Plan Review, Inspection and Permit Fees
Application Number 10- 50024534
$150.00 ❑ Explosive Mat. (90 Days)
$ 75.00 ❑ Explosive Mat. (72 Hrs)
$ 25.00 ❑ Fireworks Public Display
$ 35.00 ❑ Final Inspection
$ 35.00 +2.00 per device ❑ Fire Alarm Testing
$ 35.00 + 2.00 per nozzle ❑ Fixed Fire Suppression
$ 25.00 ❑ Insecticide Fog/Fumigation
$ 50.00 Pipe Test/UST /AGST
$ 50.00 n Plans up to 5000 ft
$100.00 n Plans 5001 ft to 10,000 ft
$150.00 ❑ Plans 10,001 ft to 25,000 ft
$250.00 ❑ Plans 25,001 ft and over
$ 35.00 + 2.00 per Head ❑ Sprinkler Certification Test
$ 35.00 ❑ Standpipe Testing
$ 25.00 Z Special Assembly
$ 25.00 ❑ Temporary Kiosks/Displays
$ 25.00 ❑ Tents, Canopies, Air Supported
$ 50.00 ❑ Tank Installation (charge for each tank)
$ 50.00 ❑ Tank Removal (charge for each tank)
$ 25.00 Total
Total device /heads
Teddy Joe McLamb 06/03/10
Code Enforcement Official Date
ir Harnett
i ntim ' emergency SarnOerl?epartnwit
A,iSR;ii '.�RC Nt. vrawharaattorg
Nit
Fire Marshal Division
June 3, 2010
Cindy Hunter
P.O. Box 47
Angier, NC 27501
Angier Bike Fest 2010
19 W. Depot St.
Angier, NC 27501
Application Number 10- 50024534
Mrs. Hunter,
Thank you for submitting the plans for the Angier Bike Fest. The plans have been
carefully reviewed by a qualified code enforcement official to examine for full
compliance with the North Carolina Fire Prevention Code and all other fire protection
regulatory documents. There are some items that were found during the plan review
process that need to be addressed before a final inspection of the new facility can be
given. These items are outlined and described below.
• Permits
o A permit will be issued for the special assembly that will include the event
as a whole.
o A permit may be issued for other tent areas if the individual tent exceeds
700 ft2 or the aggregate area of multiple canopies placed side by side
without a fire break clearance of 12'
• Fire Extinguishers
o Portable fire extinguishers shall be provided within a 30 -foot (9144 mm)
travel distance of commercial -type cooking equipment. Cooking
equipment involving vegetable or animal oils and fats shall be protected
by a Class K rated portable extinguisher.
o 2A -10B:C fire extinguisher shall be placed at tents /canopies with a travel
distance not to exceed 100' from any fire extinguisher
dr Nip
Rain Harnett
J 4n t —44
C 0 1M N t Y ,/�► Emergency Semmes Department
KO R7n :A flt :NA
{ www.barnatt.erg
• 2411.6 Outdoor cooking.
o Outdoor cooking that produces sparks or grease -laden vapors shall not be
performed within 20 feet (6096 mm) from a tent, air - supported, air -
inflated or tensioned membrane structure, temporary membrane structure
or canopy
• 2415 Generators
o Generators and other internal combustion power sources shall be separated
from tents, air- supported, air - inflated or tensioned membrane structures,
temporary membrane structures or canopies by a minimum of 20 feet
(6096 mm) and shall be isolated from contact with the public by fencing,
enclosure or other approved means.
• 2413.3 Refueling.
o Refueling shall be performed in an approved location not less than 20 feet
(6096 mm) from tents, air - supported, air- inflated or tensioned membrane
structures, temporary membrane structures or canopies.
• Crowd managers.
o When, in the opinion of the code official, it is essential for public safety in
a place of assembly or any other place where people congregate, because
of the number of persons, or the nature of the performance, exhibition,
display, contest or activity, the owner, agent or lessee shall employ one or
more qualified persons, as required and approved, to remain on duty
during the times such places are open to the public, or when such activity
is being conducted.
o Before each performance or the start of such activity, standby personnel
shall keep diligent watch for fires during the time such place is open to the
public or such activity is being conducted and take prompt measures for
extinguishment of fires that occur and assist in the evacuation of the public
from the structure.
o There shall be trained crowd managers or crowd manager supervisors at a
ratio of one crowd manager /supervisor for every 250 occupants, as
approved.
Harnett
COUNTY _ 'i ! no Emergency Servian @aperenwnt
tx«0Rlzl c; �I hft � _.
wwwfisrn•tt,org
• Permits
o Final inspection will be conducted that day of the event and the permit
will be issued
• 2406.4 Combustible materials.
o Hay, straw, shavings or similar combustible materials shall not be
located within any tent or air - supported structure containing an
assembly occupancy, except the materials necessary for the daily
feeding and care of animals. Sawdust and shavings utilized for a public
performance or exhibit shall not be prohibited provided the sawdust
and shavings are kept damp. Combustible materials shall not be
permitted under stands or seats at any time. The areas within and
adjacent to the tent or air - supported structure, shall be maintained clear
of all combustible materials or vegetation that could create a fire
hazard within 20 feet (6096 mm) from the structure. Combustible trash
shall be removed at least once a day from the structure during the
period the structure is occupied by the public.
Thank you again for submitting the plans for Angier Bike Fest. Please review the plans
and adhere to any notes and alterations that were made in addition to the original
drawings. These remarks are for the plans that were submitted and its original intent.
These remarks do not apply if the original intent changes or what was submitted on the
above date changes. If you have any questions, please do not hesitate to call this office.
Again, thank you and we look forward to working with you during the construction
period!
Sincerely,
T. J McLamb, CFI
Chief Deputy Fire Marshal