Loading...
FM PLAN REVIEW ride Harnett COUNTY apt—A— (T~) u,wyouv sewn apartment Plan Review, Inspection, and Permite Fees Application Number 17-50041218 $100.00 El DRB Major Sub Division Prelim Site Plans $ - $200.00 ❑ Explosive Material (90 Days) $ - $100.00 ❑ Explosive Materials (72 Hours) $ $100.00 ❑ Fireworks Public Display $ - $50.00 E Final Inspection $ 50.00 $35.00 +$2.00 per device ❑ Fire Alarm Testing $ - $35.00 +$2.00 per nozzle ❑ Fixed Fire Suppression $ - $75.00 ❑ Insecticide Fog/Fumigation $ - $100.00 ❑ Pipe Test/UST/AGST _ $50.00 E Plans up to 5000 sq ft $ 5 50.00 $100.00 ❑ Plans 5001 sq ft to 10,000 sq ft $ - $150.00 ❑ Plans 10,001 sq ft to 25,000 sq ft $ - $250.00 ❑ Plans 25,001 sq ft and over5 - $35.00 +2.00 per head ❑ Sprinkler Certification Test $ $50.00 ❑ Standpipe Testing $ - $50.00 ❑ Special Assembly (ie. amusement buildings,carnivals,fairs) $ - $75.00 Tents/Canopies/Air Supported Structure 5 - ID $100.00 Tank Installation (charge for each tank) 5 - $100.00 ❑ Tank Removal (charge for each tank) $ - Total Devices/Heads $ - Total Cost $ 100.00 Code Enforcement Official Jeff D. Johnson 4/27/2017 Harnett COUNTY Emergency Services Mpnrrmnnt ww*'.hrirtt.wp Fire Marshal Division yrI April 27, 2017 /Wr2rs on lnt_{-&t s Re: Kidz Care Pediatrics 1406 5. Main St. Lillington, NC 27546 Application Number 17-50041218 To whom it may concern, Thank you for submitting the plans for the new building. The plans have been carefully reviewed by a qualified code enforcement official to examine for compliance with the North Carolina Fire Prevention Code and all other fire protection regulatory documents. There are some items that were found during the plan review process that need to be addressed before a final inspection of the new facility can be given. These items are outlined and described below. • Comments o The required fire flow for this building is 1500gpm. (3,448sf&Type VB) o Show existing fire hydrant(s) on site plan and submit an amended site plan. • 506.1 Knox Box o A Knox Box is required to be installed on the building. Please see the link below to order Knox box. Paper order form available upon request. o https://www.knoxbox.com/store/Knox-Box-3200-Series.cfm • 505.1 Address Numbers o The physical address shall be installed on the building so that it is visible from the approach side contrasting color and a minimum size of 6 inch. • 906.1 Fire Extinguishers required. o A minimum 2A10BC classification of fire extinguisher is required on each floor and located so that the maximum travel distance to reach an extinguisher does not exceed 75ft. o Fire Extinguishers shall be located in approved cabinets along corridors and hallways. o All fire extinguishers shall be mounted not higher than 5ft. above the finished floor and in accordance with NFPA 10. WEHarnett COUNT,Y M1 * Emergency Unites Dna/tenant wwwlitrmtt.wy • 1006 Illumination emergency power. o In the event of power supply failure, an emergency electrical system shall automatically illuminate corridors, exit enclosures in buildings required to have two or more exits.o Install emergency light/exit combinations in corridor, per life safety plan. o Install directional exit signs on back corridor per the life safety plan. • 1021.2 Single Exits o A second means of egress is required where travel distance exceeds 75 ft. (See table 1021.2) Resubmit plans with an additional remote exit. • Comments o A final fire inspection is required. o Schedule all fire inspections through the Fire Marshal's Office. (910)893-0743 Thank you again for submitting the plans for the new building. Please review the plans and adhere to any notes and alterations that were made in addition to the original drawings. These remarks are for the plans that were submitted and its original intent. These remarks do not apply if the original intent changes or what was submitted on the above date changes. If you have any questions, please do not hesitate to call this office. Sincerely, ,J/n Jeff D. Johnson Deputy Fire Marshal