Loading...
FM REVIEW f ib Harnett C O U N T Y A tFMy Emw9�Y Senna,DcWrbcont -- NORTiI {hpp ;NA �► vnws Plan Review, Inspection and Permit Fees Application Number 10- 50024633 $150.00 n Explosive Mat. (90 Days) $ 75.00 n Explosive Mat. (72 Hrs) $ 25.00 n Fireworks Public Display $ 35.00 Z Final Inspection $ 35.00 +2.00 per device Fire Alarm Testing $ 35.00 + 2.00 per nozzle ❑ Fixed Fire Suppression $ 25.00 El Insecticide Fog/Fumigation $ 50.00 F Pipe Test/UST /AGST $ 50.00 Z Plans up to 5000 ft $100.00 E Plans 5001 ft to 10,000 ft $150.00 n Plans 10,001 ft to 25,000 ft $250.00 ❑ Plans 25,001 fl and over $ 35.00 + 2.00 per Head ❑ Sprinkler Certification Test $ 35.00 E Standpipe Testing $ 25.00 [ Special Assembly $ 25.00 Temporary Kiosks/Displays $ 25.00 n _ Tents, Canopies, Air Supported $ 50.00 ❑ Tank Installation (charge for each tank) $ 50.00 ❑ Tank Removal (charge for each tank) $ 85.00 Total Total device/heads Teddy Joe McLamb 06/19/10 Code Enforcement Official Date Harnett , C O U N T Y w Emergency Services Department FF NORTH CAROLINA SVAL trovi www.hamea.org 200 N. 13th Street Suite 19 Ervin, NC 28339 June 19, 2010 Mailing Address: Harry Lee PO Box 370 353 A East Williams St ulOng an, NO 27546 Angier, NC 27501 ph'. 910- 893 -7580 fax: 910 -893 -5025 L Nails 333 N Raleigh St suite F Angier, NC 27501 Application Number 10- 50024633 Mr. Lee, Thank you for submitting the plans for the L Nail. The plans have been carefully reviewed by a qualified code enforcement official to examine for full compliance with the North Carolina Fire Prevention Code and all other fire protection regulatory documents. There are some items that were found during the plan review process that need to be addressed before a final inspection of the new facility can be given. These items are outlined and described below. • 1003.2.11 Means of egress illumination. o The means of egress, including the exit discharge, shall be illuminated at all times the building space served by the means of egress is occupied o Bathrooms to have emergency lights installed. • 1003.2.11.1 Illumination level o The means of egress illumination level shall not be less than 1 foot- candle (11 lux) at the floor level • 1003.2.11.2 Illumination emergency power o The power supply for means of egress illumination shall normally be provided by the premise's electrical supply. o In the event of power supply failure, an emergency system shall automatically illuminate all of the following areas: strong roots • new growth o Exit access corridors, passageways, and aisles in rooms and spaces which require two or more means of egress. o Exit access corridors and exit stairways located in buildings required to have two or more exits. o Interior exit discharge elements, as permitted in Section 1006.1, in buildings required to have two or more exits. o The portion of the exterior exit discharge immediately adjacent to exit discharge doorways in buildings required to have two or more exits. The emergency power system shall provide power for a duration of not less than 90 minutes and shall consist of storage batteries, unit equipment or an on -site generator. The installation of the emergency power system shall be in accordance with Section 604. • Emergency Light to be installed as noted on plans • Exit lights to be illuminated at all times and have battery back -up • 906.1 Fire Extinguishers o Fire extinguishers shall be placed in approved locations as drawn by the code enforcement official on the approved plans. o The fire extinguishers provided shall have a minimum rating of 2A 5B:C and shall not be installed higher than 5 feet above the finished floor • 506.1 Knox Box o A secure key box shall be installed on the new building that houses all keys to all the doors within the building in which the fire department would need access to in the event of an emergency o Box to be placed on the front of the building where the fire department would access and to be mounted no higher than 5' • 505.1 Physical Address o The physical address of the building shall be posted in a conspicuous place so that it can be seen on approach from the road, access road, and/or parking lot. o The numbers used to make up the physical address shall be at least 5 inches in height. Thank you again for submitting the plans for the L Nail. Please review the plans and adhere to any notes and alterations that were made in addition to the original drawings. These remarks are for the plans that were submitted and its original intent. These remarks do not apply if the original intent changes or what was submitted on the above date changes. If you have any questions, please do not hesitate to call this office. Again, thank you and we look forward to working with you during the construction period! Sincerely, cere C.ia' Teddy I McLamb, CFI Chief Deputy Fire Marshal