FM REVIEW SPRINKLER Harnett
(--Th COUNTY * ® 1 Ospe
QUO I/{:T Y �f�1 EMawep Services ,art
Plan Review, Inspection, and Permit Fees
Application Number 17-50041101
$200.00 0 Explosive Material (90 Days) $ -
$100.00 ❑ Explosive Materials (72 Hours) $ -
$100.00 0 Fireworks Public Display $ -
$50.00 E Final Inspection $ -
$35.00 +$2.O0per device ❑ Fire Alarm Testing $ -
$35.00 +$2.00 per nozzle ❑ Fixed Fire Suppression $ -
$75.00 0 Insecticide Fog/Fumigation $ -
$100.00 0 Pipe Test/UST/AGST $ -
$50.00 ❑ Plans up to 5000 sq ft $ -
$100.00 0 Plans 5001 sq ft to 10,000 sq ft $ -
$150.00 E Plans 10,001 sq ft to 25,000 sq ft $ -
$250.00 ❑ Plans 25,001 sq ft and over $ -
$35.00 +2.00 per head EJ Sprinkler Certification Test $ 35.00
$50.00 ❑ Standpipe Testing $ -
❑ Special Assembly
$50.00
(ie.amusement buildings,carnivals,fairs) $ -
$75.00 ❑ Tents/Canopies/Air Supported Structure $ -
$100.00 ❑ Tank Installation (charge for each tank) $ -
$100.00 ❑ Tank Removal (charge for each tank) $ -
26 Total Devices/Heads $ 52.00
Total Cost S 87.00
Code Enforcement Official Rodney Daniels 4/25/2017
HCFM
Office of the Flre Marshal
P.O. Box 370
Lillington, N.C. 27546
(910)493.7580
Permit Certificate
Business Name: CAMPBELL UNIVERSITY SMITH BUILDING
Address: 4150 US 421 S
LILLINGTON, NC 27546
Phone:
The following permit has been issued: Permit No. 17-50041101
Type: 044 Sprinkler System Permit
Issued Date: 04/25/2017
Effective Date: 04/25/2017
Expiration Date: 10/25/2017
This permit certificate has been issued for[ ]construction/[ ]operational purposes located
at the above business location.This permit has been issued and will be enforced in accordance
with section tog of the N.C.State Fire Prevention Code. Please contact our office for any further
questions regarding this permit.
2 �9L��GJ //Z Ili
Inspector: R ne Keith Daniels
Y Date
04/25/2017 Page 1
Harnett
Thrm P,. :,HTY ® Enw•s�rs.wu wr.�••nt
r : ., (FMA r.•nt
Fire Marshal Division
April 25, 2017
Re: Campbell University Smith Hall
4350 US 421
Lillington, NC 27546
Application Number 17-50041101 (Sprinkler Plan Review)
Brett Strickland,
Thank you for submitting the plans for the new Smith Hall 4'h floor sprinkler up fit. The
plans have been carefully reviewed by a qualified code enforcement official to examine
for compliance with the North Carolina Fire Prevention Code and all other fire
protection regulatory documents. There are some items that were found during the
plan review process that need to be addressed before a final inspection of the new
facility can be given. These items are outlined and described below.
• 901.2.1 State of Compliance.
o Before requesting final approval of the installation, where required by the
fire code official, the installing contactor shall furnish a written statement
to the fire code official that the subject fire protection system has been
installed in accordance with the manufacture's specifications and the
appropriate installation standard. Any deviations from the design
standards shall be noted and copies of the approvals for such deviations
shall be attached to the written statement.
o All work shall be performed in accordance with NFPA 13 and the
NCSFC.
• 901.5 Installation acceptance testing.
o All piping and attached appurtenances subjected to system working
pressure shall be hydrostatically tested at 200 psi or 50 psi in excess of the
system working pressure, whichever is greater, and shall maintain that
pressure without loss for 2 hours. This test is required to be witnessed by a
representative from the Harnett County Fire Marshal's Office.
o A contractor's material and test certificate shall be furnished by the
trained representative of Crossroads Fire Protection before final
approval.
Harnett
COUNTY A Emergency
�� _, :�:,. (FAO rys...�ww
wwvhr'rrt.arq
• Notes
o A sprinkler system construction permit is required.
o Please schedule all inspections through the Fire Marshal's Office.
o 910-893-0743
Thank you again for submitting the plans for the Smith Hall 4'h floor sprinkler up fit.
Please review the plans and adhere to any notes and alterations that were made in
addition to the original drawings. These remarks are for the plans that were submitted
and its original intent. These remarks do not apply if the original intent changes or what
was submitted on the above date changes. If you have any questions, please do not
hesitate to call this office.
Sincerely,
Rodney Daniels
Chief Deputy Fire Marshal