FM REVIEW Harnett
a c o u w r r A (Flo Emergency S Senecas Department
RC1RTf1 iAfl OLSNA Y wirmharnntt.Gag
Plan Review, Inspection and Permit Fees
Application Number 10- 50024800
$150.00 E Explosive Mat. (90 Days)
$ 75.00 [ Explosive Mat. (72 Hrs)
$ 25.00 ❑ Fireworks Public Display
$ 35.00 ® Final Inspection
$ 35.00 +2.00 per device ❑ Fire Alarm Testing
$ 35.00 + 2.00 per nozzle ❑ Fixed Fire Suppression
$ 25.00 ❑ Insecticide Fog/Fumigation
$ 50.00 ❑ Pipe Test/UST /AGST
$ 50.00 ® Plans up to 5000 ft
$100.00 n Plans 5001 ft to 10,000 ft
$150.00 ❑ Plans 10,001 ft to 25,000 ft
5250.00 ❑ Plans 25,001 ft and over
$ 35.00 + 2.00 per Head ❑ Sprinkler Certification Test
$ 35.00 E Standpipe Testing
$ 25.00 ❑ Special Assembly
$ 25.00 ❑ Temporary Kiosks/Displays
$ 25.00 _ Tents, Canopies, Air Supported
$ 50.00 ❑ Tank Installation (charge for each tank)
$ 50.00 ❑ Tank Removal (charge for each tank)
$ 85.00 Total
Total device/heads
Teddy Joe McLamb 09/13/10
Code Enforcement Official Date
^C 0 U N e T Y
NORTH CAROLINA A. it M _ AA te► ^ Emergency Services Department
%
www.hamep.org
' 200 N. 13th Street
Suite 19
September 13, 2010 Erwin, NC 28339
Mailing Address:
Robert Davis PO Box 370
P.O. Box 1216 ul;ngmn, B x 3
Broadway, NC 27505 ph: 910-893 -7580
fax: 910- 893 -5025
Old Fashion Independent Baptist Church
2156 Rosser Pittman Rd
Broadway, NC 27505
Application Number 10- 500248
Mr. Davis, -
u Thank yo
for carefully revi plans for the wed by a qualified ifred code enforcement ement offc ial to Church.
examine The
plans have been carefully
pr t e c l on regulatory North Carolina
lato y documents.Therare Fire
ome items that Code
ere ound the plan
review regu rY
rew process that need to be addressed before a final inspection of the new facility can
be given. These items are outlined and described below.
• 906.1 Fire Extinguishers
o Fire extinguishers shall be placed in approved locat as drawn by the
code enforcement official on the approved
o The fire extinguishers provided shall have a minimum rating of 2A 5B:C
and shall not be installed higher than 5 feet above the finished floor
o As noted on plans
• 506.1 Knox Box
o A secure key box shall be installed on the new building that houses all
keys to all the doors within the building in which the fire department
would need access to in the event ef
o Knox Box ID stickers shall be placed on all exterior doors in which entry
to the building may be gained.
o The box shall be mounted not to exceed 48 — 60 inches in height.
o An authorized order form is included with this letter.
strong roots • new growth
• 505.1 Physical Address
o The physical address of the building shall be posted in a conspicuous
place so that it can be seen on approach from the road, access road, and/or
parking lot.
o The numbers used to make up the physical address shall be at least 5
inches in height
• 1006.1 illumination required.
o The means of egress, including the exit discharge, shall be illuminated at
all times the building space served by the means of egress is occupied
Thank you again for submitting the plans for the Old Fashion Independent Baptist
Church. Please review the plans and adhere to any notes and alterations that were made
in addition to the original drawings. These remarks are for the plans that were submitted
and its original intent. These remarks do not apply if the original intent changes or what
was submitted on the above date changes. If you have any questions, please do not
hesitate to call this office.
Again, thank you and we look forward to working with you during the construction
period!
Thank You,
(, fI
T.J. McLamb, CFI
Chief Deputy Fire Marshal