3rd Party Final Inspection Report for Spray-Applied Fire Resistive MaterialsKAM Geotechnical Engineering Services Construction Material Testing Civil Quality Control iag Services, F.C. October 31,2012 Harnett Health System 800 Tilgman Drive Dunn,NC 28335 Attention: Mike Jones and Mr. Chas Fare RE: Special Inspections Final Report - Spray-Applied Fire Resistive Materials Harnett Health Complex Lillington, North Carolina KAM Project Number 11-0114 Gentlemen: KAM Engineering Services, P.C. has completed the materials testing services for the above stated project. This Special Inspections Final Report is intended to confirm that KAM Engineering was present periodically during the installation and curing process for the Spray-Applied Fire Resistive Materials (SFRM). A series of six (6) tests were performed by our staff to provide a random sampling for the SFRM that was applied to the structural steel at the project site. It is our opinion that the test locations were representative of workmanship of the remainder of the un-tested elements. Our thickness and density testing was performed in general accordance with ASTM E-605, while our bond strength testing was performed in general accordance with ASTM E-736. At the time of testing, test results indicated that the thickness, density and bond strength of the SFRM materials were installed in general accordance with the approved project plans and specifications, and applicable workmanship of the International Building Code. Respectfully submitted, KAM Engineering Kurt A. Miller, PE •„• , Senior Geotechnical Engineer 610 Spring Branch Road Dunn, NC 28334 Phone(910)292-2085 I a\(910)292-2087 www.KAM-Engineering.com