting the website
htto Ilhteweb harnett orgjClick2GovBPllndey.ise or by calling the Harnett County Central Permitting
Office (910-893-7525,Option#2),or the Harnett County Fire Marshal's Office (910.893-7580).
• Approved plans must be picked up from the Central Permitting Office and all fees paid before any
required inspections can be conducted.
In Harnett _ (Flo `. `•—
COUNTY * ,,,,�., .>
a
Plan Review, Inspection, and Permite Fees
Application Number . 17-50041182
-
$100.00 ❑ DRB Major Sub Division Prelim Site Plans $
$200.00 ❑ Explosive Material (90 Days) $ -$
$100.00 ❑ Explosive Materials (72 Hours) $
$100.00 ❑ Fireworks Public Display $ 50.00
$50.00 O Final Inspection $
$35.00 +$2.00 per device ❑ Fire Alarm Testing $
$35.00 +$2.00 per nozzle ❑ Fixed Fire Suppression $
$75.00 ❑ Insecticide Fog/Fumigation $
$100.00 ❑ Pipe Test/UST/AGST $
$50.00 ❑ Plans up to 5000 sq ft $ too.00
$100.00 O Plans 5001 sq ft to 10,000 sq ft
$150.00 ❑ Plans 10,001 sq ft to 25,000 sq ft $
$250.00 ❑ Plans 25,001 sq ft and over $
$35.00 +2.00 per head ❑ Sprinkler Certification Test $
$50.00 ❑ Standpipe Testing
❑ Special Assembly $
$50.00 (ie. amusement buildings,carnivals,fairs)
❑ $
$75.00 Tents/Canopies/Air Supported Structure
❑ $
$100.00 Tank Installation (charge for each tank)
$100.00 ❑ Tank Removal (charge for each tank) $
Total Devices/Heads $ 150.00
Total Cost
Code Enforcement Official Jeff D. Johnson
4/27/2017
yHarnett
H D V R T Y tmnq•ncy s•rnut p+B+rtabent
wwrh++Mtt.++B
Fire Marshal Division
April 27, 2017
Re: Engineered Control Solutions
230 Jarco Dr.
Fuquay-Varina, NC 27526
Application Number 17-50041182
Lee Bevis,
Thank you for submitting the plans for the alterations to Engineered Control Solutions
on Jarco Drive. The plans have been carefully reviewed by a qualified code enforcement
official to examine for compliance with the North Carolina Fire Prevention Code and all
other fire protection regulatory documents. There are some items that were found
during the plan review process that need to be addressed before a final inspection of
the new facility can be given. These items are outlined and described below.
• Comments
o The classroom seating plan submitted and approved by the building
official must be maintained at 30 occupants. A copy of the seating plan
and occupant capacity should also be posted in the classroom.
• 506.1 Knox Box
o A Knox Box is required to be installed on the building. Please see the link
below to order Knox box. Paper order form available upon request.
o https://www.knoxbox.com/store/Knox-Box-3200-Series.cfm
• 505.1 Address Numbers
o The physical address shall be installed on the building so that it is visible
from the approach side contrasting color and a minimum size of 6 inch.
• 906.1 Fire Extinguishers required.
o A minimum 2A1OBC classification of fire extinguisher is required on each
floor and located so that the maximum travel distance to reach an
extinguisher does not exceed 75ft.
o Fire Extinguishers shall be located in approved cabinets along corridors
and hallways.
o All fire extinguishers shall be mounted not higher than 5ft. above the
finished floor and in accordance with NFPA 10.
Harnett ■
' �
COUNTY (' o Emergency SernGsDepumwnt
.4. . r' wwwJ�airetaq
Y
• 1006 Illumination emergency power.
o In the event of power supply failure, an emergency electrical system shall
automatically illuminate corridors, exit enclosures in buildings required to
have two or more exits.
o Emergency lighting required in classroom and adjacent exit.
o Exit aisles from new offices on both first and second floor.
• Comments
o A final fire inspection is required.
o Schedule all fire Inspections through the Fire Marshal's Office.
(910) 893-0743
Thank you again for submitting the plans for the alterations to the Engineered Control
Solutions building. Please review the plans and adhere to any notes and alterations that
were made in addition to the original drawings. These remarks are for the plans that
were submitted and its original intent. These remarks do not apply if the original intent
changes or what was submitted on the above date changes. If you have any questions,
please do not hesitate to call this office.
Sincere
firl C____,
Ct
.Johnson
Deputy Fire Marshal