FM PLAN REVIEW 1C-5002_4008
P.O. Box 14747 t: 919.433.5300
Research Triangle Park, NC 27709 f: 919.433.5301
www.perklnswili.com
PERKINS
+WILL
Transmittal
To: TJ McLamb Date: December 3, 2010
Chief Deputy Fire Marshall
Harnett County
108 E Front Street
Lillington, NC 27546
From: Sean Murphy Project Name: Harnett Health System
Subject: Construction Documents Project No: 830147.000
Sent Via: Ground Delivery
Qty. Dated Item
1 12/03/10 Construction Document Comments and Responses
1 12/03/10 Specifications Vol 1 and Vol 2
1 12/03/10 Full Size Construction Documents Vol 1 and Vol 2
•
P:\RTP \830147 -000 Harnett Health Hospital \DOCS\ 03.0 - ClientArchCorresp \Tr - Harnett
FM- CD.docx
NORTH AMERICA 1 ASIA I MIDDLE EAST 1 AFRICA I EUROPE
I 0 5002a 0(c
�. r xt Harnett r.
e i , :� C O U N Y Y FAO emergency Parkes Department
� '..FirS ar ±R LAkW_3MP, www.hern•tt,org
Y
Fire Marshal Division
October 5, 2010
Sean Murphy, AIA
Perkins + Will
P.O. Box 14747
Research Triangle Park, NC 27709
Harnett Health System
Brightwater Park
Lillington, NC 27546
Application Number 10- 50024068
Mr. Murphy,
Thank you for submitting the plans for the Harnett Health System. The plans have been
carefully reviewed by a qualified code enforcement official to examine for full
compliance with the North Carolina Fire Prevention Code and all other fire protection
regulatory documents. There are some items that were found during the plan review
process that need to be addressed before a final inspection of the new facility can be
given. These items are outlined and described below.
• 906.1 Fire Extinguishers
o Fire Extinguisher to be added in the Administration area near room 1505
Response: Fire Extinguisher has been added in the Waiting area of Administration.
o 80 B:C fire extinguisher to be placed in service near the Helipad
Response: 80 B:C Fire Extinguisher has been added at the helipad.
• 505.1 Physical Address
o The physical address of the building shall be posted in a conspicuous place
so that it can be seen on approach from the road, access road, and /or
parking lot.
o The numbers used to make up the physical address shall be at least 5
inches in height.
` U ';' Y 'Emery arcy3•rricer F7apartmaot
lost
'* k�3 10 Et Pr.: PArt � ... - .. .. LE iv www.baroatt.azg
Response: The address has been added to the sign in 5" letters. See
landscape drawing L -402 and L -405 for signage details.
• Duct Detectors
o l floor Area A near room 1302 has not relay associated with the Duct
detector Response:
RESPONSE: All duct detectors are now being provided with a relay in room
1302.
• 903 Automatic Sprinkler Systems
Rooms such as Telecommunications, Electrical, IT Server rooms shall be
provided with coverage from Automatic Sprinkler System
RESPONSE: Please refer to the updated fire protection drawings. General
note 1 states all work shall be fully sprinklered in accordance with NFPA 13,
refer to specifications for performance requirements. General note 2 states
all interior areas /rooms shall be sprinklered, whether heads are shown or
not. Areas where heads are shown are for coordination only. Sprinkler
systems shall be design and submittal approvals as specified in division
210000.
• 901.2 Fire Sprinkler Construction Drawings
Submit fire sprinkler construction drawings and hydraulic calculations for the
system.
Water Flow data may be obtained from Lillington Fire Dept @ 910 - 893 -9842
RESPONSE: This is a performance based design and spec. Once the sprinkler
contract has been awarded, the contractor will submit sprinkler construction
drawings and calculations for their review.
• 907 Fire Alarm System
o The following items need to be addressed:
r.)-s Harnett
COUNTY •• ■a imaagwuy
(( wvnthxnatt.arg
1 Floor Area A
No strobe in bathroom Rm #1316 Compare #1231
RESPONSE: Strobe has been added.
No strobe in bathroom Rm #1315 Compare #1231
RESPONSE: Strobe has been added.
No strobe in bathroom Rm #1213B Compare #1231
RESPONSE: Strobe has been added.
DD has no RAL near Rm # 1302
RESPONSE: Strobe has been added.
No smoke in Janitor Closet Rm # 1221 Compare # 1334, 1234
RESPONSE: Strobe has been added.
1" Floor Area B
No heat detector in vestibule Rm # 1100B Compare # 1000A
RESPONSE: Heat detector in 1000A is designed because one is required near the
Remote Aunnicator panel. Detectors are not to be installed in the other vestibules.
1" Floor Area C
No strobe in bathroom Rm # 1608 Compare # 1019
RESPONSE: Strobe has been added.
No strobe in bathroom Rm # 1613 Compare # 1018
RESPONSE: Strobe has been added.
No smoke in Janitor closet Rm #1625 Compare #1722
RESPONSE: Smoke detector has been added.
No smoke in Janitor closet Rm #1100C Compare #1722
H arnett
"x r COUNTY tmng {Y 5arvxaa, C.topartment
"P NuR1, E. kG. N:A t vera• atnettmrg
RESPONSE: Smoke detector has been added.
No smoke in Janitor closet Rm #1021 Compare #1722
RESPONSE: Smoke detector has been added.
No strobe in bathroom Rm #1706 Compare #1701
RESPONSE: Smoke detector has been added.
No smoke in MEDS Rm # 1627 Compare #2150
RESPONSE: Smoke detector has been added.
2 " Floor Area A
No smoke in MEDS Rm # 2141 Compare #2150
RESPONSE: Smoke detector has been added.
No strobe in bathroom Rm # 2127 Compare #2113
RESPONSE: Strobe detector has been added.
No hold open devices in this area Compare Area C
RESPONSE: Door hold opens have been added.
2 " Floor Area B
No smoke in Stair #1 Compare Stair # 2
RESPONSE: Smoke detector has been added.
2 " Floor Area C
No strobe in bathroom Rm # 2217 Compare # 2248
RESPONSE: Strobe has been added.
Harnett
'rz• t ' t r A . C O UN T Y Ema
O V I _ . i t i\ gaicy Services bat6no
apnt
� :`' axsR*" X 0 0.T3iCA B i. !.'All \ \ - -^^— www baa na t6arg ,
No smoke in Janitor's closet Rm # 2216 Compare #1722
RESPONSE: Smoke detector has been added
No smoke in MEDS Rm 2244 Compare #2150
RESPONSE: Smoke detector has been added.
Signage
Signage package shall include all fire protections systems, FACP, RISER ROOM, and
FDC
Thank you again for submitting the plans for the Hamett Health System. Please review
the plans and adhere to any notes and alterations that were made in addition to the
original drawings. These remarks are for the plans that were submitted and its original
intent. These remarks do not apply if the original intent changes or what was submitted
on the above date changes. If you have any questions, please do not hesitate to call this
office
Again, thank you and we look forward to working with you during the construction
period!
Sincerely,
7ed4 foe 711e4 m6
Teddy Joe Mclamb, CFI