INSPECTIONS
PREPARED 9/24/09, 14:07:23 INSPECTION TICKET PAGE 26
Harnett County INSPECTOR: IVR DATE 9/25/09
-
ADDRESS . : 1984 OLD US 421 SUBDIV:
CONTRACTOR ARUSS ELECTRICAL CONTRACTOR IN PHONE (910) 670-7942
OWNER BLUE RIDGE HEALTH PHONE
PARCEL 13-0640- - -0059- - -
APPL NUMBER: 09-50022840 CP STANDALONE TRADE - COMMERCIAL
DIRECTIONS : T/S: 09/15/2009 09:44 AM RDCONTE
1984 OLD US 421 TAKE 421 TOWARD
SANFORD. NURSING HOME IS ON THE RIGHT.
STRUCTURE: 000 000 MISC ELEC TO CORRECT VIOLATIONS
PROPOSED USE . . . . . . . : ELEC
PERMIT: CPEC 00 CP ELECTRICAL COMMERCIAL.
REQUESTED INSP DESCRIPTION
TYP/SQ COMPLETED RESULT RESULTS/COMMENTS
- -
E265 01 9// C*ELEC FINAL VRU 001826957
COMMENTS AND NOTES
it
T
Violation Notice
Do Not Remove
Harnett County Inspection Department
102 East Front St P.O. Box 65
I.111ington, NC 27546
Phone (910) 893-7525 Fax (910) 895-2795
09-50022840 September 28, 2009
1. Second floor attic has some wires leaving a junction boa that are taped up
and are unused. Remove any unused wiring.
2. Romea in basement passes thru concrete unprotected.
3. Conduits not secure.
4. Wire laying on ground in crawl space.
5. Wire run thru open LB connector.
6. Basement not cleaned up like god floor attic.
First floor attic OK
Ken Slattum Fred Spivey
Harnett County Code Officials
PREPARED 9/30/09, 13:59:57 INSPECTION TICKET PAGE 50
Harnett County INSPECTOR: IVR DATE 10/01/09
ADDRESS . : 1984 OLD US 421 SUBDIV:
CONTRACTOR ARUSS ELECTRICAL CONTRACTOR IN PHONE (910) 670-7942
OWNER BLUE RIDGE HEALTH PHONE
PARCEL 13-0640- - -0059- - -
APPL NUMBER: 09-50022840 CP STANDALONE TRADE - COMMERCIAL
DIRECTIONS : T/S: 09/15/2009 09:44 AM RDCONTE
1984 OLD US 421 TAKE 421 TOWARD
SANFORD. NURSING HOME IS ON THE RIGHT.
-
STRUCTURE: 000 000 MISC ELEC TO CORRECT VIOLATIONS
PROPOSED USE . . . . . . . : ELEC
PERMIT: CPEC 00 CP ELECTRICAL COMMERCIAL
REQUESTED INSP DESCRIPTION
TYP/SQ COMPLETED RESULT RESULTS/COMMENTS
E265 01 9/25/09 C*ELEC FINAL VRU 001826957 lj~ 9/30/09 DA Cleanup wire in basement
Remove unused wire in attic
support conduit
use correct fiting for box connector.
T/S: 09/30/2009 07:55 AM KSLATTUM
E265 02 11 /011/ ; C*ELEC FINAL VRU 001829555
COMMENTS AND NOTES -