INSPECTIONS PREPARED 1/14/10, 13:58:51 INSPECTION TICKET PAGE 40
Harnett County INSPECTOR: IVR DATE 1/15/10
ADDRESS . : 32 YANCEY CT SUBDIV: OVERHILLS CREEK SCT 7 92LOTS
CONTRACTOR : WELLCO CONTRACTORS, INC. PHONE : (910) 436 -3131
OWNER . . : WELLCO CONTRACTORS INC PHONE : (910) 436 -3131
PARCEL . . : 01- 0514 -03- -0006- -40-
APPL NUMBER: 09- 50023391 CP NEW RESIDENTIAL (SFD)
DIRECTIONS : T /S: 12/09/2009 11:33 AM RDCONTE - --
32 YANCEY DRIVE / OVERHILLS CREEK #550
TAKE 2105, T/R ON RAY ROAD. T/R ON
OVERHILLS ROAD. T/R ON LENOIR. T/L ON
CALDWELL. TURN ONTO YANCEY
***SOUTH RIVER***
STRUCTURE: 000 000 55X33 SLAB 3BD /2.5BA W /GAR & DECK
FLOOD ZONE - FLOOD ZONE X
# BEDROOMS 3.00 PROPOSED USE - SFD
SEPTIC - EXISTING' • SEWER WATER SUPPLY • COUNTY
PERMIT: CPSF 00 CP * SFD
REQUESTED INSP DESCRIPTION
TYP /SQ COMPLETED RESULT RESULTS /COMMENTS
B101 01 1/15/10 TI R *BLDG FOOTING / TEMP SVC POLE TIME: 17:00 VRU #: 001871375
T /S: 01/14/2010 01:21 PM RDCONTE
FOOTING
COMMENTS AND NOTES
PREPARED 1/20/10, 14:06:17 INSPECTION. TICKET PAGE 33
Harnett County INSPECTOR: IVR DATE 1/21/10
,ADDRESS . : 32 YANCEY CT SUBDIV: OVERHILLS CREEK SCT 92LOTS
CONTRACTOR : WELLCO CONTRACTORS, INC. PHONE : (910) 436 -3131
OWNER . . : WELLCO CONTRACTORS INC PHONE : (910) 436 -3131
PARCEL . . : 01- 0514 -03- -0006- -40-
APPL NUMBER: 09- 50023391 CP NEW.RESIDENTIAL (SFD)
DIRECTIONS T /S: 12/09/2009 11:33 AM RDCONTE - --
32 YANCEY DRIVE / OVERHILLS CREEK #550
TAKE 2105, T/R ON RAY ROAD. T/R ON
OVERHILLS ROAD. T/R ON LENOIR. T/L ON
CALDWELL. TURN ONTO YANCEY
** *SOUTH RIVER * **
STRUCTURE: 000,000 55X33 SLAB 3BD /2.5BA W /GAR.& DECK
FLOOD ZONE FLOOD ZONE X
# BEDROOMS . . . . . : 3.00 PROPOSED USE SFD
SEPTIC - EXISTING' SEWER WATER SUPPLY • COUNTY
PERMIT: CPSF 00 CP * SFD
REQUESTED INSP DESCRIPTION
TYP /SQ COMPLETED RESULT RESULTS /COMMENTS
B101 01 1/15/10 JH R *BLDG FOOTING / TEMP SVC POLE TIME: 17:00 VRU #: 001871375
1/15/10 AP T /S: 01/14/2010 01:21 PM RDCONTE
FOOTING
no t -pole
B103 01 1/21/10 T R *BLDG FOUND & TEMP SVC POLE VRU #: 001873627
J,,2! - 10
CO ENTS AND NOTES
PREPARED 1/28/10, 13:59:22 INSPECTION TICKET PAGE 27
Harnett County INSPECTOR: IVR DATE 1/29/10
ADDRESS . : 32 YANCEY CT SUBDIV: OVERHILLS CREEK SCT 7 92LOTS
CONTRACTOR : WELLCO CONTRACTORS, INC. PHONE : (910) 436 -3131
OWNER . . : WELLCO CONTRACTORS INC PHONE : (910) 436 -3131
PARCEL . . : 01- 0514 -03- -0006- -40-
APPL NUMBER: 09- 50023391 CP NEW RESIDENTIAL (SFD)
DIRECTIONS : T /S: 12/09/2009 11:33 AM RDCONTE - --
32 YANCEY DRIVE / OVERHILLS CREEK #550
TAKE 2105, T/R ON RAY ROAD. T/R ON
OVERHILLS ROAD. T/R ON LENOIR. T/L ON
CALDWELL. TURN ONTO YANCEY
** *SOUTH RIVER * **
STRUCTURE: 000 000 55X33 SLAB 3BD /2.5BA W /GAR & DECK
FLOOD ZONE • FLOOD ZONE X
# BEDROOMS 3.00 PROPOSED USE • SFD
SEPTIC - EXISTING' • SEWER WATER SUPPLY • COUNTY
PERMIT: CPSF 00 CP * SFD
REQUESTED INSP DESCRIPTION
TYP /SQ COMPLETED RESULT RESULTS /COMMENTS
B101 01 1/15/10 JH R *BLDG FOOTING / TEMP SVC POLE TIME: 17:00 VRU #: 001871375
1/15/10 AP T /S: 01/14/2010 01:21 PM RDCONTE
FOOTING
no t -pole
B103 01 1/21/10 JH R *BLDG FOUND & TEMP SVC POLE VRU #: 001873627
1/21/10 AP t -pole passed
A814 01 1/26/10 FB ADDRESS CONFIRMATION VRU #: 001873636
1/28/10 AP T /S: 01/28/2010 11:09 AN FBURGESS
32 YANCEY CT SPRING LAKE,NC 28390 LOT 550
P309 01 1/2,9/10 TI _ R *PLUMB UNDER SLAB VRU #: 001877632
COMMENTS AND NOTES
PREPARED 1/29/10, 13:59:28 INSPECTION TICKET PAGE 21
Harnett County INSPECTOR: IVR DATE 2/01/10
ADDRESS . : 32 YANCEY CT SUBDIV: OVERHILLS CREEK SCT 7 92LOTS
CONTRACTOR : WELLCO CONTRACTORS, INC. PHONE : (910) 436 -3131
OWNER . . : WELLCO CONTRACTORS INC PHONE : (910) 436 -3131
PARCEL . . : 01- 0514 -03- -0006- -40-
APPL NUMBER: 09- 50023391 CP NEW RESIDENTIAL (SFD)
DIRECTIONS : T /S: 12/09/2009 11:33 AM RDCONTE - --
32 YANCEY DRIVE / OVERHILLS CREEK #550
TAKE 2105, T/R RAY ROAD. T/R ON
OVERHILLS ROAD. T/R ON LENOIR. T/L ON
CALDWELL. TURN ONTO YANCEY
** *SOUTH RIVER * **
STRUCTURE: 000 000 55X33 SLAB 3BD /2.5BA W /GAR & DECK
FLOOD ZONE • FLOOD ZONE X
# BEDROOMS 3.00 PROPOSED USE • SFD
SEPTIC - EXISTING' • SEWER WATER SUPPLY • COUNTY
PERMIT: CPSF 00 CP * SFD
REQUESTED INSP DESCRIPTION
TYP /SQ COMPLETED RESULT RESULTS /COMMENTS
B101 01 1/15/10 JH R *BLDG FOOTING / TEMP SVC POLE TIME: 17:00 VRU #: 001871375
1/15/10 AP T /S: 01/14/2010 01:21 PM RDCONTE
FOOTING
no t -pole
B103 01 1/21/10 JH R *BLDG FOUND & TEMP SVC POLE VRU #: 001873627
1/21/10 AP t -pole passed
A814 01 1/26/10 FS ADDRESS CONFIRMATION VRU #: 001873636
1/28/10 AP T /S: 01/28/2010 11:09 AM FBURGESS
32 YANCEY CT SPRING LAKE,NC 28390 LOT 550
P309 01 1/29/10 BS R *PLUMB UNDER SLAB VRU #: 001877632
1/29/10 AP T /S: January 29, 2010 09:37 AM BSUTTON
B111 01 2/01//10 bi . R *BLDG SLAB INSP VRU #: 001878392
1/ r/ COMMENTS AND NOTES
PREPARED 2/03/10, 13:58:02 INSPECTION TICKET PAGE 24
Harnett County INSPECTOR: IVR DATE 2/04/10
ADDRESS 32 YANCEY CT SUBDIV: OVERHILLS CREEK SCT 7 92LOTS
CONTRACTaR`: WELLCO CONTRACTORS, INC. PHONE : (910) 436 -3131
OWNER . . : WELLCO CONTRACTORS INC PHONE : (910) 436 -3131
PARCEL . . : 01- 0514 -03- -0006- -40-
APPL NUMBER: 09- 50023391 CP NEW RESIDENTIAL (SFD)
DIRECTIONS : T /S: 12/09/2009 11:33 AM RDCONTE - --
32 YANCEY DRIVE / OVERHILLS CREEK #550
TAKE 210S, T/R ON RAY ROAD. T/R ON
OVERHILLS ROAD. T/R ON LENOIR. T/L ON
CALDWELL, TURN ONTO YANCEY
** *SOUTH RIVER * **
STRUCTURE: 000 000 55X33 SLAB 3BD /2.5BA W /GAR & DECK
FLOOD ZONE • FLOOD ZONE X
# BEDROOMS 3.00 PROPOSED USE • SFD
SEPTIC - EXISTING' • SEWER WATER SUPPLY COUNTY
PERMIT: CPSP 00 CP * SFD
REQUESTED INSP DESCRIPTION
TYP /SQ COMPLETED RESULT RESULTS /COMMENTS
B101 01 1/15/10 JH R *BLDG FOOTING / TEMP SVC POLE TIME: 17:00 VRU #: 001871375
1/15/10 AP T /S: 01/14/2010 01:21 PM RDCONTE
FOOTING
no t -pole
B103 01 1/21/10 JH R *BLDG FOUND & TEMP SVC POLE VRU #: 001873627
1/21/10 AP t -pole passed
A814 01 1/26/10 FB ADDRESS CONFIRMATION VRU #: 001873636
1/28/10 AP T /S: 01/28/2010 11:09 AM FBURGESS
32 YANCEY CT SPRING LAKE,NC 28390 LOT 550
P309 01 1/29/10 BS R *PLUMB UNDER SLAB VRU #: 001877632
1/29/10 AP T /S: January 29, 2010 09:37 AM BSUTTON
3111 01 2/01/10 + R *BLDG SLAB INSP VRU #: 001878392
2/02/10 DA 1. Floor not completely covered in plastic.
2. Slab must be insulated or res check 4.0 or greater needed
T /S: 02/02/2010 10:07 AM DETAYLOR
3111 02 2/04/10 TI R *BLDG SLAB INSP VRU #:.001879113
COMMENTS AND NOTES
t 1
i if
0 Generated by REScheck -Web Software
Compliance Certificate
Project Title: Various Lots
Energy Code: 2006 IRC
Location: Harnett County, North Carolina
Construction Type: Single Family
Glazing Area Percentage: 9%
Heating Degree Days: 3499
Climate Zone: 4
Construction Site: Owner /Agent: Designer /Contractor:
North Carolina North Carolina Ace Construction
Spring Lake, North Carolina
Corn Hance= asses.... -- --- tea»—,- — '" _„ ..... ,Th''..
Compliance: Maximum UA: 508 Your UA 397
.._..
Gross . Cavity Cont , Glazing T, UA
Assembly • Area or R -Value R -Value or Door
Ceiling: Flat or Scissor Truss 1350 38.0 38.0 19
Wall: Wood Frame, 18in. o.c. 3029 13.0 13.0 130
Window: Vinyl Frame, 2 Pane we Low-E 218 0.350 76
Door: Solid 18 0.380 7
Door: Solid 33 0.380 13
Door: Glass 42 0.200 8
Floor: All -Wood Joist/Truss Over Uncond. Space 436 19.0 19.0 11
Floor. All -Wood Joist/Truss Over Uncond. Space 31 19.0 19.0 1
Floor. Unheated Slab-On -Grade 127 0.0 132
Insulation depth: 0.0'
Compliance Statement: The proposed building design described here is consistent with - building plans, spec • - Lions, and other
calculations submitted with the permit application. The proposed building has bee •e 'ened a 200; - C requirements in
REScheck -Web and to comply with the mandatory requirements e• n the ' • c . ck Ins; f'; heck - .
t
Ili t `/ _ ,✓ cr.. d
N ame - rs j,y_rnt of f�nk5 i, r- P / Date
Project Notes: K,J4 '
The Cape Plan
•
Project Tide: Various Lots Report date: 02/03/10
Data filename: Page 1 of 3
ni t 2006 9RC Energy
Efficiency Certificate
Insul Rating - � .,_.._. `" °""""""'�' Value``""""`"'"'°
Ceiling 1 Roof 78.00
Wall 28.00
Floor 1 Foundation 38.00
Ductwork (unconditioned spaces): _
Glass. & =Door-Rating.,—. --:- _ ; Factor.......,wSHGC....
Window 0.35 1.00
Door 0.20 NA
Heating Cooling Equipment ': Efficiency
Heating System:
Cooling System
Water Heater i
Name: /. t���— Date:
Comma i f s/ /`�/� a' 5��
C j
Generated by REScheck -Web Software
inspection Checklist
Ceilings:
❑ Ceiling: Flat or Scissor Truss, R38.0 cavity + R -38.0 continuous insulation
Comments:
Above - Grade Wails:
❑ Wall: Wood Frame, 16in. o.c., R -13.0 cavity + R -13.0 continuous insulation
Comments:
Windows:
❑ Window: Vinyl Frame, 2 Pane w/ Low -E, U- factor. 0.350
For windows without labeled U- factors, describe features:
#Panes _ Frame Type Thermal Break? — Yes _ No
Comments:
Note: Up to 15 sq.ft. of glazed fenestration per dwelling is exempt from U -factor and SHGC requirements.
Doors:
❑ Door. Solid, U- factor: 0.380
Comments:
❑ Door: Solid, U- factor: 0.380
Comments:
❑ Door: Glass, U- factor. 0.200
Comments:
Floors:
❑ Floor: All -Wood Joist/Truss Over Uncond. Space, R -19.0 cavity + R -19.0 continuous Insulation
Comments:
Floor insulation is Installed in permanent contact with the underside of the subfloor decking.
❑ Floor: All -Wood Joist/Truss Over Uncond. Space, R -19.0 cavity + R -19.0 continuous insulation
Comments:
Floor insulation is Installed In permanent contact with the underside of the subfloor decking.
❑ Floor: Unheated Slab-On-Grade, R -0 (uninsulated)
Comments:
Air Leakage:
❑ Joints, penetrations, and all other such openings in the building envelope that are sources of alr leakage are sealed.
❑ Recessed lights are either 1) Type IC rated with enclosures sealed /gasketed against leaks to the ceiling, or 2) Type IC rated and ASTM
E283 labeled, or 3) installed inside an air -tight assembly with a 0.5" clearance from combustible materials and a 3" clearance from
insulation.
Materials Identification and Installation:
❑ Materials and equipment are installed in accordance with the manufacturer's installation instructions.
❑ Insulation is installed in substantial contact with the surface being insulated and in a manner that achieves the rated R-value.
❑ Materials and equipment are identified so that compliance can be determined.
❑ Manufacturer manuals for all installed heating and cooling equipment and service water heating equipment have been provided.
❑ Insulation R- values and glazing U -factors are clearly marked on the building plans or specifications.
Duet Insulation:
❑ Ducts in unconditioned spaces or outside the building are Insulated to at least R-8.
Project Title: Various Lots Report date: 02/03/10
Data filename: Page 2 of 3
D Ducts in floor trusses above unconditioned spaces or above the outdoors are insulated to at least R -6.
Duct Construction:
O Air handlers, filter boxes, and duct connections to flanges of air distribution system equipment or sheet metal fittings are sealed and
mechanically fastened.
0 All joints, seams, and connections are made substantially airtight with tapes, gasketing, mastics (adhesives) or other approved closure
systems. Tapes and mastics are rated UL 181A or UL 181B.
D Building framing cavities are not used as supply ducts.
• Automatic or gravity dampers are installed on all outdoor air intakes and exhausts.
o Additional requirements for tape sealing and metal duct crimping are included by an inspection for compliance with the International
Mechanical Code.
Temperature Controls:
Thermostats exist for each separate HVAC system. A manual or automatic means to partially restrict or shut off the heating and /or
cooling input to each zone or floor is provided.
Circulating Service Hot Water Systems:
O Circulating service hot water pipes are insulated to R -2.
• Circulating service hot water systems include an automatic or accessible manual switch to tum off the circulating pump when the
system is not In use.
Certificate:
• A permanent certificate Is provided on or in the electrical distribution panel listing the predominant insulation R- values; window
U- factors; type and efficiency of space - conditioning and water heating equipment.
NOTES TO FIELD: (Building Department Use Only)
ProjectTitle :- VariousLots ..- .-- _.Report . date.02/03/10
Data filename: Page 3 of 3
•
PREPARED 3/08/10, 13:58:54 INSPECTION TICKET PAGE 34
Harnett County INSPECTOR: IVR DATE 3/09/10
ADDRESS . :. 32 YANCEY CT SUBDIV: OVERHILLS CREEK SCT 7 92LOTS
CONTRACTOR : WELLCO CONTRACTORS, INC. PHONE : (910) 436 -3131
OWNER . : WELLCO CONTRACTORS INC PHONE : (910) 436 -3131
PARCEL . . : 01- 0514 -03- -0006- -40-
APPL NUMBER: 09- 50023391 CP NEW RESIDENTIAL (SFD)
DIRECTIONS : T /S: 12/09/2009 11:33 AM RDCONTE - --
32 YANCEY DRIVE / OVERHILLS CREEK #550
TAKE 210S, T/R ON RAY ROAD. T/R ON
OVERHILLS ROAD. T/R ON LENOIR. T/L ON
CALDWELL. TURN ONTO YANCEY
** *SOUTH RIVER * **
STRUCTURE: 000 000 55X33 SLAB 3BD /2.5BA W /GAR & DECK
FLOOD ZONE FLOOD ZONE X
# BEDROOMS 3.00 PROPOSED USE • SFD
SEPTIC - EXISTING' - SEWER WATER SUPPLY COUNTY
PERMIT: CPSF 00 CP * SFD
REQUESTED INSP DESCRIPTION
TYP /SQ COMPLETED RESULT RESULTS /COMMENTS
B101 01 1/15/10 JH R *BLDG FOOTING / TEMP SVC POLE TIME: 17:00 VRU #: 001871375
1/15/10 AP T /S: 01/14/2010 01:21 PM RDCONTE
FOOTING
no t -pole
B103 01 1/21/10 JH R *BLDG FOUND & TEMP SVC POLE VRU #: 001873627
1/21/10 AP t -pole passed
A814 01 1/26/10 FB ADDRESS CONFIRMATION VRU #: 001873636
1/28/10 AP T /S: 01/28/2010 11:09 AM FBURGESS
32 YANCEY CT SPRING LAKE,NC 28390 LOT 550
P309 01 1/29/10 BS R *PLUMB UNDER SLAB VRU #: 001877632
1/29/10 AP T /S: January 29, 2010 09:37 AM BSUTTON
Bill 01 2/01/10 DT R *BLDG SLAB INSP VRU #: 001878392
2/02/10 DA 1. Floor not completely covered in plastic.
2. Slab must be insulated or res check 4.0 or greater needed
T /S: 02/02/2010 10:07 AM DETAYLOR
B111 02 2/04/10 DT R *BLDG SLAB INSP VRU #: 001879113
2/04/10 AP
R427 01 3/09/10 TI / FOUR TRADE ROUGH IN >2500 VRU #: 001891787
3 -4-io
COMMENTS AND NOTES
•
'PREPARED 3/11/10, 14:01:41 INSPECTION TICKET PAGE - 25
Harnett County INSPECTOR: IVR DATE 3/12/10 '
ADDRESS . : 32 YANCEY CT SUBDIV: OVERHILLS CREEK SCT 7 92LOTS
CONTRACTOR : WELLCO CONTRACTORS, INC. PHONE : (910) 436 -3131
OWNER . . : WELLCO CONTRACTORS INC PHONE : (910) 436 -3131
PARCEL . . : 01- 0514 -03- -0006- -40-
APPL NUMBER: 09- 50023391 CP NEW RESIDENTIAL (SFD)
DIRECTIONS : T /S: 12/09/2009 11:33 AM RDCONTE - --
32 YANCEY DRIVE / OVERHILLS CREEK #550
TAKE 2105, T/R ON RAY ROAD. T/R ON
OVERHILLS ROAD. T/R ON LENOIR. T/L ON
CALDWELL. TURN ONTO YANCEY
** *SOUTH RIVER * **
STRUCTURE: 000 000 55X33 SLAB 3BD /2.5BA W /GAR & DECK
FLOOD ZONE • FLOOD ZONE X
# BEDROOMS 3.00 PROPOSED USE • SFD
SEPTIC - EXISTING' • SEWER WATER SUPPLY • COUNTY
PERMIT: CPSF 00 CP * SFD
REQUESTED INSP DESCRIPTION
TYP /SQ COMPLETED RESULT RESULTS /COMMENTS
B101 01 1/15/10 JH R *BLDG FOOTING / TEMP SVC POLE TIME: 17:00 VRU #: 001871375
1/15/10 AP T /S: 01/14/2010 01:21 PM RDCONTE
FOOTING
no t -pole
B103 01 1/21/10 JH R *BLDG FOUND & TEMP SVC POLE VRU #: 001873627
1/21/10 AP t -pole passed
A814 01 1/26/10 FB ADDRESS CONFIRMATION VRU #: 001873636
1/28/10 AP T /S: 01/28/2010 11:09 AM FBURGESS
32 YANCEY CT SPRING LAKE,NC 28390 LOT 550
P309 01 1/29/10 BS R *PLUMB UNDER SLAB VRU #: 001877632
1/29/10 AP T /S: January 29, 2010 09:37 AM BSUTTON
B111 01 2/01/10 DT R *BLDG SLAB INSP VRU #: 001878392
2/02/10 DA 1. Floor not completely covered in plastic.
2. Slab must be insulated or res check 4.0 or greater needed
T /S: 02/02/2010 10:07 AM DETAYLOR
B111 02 2/04/10 DT R *BLDG SLAB INSP VRU #: 001879113
2/04/10 AP
R427 01 3/09/10 JH FOUR TRADE ROUGH IN >2500 VRU #: 001891787
3/09/10 AP
I129 01 3/12/10 TI R *INSULATION INSPECTION VRU #: 001893892
/9 - /p
COMMENTS AND NOTES
PREPARED 5/21/10, 14:00:47 INSPECTION TICKET PAGE 11
Harnett County INSPECTOR: IVR DATE 5/24/10
ADDRESS . : 32 YANCEY CT SUBDIV: OVERHILLS CREEK SCT 7 92LOTS
CONTRACTOR : WELLCO CONTRACTORS, INC. PHONE : (910) 436 -3131
OWNER . . : WELLCO CONTRACTORS INC PHONE : (910) 436 -3131
PARCEL . . : 01- 0514 -03- -0006- -40-
APPL NUMBER: 09- 50023391 CP NEW RESIDENTIAL (SFD)
DIRECTIONS : T /S: 12/09/2009 11:33 AM RDCONTE - --
32 YANCEY DRIVE / OVERHILLS CREEK #550
TAKE 2105, T/R ON RAY ROAD. T/R ON
OVERHILLS ROAD. T/R ON LENOIR. T/L ON
CALDWELL. TURN ONTO YANCEY
** *SOUTH RIVER * **
STRUCTURE: 000 000 55X33 SLAB 3BD /2.5BA W /GAR & DECK
FLOOD ZONE • FLOOD ZONE X
# BEDROOMS 3.00 PROPOSED USE • SFD
SEPTIC - EXISTING' • SEWER WATER SUPPLY • COUNTY
PERMIT: CPSF 00 CP * SFD
REQUESTED INSP DESCRIPTION
TYP /SQ COMPLETED RESULT RESULTS /COMMENTS
B101 01 1/15/10 JH R *BLDG FOOTING / TEMP SVC POLE TIME: 17:00 VRU #: 001871375
1/15/10 AP T /S: 01/14/2010 01:21 PM RDCONTE
FOOTING
no t -pole
3103 01 1/21/10 JH R *BLDG FOUND & TEMP SVC POLE VRU #: 001873627
1/21/10 AP t -pole passed
A814 01 1/26/10 FB ADDRESS CONFIRMATION VRU #: 001873636
1/28/10 AP T /S: 01/28/2010 11:09 AM FBURGESS
\/32 YANCEY CT SPRING LAKE,NC 28390 LOT 550
P309 01 1/29/10 BS R *PLUMB UNDER SLAB VRU #: 001877632
1/29/10 AP T /S: January 29, 2010 09:37 AM BSUTTON
B111 01 2/01/10 DT R *BLDG SLAB INSP VRU #: 001878392
2/02/10 DA 1. Floor not completely covered in plastic.
2. Slab must be insulated or res check 4.0 or greater needed
T /S: 02/02/2010 10:07 AM DETAYLOR
3111 02 2/04/10 DT R *BLDG SLAB INSP VRU #: 001879113
2/04/10 AP
R427 01 3/09/10 JH FOUR TRADE ROUGH IN >2500 VRU #: 001891787
3/09/10 AP
I129 01 3/12/10 JH R *INSULATION INSPECTION VRU #: 001893892
3/12/10 AP
R431 01 5/24/10 / � T � I �� ' FOUR TRADE FINAL >2500 TIME: 17:00 VRU #: 001931302
5'7N -1Q I/ T /S: 05/21/2010 01:11 PM NTART
COMMENTS AND NOTES
PREPARED 5/26/10, 14:22:35 INSPECTION TICKET PAGE 21
Harnett County INSPECTOR: IVR DATE 5/27/10
ADDRESS . : 32 YANCEY CT SUBDIV: OVERHILLS CREEK SCT 7 92LOTS
CONTRACTOR : WELLCO CONTRACTORS, INC. PHONE : (910) 436 -3131
OWNER . . : WELLCO CONTRACTORS INC PHONE : (910) 436 -3131
PARCEL . . : 01- 0514 -03- -0006- -40-
APPL NUMBER: 09- 50023391 CP NEW RESIDENTIAL (SFD)
DIRECTIONS : T /S: 12/09/2009 11:33 AM RDCONTE - --
32 YANCEY DRIVE / OVERHILLS CREEK #550
TAKE 2105, T/R ON RAY ROAD. T/R ON
OVERHILLS ROAD. T/R ON LENOIR. T/L ON
CALDWELL. TURN ONTO YANCEY
** *SOUTH RIVER * **
STRUCTURE: 000 000 55X33 SLAB 3BD /2.5BA W /GAR & DECK
FLOOD ZONE • FLOOD ZONE X
# BEDROOMS 3.00 PROPOSED USE • SFD
SEPTIC - EXISTING' • SEWER WATER SUPPLY • COUNTY
PERMIT: CPSF 00 CP * SFD
REQUESTED INSP DESCRIPTION
TYP /SQ COMPLETED RESULT RESULTS /COMMENTS
B101 01 1/15/10 JH R *BLDG FOOTING / TEMP SVC POLE TIME: 17:00 VRU #: 001871375
1 /15 /10 AP T /S: 01/14/2010 01:21 PM RDCONTE
FOOTING
no t -pole
B103 01 1/21/10 JH R *BLDG FOUND & TEMP SVC POLE VRU #: 001873627
1/21/10 AP t -pole passed
A814 01 1/26/10 FE ADDRESS CONFIRMATION VRU #: 001873636
1/28/10 AP T /S: 01/28/2010 11:09 AM FBURGESS
N/32 YANCEY CT SPRING LAKE,NC 28390 LOT 550
P309 01 1/29/10 BS R *PLUMB UNDER SLAB VRU #: 001877632
1/29/10 AP T /S: January 29, 2010 09:37 AM BSUTTON
B111 01 2/01/10 DT R *BLDG SLAB INSP VRU #: 001878392
2/02/10 DA 1. Floor not completely covered in plastic.
2. Slab must be insulated or res check 4.0 or greater needed
T /S: 02/02/2010 10:07 AM DETAYLOR
2111 02 2/04/10 DT R *BLDG SLAB INSP VRU #: 001879113
2/04/10 AP
R427 01. 3/09/10 JH FOUR TRADE ROUGH IN >2500 VRU #: 001891787
3/09/10 AP
I129 01 3/12/10 JH R *INSULATION INSPECTION VRU #: 001893892
3/12/10 AP
R431 01 5/24/10 JH FOUR TRADE FINAL >2500 TIME: 17:00 VRU #: 001931302
5/24/10 DA T /S: 05/21/2010 01:11 PM NTART
1)Caulk window to brick on front of house.
2)Insulation card in attic calls for 14 1/2" of insulation
there is only 10 ".
3)Need insulation markers every 300 square feet.
R431 02 /27/10 I FOUR TRADE FINAL >2500 VRU #: 001932957
■
COMMENTS AND NOTES
'aalc J#' ITM ar,"?. .1t g e' .s - •�r+m�•' @la+ '1 m a yn:.Faa r 1 x "T. ". r: .:i Y x T 1 t e .
e/ , •.frn
' 4 li v t ' l l ii' '' 4414t 'ik' d'aiM'itH ''"4„Ht '''''S .-
. .
. .
., .
„ . , County'of Harnett "'
Building Inspections. Department '
Planning Services
-0 , ' . : :" : • ;. ... c
Certificate of Com lluannce: O c c un , a ney . I :
Certificate issued pursuant to the requirements of North Carolina General Statute 153A -363 and Hamett ,'
County Zoning Ordinances. This certifies at the time of issuance, this structure was in compliance with the
ti st - i various ordinances of the CounD4A Harnett and the North Carolina State Building Codes. For the following:
0 Use Classification: , cf i Permit Numbers
Name: JAIr[ /n lar /✓c( /pff j2 ( Building:
,,,,, e,...
11
4
Electrical:
R • Address: T Insulation: M
,� Plumbing:
Mechanical:
4 MFG Home: ,,,
.. Date: (; 9 _ /0 Building Official: /vv . 7 fr � V