Plan Review, Inspection and Permit Fees
Application Number 10- 50024493
$150.00 n Explosive Mat. (90 Days)
$ 75.00 n Explosive Mat. (72 Hrs)
$ 25.00 ❑ Fireworks Public Display
$ 35.00 ® Final Inspection
$ 35.00 +2.00 per device I I Fire Alarm Testing
$ 35.00 + 2.00 per nozzle ❑ Fixed Fire Suppression
$ 25.00 n Insecticide Fog/Fumigation
$ 50.00 ❑ Pipe Test/UST /AGST
$ 50.00 ® Plans up to 5000 ft
$100.00 n Plans 5001 ft to 10,000 ft
$150.00 n Plans 10,001 ft2 to 25,000 ft
$250.00 n Plans 25,001 ft and over
$ 35.00 + 2.00 per Head n Sprinkler Certification Test
$ 35.00 n Standpipe Testing
$ 25.00 ❑ Special Assembly
$ 25.00 7 Temporary Kiosks/Displays
$ 25.00 7 Tents, Canopies, Air Supported
$ 50.00 n Tank Installation (charge for each tank)
$ 50.00 ❑ Tank Removal (charge for each tank)
$ 85.00 Total
n/a Total device/heads
Michael L. Martin 6/9/10
Code Enforcement Official Date
•
•
„
•
•
'
; • .•
. . • , ' •
. .
J 44.
• ,
i
H arnett
eitga t o u a t r OF 10 Em•ncricy union Department
roAS, cnac:sNn wvnaarnattorg
Y
June 9, 2010
Linda and Ervin Monroe
7084 NC 210 South
Bunnlevel, NC 28323
Family Center
7084 NC 210 South
Bunnlevel, NC 28323
Application Number 10- 50024493
Mr. Monroe,
Thank you for submitting the plans for the family center. The plans have been carefully
reviewed by a qualified code enforcement official to examine for full compliance with
the North Carolina Fire Prevention Code and all other fire protection regulatory
documents. There are some items that were found during the plan review process that
need to be addressed before a final inspection of the new facility can be given. These
items are outlined and described below.
• 906.1 Fire Extinguishers
o Fire extinguishers shall be placed in approved locations as drawn by the
code enforcement official on the approved plans.
o The fire extinguishers provided shall have a minimum rating of 2A 10B:C
and shall not be installed higher than 5 feet above the finished floor
• 506.1 Knox Box
o A secure key box shall be installed on the new building that houses all
keys to all the doors within the building in which the fire department
would need access to in the event of an emergency.
o Knox Box ID stickers shall be placed on all exterior doors in which entry
to the building may be gained.
o The box shall be mounted not to exceed 48 — 60 inches in height.
o An authorized order form is included with this letter.
•
•
•
•
.
H arnett
{ O U w T Y � mory �� � E se, ,;m, wwrharn• oop.rctt.mg mo•�
.vm
e,5:9 _- a NORTri CAROL ?NA
•0
• 505.1 Physical Address
o The physical address of the building shall be posted in a conspicuous
place so that it can be seen on approach from the road, access road, and/or
parking lot.
o The numbers used to make up the physical address shall be at least 5
inches in height
• 503.1.1 Fire Department Access
o The fire department access shall extend to within 150 feet of all portions
of the facility.
o The fire department access road shall be of an unobstructed width of not
less than 20 feet and shall have an unobstructed vertical clearance of not
less the 13 feet 6 inches.
o 2403.12.7 Means of egress illumination.
• Means of egress shall be illuminated with light having an intensity of not
less than 1 foot -candle (11 lux) at floor level while the structure is
occupied. Fixtures required for means of egress illumination shall be
supplied from a separate circuit or source of power.
• EXIT/Emergency Lighting shall be installed as drawn on the plans by the
fire code official.
• Exterior Egress Lighting shall be installed as indicated on the plans.
Thank you again for submitting the plans for the family center. Please review the plans
and adhere to any notes and alterations that were made in addition to the original
drawings. These remarks are for the plans that were submitted and its original intent.
These remarks do not apply if the original intent changes or what was submitted on the
above date changes. If you have any questions, please do not hesitate to call this office.
Again, thank you and we look forward to working with you during the construction
period!
Thank You,
Mich 1 L. Martin
Deputy Fire Marshal