Loading...
Boon Edam, Office Addition Fire Marshal Division March 8, 2017 Mr. John Kutcha 8708 Penny Road Raleigh, NC 27606 Re: Boon Edam 402 McKinney Parkway Lillington, NC 27546 Application Number 17-50040796 Mr. Kutcha, Thank you for submitting the plans for the office addition. The plans have been carefully reviewed by a qualified code enforcement official to examine for compliance with the North Carolina Fire Prevention Code and all other fire protection regulatory documents. There are some items that were found during the plan review process that need to be addressed before a final inspection of the new facility can be given. These items are outlined and described below. 906.1 Fire Extinguishers Minimum of (1) 2A10:BC fire extinguisher shall be installed per 75’ distance of travel. All Fire extinguisher shall be properly mounted and tagged by a fire extinguisher company. 1006.1 Means of Egress Illumination The means of egress, including the exit discharge, shall be illuminated at all time the building space is served by the means of egress is occupied. Means of egress consist of three separate and distinct parts: the exit access, the exit and the exit discharge. The means of egress illumination shall not be less than 1 foot-candle at the walking surface. 901.2.1 State of Compliance. Before requesting final approval of the installation, where required by the fire code official, the installing contactor shall furnish a written statement to the fire code official that the subject fire protection system has been installed in accordance with the manufacture’s specifications and the appropriate installation standard. Any deviations from the design standards shall be noted and copies of the approvals for such deviations shall be attached to the written statement. All work shall be performed in accordance with NFPA 13 and the NCSFC. 901.5 Installation acceptance testing. Contractor’s material and test certificate shall be furnished by the trained representative of BFPE Fire Protection before final approval. Notes A sprinkler system construction permit is required. An above ceiling inspection is required. Please schedule all inspections through the Fire Marshal’s Office. (919)893-0743 Thank you again for submitting the plans for the office addition. Please review the plans and adhere to any notes and alterations that were made in addition to the original drawings. These remarks are for the plans that were submitted and its original intent. These remarks do not apply if the original intent changes or what was submitted on the above date changes. If you have any questions, please do not hesitate to call this office. Sincerely, Rodney Daniels Chief Deputy Fire Marshal